Air-cooled scroll chiller controller · BACnet points list

Trane Symbio 800 CGAM (CH530) BACnet points list

Updated 28 October 2026

Short answer

A short list of 72 BACnet objects for CGAM chillers, using low instance numbers and output objects for the BAS commands: AO for chilled water, hot water, heat recovery and demand limit setpoints, BO for auto/stop, diagnostic reset, noise reduction and heat recovery enable, and MO for the chiller mode. There are no per-alarm diagnostic objects; BI 23 Alarm Present is the summary alarm.

This page lists 72 BACnet objects for the Trane Symbio 800 CGAM (CH530) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 CGAM (CH530)
Equipment
Air-cooled scroll chiller controller
Equipment type
Chillers
BACnet objects
72 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027
Source document
Symbio 800 Integration Points List BACnet - CGAM (CH530) · BAS-PTS027A-EN · rev. 12/6/2024
Download CSV 72 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 CGAM (CH530)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. The commands are AO/BO/MO objects; everything else is read-only status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Chiller Auto Stop CommandBMS auto/stop (enable) commandWrite
MO 1Chiller Mode CommandCool/heat/ice mode commandWrite
AO 1Chilled Water SetpointChilled water setpoint from the BMSWrite
AO 3Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 4Chiller Running StateChiller on/off statusRead
BI 2Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 45Evaporator Leaving Water TempLeaving chilled water temperatureRead
AI 5Actual Running CapacityActual running capacity in percentRead
BI 23Alarm PresentAny active alarm on the chillerRead

Enable & remote start

BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto; relinquish default Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 1 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Network setup

Watch out for

Trane Symbio 800 CGAM (CH530) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

72 of 72 shown
Type
Access
Show
Trane Symbio 800 CGAM (CH530) BACnet Points List
DescriptionStates
AI1Active Cool/Heat Setpoint TemperatureActive chiller water or hot water setpointTemperatureRead
AI3Active Demand Limit SetpointPercentRead
AImin5Actual Running CapacityLevel of capacity that the chiller is currently running atPercentRead
AI8Suction Pressure- Ckt 1Circuit 1 suction pressurePressureRead
AI11Suction Pressure- Ckt 2Circuit 2 suction pressurePressureRead
AI13Suction Saturated Refrigerant Temperature- Ckt 1Circuit 1 suction refrigerant temperatureTemperatureRead
AI15Suction Saturated Refrigerant Temperature- Ckt 2Circuit 2 suction refrigerant temperatureTemperatureRead
AI17Discharge Pressure- Ckt 1Circuit 1 discharge pressurePressureRead
AI19Discharge Pressure- Ckt 2Circuit 2 discharge pressurePressureRead
AI21Discharge Saturated Refrigerant Temperature- Ckt 1Circuit 1 discharge refrigerant temperatureTemperatureRead
AI23Discharge Saturated Refrigerant Temperature- Ckt 2Circuit 2 discharge refrigerant temperatureTemperatureRead
AI25Local Atmospheric PressurePressureRead
AI26Starts- Compressor 1ANumber of starts for compressor 1ARead
AI27Starts- Compressor 1BNumber of starts for compressor 1BRead
AI30Starts- Compressor 1CNumber of starts for compressor 1CRead
AI31Starts- Compressor 2ANumber of starts for compressor 2ARead
AI32Starts- Compressor 2BNumber of starts for compressor 2BRead
AI33Starts- Compressor 2CNumber of starts for compressor 2CRead
AI34Run Time- Compressor 1ATotal run time of compressor 1ATimeRead
AI35Run Time- Compressor 1BTotal run time of compressor 1BTimeRead
AI38Run Time- Compressor 1CTotal run time of compressor 1CTimeRead
AI39Run Time- Compressor 2ATotal run time of compressor 2ATimeRead
AI40Run Time- Compressor 2BTotal run time of compressor 2BTimeRead
AI41Run Time- Compressor 2CTotal run time of compressor 2CTimeRead
AI42Airflow Percentage- Circuit 1Approximate airflow percentage of circuit 1PercentRead
AI43Airflow Percentage- Circuit 2Approximate airflow percentage of circuit 2PercentRead
AI44Evaporator Entering Water TempTemperature of the water entering the evaporatorTemperatureRead
AImin45Evaporator Leaving Water TempTemperature of the water leaving the evaporatorTemperatureRead
AI57Outdoor Air TemperatureTemperatureRead
AI95Number of CircuitsRead
AI96Number of Compressors, Ckt 1Read
AI97Number of Compressors, Ckt 2Read
AI98Chiller Design CapacityDesign Capacity of the ChillerRead
AI99Heat Recovery Entering Water TemperatureTemperature of the water entering the auxiliary heat exchangerTemperatureRead
AI100Heat Recovery Leaving Water TemperatureTemperature of the water leaving the auxiliary heat exchangerTemperatureRead
AI101Heat Recovery Control StatusPercentRead
AI102Supplemental Heat StatusSupplemental Heat Control output status which is expressed as a percentagePercentRead
AOmin1Chilled Water SetpointRange 0°F to 75°F (-17.8°C to 23.8°C); default 44°F (6.7°C)TemperatureWrite
AOmin3Demand Limit SetpointRange 0% to 120%; default 100%PercentWrite
AO4Hot Water SetpointRange 80°F to 140°F (26.7°C to 60°C); default 120°F (48.9°C)TemperatureWrite
AO6Heat Recovery Leaving Water Temperature Setpoint BASRange 80°F to 140°F (26.7°C to 60°C); default 122°F (50°C)TemperatureWrite
BI1Run EnabledThe chiller is available to run or is currently runningReadInactive = Stop, Active = Auto
BImin2Local Setpoint ControlThe chiller is being controlled by local setpoints instead of BAS setpointsReadInactive = Remote Control, Active = Local Control
BI3Capacity LimitedConditions may exist that prevent the chiller from reaching setpointReadInactive = Not Limited, Active = Limited
BImin4Chiller Running StateThe chiller is running or stoppedReadInactive = Off, Active = On
BI6Maximum CapacityAll available chiller capacity is being usedReadInactive = Off, Active = On
BI9Compressor 1A RunningCompressor 1A is runningReadInactive = Off, Active = Running
BI10Compressor 1B RunningCompressor 1B is runningReadInactive = Off, Active = Running
BI13Compressor 1C RunningCompressor 1C is runningReadInactive = Off, Active = Running
BI14Compressor 2A RunningCompressor 2A is runningReadInactive = Off, Active = Running
BI15Compressor 2B RunningCompressor 2B is runningReadInactive = Off, Active = Running
BI16Compressor 2C RunningCompressor 2C is runningReadInactive = Off, Active = Running
BI18Water Pump RequestRequest from the chiller to turn on the water pumpReadInactive = Off, Active = On
BI20Noise Reduction ActiveThe chiller is in a state where noise is being reducedReadInactive = Off, Active = On
BI21Defrost Mode (or in Defrost)One or more circuits are in a defrost modeReadInactive = Not in Defrost, Active = Defrost
BI22Evaporator Water Flow StatusWater is flowing through the evaporatorReadInactive = No Flow, Active = Flow
BImin23Alarm PresentAn alarm is activeReadInactive = No Alarm, Active = Alarm
BI24Shutdown Alarm PresentA shutdown alarm is activeReadInactive = No Alarm, Active = None
BI25Last DiagnosticLast diagnostic for the chillerReadInactive = Off, Active = On
BI26Heat Recovery Control Active StatusThe chiller is changing behavior to get heat recoveryReadInactive = Off, Active = On
BOmin1Chiller Auto Stop CommandAllows the chiller to run if conditions for running are metWriteInactive = Stop, Active = Auto
BO2Remote Diagnostic Reset CommandResets remotely diagnostics that can be resetWriteInactive = No Reset Request, Active = Reset Request
BO4Noise Reduction RequestRequests chiller to enter mode to reduce noiseWriteInactive = Normal, Active = Reduced Noise
BO5Heat Recovery Enable BASRequest chiller to enter in Heat Recovery control modeWriteInactive = Normal, Active = Heat Recovery
MI1Running ModePrimary running mode of the chillerRead1 = Chiller Off, 2 = Chiller in Start Mode, 3 = Chiller in Run Mode, 4 = Chiller in Pre-shutdown Mode, 5 = Chiller in Service Mode
MI2Operating ModePrimary operating mode of the chillerRead1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (a), 4 = Not Used
MI3MP Communication StatusDo Not Use This PointReadDo Not Use This Point
MI4Refrigerant TypeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134A, 6 = R407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A
MI5Model InformationModel type of the chillerRead1 = RTA, 2 = CVH, 3 = CVG, 4 = CVR, 5 = CDH, 6 = RTH, 7 = CGW, 8 = CGA, 9 = CCA, 10 = RTW, 11 = RTX, 12 = RTU, 13 = CCU, 14 = CXA, 15 = CGC, 16 = RAU
MI6Cooling TypeCooling type of the condenserRead1 = Water Cooled, 2 = Air Cooled
MI7Manufacturing LocationLocation where chiller was manufacturedRead1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey
MOmin1Chiller Mode CommandMode of operation of the chillerWrite1 = HVAC _Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (a), 4 = Not Used

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CGAM (CH530) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 CGAM (CH530)

How many BACnet points does the Trane Symbio 800 CGAM (CH530) have?

This list has 72 BACnet objects: 37 analog inputs, 4 analog outputs, 19 binary inputs, 4 binary outputs, 7 multi-state inputs, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 CGAM (CH530) BACnet points are writable?

9 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 CGAM (CH530) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - CGAM (CH530) (BAS-PTS027A-EN), revision 12/6/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS027A-EN_12062024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 CGAM (CH530)?

Start with BO 1 Chiller Auto Stop Command (BMS auto/stop (enable) command); MO 1 Chiller Mode Command (Cool/heat/ice mode command); AO 1 Chilled Water Setpoint (Chilled water setpoint from the BMS); AO 3 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 4 Chiller Running State (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 45 Evaporator Leaving Water Temp (Leaving chilled water temperature); AI 5 Actual Running Capacity (Actual running capacity in percent); BI 23 Alarm Present (Any active alarm on the chiller).

How do I enable BMS control of the Trane Symbio 800 CGAM (CH530)?

BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto; relinquish default Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 1 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

How do I check these points on the real Symbio 800 CGAM (CH530)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - CGAM (CH530) · BAS-PTS027A-EN · rev. 12/6/2024. Object names, instances and units are reproduced as published; descriptions are our own.