Self-contained unit controller · BACnet points list

Trane Symbio 500 Commercial Self-Contained (SWUD) BACnet points list

Updated 28 October 2026

Short answer

The Symbio 500 on commercial self-contained (SWUD) units exposes about 355 objects, including hardware AI/AO/BI/BO points. Writable setpoints are AVs and BVs with relinquish defaults, and the space temperature BAS value has a heartbeat. Points depend on the unit's control type (space or VAV), compressor and supply fan count, economizer and heat options.

This page lists 356 BACnet objects for the Trane Symbio 500 Commercial Self-Contained (SWUD) — 89 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 500 Commercial Self-Contained (SWUD)
Equipment
Self-contained unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
356 (89 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
V1.X
Also known as
Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038
Source document
Symbio 500 Integration Point List BACnet - Commercial Self-Contained (SWUD*) · BAS-PTS038B-EN · rev. 09/26/2025
Download CSV 356 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 500 Commercial Self-Contained (SWUD)

Integration in brief

In the Symbio UI (USB, http://198.80.18.1), use BAS Control Selection to set each sensor and setpoint to BAS or Local. Then schedule with MV 1 Occupancy Request, write the setpoint BAS AVs and use BV 329 Front Panel Auto Stop to run or stop the unit. MV 60/61/62 show whether each value is coming from the BAS, local or default.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Occupancy RequestOccupancy command from the BMS scheduleWrite
BV 329Front Panel Auto StopAuto/stop of the unit (relinquish default is Stop)Write
MV 3Heat Cool Mode RequestMode command from the BMSWrite
AV 7Space Temperature Setpoint BASSpace setpoint from the BMSWrite
AV 24Discharge Air Cooling Setpoint BASSupply air cooling setpoint from the BMSWrite
AV 91Duct Static Pressure Setpoint BASDuct static setpoint from the BMSWrite
MV 2Occupancy StatusConfirms the occupancy in effectRead
BV 360Supply Fan Calculated StatusAny supply fan runningRead
AI 11Discharge Air TemperatureSupply air temperatureRead
MV 189CSC Unit StatusOverall unit status: normal, off, warning, alarm, stopsRead

Enable & remote start

BAS vs Local is chosen per sensor and setpoint with the BAS Control Selection tool in the Symbio UI. BV 329 Front Panel Auto Stop (Auto/Stop, relinquish default Stop) and BI 10 External Auto Stop Input Status cover unit start/stop. The documents don't spell out how those two interact.

Heartbeat & communication loss

Among the BAS inputs only AV 73 Space Temperature BAS lists a heartbeat (900 s) in the points list (AV 901 and AV 903-906 list 1); the documents don't describe what happens on expiry. BV 11 'Diagnostic: Space Temperature Source Failure' is the related alarm flag.

Sensors & values from the BMS

Set the sensor to BAS in BAS Control Selection, then write AV 73 Space Temperature BAS, AV 75 Outdoor Air Temperature BAS, AV 79 Space Humidity BAS or AV 81 Outdoor Air Humidity BAS. MV 62 Space Temperature Source Status shows BAS/Local/Default, and the 'Source Failure' BVs (BV 11-14, BV 42) flag a lost source.

Network setup

Watch out for

Trane Symbio 500 Commercial Self-Contained (SWUD) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

356 of 356 shown
Type
Multi-state
Access
Show
Trane Symbio 500 Commercial Self-Contained (SWUD) BACnet Points List
DescriptionStates
AI1Space Temperature LocalSpace temperature value from a sensor wired to the controller°FRead
AI2Space Temperature Setpoint LocalSpace Temperature Setpoint value from a sensor wired to the controller°FRead
AImin11Discharge Air TemperatureDischarge air temperature value from a sensor wired to the controller°FRead
AI12Duct Static Pressure LocalDuct static pressure value from a sensor wired to the controllerin(H2O)Read
AI21Outdoor Air Temperature LocalOutdoor Air Temperature value from a sensor wired to the controller°FRead
AI22Outdoor Air Relative Humidity LocalOutdoor Air Humidity value from a sensor wired to the controller%Read
AI32Return Air Temperature LocalReturn temperature value from a sensor wired to the controller°FRead
AI33Return Air Humidity LocalReturn Air Humidity value from a sensor wired to the controller%Read
AI45Entering Air TemperatureEntering air temperature value from a sensor wired to the controller°FRead
AI46Condenser Water Entering TemperatureCondenser Water Entering Temperature from a connected wired sensor°FRead
AI47Condenser Water Leaving TemperatureCondenser Water Leaving Temperature value from a sensor wired to the controller°FRead
AI62Primary Filter Differential Pressure LocalPressure drop across the filter bankin(H2O)Read
AI250Discharge Gauge Pressure Circuit 1Compressor 1 discharge pressure value from a sensor wired to the controllerpsiRead
AI251Suction Gauge Pressure Circuit 1Compressor 1 suction pressurepsiRead
AI252Suction Temperature Circuit 1Compressor 1 suction temperature value from a sensor wired to the controller°FRead
AI255Discharge Gauge Pressure Circuit 2Compressor 2 discharge pressurepsiRead
AI256Suction Gauge Pressure Circuit 2Compressor 2 suction pressure value from a sensor wired to the controllerpsiRead
AI257Suction Temperature Circuit 2Compressor 2 suction temperature°FRead
AI280Refrigerant LFL Concentration Sensor CompressorConcentration level of refrigerant in the compressor section% LFLRead
AI281Refrigerant LFL Concentration Sensor EvaporatorConcentration level of refrigerant in the evaporator section% LFLRead
AO11Heating Output CommandHeating Output Command (%)%Read
AO20Outdoor Air Damper CommandUnit commanded outside air damper position%Read
AO81Condenser Water Regulating ValveCommand used (%) to control the condenser regulating valve command%Read
AO86Heating Output 1 CommandDemand requested for the electric modulating heat%Read
AO96Supply Fan 1 Speed CommandSpeed command (%) used to control Supply Fan 1%Read
AO97Supply Fan 2 Speed CommandSpeed command (%) used to control Supply Fan 2%Read
AO98Supply Fan 3 Speed CommandSpeed command (%) used to control Supply Fan 3%Read
AO99Supply Fan 4 Speed CommandSpeed command (%) used to control Supply Fan 4%Read
AO100Supply Fan 5 Speed CommandSpeed command (%) used to control Supply Fan 5%Read
AO101Supply Fan 6 Speed CommandSpeed command (%) used to control Supply Fan 6%Read
AO102Supply Fan 7 Speed CommandSpeed command (%) used to control Supply Fan 7%Read
AO105Water Side Economizer ValveCommand (%) used to control the waterside economizer control valve%Read
AV1Occupied Cooling SetpointDefine the occupied cooling setpoint°FRead
AV2Occupied Heating SetpointDefine the occupied heating setpoint°FRead
AV3Occupied OffsetDifference between the occupied cool and heat setpointsΔ °FWrite
AV4Occupied Standby OffsetDifference between the occupied standby cool and heat setpointsΔ °FWrite
AV5Unoccupied Cooling SetpointDefine the cooling temperature setpoint used for control in unoccupied mode°FWrite
AV6Unoccupied Heating SetpointDefine the heating temperature setpoint used for control in unoccupied mode°FWrite
AVmin7Space Temperature Setpoint BASBAS-supplied space temperature setpoint value°FWrite
AV8Space Temperature Setpoint ActiveActive space temperature setpoint being used by the controller°FRead
AV11Outdoor Air Damper PositionOA Damper Actuator feedback signal%Read
AV18Discharge Air Reset Setpoint Max BASValue used to limit the Discharge Air Setpoint maximum value°FWrite
AV21Discharge Air Temperature Setpoint ActiveDischarge air temperature setpoint actively being used for control°FRead
AV22Discharge Air Temperature Setpoint PgainProportional gain for Discharge fan speed on duct static pressure controlWrite
AVmin24Discharge Air Cooling Setpoint BASRequest the discharge air temperature cooling setpoint value°FWrite
AV25Discharge Air Heating Setpoint BASRequest the discharge air temperature heating setpoint value°FWrite
AV28Discharge Air Temperature Setpoint LocalCalculated setpoint to control the Discharge Air Tempeature°FRead
AV35Return Air Enthalpy ActiveThe return air enthalpy value being utilized by the unitBTU/lbRead
AV36Economizer Minimum Position Setpoint BASRequest the economizer minimum position setpoint%Write
AV38Economizer PgainProportional gain for Economizer PI controllerWrite
AV39Mixed Air Low Limit Setpoint BASMixed air temperature setpoint Low Limit°FWrite
AV41Outdoor Air Damper Safety PgainProportional gain for Outdoor Air Damper to prevent a freezestat tripWrite
AV47Economizer Outdoor Air Enable Setpoint BASTemperature setpoint below which economizing can be used°FWrite
AV48Economizer Outdoor Air Enthalpy Enable Setpoint BASDetermine the outdoor air enthalpy below which economizing is enabledBTU/lbWrite
AV49Outdoor Air Enthalpy BASOutdoor air enthalpy BAS valueBTU/lbWrite
AV50Outdoor Air Enthalpy ActiveThe outdoor air enthalpy value being utilized by the unitBTU/lbRead
AV52Cooling Capacity StatusActual operating unit cooling capacity, in percent%Read
AV61Heat Control PgainProportional gain for Heating PI controllerWrite
AV62Heating Capacity Primary StatusUnit (primary) heating capacity, in percent%Read
AV72Duct Static Pressure ActiveDuct static pressure active value from a sensor connected to the controllerin(H2O)Read
AV73Space Temperature BASSend the space temperature value°FWrite
AV74Space Temperature ActiveActive space temperature being used by the controller°FRead
AV75Outdoor Air Temperature BASSend the outdoor air temperature sensor value°FWrite
AV76Outdoor Air Temperature ActiveActive OA temperature currently being used by the controller°FRead
AV79Space Humidity BASSend the space relative humidity value%Write
AV80Space Humidity ActiveActive space relative humidity being used by the controller%Read
AV81Outdoor Air Humidity BASSend the outdoor air humidity sensor value%Write
AV82Outdoor Air Humidity ActiveActive outdoor air humidity value used by the controller%Read
AVmin91Duct Static Pressure Setpoint BASRequest the duct static pressure setpoint valuein(H2O)Write
AV92Duct Static Pressure Setpoint ActiveDuct static pressure control setpoint value resulting from arbitrationin(H2O)Read
AV101Supply Fan Speed PgainProportional gain for Supply Fan PI controllerWrite
AV104Supply Fan Minimum Speed BASMinimum Speed value used for Supply Fan Speed Control%Write
AV115Supply Fan Speed StatusEstimated supply fan speed being utilized%Read
AV118Space Temperature Setpoint DefaultDefault value of Space Temperature setpoint°FWrite
AV124Cooling Command RequestInternal value actual operating unit cooling capacity, in percentRead
AV125Cooling Setpoint High LimitValue used to limit cooling setpoint°FWrite
AV126Cooling Setpoint Low LimitValue used to limit cooling setpoint°FWrite
AV127Heating Setpoint High LimitValue used to limit heating setpoint°FWrite
AV128Heating Setpoint Low LimitValue used to limit heating setpoint°FWrite
AV133Active CoolCoil Control SensorActual sensor value used for Cooling Control°FRead
AV134Active CoolCoil Control SetpointActual setpoint value used for Cooling Control°FRead
AV135Active HeatCoil Control SensorActual sensor value used for Heating Control°FRead
AV136Active HeatCoil Control SetpointActual setpoint value used for Heating Control°FRead
AV139Cooling PID OutputCooling PI controller output signal used in equipment logic%Read
AV140Heating PID OutputHeating PI controller output signal used in equipment logic%Read
AV141Optional Outdoor Air Minimum Position%Read
AV142Damper Position RequestCalculated position request to be used for outdoor air damper control%Read
AV143Heat Command RequestCalculated command to be used for heating control%Read
AV145Heating PID Maximum ValueMaximum value limit used for PI controller output for heating control%Read
AV148Humidity Control SensorValue of sensor being used for humidity control%Read
AV149Cooling PID Maximum ValueMaximum value limit used for PI controller output for cooling control%Read
AV150Cooling Stages RequestedCalculated number of cooling stages required for cooling controlRead
AV154Economizer Minimum Position Setpoint ActiveEconomizer minimum position setpoint value resulting from arbitration%Read
AV173Compressor P GainProportional gain for Variable Speed Compressor PI controllerWrite
AV189Discharge Air High Temperature CutoutDischarge air temperature high limit safety setpoint°FWrite
AV190Discharge Air Low Temperature CutoutDischarge air temperature low limit safety setpoint°FWrite
AV191Maximum Discharge Air Heating SetpointMaximum value for discharge air temperature heating setpoint°FWrite
AV193Discharge Air Reset Setpoint Min BASMinimum value used for discharge air setpoint reset°FWrite
AV203Supply Fan Maximum Speed LocalMaximum local value of supply fan speed%Read
AV204Supply Fan Minimum Speed LocalMinimum local value of supply fan speed%Read
AV227Return Temperature Setpoint BASDefine the return temperature Setpoint°FWrite
AV281Supply Fan Maximum Speed BASBAS value for supply fan maximum speed%Write
AV314Run Time - Compressor 1 (Hours)Compressor 1 RuntimeRead
AV315Compressor 1 Sequence NumberRead
AV327Run Time - Compressor 2 (Hours)Compressor 2 RuntimeRead
AV328Compressor 2 Sequence NumberRead
AV341Run Time - Compressor 3 (Hours)Compressor 3 RuntimeRead
AV342Compressor 3 Sequence NumberRead
AV355Run Time - Compressor 4 (Hours)Compressor 4 RuntimeRead
AV356Compressor 4 Sequence NumberRead
AV360Compressor Interstage DelayTime in minutes between compressor stages to be added or subtractedWrite
AV361Compressors AvailableTotal number of compressors available to be used for mechanical coolingRead
AV362Frostat Cutout Temperature SetptLow limit safety cutout temperature setpoint°FWrite
AV363Condenser Control Percent of Design%Write
AV364Condenser Design Max PressureMaximum design pressure of the condenserpsiRead
AV365Condenser Purge Time(Min)Defines the condenser purge time (minutes)Write
AV366Condenser Control Pressure SetpointPressure Setpoint used to modulate condenser regulating valvespsiRead
AV368Condenser Tee Strainer Calculated Diff PressSoftware calculated differential pressure across the condenser strainerpsiRead
AV374Condenser Water Low Temperature Cutout°FWrite
AV375Condenser Valve Control P GainProportional gain for Condenser valve PI controllerWrite
AV378Duct Static Pressure Safety Lockout SetpointSoftware safety setpoint for High Static Pressure Cut outin(H2O)Write
AV382Water Side Econ Calculated Enable SetpointDefines the temperature setpoint to enable waterside economizer°FRead
AV383Water Side Econ Sample Time (Min)Defines the interval timeWrite
AV384Water Side Econ Valve Control P GainProportional gain for waterside economizer valve PI controllerWrite
AV385Water Side Economizer Enable OffsetDefines offset used to disable waterside economizerΔ °FWrite
AV386Supply Fan Wall Harmonic OffsetOffset used to skip supply fan speedsRead
AV399WSE Mech Cool Delay Time (Min)Delay time used to call for mechanical coolingWrite
AV493Economizer Outdoor Air Temperature DeadbandOutdoor air temperature deadband used for economizer decisionΔ °FWrite
AV494Economizer Outdoor Air Enthalpy DeadbandEnthalpy deadband used for economizer decisionBTU/lbWrite
AV559Discharge Air Setpoint MaximumDischarge air temperature maximum setpoint°FWrite
AV560Discharge Air Setpoint MinimumDischarge air temperature minimum setpoint°FWrite
AV765Cool TypeDescribes the type of cooling in the unitRead
AV768Reheat TypeIdentifies the product reheat typeRead
AV770Compressors RunningTotal number of compressors actively operating in the unitRead
AV774Primary Filter Differential Pressure Alarm Setpoint BASSetpoint value used to generate dirty filter alarmin(H2O)Write
AV850Differential Refrigerant Pressure Circuit 1Differential pressure between condenser discharge and suction pressures for Compressor 1psiRead
AV851Suction Saturated Refrigerant Temperature Circuit 1Condenser suction saturated refrigerant temperature for Compressor 1°FRead
AV852Superheat Temperature Circuit 1Superheat Temperature for Compressor 1°FRead
AV853Evaporator Approach Temperature Circuit 1Evaporator approach temperature for Compressor 1°FRead
AV854Frostat Trips Today Circuit 1Total number of froststat trips for Compressor 1Read
AV855Max Stages Allowed Circuit 1Maximum compressors allowed to run on the circuitRead
AV856Condenser Approach Temperature Circuit 1Condenser approach temperature for Compressor 1Δ °FRead
AV857Discharge Saturated Refrigerant Temperature Circuit 1Condenser Saturated Refrigerant Temperature for Compressor 1°FRead
AV861Differential Refrigerant Pressure Circuit 2Differential pressure between condenser discharge and suction pressures for Compressor 2psiRead
AV862Suction Saturated Refrigerant Temperature Circuit 2Condenser suction saturated refrigerant temperature for Compressor 2°FRead
AV863Superheat Temperature Circuit 2Superheat Temperature for Compressor 2°FRead
AV864Evaporator Approach Temperature Circuit 2Evaporator approach temperature for Compressor 2°FRead
AV865Frostat Trips Today Circuit 2Total number of froststat trips for Compressor 2Read
AV866Max Stages Allowed Circuit 2Maximum compressors allowed to run on the circuitRead
AV867Condenser Approach Temperature Circuit 2Condenser approach temperature for Compressor 2Δ °FRead
AV868Discharge Saturated Refrigerant Temperature Circuit 2Condenser Saturated Refrigerant Temperature for Compressor 1°FRead
AV894Testing Run Time (Min)Sets the test step time duration (minutes)Read
AV895Testing Time Remaining (Min)Read
AV896Refrigerant LFL Concentration Alarm ThresholdAlarm setpoint for the concentration of refrigerant% LFLRead
AV897Refrigerant LFL Concentration Warning ThresholdWarning setpoint for the concentration of refrigerant% LFLRead
AV898Condenser Design Leaving Water TemperatureDesign value used condenser leaving water temperature°FRead
AV899Condenser Design Entering Water TemperatureDesign value used condenser entering water temperature°FRead
AV900Condenser Water Design Delta TemperatureDesign value of condenser water delta temperatureΔ °FRead
AV901Evaporator Coil Delta TemperatureΔ °FRead
AV902Testing Mode Staging Time (sec)Write
AV903Condenser Water Min Valve SetpointFactroy set valuve for the minimum valve is allowed to close%Read
AV904Condenser Water Max Valve SetpointFactroy set valuve for the maximum valve is allowed to open%Read
AV905Condenser Min Valve Setpt LocalUser set valuve for the minimum valve is allowed to close%Write
AV906Condenser Water Min Valve Setpt ActiveThe Active setpoint used for how much the valve can close%Read
BI6Mixed Air Low Temperature Cutout AlarmSafety input for Low Limit Temperature cutoutReadfalse = Normal, true = Alarm
BI9Emergency Stop MSCEmergency Stop commandReadfalse = Stopped, true = Auto
BI10External Auto Stop Input StatusStatus of the externally-wired auto/stop inputReadfalse = Stop, true = Auto
BI29Occupancy InputStatus of the wired occupancy inputReadfalse = Occupied, true = Unoccupied
BI35Phase Monitor StatusStatus of local Phase Monitor InputReadfalse = Tripped, true = Okay
BI42Condenser Water Flow SwitchWater flow proof in the condenserReadfalse = No Flow, true = Flow
BI43Ventilation Relay StatusVentillation mode needs to runReadfalse = Inactive, true = Active
BI104Refrigerant Leak Detection System Input CompressorA2L sensor input in the condenser sectionReadfalse = Alarm, true = Normal
BI105Refrigerant Leak Detection System Input EvaporatorA2L sensor input in the evaporator sectionReadfalse = Alarm, true = Normal
BI106Safety Circuit Status Compressor 1Status of the safety circuit for Compressor 1Readfalse = Open, true = Closed
BI107Safety Circuit Status Compressor 2Status of the safety circuit for Compressor 2Readfalse = Open, true = Closed
BI108Safety Circuit Status Compressor 3Status of the safety circuit for Compressor 3Readfalse = Open, true = Closed
BI109Safety Circuit Status Compressor 4Status of the safety circuit for Compressor 4Readfalse = Open, true = Closed
BI130High Pressure Cutout Circuit 1Status of High Pressure cutout safety device for Circuit 1Readfalse = Alarm, true = Normal
BI131High Pressure Cutout Circuit 2Status of High Pressure cutout safety device for Circuit 2Readfalse = Alarm, true = Normal
BI137ECM Fault Supply Fan 1Fault status for Supply Fan 1Readfalse = Alarm, true = Normal
BI138ECM Fault Supply Fan 2Fault status for Supply Fan 2Readfalse = Alarm, true = Normal
BI139ECM Fault Supply Fan 3Fault status for Supply Fan 3Readfalse = Alarm, true = Normal
BI140ECM Fault Supply Fan 4Fault status for Supply Fan 4Readfalse = Alarm, true = Normal
BI141ECM Fault Supply Fan 5Fault status for Supply Fan 5Readfalse = Alarm, true = Normal
BI142ECM Fault Supply Fan 6Fault status for Supply Fan 6Readfalse = Alarm, true = Normal
BI143ECM Fault Supply Fan 7Fault status for Supply Fan 7Readfalse = Alarm, true = Normal
BO1Supply Fan Start Stop CommandFans 1-4 are being commanded onReadfalse = Off, true = On
BO11Compressor 1 CommandCompressor 1 Start/Stop CommandReadfalse = Normal, true = Estop Active
BO12Compressor 2 CommandCompressor 2 Start/Stop CommandReadfalse = Normal, true = Reset
BO13Compressor 3 CommandCompressor 3 Start/Stop CommandReadfalse = Off, true = On
BO14Compressor 4 CommandCompressor 4 Start/Stop CommandReadfalse = Off, true = On
BO21Heat Output 1Heat Output 1 Start/Stop CommandReadfalse = Off, true = On
BO22Heat Output 2Heat Output 2 Start/Stop CommandReadfalse = Off, true = On
BO23Heat Output 3Heat Output 3 Start/Stop CommandReadfalse = Off, true = On
BO44Refrigerant Mitigation PushUnit is in Refrigerant MitigationReadfalse = Normal, true = Alarm
BO101Supply Fan Start Stop Command 2Fans 5-7 are being commanded onReadfalse = Off, true = On
BO111Supply Fan Status OutputOutput indicating the Supply Fan has statusReadfalse = Off, true = On
BO125Cooling Tower Pump RequestOutput to request Cooling Tower Pump operationReadfalse = Off, true = On
BO126Unit Alarm Output CommandUnit level alarm outputReadfalse = Normal, true = Alarm Present
BV2Supply Fan Failure ResetReset Supply fan failureWritefalse = Normal, true = Reset
BV11Diagnostic: Space Temperature Source FailureReadfalse = Normal, true = In Alarm
BV12Diagnostic: Space Humidity Source FailureReadfalse = Normal, true = Fail
BV13Diagnostic: Outdoor Air Temperature Source FailureReadfalse = Normal, true = In Alarm
BV14Diagnostic: Outdoor Air Humidity Source FailureReadfalse = Normal, true = In Alarm
BV15Diagnostic: Duct Static Pressure FailureReadfalse = Normal, true = Fail
BV18Cooling Safeties OKThat cooling permissive safeties statusReadfalse = No, true = Yes
BV21Heat Cool Mode ActiveUnit active modeReadfalse = Heat, true = Cool
BV22Night Heat CoolStatus of Unoccupied Heat/Cool operationReadfalse = Off, true = On
BV29Compressor 1 Lockout BASLockout Compressor 1Writefalse = Available, true = Locked Out
BV30Compressor 2 Lockout BASLockout Compressor 2Writefalse = Available, true = Locked Out
BV31Compressor 3 Lockout BASLockout Compressor 3Writefalse = Available, true = Locked Out
BV32Compressor 4 Lockout BASLockout Compressor 4Writefalse = Available, true = Locked Out
BV35Circuit 2 Enable StatusCircuit 2 is enabledReadFalse = Disable, True = Enable
BV36Alarm ResetReset unit latching alarmsWritefalse = Normal, true = Reset
BV37Diagnostic: Auto ResetReadfalse = Normal, true = In Alarm
BV41Diagnostic: Discharge Air High Temperature LockoutReadfalse = Normal, true = In Alarm
BV42Diagnostic: Discharge Air Temperature Source FailureReadfalse = Normal, true = In Alarm
BV47Discharge Air Reset LockoutAllows the unit to do a Fixed or Reset Discharge Air ControlWritefalse = Reset Active, true = Reset Locked Out
BV52Mixed Air Low Limit ActiveMixed air low limit temperature safety is activeReadfalse = Off, true = On
BV62Fan LatchInternal point used to latch supply fan operationReadfalse = Off, true = On
BV63Startup Delay CompletedDelay startup is completed to allow cooling/heatingReadfalse = No, true = Yes
BV64Outdoor Air Damper at MaxOutdoor Air Damper is at maximum open positionReadfalse = No, true = Yes
BV65Fan Safeties OKFan safeties statusReadfalse = No, true = Yes
BV69Circuit 1 Enable StatusCircuit 1 is enabledReadFalse = Disable, True = Enable
BV70Diagnostic: Condenser Water Low Temperature LockoutReadfalse = Normal, true = In Alarm
BV75Economizer Interlock OKEconomizer is unable to keep up and needs mechanical coolingReadfalse = No, true = Yes
BV76Active CoolCoil Control Sensor FailedThe sensor used to control Cooling Coil has failedReadfalse = No, true = Yes
BV77Active HeatCoil Control Sensor FailedThe sensor used to control Heating Coil has failedReadfalse = No, true = Yes
BV78Optional Heat Enable CommandLock enable the heat in specific conditions determined by the controllerReadfalse = Off, true = On
BV79Optional Heat LockoutLock out the heat in specific conditions determined by the controllerReadfalse = Inactive, true = Locked Out
BV80Heating Lockout BASLockout HeatingWritefalse = Inactive, true = Locked Out
BV81Diagnostic: Humidity Control Sensor FailureReadfalse = Normal, true = Fail
BV108Diagnostic: Discharge Air Low Temperature LockoutReadfalse = Normal, true = In Alarm
BV182Economizer Include Outdoor Air Temp LimitWritefalse = No, true = Yes
BV184Supply Air Tempering StatusStatus of the Supply Air Tempering functionReadfalse = Inactive, true = Active
BV190Compressor 1 Calculated StatusCompressor 1 statusReadfalse = Off, true = On
BV191Compressor 1 CallCompressor 1 call from Test routineReadfalse = Stop, true = Run
BV196Compressor 1 Run Time ResetCompressor 1 Runtime ResetWritefalse = Normal, true = Reset
BV197Compressor 1 Safety LockoutStatus of safety lockout of Compressor 1Readfalse = Off, true = On
BV200Compressor 2 Calculated StatusCompressor 2 statusReadfalse = Off, true = On
BV201Compressor 2 CallCompressor 2 call from Test routineReadfalse = Stop, true = Run
BV206Compressor 2 Run Time ResetCompressor 2 Runtime ResetWritefalse = Normal, true = Reset
BV207Compressor 2 Safety LockoutStatus of safety lockout of Compressor 2Readfalse = Off, true = On
BV210Compressor 3 Calculated StatusCompressor 3 statusReadfalse = Off, true = On
BV211Compressor 3 CallCompressor 3 call from Test routineReadfalse = Stop, true = Run
BV216Compressor 3 Run Time ResetCompressor 3 Runtime ResetWritefalse = Normal, true = Reset
BV217Compressor 3 Safety LockoutStatus of safety lockout of Compressor 3Readfalse = Off, true = On
BV220Compressor 4 Calculated StatusCompressor 4 statusReadfalse = Off, true = On
BV221Compressor 4 CallCompressor 4 call from Test routineReadfalse = Stop, true = Run
BV226Compressor 4 Run Time ResetCompressor 4 Runtime ResetWritefalse = Normal, true = Reset
BV227Compressor 4 Safety LockoutStatus of safety lockout of Compressor 4Readfalse = Off, true = On
BV250Compressor Cond Valve InstalledCondenser Valves are installed or notWritefalse = Not Installed, true = Installed
BV251Condenser Water Flow TypeDefine type of Condenser water flow (Variable or Constant)Writefalse = Variable Flow, true = Constant Flow
BV255Water Side Economizer Lockout BASLockout Waterside EconomizerWritefalse = Available, true = Locked Out
BV257Water Side Econ Purge StatusWaterside Economizer Purge StatusWritefalse = Off, true = Active Purge
BV265Diagnostic: Compressor 1 Safety Circuit AlarmReadfalse = Normal, true = Failure
BV275Diagnostic: Compressor 2 Safety Circuit AlarmReadfalse = Normal, true = Failure
BV285Diagnostic: Compressor 3 Safety Circuit AlarmReadfalse = Normal, true = Failure
BV295Diagnostic: Compressor 4 Safety Circuit AlarmReadfalse = Normal, true = Failure
BV321Diagnostic: Software High Duct Static AlarmReadfalse = Normal, true = In Alarm
BV322Diagnostic: Condenser Water Flow LossReadfalse = Normal, true = Flow Loss
BV326Fixed Speed Compressor Rotate BASUser point to force rotate the compressor sequenceWritefalse = Normal, true = Rotate
BV327Fixed Speed Compressor Rotate Schedul= BAS/LocalWritefalse = Local, true = BAS
BVmin329Front Panel Auto StopWritefalse = Stop, true = Auto
BV330Supply Fan 1 Calculated StatusReadfalse = Off, true = Running
BV331Supply Fan 1 FailureSupply Fan 1 failure statusReadfalse = Normal, true = Failed
BV335Supply Fan 2 Calculated StatusReadfalse = Off, true = Running
BV336Supply Fan 2 FailureSupply Fan 2 failure statusReadfalse = Normal, true = Failed
BV340Supply Fan 3 Calculated StatusReadfalse = Off, true = Running
BV341Supply Fan 3 FailureSupply Fan 3 failure statusReadfalse = Normal, true = Failed
BV345Supply Fan 4 Calculated StatusReadfalse = Off, true = Running
BV346Supply Fan 4 FailureSupply Fan 4 failure statusReadfalse = Normal, true = Failed
BV350Supply Fan 5 Calculated StatusReadfalse = Off, true = Running
BV351Supply Fan 5 FailureSupply Fan 5 failure statusReadfalse = Normal, true = Failed
BV355Supply Fan 6 Calculated StatusReadfalse = Off, true = Running
BV356Supply Fan 6 FailureSupply Fan 6 failure statusReadfalse = Normal, true = Failed
BVmin360Supply Fan Calculated StatusAny Supply Fan is runningReadfalse = Off, true = Running
BV363Warning: High Condenser Water Delta TemperatureReadfalse = Normal, true = Warning Active
BV364Warning: High Condenser Water Entering TemperatureReadfalse = Normal, true = Warning Active
BV388Diagnostic Dirty Primary FilterResets the primary air filter alarmReadfalse = Normal, true = Dirty
BV556Refrigerant Mitigation ActiveActive when the Controller is in a mitigation state for any reasonReadfalse = Normal, true = Alarm
BV558Diagnostic: Refrigerant LVL Concentration Sensor CompressorThe A2L concentration sensor has failedReadfalse = Normal, true = Alarm
BV559Diagnostic: Refrigerant LVL Concentration Sensor EvaporatorThe A2L concentration sensor has failedReadfalse = Normal, true = Alarm
BV579Factory StartupWritefalse = Field Startup, true = Factory Startup
BV600Circuit 1 Failure ResetReset Circuit 1 latching failure alarmReadfalse = Off, true = On
BV601Circuit 2 Failure ResetReset Circuit 2 latching failure alarmReadfalse = Off, true = On
BV605Reset Dirty Air filterReset the dirty air filter alarmWritefalse = Off, true = Reset
BV606Circuit 1 Safety LockoutSafety lockout has occured on circuit 1Readfalse = Normal, true = Failure
BV607Circuit 2 Safety LockoutSafety lockout has occured on circuit 2Readfalse = Normal, true = Failure
BV610Diagnostic: Circuit 1 Discharge Pressure Sensor FailureDischarge pressure sensor has failed on circuit 1Readfalse = Normal, true = Alarm
BV611Diagnostic: Circuit 1 High Pressure ShutdownHigh pressure switch has opened on compressor 1Readfalse = Normal, true = In Alarm
BV612Diagnostic: Circuit 1 High SuperheatUnit has calculated a high superheat condition on compressor 1Readfalse = Normal, true = In Alarm
BV613Diagnostic: Circuit 1 Low SuperheatUnit has calculated a low superheat condition on compressor 1Readfalse = Normal, true = In Alarm
BV615Diagnostic: Circuit 1 Suction Pressure Sensor FailureSuction pressure sensor has failed on circuit 1Readfalse = Normal, true = In Failure
BV616Diagnostic: Circuit 1 Suction Temperature Sensor FailureSuction temperature sensor has failed on circuit 1Readfalse = Normal, true = In Failure
BV620Diagnostic: Circuit 2 Discharge Pressure Sensor FailureDischarge pressure sensor has failed on circuit 2Readfalse = Normal, true = Alarm
BV621Diagnostic: Circuit 2 High Pressure ShutdownHigh pressure switch has opened on compressor 2Readfalse = Normal, true = In Alarm
BV622Diagnostic: Circuit 2 High SuperheatUnit has calculated a high superheat condition on compressor 2Readfalse = Normal, true = In Alarm
BV623Diagnostic: Circuit 2 Low SuperheatUnit has calculated a low superheat condition on compressor 2Readfalse = Normal, true = In Alarm
BV625Diagnostic: Circuit 2 Suction Pressure Sensor FailureSuction pressure sensor has failed on circuit 2Readfalse = Normal, true = In Failure
BV626Diagnostic: Circuit 2 Suction Temperature Sensor FailureSuction temperature sensor has failed on circuit 2Readfalse = Normal, true = In Failure
BV650Warning Circuit 1 Cond Limit StatusCondenser pressure is reaching the warning setpoint for circuit 1Readfalse = Normal, true = Limited Capacity
BV652Warning: Circuit 1 Frostat WarningFrost condition exists on circuit 1Readfalse = Normal, true = Warning Active
BV656Warning: Circuit 2 Cond Limit StatusCondenser pressure is reaching the warning setpoint for circuit 2Readfalse = Normal, true = Limited Capacity
BV658Warning: Circuit 2 Frostat WarningFrost condition exists on circuit 2Readfalse = Normal, true = Warning Active
BV664Warning: Refrigerant LVL Lower Level Threshold ActiveRefrigerant concentration is at the warning levelReadfalse = Normal, true = Warning Active
BV665Compressor Condenser Valve OpenCompressor condenser valves open statusReadfalse = Closed, true = Open
BV666Compressor Condenser Purge StatusPurge status of the condenserWritefalse = Off, true = Active Purge
BV667Set Flow SwitchWritefalse = Off, true = On
BV690Supply Fan 7 Calculated StatusReadfalse = Off, true = Running
BV691Supply Fan 7 FailureSupply Fan 7 failure statusReadfalse = Normal, true = Failed
BV730CSC Heat PlacementRemote heat is installed in the unitReadfalse = Not Remote, true = Remote
MVmin1Occupancy RequestUsed by the BMS to command the unit into an occupancy modeWrite1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MVmin2Occupancy StatusActive occupancy mode of the controllerRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MVmin3Heat Cool Mode RequestCommand the unit into a heat/cool modeWrite1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Maximum Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MV4Heat Cool Mode StatusCurrent heat cool mode of the controllerRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Maximum Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MV8Emergency Override BASCommand the unit into an emergency mode of operationWrite1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV9Water Valve OverrideOverride the Hot water valveWrite1 = Off, 2 = Not Valid, 3 = CHW Open, 4 = HW Open, 5 = Open, 6 = Close
MV11Economizer Airside Enable BASEnable airside economizingWrite1 = Disabled, 2 = Enabled, 3 = Auto
MV14Economizer ModeIndicate the method of enabling airside economizingRead1 = Disabled, 2 = Fixed Dry Bulb, 3 = Differential Dry Bulb, 4 = Fixed Enthalpy, 5 = Differential Enthalpy, 6 = Fixed Dewpoint and Dry Bulb, 7 = BAS Control
MV15Economizer System StatusOperating state of the airside economizer systemRead1 = Disabled, 2 = Enabled, 3 = Not Present
MV36Heat Cool Mode Display StatusCurrent heat cool mode of the controllerRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Dehum-Heating, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Maximum Heat, 14 = Economizer, 15 = Dehumidify, 16 = Dehum-Cooling
MV42DX Staging StatusCurrent status of DX cooling staging algorithmRead1 = Normal, 2 = Start Interval Active, 3 = Shutdown Delay Active, 4 = Subtract Suspended
MV43Heat Staging StatusCurrent status of Heating staging algorithmRead1 = Normal, 2 = Start Interval Active, 3 = Shutdown Delay Active, 4 = Subtract Suspended
MV60Discharge Air Temperature Setpoint Source StatusSource of Discharge Air Temperature setpointRead1 = BAS Control, 2 = Local Control, 3 = BAS Default, 4 = Not Controlled, 5 = Space Comfort Not in Control
MV61Space Temperature Setpoint Source StatusSource of Space Temperature setpointRead1 = BAS, 2 = Local, 3 = Default, 4 = Not Controlled
MV62Space Temperature Source StatusSource of Space TemperaureRead1 = BAS, 2 = Local, 3 = Default, 4 = Not Controlled
MV70Compressor 1 ModeCompressor 1 current control modeRead1 = Off, 2 = Starting, 3 = Running, 4 = Diag: Safety Circuit Alarm, 5 = Diag: Low Superheat, 6 = Diag: Suction Press Sensor Failure, 7 = Diag: Suction Temp Sensor Failure, 8 = Diag: Frostat Aarm, 9 = Diag: Discharge Press Sensor Failure, 10 = Diag: High Pressure Cutout Alarm, 11 = VFD Fault/Comp Fault, 12 = Diag: High Superheat, 13 = Warn: Cond Limit Active, 14 = Comp Locked Out, 15 = Warn: Frostat Limit Active, 16 = Running Unloaded
MV71Compressor 2 ModeCompressor 2 current control modeRead1 = Off, 2 = Starting, 3 = Running, 4 = Diag: Safety Circuit Alarm, 5 = Diag: Low Superheat, 6 = Diag: Suction Press Sensor Failure, 7 = Diag: Suction Temp Sensor Failure, 8 = Diag: Frostat Aarm, 9 = Diag: Discharge Press Sensor Failure, 10 = Diag: High Pressure Cutout Alarm, 11 = VFD Fault/Comp Fault, 12 = Diag: High Superheat, 13 = Warn: High Disc Press, 14 = Comp Locked Out, 15 = Warn: Frostat Warning
MV72Compressor 3 ModeCompressor 3 current control modeRead1 = Off, 2 = Starting, 3 = Running, 4 = Diag: Safety Circuit Alarm, 5 = Diag: Low Superheat, 6 = Diag: Suction Press Sensor Failure, 7 = Diag: Suction Temp Sensor Failure, 8 = Diag: Frostat Aarm, 9 = Diag: Discharge Press Sensor Failure, 10 = Diag: High Pressure Cutout Alarm, 11 = VFD Fault/Comp Fault, 12 = Diag: High Superheat, 13 = Warn: High Disc Press, 14 = Comp Locked Out, 15 = Warn: Frostat Warning
MV73Compressor 4 ModeCompressor 4 current control modeRead1 = Off, 2 = Starting, 3 = Running, 4 = Diag: Safety Circuit Alarm, 5 = Diag: Low Superheat, 6 = Diag: Suction Press Sensor Failure, 7 = Diag: Suction Temp Sensor Failure, 8 = Diag: Frostat Aarm, 9 = Diag: Discharge Press Sensor Failure, 10 = Diag: High Pressure Cutout Alarm, 11 = VFD Fault/Comp Fault, 12 = Diag: High Superheat, 13 = Warn: High Disc Press, 14 = Comp Locked Out
MV79Mechanical Cooling Stages FailedTotal ammount of current compressors that have failedRead1 = 1 Comp Failed, 2 = 2 Comp Failed, 3 = 3 Comp Failed, 4 = 4 Comp Failed, 5 = None Failed
MV80Mechanical Cooling Stages ActiveTotal ammount of current compressors that are actively operatingRead1 = 0 Compressors, 2 = 1 Compressor, 3 = 2 Compressors, 4 = 3 Compressors, 5 = 4 Compressors
MV85Water Side Economizer Mode StatusStatus of water side economizerRead1 = Disabled, 2 = Sampling, 3 = Enabled, 4 = WSE and Mech, 5 = WSE Locked Out, 6 = Not Present
MV86Ventilation Override Input ModeRequested ventilation modeWrite1 = Inactive, 2 = Mode A Active, 3 = Mode B Active, 4 = Mode C Active, 5 = Mode D Active, 6 = Mode E Active
MV87Ventilation Override StatusStatus of ventilation override modeRead1 = Inactive, 2 = Mode A Active, 3 = Mode B Active, 4 = Mode C Active, 5 = Mode D Active, 6 = Mode E Active
MV89Supply Fans InstalledNumber of Supply Fans on the unitRead1 = 1 Fan, 2 = 2 Fans, 3 = 3 Fans, 4 = 4 Fans, 5 = 5 Fans, 6 = 6 Fans, 7 = 7 Fans, 8 = None
MV90Supply Fans FailedTotal ammount of current compressors that have failedRead1 = 1 Fan Failed, 2 = 2 Fans Failed, 3 = 3 Fans Failed, 4 = 4 Fans Failed, 5 = 5 Fans Failed, 6 = 6 Fans Failed, 7 = None Failed
MV100Unit InformationInternal unit information valueRead
MV170Supply Fan 1 ModeSupply Fan 1 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV171Supply Fan 2 ModeSupply Fan 2 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV172Supply Fan 3 ModeSupply Fan 3 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV173Supply Fan 4 ModeSupply Fan 4 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV174Supply Fan 5 ModeSupply Fan 5 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV175Supply Fan 6 ModeSupply Fan 6 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV176Supply Fan 7 ModeSupply Fan 6 current control modeRead1 = Off, 2 = Start, 3 = Run, 4 = Alarm
MV179Refrigerant TypeType of refrigerant in the unitWrite
MV180CSC Testing OverrideWrite1 = Test Inactive, 2 = Start Test, 3 = SF Cmd 1 On, 4 = SFCmd 2 On, 5 = Fan 1 On 30%, 6 = Fan 1 Off, 7 = Fan 2 On 30%, 8 = Fan 2 Off, 9 = Fan 3 On 30%, 10 = Fan 3 Off, 11 = Fan 4 On 30%, 12 = Fan 4 Off, 13 = Fan 5 On 30%, 14 = Fan 5 Off, 15 = Fan 6 On 30%, 16 = Fan 6 Off, 17 = Fan 7 On 30%, 18 = Fan 7 Off, 19 = All Fans On 25%, 20 = All Fans On 50%, 21 = All Fans Auto, 22 = Cooling Test Start, 23 = Heating Test Start, 24 = Economizer Test Start, 25 = Test Disable/Auto Release
MV181CSC Testing StatusRead1 = Test Inactive, 2 = Test Starting, 3 = Test Ready, 4 = Test Running, 5 = Fan Contactor 1 On, 6 = Fan Contactor 2 On, 7 = Fan 1 On 30%, 8 = Fan 1 Off, 9 = Fan 2 On 30%, 10 = Fan 2 Off, 11 = Fan 3 On 30%, 12 = Fan 3 Off, 13 = Fan 4 30%, 14 = Fan 4 Off, 15 = Fan 5 30%, 16 = Fan 5 Off, 17 = Fan 6 30%, 18 = Fan 6 Off, 19 = Fan 7 On 30%, 20 = Fan 7 Off, 21 = All fans 25%, 22 = All fans 50%, 23 = All Fan Auto, 24 = Cooling Test Active, 25 = Heating Test Active, 26 = Econ Test Active, 27 = Test Fail/Check Diag, 28 = Cool Test Fail/Check Diag, 29 = Heat Test Fail/Check Diag, 30 = Test Stoppped/No Fan Stat
MV182CSC Current Testing OverrideWrite1 = Test Inactive, 2 = Start Test, 3 = SF Cmd 1 On, 4 = SFCmd 2 On, 5 = Fan 1 On 30%, 6 = Fan 1 Off, 7 = Fan 2 On 30%, 8 = Fan 2 Off, 9 = Fan 3 On 30%, 10 = Fan 3 Off, 11 = Fan 4 On 30%, 12 = Fan 4 Off, 13 = Fan 5 On 30%, 14 = Fan 5 Off, 15 = Fan 6 On 30%, 16 = Fan 6 Off, 17 = Fan 7 On 30%, 18 = Fan 7 Off, 19 = All Fans On 25%, 20 = All Fans On 50%, 21 = All Fans Auto, 22 = Cooling Test Start, 23 = Heating Test Start, 24 = Test Disable/Auto Release
MV183CSC Cooling Test OverrideWrite1 = Test Inactive, 2 = All Comp Off, 3 = Comp 1 On, 4 = Comp 2 On, 5 = Comp 3 On, 6 = Comp 4 On, 7 = Test Complete/Auto Release
MV184CSC Cooling Test StatusRead1 = Test Inactive, 2 = Test Starting, 3 = Test Ready, 4 = Test Running, 5 = No Fan Status, 6 = Test Fail/Check Diag, 7 = Comp 1 Start, 8 = Comp 1 On, 9 = Comp 1 Fail, 10 = Comp 2 Start, 11 = Comp 2 On, 12 = Comp 2 Fail, 13 = Comp 3 Start, 14 = Comp 3 On, 15 = Comp 3 Fail, 16 = Comp 4 Start, 17 = Comp 4 On, 18 = Comp 4 Fail, 19 = Comp 5 Start, 20 = Comp 5 On, 21 = Comp 5 Fail, 22 = Comp 6A Start, 23 = Comp 6A On, 24 = Comp 6A Fail, 25 = Comp 6B Start, 26 = Comp 6B On, 27 = Comp 6B Fail, 28 = Circ 6 Start, 29 = Circ 6 On, 30 = Circ 6 Fai, 31 = Test Done/Auto Release
MV187CSC Economizer Test OverrideWrite1 = Test Inactive, 2 = Start Test, 3 = Open Economizer, 4 = Close Economizer, 5 = Test Complete/Auto Release
MV188CSC Economizer Test StatusRead1 = Test Inactive, 2 = Test Starting, 3 = Test Ready, 4 = Test Running, 5 = No Fan Status, 6 = Test Fail/Check Diag, 7 = Econ Open Cmd, 8 = Econ Calc Open, 9 = Econ Close Cmd, 10 = Econ Calc Closed, 11 = Test Done/Auto Release
MVmin189CSC Unit StatusOperationg status of the unitRead1 = Normal, 2 = Unit Off, 3 = Warning Present, 4 = Alarm Present, 5 = Exterior Stop, 6 = Local Stop, 7 = E-Stop, 8 = BAS Fire, 9 = BAS Shutdown
MV190CSC Unit Discharge Air Control StrategyDischarge air control strategy used by the unitRead1 = Test Inactive, 2 = Test Starting, 3 = Test Ready, 4 = Test Running, 5 = No Fan Status, 6 = Test Fail/Check Diag, 7 = Econ Open Cmd, 8 = Econ Calc Open, 9 = Econ Close Cmd, 10 = Econ Calc Closed, 11 = Test Done/Auto Release

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 500 Commercial Self-Contained (SWUD) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 500 Commercial Self-Contained (SWUD)

How many BACnet points does the Trane Symbio 500 Commercial Self-Contained (SWUD) have?

This list has 356 BACnet objects: 20 analog inputs, 12 analog outputs, 132 analog values, 22 binary inputs, 13 binary outputs, 113 binary values, 44 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 500 Commercial Self-Contained (SWUD) BACnet points are writable?

89 of the 356 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane Symbio 500 Commercial Self-Contained (SWUD) BACnet documentation?

The source is Symbio 500 Integration Point List BACnet - Commercial Self-Contained (SWUD*) (BAS-PTS038B-EN), revision 09/26/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS038B-EN_09262025.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 500 Commercial Self-Contained (SWUD)?

Start with MV 1 Occupancy Request (Occupancy command from the BMS schedule); BV 329 Front Panel Auto Stop (Auto/stop of the unit (relinquish default is Stop)); MV 3 Heat Cool Mode Request (Mode command from the BMS); AV 7 Space Temperature Setpoint BAS (Space setpoint from the BMS); AV 24 Discharge Air Cooling Setpoint BAS (Supply air cooling setpoint from the BMS); AV 91 Duct Static Pressure Setpoint BAS (Duct static setpoint from the BMS); MV 2 Occupancy Status (Confirms the occupancy in effect); BV 360 Supply Fan Calculated Status (Any supply fan running); AI 11 Discharge Air Temperature (Supply air temperature); MV 189 CSC Unit Status (Overall unit status: normal, off, warning, alarm, stops).

How do I enable BMS control of the Trane Symbio 500 Commercial Self-Contained (SWUD)?

BAS vs Local is chosen per sensor and setpoint with the BAS Control Selection tool in the Symbio UI. BV 329 Front Panel Auto Stop (Auto/Stop, relinquish default Stop) and BI 10 External Auto Stop Input Status cover unit start/stop. The documents don't spell out how those two interact.

Does the Trane Symbio 500 Commercial Self-Contained (SWUD) need a BACnet heartbeat or have a communication timeout?

Among the BAS inputs only AV 73 Space Temperature BAS lists a heartbeat (900 s) in the points list (AV 901 and AV 903-906 list 1); the documents don't describe what happens on expiry. BV 11 'Diagnostic: Space Temperature Source Failure' is the related alarm flag.

Can the BMS supply sensor values to the Trane Symbio 500 Commercial Self-Contained (SWUD)?

Set the sensor to BAS in BAS Control Selection, then write AV 73 Space Temperature BAS, AV 75 Outdoor Air Temperature BAS, AV 79 Space Humidity BAS or AV 81 Outdoor Air Humidity BAS. MV 62 Space Temperature Source Status shows BAS/Local/Default, and the 'Source Failure' BVs (BV 11-14, BV 42) flag a lost source.

How do I check these points on the real Symbio 500 Commercial Self-Contained (SWUD)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 500 Integration Point List BACnet - Commercial Self-Contained (SWUD*) · BAS-PTS038B-EN · rev. 09/26/2025. Object names, instances and units are reproduced as published; descriptions are our own.