Air-cooled chiller controller · BACnet points list

Trane Symbio 800 ACSA (UC800) BACnet points list

Updated 28 October 2026

Short answer

This Symbio 800 list for ACSA chillers has about 340 BACnet objects with low instance numbers: AI 1-150, BI 1-26 for status and BI 506-943 for diagnostics. The BAS writes chilled and hot water setpoints, demand limit, heat recovery, noise reduction, circuit lockouts, mode and auto/stop; auto/stop and mode are multistate values.

This page lists 342 BACnet objects for the Trane Symbio 800 ACSA (UC800) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 ACSA (UC800)
Equipment
Air-cooled chiller controller
Equipment type
Chillers
BACnet objects
342 (13 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026
Source document
Symbio 800 Integration Points List BACnet - ACSA (UC800) · BAS-PTS026A-EN · rev. 12/6/2024
Download CSV 342 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 ACSA (UC800)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1BAS Chiller Auto Stop CommandBMS auto/stop command (1 = Stop, 2 = Auto)Write
MV 2BAS Chiller Mode CommandCool/heat/ice mode commandWrite
AV 1Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 3Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 4Chiller Running StateChiller on/off statusRead
BI 2Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 4Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 21Actual Running CapacityActual running capacity in percentRead
BI 10Alarm PresentAny active alarm on the chillerRead

Enable & remote start

MV 1 BAS Chiller Auto Stop Command (1 = Stop, 2 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. MI 7 External Auto Stop reports the hardwired external auto/stop input, and BI 1 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 5 Active Chilled Water Setpoint Source shows front panel, external, ice machine or BAS.

Heartbeat & communication loss

No timeout or heartbeat is described. The list includes the diagnostic flags BI 881 'BAS Communication Lost', BI 882 'BAS Failed to Establish Communication' and BI 600 'Comm Loss: Local BAS Interface'; the document doesn't say what timeout sets them or what the chiller does when they are set.

Network setup

Watch out for

Trane Symbio 800 ACSA (UC800) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

342 of 342 shown
Type
Access
Show
Trane Symbio 800 ACSA (UC800) BACnet Points List
DescriptionStates
AI1Active Cool/Heat Water Setpoint TemperatureRead
AI2Front Panel Chilled Water SetpointRead
AI3Evaporator Entering Water TemperatureRead
AImin4Evaporator Leaving Water TemperatureRead
AI5Active Demand Limit SetpointRead
AI6Front Panel Demand Limit SetpointRead
AI7Unit Power ConsumptionRead
AI8Outdoor Air TemperatureRead
AI9External Chilled/Hot Water SetpointRead
AI10External Demand Limit SetpointRead
AI11Evaporator Refrigerant Pressure Ckt1Read
AI12Condenser Refrigerant Pressure Ckt1Read
AI13Differential Refrigerant Pressure Ckt1Read
AI14Suction(Evaporator) Saturated Rfgt Temp Ckt1Read
AI15Condenser Saturated Rfgt Temp Ckt1Read
AI16Evaporator Refrigerant Pressure Ckt2Read
AI17Condenser Refrigerant Pressure Ckt2Read
AI18Differential Refrigerant Pressure Ckt2Read
AI19Suction(Evaporator) Saturated Rfgt Temp Ckt2Read
AI20Condenser Saturated Rfgt Temp Ckt2Read
AImin21Actual Running CapacityRead
AI22Active Heat Recovery SetpointRead
AI23Front Panel Hot Water SetpointRead
AI24Active Hot Water SetpointRead
AI25Liquid Line Temperature Ckt1Read
AI26Liquid Line Temperature Ckt2Read
AI27Liquid Line Pressure Ckt1Read
AI28Liquid Line Pressure Ckt2Read
AI30Air Flow Ckt1Read
AI31Air Flow Ckt2Read
AI35Starts Cprsr1ARead
AI36Run Time Cprsr1ARead
AI51Starts Cprsr2ARead
AI52Run Time Cprsr2ARead
AI69Heat Recovery Entering Water TempRead
AI70Heat Recovery Leaving Water TempRead
AI71Chiller Design CapacityRead
AI128Starts Cprsr1BRead
AI129Run Time Cprsr1BRead
AI130Starts Cprsr2BRead
AI131Run Time Cprsr2BRead
AI132Number of CircuitsRead
AI133Number of Compressors, Circuit 1Read
AI134Number of Compressors, Circuit 2Read
AI136Free Cooling CapacityRead
AI137Free Cooling Entering Water TemperatureRead
AI138Free Cooling Entering Glycol TemperatureRead
AI139Free Cooling Leaving Glycol TemperatureRead
AI141Energy Consumption NonResetRead
AI142Energy Consumption ResettableRead
AI143Starts Cprsr1CRead
AI144Run Time Cprsr1CRead
AI145Starts Cprsr2CRead
AI146Run Time Cprsr2CRead
AI147Discharge Temperature Ckt1Read
AI148Discharge Temperature Ckt2Read
AI149Compressor Discharge Temperature Ckt1Read
AI150Compressor Discharge Temperature Ckt2Read
AVmin1Chilled Water SetpointWrite
AV2Hot Water SetpointWrite
AVmin3Demand Limit SetpointWrite
AV4BAS Heat Recovery SetpointWrite
BI1Run EnableRead0 = no, 1 = yes
BImin2Local Setpoint ControlRead0 = no, 1 = yes
BI3Limit Mode Relay StatusRead0 = off, 1 = on
BImin4Chiller Running StateRead0 = no (not running), 1 = yes (running)
BI5Maximum Capacity RelayRead0 = off, 1 = on
BI6Evaporator Water Pump CommandRead0 = off (pump off), 1 = on (pump on)
BI7Evaporator Water Flow StatusRead0 = no flow, 1 = flow
BI8Manual Override ExistsRead0 = false, 1 = true
BI9Emergency Stop InputRead0 = emergency shutdown, 1 = auto
BImin10Alarm PresentRead0 = no, 1 = yes
BI11Running Status Cprsr1ARead1 = off, 2 = on
BI12Running Status Cprsr2ARead1 = off, 2 = on
BI13Running Status Cprsr1BRead1 = off, 2 = on
BI14Running Status Cprsr2BRead1 = off, 2 = on
BI15Free Cooling ActiveRead0 = Active, 1 = Inactive
BI16Heat Recovery ActiveRead0 = Active, 1 = Inactive
BI17Active Heat Recovery CommandRead0 = Active, 1 = Inactive
BI18Latching Alarm Present, Circuit 1Read0 = no, 1 = yes
BI19Latching Alarm Present, Circuit 2Read0 = no, 1 = yes
BI20Non-Latching Alarm Present, Circuit 1Read0 = no, 1 = yes
BI21Non-Latching Alarm Present, Circuit 2Read0 = no, 1 = yes
BI22Running Status Cprsr1CRead1 = off, 2 = on
BI23Running Status Cprsr2CRead1 = off, 2 = on
BI24Emergency Stop Unit StatusRead0 = emergency shutdown, 1 = auto
BI25Noise Reduction ActiveRead
BI26No assignment - reserved as obsoleteReadNA
BI506Comm Loss: Evaporator Anti-Freeze HeaterRead
BI507Comm Loss: Auxiliary Setpoint CommandRead
BI508Comm Loss: Evaporator Water Flow SwitchRead
BI509Comm Loss: Compressor Fault InputRead
BI510Comm Loss: Compressor Fault InputRead
BI511Comm Loss: Compressor Fault InputRead
BI512Comm Loss: Compressor Fault InputRead
BI513Comm Loss: Compressor Fault InputRead
BI514Comm Loss: Compressor Fault InputRead
BI518Comm Loss: Cond Fan Enbl Shared Ckt 1&2Read
BI520Comm Loss: Condenser Fan EnableRead
BI521Comm Loss: Condenser Fan EnableRead
BI533Comm Loss: Discharge Temperature SensorRead
BI534Comm Loss: Discharge Temperature SensorRead
BI535Comm Loss: Discharge Pressure TransducerRead
BI536Comm Loss: Discharge Pressure TransducerRead
BI537Comm Loss: Electronic Expansion ValveRead
BI538Comm Loss: Electronic Expansion ValveRead
BI539Comm Loss: Emergency Stop Feedback InputRead
BI541Comm Loss: Evap Entering Water TempRead
BI543Comm Loss: Evap Leaving Water TempRead
BI545Comm Loss: Evap Pump Inv1 Fault InputRead
BI546Comm Loss: Evap Pump Inv1 Freq FeedbackRead
BI547Comm Loss: Evap Pump Inv1 Run CommandRead
BI550Comm Loss: Evaporator Water Pump 1 RelayRead
BI551Comm Loss: Evaporator Water Pump 2 RelayRead
BI556Comm Loss: Ext Chilled Water SetpointRead
BI557External Demand Limit SetpointRead
BI558Comm Loss: Ext Noise Reduction RequestRead
BI559Comm Loss: External Auto/StopRead
BI560Comm Loss: External Ckt LockoutRead
BI561Comm Loss: External Ckt LockoutRead
BI562Comm Loss: External Heat Recovery CommandRead
BI563Comm Loss: External Ice Building CommandRead
BI564Comm Loss: Fan Board 1 Relay 1Read
BI565Comm Loss: Fan Board 1 Relay 1Read
BI566Comm Loss: Fan Board 1 Relay 2Read
BI567Comm Loss: Fan Board 1 Relay 2Read
BI568Comm Loss: Fan Board 1 Relay 3Read
BI569Comm Loss: Fan Board 1 Relay 3Read
BI570Comm Loss: Fan Board 1 Relay 4Read
BI571Comm Loss: Fan Board 1 Relay 4Read
BI572Comm Loss: Fan Speed Select Board Relay 1Read
BI574Comm Loss: Fan Speed Select Board Relay 2Read
BI577Comm Loss: Fan Speed Select Board Relay 3Read
BI579Comm Loss: Fan Speed Select Board Relay 4Read
BI582Comm Loss: Fan Inv Spd Cmd, Shrd Ckt1&2Read
BI585Comm Loss: Fan Inverter Speed CommandRead
BI586Comm Loss: Fan Inverter Speed CommandRead
BI590Comm Loss: High Pressure Cutout SwitchRead
BI591Comm Loss: High Pressure Cutout SwitchRead
BI596Comm Loss: HR Entering Water Temp SensorRead
BI597Comm Loss: HR Leaving Water Temp SensorRead
BI598Comm Loss: HR Three Way ValveRead
BI600Comm Loss: Local BAS InterfaceRead
BI602Comm Loss: Programmable Relay Board 1Read
BI603Comm Loss: Outdoor Air TemperatureRead
BI604Comm Loss: Percent Capacity OutputRead
BI605Comm Loss: Phase Protection Fault InputRead
BI606Comm Loss: Programmable Relay Board 2Read
BI617Comm Loss: Run Command Compressor ARead
BI618Comm Loss: Run Command Compressor ARead
BI619Comm Loss: Run Command Compressor BRead
BI620Comm Loss: Run Command Compressor BRead
BI621Comm Loss: Run Command Compressor CRead
BI622Comm Loss: Run Command Compressor CRead
BI628Comm Loss: Suction Rfgt PressureRead
BI629Comm Loss: Suction Rfgt PressureRead
BI630Comm Loss: Suction TemperatureRead
BI631Comm Loss: Suction TemperatureRead
BI636Compressor A FaultRead
BI637Compressor A FaultRead
BI638Compressor B FaultRead
BI639Compressor B FaultRead
BI640Compressor C FaultRead
BI641Compressor C FaultRead
BI642Compressor Fault LockoutRead
BI643Compressor Fault LockoutRead
BI644Compressor Fault LockoutRead
BI645Compressor Fault LockoutRead
BI646Compressor Fault LockoutRead
BI647Compressor Fault LockoutRead
BI650Discharge Pressure TransducerRead
BI651Discharge Pressure TransducerRead
BI669Emergency StopRead
BI691Evap Pump 1 Starts/Hours ModifiedRead
BI692Evap Pump 2 Starts/Hours ModifiedRead
BI694Evaporator Entering Water Temp SensorRead
BI696Evaporator Leaving Water Temp SensorRead
BI698Evaporator Pump 1 FaultRead
BI699Evaporator Pump 2 FaultRead
BI700Evaporator Water Flow LostRead
BI701Evaporator Water Flow Lost LockoutRead
BI702Evaporator Water Flow Lost - Pump1Read
BI703Evaporator Water Flow Lost - Pump2Read
BI704Evaporator Water Flow OverdueRead
BI705Evaporator Water Flow Overdue - Pump1Read
BI706Evaporator Water Flow Overdue - Pump2Read
BI707Evaporator Water Flow Too LowRead
BI708External Chilled/Hot Water SetpointRead
BI711Heat Recovery Entering Water Temp SensorRead
BI712Heat Recovery Leaving Water Temp SensorRead
BI713High Compressor Pressure DifferentialRead
BI714High Compressor Pressure DifferentialRead
BI715High Discharge Refrigerant PressureRead
BI716High Discharge Refrigerant PressureRead
BI717High Discharge TemperatureRead
BI718High Discharge TemperatureRead
BI731High Discharge Temperature LockoutRead
BI732High Discharge Temperature LockoutRead
BI733High Evaporator Water TemperatureRead
BI746High Pressure CutoutRead
BI747High Pressure CutoutRead
BI748High Suction Rfgt PressureRead
BI768Inverted Evaporator Water TemperatureRead
BI769Inverted Water Temp (Heating)Read
BI770LCI-C Software Mismatch: Use BAS ToolRead
BI771Loss of ChargeRead
BI772Loss of ChargeRead
BI775Low Discharge Saturated TemperatureRead
BI776Low Discharge Saturated TemperatureRead
BI777Low Evaporator Water Temp (Unit Off)Read
BI778Low Evaporator Water Temp (Unit On)Read
BI779Low Suction Refrigerant TemperatureRead
BI780Low Suction Refrigerant TemperatureRead
BI782Low Suction Refrigerant PressureRead
BI783Low Refrigerant Pressure RatioRead
BI784Low Refrigerant Pressure RatioRead
BI785Low Suction Refrigerant PressureRead
BI786Low Suction SuperheatRead
BI787Low Suction SuperheatRead
BI827MP: Invalid ConfigurationRead
BI829MP: Reset Has OccurredRead
BI832Pumpdown Terminated By TimeRead
BI833Outdoor Air Temperature SensorRead
BI834Phase Protection FaultRead
BI835No Total Heat RecoveryRead
BI838Restart Inhibit Invoked - 1ARead
BI839Restart Inhibit Invoked - 2ARead
BI840Restart Inhibit Invoked - 1BRead
BI841Restart Inhibit Invoked - 2BRead
BI842Restart Inhibit Invoked - 1CRead
BI843Restart Inhibit Invoked - 2CRead
BI848Starts/Hours Modified 1CRead
BI849Starts/Hours Modified 2ARead
BI850Starts/Hours Modified 1BRead
BI851Starts/Hours Modified 1ARead
BI852Starts/Hours Modified 2BRead
BI853Starts/Hours Modified 2CRead
BI856Suction Pressure TransducerRead
BI857Suction Pressure TransducerRead
BI858Suction Temperature SensorRead
BI859Suction Temperature SensorRead
BI860Suction Temperature Too HighRead
BI861Suction Temperature Too HighRead
BI862Very Low Suction Pressure - Circuit 1Read
BI863Very Low Suction Pressure - Circuit 2Read
BI864Chiller Service RecommendedRead
BI865Pumpdown Terminated By TimeRead
BI866Comm Loss: Energy Meter Pulse InputRead
BI867Comm Loss: Evap Pump Inverter 1 SpeedRead
BI868Comm Loss: Ext Demand Limit StptRead
BI869Comm Loss: Heat Recovery Anti-Freeze HeaterRead
BI871Comm Loss: Evaporator Pump 1 Fault InputRead
BI872Comm Loss: Evaporator Pump 2 Fault InputRead
BI873Evap Water Pump 1 Svc RecommendedRead
BI874Evap Water Pump 2 Svc RecommendedRead
BI875Mfr Maintenance Recommended - 1ARead
BI876Mfr Maintenance Recommended - 1BRead
BI877Mfr Maintenance Recommended - 1CRead
BI878Mfr Maintenance Recommended - 2ARead
BI879Mfr Maintenance Recommended - 2BRead
BI880Mfr Maintenance Recommended - 2CRead
BI881BAS Communication LostRead
BI882BAS Failed to Establish CommunicationRead
BI883Comm Loss: FC Entering Glycol TempRead
BI884Comm Loss: FC Entering Water TempRead
BI885Comm Loss: FC Leaving Glycol TempRead
BI886Comm Loss: Free Cooling PumpRead
BI887Comm Loss: Free Cooling ValveRead
BI888Free Cooling Entering Glycol TemperatureRead
BI889Free Cooling Entering Water TemperatureRead
BI890Free Cooling Glycol Temp Equalization OverdueRead
BI891Free Cooling Leaving Glycol TemperatureRead
BI892Low Glycol Temperature Free CoolingRead
BI893Comm Loss: External Heat Recovery SetpointRead
BI894Comm Loss: Fan Board 2 Relay 1Read
BI895Comm Loss: Fan Board 2 Relay 1Read
BI896Comm Loss: Fan Board 2 Relay 2Read
BI897Comm Loss: Fan Board 2 Relay 2Read
BI898Comm Loss: Fan Board 2 Relay 3Read
BI899Comm Loss: Fan Board 2 Relay 3Read
BI900Comm Loss: Fan Board 2 Relay 4Read
BI901Comm Loss: Fan Board 2 Relay 4Read
BI902External Heat Recovery SetpointRead
BI903Comm Loss: HR Refrigerant Bypass ValveRead
BI904Comm Loss: HR Refrigerant Bypass ValveRead
BI905Comm Loss: Reversing ValveRead
BI906Comm Loss: Reversing ValveRead
BI907Comm Loss: Hot Gas Bypass ValveRead
BI908Comm Loss: Dynamic Receiver Fill ValveRead
BI909Comm Loss: Hot Gas Bypass ValveRead
BI910Comm Loss: Dynamic Receiver Fill ValveRead
BI912Comm Loss: External Hot Water CommandRead
BI913Comm Loss: Supplemental Heater Relay 1Read
BI915Comm Loss: Supplemental Heater Relay 2Read
BI916Comm Loss: Supplemental Heater Relay 3Read
BI917Comm Loss: Supplemental Heater Relay 4Read
BI918Comm Loss: Liquid Line TemperatureRead
BI919Comm Loss: Liquid Line PressureRead
BI920Liquid Line Temp SensorRead
BI921Liquid Line Pressure TransducerRead
BI922Comm Loss: Liquid Line TemperatureRead
BI923Comm Loss: Liquid Line PressureRead
BI924Liquid Line Temp SensorRead
BI925Liquid Line Pressure TransducerRead
BI926Comm Loss: Shared V Coil Isolation ValveRead
BI927Comm Loss: Shared V Coil Isolation ValveRead
BI928Free Cooling Glycol Flow OverdueRead
BI929Comm Loss: Free Cooling Glycol Flow SwitchRead
BI930Comm Loss: Free Cooling Glycol PressureRead
BI931Free Cooling Glycol PressureRead
BI932Low Glycol Pressure Free CoolingRead
BI933Comm Loss: Free Cooling Glycol Pump FaultRead
BI934Free Cooling Glycol Pump FaultRead
BI935Free Cooling Glycol Flow LostRead
BI936SLHX Entering Temp Sensor - Ckt1Read
BI937Comm Loss: SLHX Valve - Ckt1Read
BI938Comm Loss: SLHX Entering Refrigerant Temp - Ckt1Read
BI939SLHX Entering Temp Sensor - Ckt2Read
BI940Comm Loss: SLHX Valve - Ckt2Read
BI941Comm Loss: SLHX Entering Refrigerant Temp - Ckt2Read
BI942Comm Loss: Sump Heater - Ckt1Read
BI943Comm Loss: Sump Heater - Ckt2Read
BV2Reset DiagnosticWrite0 = false (no reset), 1 = true (can reset)
BV3BAS Noise Reduction CommandWrite0 = Auto, 1 = On
BV4BAS Heat Recovery CommandWrite0 = Auto, 1 = On
BV5Clear Energy ConsumptionWrite0 = Normal, 1 = Reset
BV6BAS Circuit 1 LockoutWrite0 = false (not locked), 1 = true (locked)
BV7BAS Circuit 2 LockoutWrite0 = false (not locked), 1 = true (locked)
MI1Chiller Running StatusRead1 = not running, 2 = starting, 3 = running, 4 = stopping
MI2Operating ModeRead1 = cool, 2 = heat, 3 = ice, 4 = free cooling
MI3Front Panel Chiller ModeRead1 = cool, 2 = heat, 3 = ice, 4 = free cooling
MI4Setpoint SourceRead1 = BAS/Ext/ FP, 2 = Ext/FP, 3 = front panel
MI5Active Chilled Water Setpoint SourceRead1 = front panel, 2 = external, 3 = ice machine, 4 = BAS
MI6Active Demand Limit Setpoint SourceRead1 = front panel, 2 = external, 3 = ice machine, 4 = BAS
MI7External Auto StopRead1 = stop, 2 = auto
MI8Front Panel Auto/StopRead1 = stop, 2 = auto
MI9Active Hot Water Setpoint SourceRead1 = front panel, 2 = external, 3 = BAS
MI10Capacity Control Mode Status Ckt1Read1 = available, 3 = cooling, 4 = heating, 5 = defrost, 6 = not available
MI11Capacity Control Mode Status Ckt2Read1 = available, 3 = cooling, 4 = heating, 5 = defrost, 6 = not available
MVmin1BAS Chiller Auto Stop CommandWrite1 = stop, 2 = auto
MVmin2BAS Chiller Mode CommandWrite1 = cool, 2 = heat, 3 = ice
MV3BAS Free Cooling Auto Stop CommandWrite1 = stop, 2 = auto

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 ACSA (UC800) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 ACSA (UC800)

How many BACnet points does the Trane Symbio 800 ACSA (UC800) have?

This list has 342 BACnet objects: 58 analog inputs, 4 analog values, 260 binary inputs, 6 binary values, 11 multi-state inputs, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 ACSA (UC800) BACnet points are writable?

13 of the 342 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 ACSA (UC800) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - ACSA (UC800) (BAS-PTS026A-EN), revision 12/6/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS026A-EN_12062024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 ACSA (UC800)?

Start with MV 1 BAS Chiller Auto Stop Command (BMS auto/stop command (1 = Stop, 2 = Auto)); MV 2 BAS Chiller Mode Command (Cool/heat/ice mode command); AV 1 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 3 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 4 Chiller Running State (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 4 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 21 Actual Running Capacity (Actual running capacity in percent); BI 10 Alarm Present (Any active alarm on the chiller).

How do I enable BMS control of the Trane Symbio 800 ACSA (UC800)?

MV 1 BAS Chiller Auto Stop Command (1 = Stop, 2 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. MI 7 External Auto Stop reports the hardwired external auto/stop input, and BI 1 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 5 Active Chilled Water Setpoint Source shows front panel, external, ice machine or BAS.

Does the Trane Symbio 800 ACSA (UC800) need a BACnet heartbeat or have a communication timeout?

No timeout or heartbeat is described. The list includes the diagnostic flags BI 881 'BAS Communication Lost', BI 882 'BAS Failed to Establish Communication' and BI 600 'Comm Loss: Local BAS Interface'; the document doesn't say what timeout sets them or what the chiller does when they are set.

How do I check these points on the real Symbio 800 ACSA (UC800)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - ACSA (UC800) · BAS-PTS026A-EN · rev. 12/6/2024. Object names, instances and units are reproduced as published; descriptions are our own.