Rooftop unit communication interface (ReliaTel) · BACnet points list

Trane BCI2-R (ReliaTel) BACnet points list

Updated 28 October 2026

Short answer

The BCI2-R is a BACnet MS/TP card for ReliaTel rooftop units. It talks Modbus to the unit's RTRM board and builds its BACnet object list from what the RTRM reports at first power-up, so only the objects for the installed option modules (RTEM, RTAM, RTDM, RTOM, RTVM...) appear. Objects use short instances (AI 1, AO 2, BO 1...). The BAS writes AO/BO/MO output objects and reads AI/BI/MI status and diagnostics.

This page lists 250 BACnet objects for the Trane BCI2-R (ReliaTel) — 53 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
BCI2-R (ReliaTel)
Equipment
Rooftop unit communication interface (ReliaTel)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
250 (53 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey
Source document
Integration Guide: BACnet Communication Interface for ReliaTel Controllers (BCI2-R) · BAS-SVP053A-EN · rev. April 2022
Download CSV 250 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane BCI2-R (ReliaTel)

Integration in brief

Set BO 1 System Control Command to Active (Trane also recommends setting its relinquish default to Active). Then put each output object the BMS will drive in service with the BCI2 Service Tool or Tracer TU. Schedule the unit with MO 7 Occupancy Request, set the mode with MO 8 and the space setpoint with AO 2. BAS sensor values must be rewritten within 900 s.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1System Control CommandActive = BAS control; Inactive = standalone, monitor onlyCommand
MO 7Occupancy RequestOccupancy command (1 = Occupied, 2 = Unoccupied)Command
MO 8Heat Cool Mode Request BASHeat/cool mode command (1 = Auto)Command
AO 2Space Temperature Setpoint BASSpace setpoint; occupied/standby offsets apply to itCommand
BI 1System Control StatusConfirms the unit is under BAS controlRead
MI 20Occupancy StatusConfirms the occupancy the unit is running inRead
MI 19Heat Cool Mode Status/ Application Mode StatusCurrent heat/cool operating modeRead
MI 41Supply Fan StatusSupply fan on/off (2 = On)Read
AI 15Space Temperature ActiveSpace temperature the unit is controlling toRead
BI 165Alarm Relay Output StatusUnit alarm relay; Active = energizedRead

Enable & remote start

BO 1 System Control Command must be in service and Active (BAS Control); while Inactive the unit runs standalone and the BMS can only monitor. BI 1 System Control Status shows which is in charge. Most output objects ship with Out_of_Service = True, so the unit uses its local value; set Out_of_Service to False (BCI2 Service Tool Points screens or Tracer TU) on each output the BMS will write.

Heartbeat & communication loss

The BAS sensor outputs with a 900 s refresh rate (AO 10, 11, 14, 15, 18, 25) must be rewritten within that time. If not, the BCI2-R puts the object in fault and the unit falls back to its own sensor. At power-up these objects start in fault until the first write. Setpoint and command outputs have no refresh limit.

Sensors & values from the BMS

Write BMS sensor values to the '... BAS' AOs (AO 11 Space Temperature BAS, AO 14 Outdoor Air Temperature BAS, AO 15 Outdoor Air Humidity BAS, AO 18 Space CO2 Concentration BAS, AO 25 Space Humidity BAS, AO 10 Space Static Pressure BAS) with the object in service, and keep refreshing them. The matching '... Active' AIs show the value in use.

Network setup

Watch out for

Trane BCI2-R (ReliaTel) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

250 of 250 shown
Type
Access
Show
Trane BCI2-R (ReliaTel) BACnet Points List
DescriptionStates
AI1Cooling Capacity StatusUnit cooling capacity being utilized%Read
AI2Heat Primary Capacity StatusUnit primary heating capacity being utilized (with modulating heat)%Read
AI3Heat Secondary Capacity StatusUnit secondary heating capacity being utilized (with RTDM installed)%Read
AI5Reheat Capacity StatusUnit reheat heating capacity being utilized (with RTDM installed)%Read
AI6Filter Runtime HoursNumber of hours air has flowed through the filterhRead
AI7Supply Fan Speed CommandUnit commanded supply fan speed%Read
AI8Exhaust Fan Speed CommandUnit commanded exhaust fan speed (with RTEM installed)%Read
AI9Exhaust Damper Position StatusUnit exhaust damper position%Read
AI11Outdoor Air Damper Position StatusUnit outdoor air damper position%Read
AImin15Space Temperature ActiveThe space temperature currently used for unit control°F / °CRead
AI16Space Humidity ActiveThe space humidity value from a unit-mounted control (with RTOM installed)%RHRead
AI18Outdoor Air Temperature ActiveThe outdoor air temperature currently used for unit control (with RTEM installed)°F / °CRead
AI20Outdoor Air Humidity ActiveThe outdoor air humidity value used for unit control (with RTEM installed)%RHRead
AI24Discharge Air Temperature ActiveThe discharge air temperature currently used for unit control (with RTOM installed)°F / °CRead
AI25Mixed Air TemperatureThe mixed air temperature value from a unit-mounted sensor°F / °CRead
AI26Return Air TemperatureThe return air temperature value from a unit-mounted sensor (with RTEM installed)°F / °CRead
AI28Duct Static Pressure ActiveDuct static air pressure value currently being used for unit control (with RTAM installed)inH2O / PaRead
AI31Space Static Air Pressure ActiveSpace static air pressure value being used for unit controlinH2O / PaRead
AI32Space CO2 Concentration ActiveSpace CO2 concentration being used for unit control (with RTEM installed)ppmRead
AI34Outdoor Air Flow ActiveOutdoor airflow utilized by the unitcfm / l/sRead
AI48Duct Static Pressure Setpoint ActiveDuct static pressure setpoint value being used for unit controlinH2O / PaRead
AI50Space Temperature Setpoint ActiveSpace temperature setpoint value being used for unit control°F / °CRead
AI52Discharge Air Temperature Setpoint ActiveDischarge air temperature setpoint value being used for unit control°F / °CRead
AI54Morning Warmup Temperature Setpoint ActiveThe air temperature setpoint used during morning warmup mode (when RTAM installed and heat installed)°F / °CRead
AI57Outdoor Air Minimum Flow Setpoint ActiveThe minimum outdoor airflow setpoint being utilized by the unitcfm / l/sRead
AI58Dehumidification High Limit SetpointHumidity setpoint value that starts dehumidification control (with RTDM installed)%Read
AI61Discharge Air Reheat Setpoint ActiveActive supply air reheat temperature setpoint (with RTDM installed)°F / °CRead
AI71Exhaust Enable Damper Position Setpoint StatusExhaust air damper minimum position to enable exhaust sequence (with RTEM installed)%Read
AI74Space Temperature Cooling Setpoint InputCooling temperature setpoint from space sensor module°F / °CRead
AI75Space Temperature Heating Setpoint InputHeating temperature setpoint from space sensor module°F / °CRead
AI78Space Temperature Setpoint LocalSetpoint derived locally by the RTRM°F / °CRead
AI79Dehumidification Capacity StatusUnit dehumidification capacity being utilized (with RTDM installed)%Read
AI80Cabinet StyleDifferent cabinet typesRead6 = Voyager/Precedent/Odyssey, 22 = Voyager Commercial
AI81Cool TypeDifferent cooling typesRead7 = 1-Stage DX, 8 = 2-Stage DX, 9 = 3-Stage DX
AI82Preheat TypeDifferent heating typesRead129 = None, 19 = 1-Stage DX, 20 = 2-Stage DX, 130 = Modulating Hot Water, 134 = Modulating Electric, 135 = 1-Stage Electric, 136 = 2-Stage Electric, 140 = 1-Stage Gas, 141 = 2-Stage Gas, 142 = Modulating Gas
AI83Reheat TypeDifferent reheat typesRead129 = None, 17 = Hot Gas, 19 = 1-Stage DX, 20 = 2-Stage DX, 130 = Modulating Hot Water, 134 = Modulating Electric, 135 = 1-Stage Electric, 136 = 2-Stage Electric, 140 = 1-Stage Gas, 141 = 2-Stage Gas, 142 = Modulating Gas
AI86Economizer Minimum Position Setpoint LocalLocal economizer minimum position setpoint (with RTEM installed)%Read
AI87Space Temperature LocalThe space air temperature measured by a unit-mounted sensor°F / °CRead
AI88Unit Energy DemandCurrent heat/cool energy demand of the unit%Read
AI89Supply Fan TypeDifferent supply fan typesRead2 = 1-Speed Supply Fan, 3 = 2-Speed Supply Fan, 4 = 3-Speed Supply Fan, 7 = 4-Speed Supply Fan, 8 = 5-Speed Supply Fan, 5 = Modulating Inlet Guide Vanes Supply Fan, 6 = Variable Speed Supply Fan, 35 = SZVAV 2-Speed Supply Fan, 36 = SZVAV 3-Speed Supply Fan, 39 = SZVAV 4-Speed Supply Fan, 40 = SZVAV 5-Speed Supply Fan, 38 = SZVAV Variable Speed Supply Fan
AI90Exhaust or Return Fan TypeDifferent exhaust or return fan typesRead1 = None, 2 = 1-Speed Exhaust Fan, 7 = 1-Speed Exhaust Fan with Modulating Exhaust Damper
AI91RTRM Major VersionMajor software version number of the RTRM moduleRead
AI92RTRM Minor VersionMinor software version number of the RTRM moduleRead
AI93RTOM Major VersionMajor software version number of the RTOM module (with RTOM installed)Read
AI94RTOM Minor VersionMinor software version number of the RTOM module (with RTOM installed)Read
AI95BCI2-R Major VersionMajor software version number of the BCI2-R moduleRead
AI96BCI2-R Minor VersionMinor software version number of the BCI2-R moduleRead
AI97RTAM Major VersionMajor software version number of the RTAM module (with RTAM installed)Read
AI98RTAM Minor VersionMinor software version number of the RTAM module (with RTAM installed)Read
AI99RTEM Major VersionMajor software version number of the RTEM module (with RTEM installed)Read
AI100RTEM Minor VersionMinor software version number of the RTEM module (with RTEM installed)Read
AI101RTDM Major VersionMajor software version number of the RTDM moduleRead
AI102RTDM Minor VersionMinor software version number of the RTDM moduleRead
AI103RTVM Major VersionMajor software version number of the RTVM moduleRead
AI104RTVM Minor VersionMinor software version number of the RTVM moduleRead
AI105VSM Major VersionMajor Software version number of the VSM moduleRead
AI106VSM Minor VersionMinor software version number of the VSM moduleRead
AI107Space Static Pressure Setpoint ActiveSpace pressure setpoint currently used for unit controlinH2ORead
AI108Tracer TD5 Major VersionMajor Software version number of the TD5 moduleRead
AI109Tracer TD5 Minor VersionMinor Software version number of the TD5 moduleRead
AO1Economizer Minimum Position Setpoint BASEconomizer minimum position; range 0 to 50 % (with RTEM installed)%Command
AOmin2Space Temperature Setpoint BASBase space setpoint (occupied/standby); range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO4Morning Warmup Setpoint BASMorning warmup setpoint; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO5Daytime Warmup Terminate Temperature Setpoint BASDaytime warmup end temperature; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO6Discharge Air Cooling Setpoint BASDischarge air cooling setpoint; range 40.0 to 80.0 °F (4.4 to 26.7 °C)°F / °CCommand
AO7Discharge Air Heating Setpoint BASDischarge air heating setpoint; range 50.0 to 158.0 °F (10.0 to 70.0 °C)°F / °CCommand
AO8Duct Static Pressure Setpoint BASDuct static setpoint; range 0.0 to 2.5 inH2O (with RTAM installed)inH2O / PaCommand
AO9Space Static Pressure Setpoint BASSpace static setpoint; range 0.3 to -0.2 inH2OinH2O / PaCommand
AO10Space Static Pressure BASSpace static pressure from BAS; range -0.67 to 0.67 inH2O; rewrite within 900 sinH2O / PaCommand
AO11Space Temperature BASSpace temperature; range -40.0 to 150.0 °F (-40.0 to 65.6 °C); rewrite within 900 s°F / °CCommand
AO14Outdoor Air Temperature BASOutdoor air; range -40.0 to 158.0 °F (-40.0 to 70.0 °C); rewrite within 900 s°F / °CCommand
AO15Outdoor Air Humidity BASOutdoor humidity from BAS; range 0 to 100 %; rewrite within 900 s%Command
AO16Outdoor Air Minimum Flow Setpoint BASMinimum outdoor airflow setpoint; range 0 to 40,000 cfmcfm / l/sCommand
AO18Space CO2 Concentration BASSpace CO2 from BAS; range 0.0 to 2000 ppm; rewrite within 900 sppmCommand
AO19Cool Capacity Enable Setpoint BASCooling capacity limit; range 0 to 100 %%Command
AO20Heat Capacity Enable Setpoint BASHeating capacity limit; range 0 to 100 % (with all heat types)%Command
AO21Space Dehumidification Setpoint BASSpace dehumidification setpoint; range 40 to 65 % (with RTDM installed)%Command
AO23Discharge Air Reheat Setpoint BASDischarge air reheat setpoint; range 65.0 to 80.0 °F (18.3 to 26.7 °C) (with RTDM installed)°F / °CCommand
AO25Space Humidity BASSpace humidity from BAS; range 10 to 100 %; rewrite within 900 s (with RTDM installed)%Command
AO29Occupied OffsetOccupied setpoint offset; range 1.0 to 5.0 °F (0.6 to 2.8 °C)°F / °CCommand
AO30Standby OffsetStandby setpoint offset; range 1.0 to 10.0 °F (0.06 to 5.6 °C)°F / °CCommand
AO31Unoccupied Cooling SetpointUnoccupied cooling setpoint; range 50 to 90 °F (10.0 to 32.2 °C)°F / °CCommand
AO32Unoccupied Heating SetpointUnoccupied heating setpoint; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO33Exhaust or Return Fan ConfigurationExhaust/return fan type setting; range 1.0 to 255Command
AO34Power Exhaust Enable Setpoint BASPower exhaust enable point; range 0.0 to 100 % (with RTEM installed)%Command
AO35Space Cooling Setpoint High Limit BASUpper clamp on space cooling setpoint; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO36Space Cooling Setpoint Low Limit BASLower clamp on space cooling setpoint; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO37Space Heating Setpoint High Limit BASUpper clamp on space heating setpoint; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO38Space Heating Setpoint Low Limit BASLower clamp on space heating setpoint; range 50.0 to 90.0 °F (10.0 to 32.2 °C)°F / °CCommand
AO41Economizing Temperature Enable SetpointEconomizer dry-bulb enable setpoint; range 50.0 to 140.0 °F (10.0 to 60.0 °C) (with RTEM installed)°F / °CCommand
AO42Economizing Enthalpy Enable SetpointEconomizer enthalpy enable setpoint; range 19.0 to 28.0 Btu/lb (with RTEM installed)Btu/lbCommand
AO43Daytime Warmup Initiate Temperature Setpoint BASDaytime warmup start temperature; range 50.0 to 87.0 °F (rTAM is present and heat is present)°FCommand
AO44Supply Fan Minimum Speed BASSupply fan minimum speed; range 0.0 to 100.0 % (supply fan is not single speed)%Command
AO45Supply Fan Maximum Speed BASSupply fan maximum speed; range 0.0 to 100.0 % (supply fan is not single speed)%Command
AO46Outdoor Air Temperature Heating Lockout Low LimitHeat pump mechanical heat OA lockout; range 0.0 to 45.0 °F (configured as a Heat Pump)°FCommand
AV1Filter Runtime Hours SetpointThe setpoint value used by the filter run hours calculation; range 0-10,000hCommand
BImin1System Control StatusControl system currently in command of the unitReadInactive = Standalone control, Active = BAS control
BI2Compressor Lockout StatusOne or more compressors are locked out with no diagnosticReadInactive = Normal, Active = Locked Out
BI9VAV Box CommandWhether VAV boxes should be in control or wide open (multi-zone VAV and RTAM installed)ReadInactive = Auto, Active = Open
BI11Service Test Mode StatusIf the unit is in service test modeReadInactive = Inactive, Active = Active
BI15Supply Fan Configuration StatusSupply fan configuration (constant volume)ReadInactive = Cycling, Active = Continuous
BI22Economizer Airside Enable StatusStatus of the airside economizer system (with RTEM Installed)ReadInactive = Disabled, Active = Enabled
BI29Diagnostic: Zone Temperature Sensor FailureDiagnostic, class 002 Service RequiredRead
BI30Diagnostic: Supply Air Temp Sensor FailDiagnostic, class 002 Service RequiredRead
BI32Diagnostic: Outdoor Air Temperature Sensor FailDiagnostic, class 002 Service RequiredRead
BI34Diagnostic: Local Cool Setpoint FailDiagnostic, class 002 Service RequiredRead
BI35Diagnostic: Local Zone Heat Setpoint FailDiagnostic, class 002 Service RequiredRead
BI36Diagnostic: SA Pressure Sensor FailDiagnostic, class 002 Service RequiredRead
BI37Diagnostic: Outdoor Humidity Sensor FailureDiagnostic, class 002 Service Required (with RTEM installed)Read
BI38Diagnostic: Local Emergency Stop InitiatedDiagnostic, class 001 CriticalRead
BI39Diagnostic: Fan FailureDiagnostic, class 001 Critical (with RTEM installed)Read
BI40Diagnostic: Exhaust Fan Proving FailureDiagnostic, class 001 Critical (with RTEM installed)Read
BI43Diagnostic: Compressor 1 LPC LockoutDiagnostic, class 001 CriticalRead
BI44Diagnostic: Compressor 2 LPC LockoutDiagnostic, class 001 CriticalRead
BI45Diagnostic: Coil Temp Sensor #1 FailDiagnostic, class 002 Service RequiredRead
BI46Diagnostic: Coil Temp Sensor #2 FailDiagnostic, class 002 Service RequiredRead
BI47Diagnostic: Compressor 1 HPC LockoutDiagnostic, class 001 CriticalRead
BI48Diagnostic: Compressor 2 HPC LockoutDiagnostic, class 001 CriticalRead
BI51Diagnostic: Heat FailureDiagnostic, class 003 AdvisoryRead
BI54Diagnostic: SA Pressure Setpoint FailureDiagnostic, class 002 Service RequiredRead
BI55Diagnostic: Space Pressure Setpoint FailDiagnostic, class 002 Service RequiredRead
BI56Diagnostic: Space Pressure Sensor FailDiagnostic, class 002 Service RequiredRead
BI57Diagnostic: Return Air Temp Sensor FailDiagnostic, class 002 Service Required (with RTEM installed)Read
BI58Diagnostic: Return Air Humidity Sensor FailDiagnostic, class 002 Service Required (with RTEM installed)Read
BI59Diagnostic: Auto - SA High Press LimitDiagnostic, class 002 Service RequiredRead
BI74Diagnostic: SA Temp Cool Setpoint FailDiagnostic, class 002 Service RequiredRead
BI75Diagnostic: SA Temp Heat Setpoint FailDiagnostic, class 002 Service RequiredRead
BI76Diagnostic: Dirty FilterDiagnostic, class 003 AdvisoryRead
BI83Diagnostic: CO2 Sensor FailureDiagnostic, class 002 Service Required (with RTEM installed)Read
BI86Diagnostic: Velocity Press Sensor FailDiagnostic, class 002 Service Required (with RTVM version 3 or greater installed)Read
BI95Diagnostic: Mixed Air Temp Sensor FailureDiagnostic, class 002 Service Required (with RTEM installed)Read
BI106Diagnostic: Space Humidity Sensor FailDiagnostic, class 002 Service Required (with RTEM installed)Read
BI107Diagnostic: Entering Evap Temp Sensor FailDiagnostic, class 002 Service RequiredRead
BI123Diagnostic: SA Reheat Setpoint FailureDiagnostic, class 002 Service RequiredRead
BI125Diagnostic: Dehumid Setpoint FailureDiagnostic, class 002 Service Required (with RTOM installed)Read
BI147Diagnostic: Maintenance RequiredDiagnostic, class 002 Service RequiredRead
BI148Diagnostic: Unit Communications FailureDiagnostic, class 002 Service RequiredRead
BI151Diagnostic: Drain Pan OverflowDiagnostic, class 004 Information (with RTOM installed)Read
BImin165Alarm Relay Output StatusState of the alarm relay on the unitReadInactive = De-energized, Active = Energized
BI239Diagnostic: Morning Warmup Setpoint FailDiagnostic, class 002 Service RequiredRead
BI242Diagnostic: Min OA Flow Setpoint FailDiagnostic, class 002 Service Required (with RTVM installed)Read
BI244Diagnostic: Comp 1 Disable Input LPCDiagnostic, class 004 InformationRead
BI245Diagnostic: Comp 2 Disable Input LPCDiagnostic, class 004 InformationRead
BI246Diagnostic: Smoke DetectorDiagnostic, class 004 Information (with RTOM installed)Read
BI247Diagnostic: FroStat TripDiagnostic, class 004 Information (with RTOM installed)Read
BI248Diagnostic: Demand Defrost Fault ADiagnostic, class 004 Information (with Heat Pump installed)Read
BI249Diagnostic: Demand Defrost Fault BDiagnostic, class 004 Information (with Heat Pump installed)Read
BI250Diagnostic: Demand Defrost Fault CDiagnostic, class 004 Information (with Heat Pump installed)Read
BI251Diagnostic: Demand Defrost Fault DDiagnostic, class 004 Information (with Heat Pump installed)Read
BI252Diagnostic: Default Defrost FlagDiagnostic, class 004 Information (with Heat Pump installed)Read
BI253Diagnostic: Vent Override - ExhaustDiagnostic, class 004 Information (with RTOM installed)Read
BI254Diagnostic: Vent Override - PurgeDiagnostic, class 004 Information (with RTOM installed)Read
BI255Diagnostic: Vent Override - PressurizeDiagnostic, class 004 Information (with RTOM installed)Read
BI256Diagnostic: Freezestat TrippedDiagnostic, class 004 Information (with RTOM installed)Read
BI257Diagnostic: CO2 Setpoint FailureDiagnostic, class 004 Information (with RTEM installed)Read
BI258Diagnostic: Heating High Temp Limit OpenDiagnostic, class 004 Information (with Gas Heat installed)Read
BI259Diagnostic: Flame Rollout Switch OpenDiagnostic, class 004 Information (with Gas Heat installed)Read
BI260Diagnostic: Inducer Proving Switch FailDiagnostic, class 004 Information (with Gas Heat installed)Read
BI261Diagnostic: No Flame Sensed on heat callDiagnostic, class 004 Information (with Gas Heat installed)Read
BI262Diagnostic: Flame Sensed with Gas Valve OffDiagnostic, class 004 Information (with Gas Heat installed)Read
BI263Diagnostic: Gas Heat Module FailureDiagnostic, class 004 InformationRead
BI264Diagnostic: Economizer Actuator FaultDiagnostic, class 004 InformationRead
BI265Diagnostic: SA Reset Amount FailureDiagnostic, class 004 Information (with RTOM installed)Read
BI266Diagnostic: SA Reset Setpoint FailureDiagnostic, class 004 Information (with RTAM installed)Read
BI267Diagnostic: SA Pressure Dead Band FailureDiagnostic, class 004 Information (with RTAM installed)Read
BI268Diagnostic: SA Pressure PWM FaultDiagnostic, class 004 Information (with RTAM installed)Read
BI269Diagnostic: Comp 1 Disable Input HPCDiagnostic, class 004 InformationRead
BI270Diagnostic: Comp 2 Disable Input HPCDiagnostic, class 004 InformationRead
BI271Diagnostic: CO2 Low Limit Setpoint FaultDiagnostic, class 004 Information (with RTEM installed)Read
BI272Diagnostic: RTOM Comm FailDiagnostic, class 004 Information (with RTOM installed)Read
BI273Diagnostic: RTEM Comm FailDiagnostic, class 004 Information (with RTEM installed)Read
BI274Diagnostic: RTAM Comm FailDiagnostic, class 004 Information (with RTAM installed)Read
BI275Diagnostic: RTVM Comm FailDiagnostic, class 004 Information (with RTVM installed)Read
BI276Diagnostic: VSM Comm FailDiagnostic, class 004 Information (with VSM installed)Read
BI277Diagnostic: RTDM Comm FailDiagnostic, class 004 Information (with RTDM installed)Read
BI278Diagnostic: Space Press Deadband FailDiagnostic, class 004 InformationRead
BI279Diagnostic: Mod Dehumid Config ErrorDiagnostic, class 004 InformationRead
BI280Diagnostic: Demand Defrost Fault A Ckt 2Diagnostic, class 004 Information (with heat pump installed)Read
BI281Diagnostic: Demand Defrost Fault B Ckt 2Diagnostic, class 004 Information (with Heat Pump installed)Read
BI282Diagnostic: Demand Defrost Fault C Ckt 2Diagnostic, class 004 Information (with Heat Pump installed)Read
BI283Diagnostic: Defrost Default Mode Ckt 2Diagnostic, class 004 Information (with Heat Pump installed)Read
BI284Diagnostic: Demand Defrost Fault A Ckt 1Diagnostic, class 004 Information (with Heat Pump installed)Read
BI285Diagnostic: Demand Defrost Fault B Ckt 1Diagnostic, class 004 Information (with Heat Pump installed)Read
BI286Diagnostic: Demand Defrost Fault C Ckt 1Diagnostic, class 004 Information (with Heat Pump installed)Read
BI287Diagnostic: Defrost Default Mode Ckt 1Diagnostic, class 004 Information (with Heat Pump installed)Read
BI288Diagnostic: Exhaust Fan Setpoint FailureDiagnostic, class 004 Information (with RTOM installed)Read
BI289Diagnostic: Discharge Air Heat Setpoint FailureDiagnostic, class 004 Information (with RTOM installed)Read
BI290Diagnostic: IGN1 Communications Timed outDiagnostic, class 004 Information (with Gas Heat installed)Read
BI291Diagnostic: IGN2 Communications Timed outDiagnostic, class 004 Information (with Gas Heat installed)Read
BI292Supply Air Tempering StatusStatus of the supply air tempering functionReadInactive = Inactive, Active = Active
BI293Diagnostic: DCV Min Position Setpoint FailDiagnostic, class 004 Information (with RTEM installed)Read
BI294Diagnostic: Design Min Position Setpoint FailDiagnostic, class 004 Information (with RTEM installed)Read
BI295Diagnostic: Enthalpy Setpoint FailDiagnostic, class 004 InformationRead
BI296Diagnostic: Design Min Position at Minimum Fan Speed FailDiagnostic, class 004 Information (with RTVM installed)Read
BI297Diagnostic: DCV Min Position at Minimum Fan SpeedDiagnostic, class 004 Information (with RTVM installed)Read
BI298Diagnostic: Design Min Position at Midpoint Fan Speed FailDiagnostic, class 004 Information (with RTVM installed)Read
BI299Diagnostic: Compressor 3 HPC Lockout StatusDiagnostic, class 001 Critical (with Compressor 3 or VSPD compressor and RTRM 16 or higher installed)Read
BI300Diagnostic: Compressor 3 LPC Lockout StatusDiagnostic, class 001 Critical (with Compressor 3 or VSPD compressor and RTRM 16 or higher installed)Read
BI301Diagnostic: Compressor 3 HPC DisableDiagnostic, class 004 Information (with Compressor 3 or VSPD compressor and RTRM 16 or higher installed)Read
BI302Diagnostic: Comp 3 Disable Input LPCDiagnostic, class 004 Information (with Compressor 3 or VSPD compressor and RTRM 16 or higher installed)Read
BI303Diagnostic: Compressor Drive FaultDiagnostic, class 001 Critical (with VSPD compressor and RTRM 16 or higher installed)Read
BI304Diagnostic: Compressor Drive LockoutDiagnostic, class 001 Critical (with Compressor 3 and RTRM 16 or higher installed)Read
BI305Diagnostic: Unit Economizing When It Should NotDiagnostic, class 004 Information (with RTEM 3 or higher installed and RTRM 16 or higher installed)Read
BI306Diagnostic: Unit Not Economizing When It ShouldDiagnostic, class 004 Information (with RTEM 3 or higher installed and RTRM 16 or higher installed)Read
BI307Diagnostic: Excessive AirDiagnostic, class 004 Information (with RTRM 16 or higher installed)Read
BI308Diagnostic: Air Damper Not ModulatingDiagnostic, class 004 Information (with RTRM 16 or higher installed)Read
BI309Diagnostic: TD5 Comm FailDiagnostic, class 004 Information (with TD5 installed and RTRM 15 or higher installed)Read
BI310Diagnostic: Mixed Air Temp Low Limit Cycle ActiveDiagnostic, class 004 InformationRead
BI311Diagnostic: Supply Airflow Sensor FailDiagnostic, class 004 InformationRead
BI312Diagnostic: Gas Heat Supply Airflow Limit TripDiagnostic, class 004 InformationRead
BOmin1System Control CommandCommand the unit to standalone- or BAS-controlled operation; default InactiveCommandInactive = Standalone Control, Active = BAS Control
BO5Heat Lockout CommandCommand the unit to prevent heating operation; default InactiveCommandInactive = Allow Heating, Active = Heating Locked Out
BO6Cool Lockout CommandCommand the unit to prevent cooling operation; default InactiveCommandInactive = Allow Cooling, Active = Cooling Locked Out
BO7Economizer Minimum Position Enable CommandCommand the unit to the minimum position operation; default Inactive (with RTEM installed)CommandInactive = Disabled, Active = Enabled
BO8Supply Fan Configuration CommandCommand the unit supply fan to cycling or continuous operation; default InactiveCommandInactive = Auto, Active = On
BO13Filter Timer ResetCommand the unit to reset the accumulated filter run hours; default InactiveCommandInactive = Accumulating, Active = Reset
BO14Reset DiagnosticCommand the unit to reset and clear diagnostics; default InactiveCommandInactive = Normal, Active = Reset
BO15Dehumidification Enable CommandCommand the operating state of the dehumidification system; default Active (with RTDM installed)CommandInactive = Disabled, Active = Auto
BO17Service Test CommandCommand the unit to step through service test; default 1 (Auto)CommandInactive = Normal, Active = Service test
BO18Supply Air Tempering Enable CommandCommand the unit supply air tempering operation; default Inactive (with all heat types)CommandInactive = Disabled, Active = Enabled
BO19Lead-Lag Enable CommandCommand the unit compressor startup order; default InactiveCommandInactive = Disabled, Active = Enabled
BO20Morning Warmup Enable CommandCommand the unit morning warmup operation; default InactiveCommandInactive = Disabled, Active = Enabled
BO21Daytime Warmup Enable CommandCommand the unit daytime warmup operation; default InactiveCommandInactive = Disabled, Active = Enabled
MI2Trane Unit TypeGeneral description of the equipment-type classificationRead1 = 1 Heat/1 Cool, 2 = Heat Pump, 3 = Blower Coil, 4 = Unit Ventilator, 5 = Fan Coil, 6 = Rooftop, 7 = Air Handler, 8 = Vertical Self Contained, 9 = Unitary, 10 = VAV Box, 11 = Fan Coil
MI9Economizer TypeGeneral description of the equipment economizer system (with RTEM installed)Read1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/Sensor, 9 = Waterside Economizer and TRAQ Damper/Sensor, 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor
MI17Cooling Reset Type StatusType of cooling reset (with Multi-zone VAV and RTAM installed or Single-zone VAV)Read1 = None, 2 = Outdoor Air, 3 = Zone
MImin19Heat Cool Mode Status/ Application Mode StatusCurrent heat/cool (application) modeRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economy Mode, 15 = Dehumidifying, 16 = Calibrate
MImin20Occupancy StatusCurrent occupancy mode of the unitRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby
MI21Unit Stop SourceSource of the stop command that turned off the equipmentRead1 = None, 2 = Emergency Stop, 3 = Drain Pan Overflow, 4 = Local HI Stop
MI22Cooling Setpoint SourceSource of the space cooling setpointRead1 = RTM Zone Sensor, 2 = Night Setback Panel, 3 = Human Interface, 4 = GBAS 0-5V, 5 = BAS/Network, 6 = GBAS 0-10V
MI23Heating Setpoint SourceSource of the space heating setpointRead1 = RTM Zone Sensor, 2 = Night Setback Panel, 3 = Human Interface, 4 = GBAS 0-5V, 5 = BAS/Network, 6 = GBAS 0-10V
MI24Timed Override StatusTimed override request or cancel from zone sensorRead1 = Idle, 2 = On, 3 = Cancel
MI25Cool Output 1Commanded state of cooling output 1Read1 = Off, 2 = On, 3 = Not Present
MI26Cool Output 2Commanded state of cooling output 2Read1 = Off, 2 = On, 3 = Not Present
MI29Heat Output 1Commanded state of heating output 1Read1 = Off, 2 = On, 3 = Not Present
MI30Heat Output 2Commanded state of heating output 2Read1 = Off, 2 = On, 3 = Not Present
MI31Heat Output 3Commanded state of heating output 3Read1 = Off, 2 = On, 3 = Not Present
MI32Heat Output 4Commanded state of heating output 4Read1 = Off, 2 = On, 3 = Not Present
MI35Primary Filter StatusPrimary filter media stateRead1 = Clean, 2 = Dirty, 3 = Not Present
MI37Supply Fan Proving StatusCurrent state of the supply fanRead1 = Off, 2 = On, 3 = Not Present
MI38Exhaust Fan StatusCommanded state of the exhaust fan (with RTEM Installed)Read1 = Off, 2 = On, 3 = Not Present
MI39Exhaust Fan Proving StatusIf the unit exhaust fan is off or onRead1 = Off, 2 = On, 3 = Not Present
MImin41Supply Fan StatusState of the supply fanRead1 = Off, 2 = On, 3 = Not Present
MI43Outdoor Damper StatusOperating state of the outdoor damper (with RTEM Installed)Read1 = At or Below Minimum Position, 2 = Above Minimum Position, 3 = Not Present
MI44Economizer System StatusOperating state of the waterside economizer system (with RTEM Installed)Read1 = Disabled, 2 = Enabled, 3 = Not Present
MI45Service Test StatusCurrent Service Test stateRead1 = Inactive, 2 = Fan On, 3 = IGV Open, 4 = IGV Close, 5 = Min Vent, 6 = Econ Open, 7 = Cool 1, 8 = Cool 2, 9 = Cool 3, 10 = Dehumidification/Reheat, 11 = Heat 1, 12 = Heat 2, 13 = Heat 3, 14 = Heat 4, 15 = Defrost, 16 = Emergency Heat
MO1Economizer Airside Enable BASCommand the state of the airside economizer system (with RTEM Installed)Command1 = Disabled, 2 = Enabled, 3 = Auto
MO2Emergency Override CommandCommand the unit into an emergency mode of operationCommand1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MOmin7Occupancy RequestCommand the unit into an occupancy modeCommand1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby
MOmin8Heat Cool Mode Request BASCommand the unit to a specific application modeCommand1 = Auto, 2 = Heat, 3 = Morning Warmup, 4 = Cool, 5 = Night Purge, 6 = Precool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice Making, 13 = Max Heat, 14 = Economy Mode, 15 = Dehumidifying, 16 = Calibrate

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BCI2-R (ReliaTel) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane BCI2-R (ReliaTel)

How many BACnet points does the Trane BCI2-R (ReliaTel) have?

This list has 250 BACnet objects: 60 analog inputs, 35 analog outputs, 1 analog value, 114 binary inputs, 13 binary outputs, 23 multi-state inputs, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane BCI2-R (ReliaTel) BACnet points are writable?

53 of the 250 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane BCI2-R (ReliaTel) BACnet documentation?

The source is Integration Guide: BACnet Communication Interface for ReliaTel Controllers (BCI2-R) (BAS-SVP053A-EN), revision April 2022, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP053A-EN_04162022.pdf.

What are the minimum BACnet points to integrate the Trane BCI2-R (ReliaTel)?

Start with BO 1 System Control Command (Active = BAS control; Inactive = standalone, monitor only); MO 7 Occupancy Request (Occupancy command (1 = Occupied, 2 = Unoccupied)); MO 8 Heat Cool Mode Request BAS (Heat/cool mode command (1 = Auto)); AO 2 Space Temperature Setpoint BAS (Space setpoint; occupied/standby offsets apply to it); BI 1 System Control Status (Confirms the unit is under BAS control); MI 20 Occupancy Status (Confirms the occupancy the unit is running in); MI 19 Heat Cool Mode Status/ Application Mode Status (Current heat/cool operating mode); MI 41 Supply Fan Status (Supply fan on/off (2 = On)); AI 15 Space Temperature Active (Space temperature the unit is controlling to); BI 165 Alarm Relay Output Status (Unit alarm relay; Active = energized).

How do I enable BMS control of the Trane BCI2-R (ReliaTel)?

BO 1 System Control Command must be in service and Active (BAS Control); while Inactive the unit runs standalone and the BMS can only monitor. BI 1 System Control Status shows which is in charge. Most output objects ship with Out_of_Service = True, so the unit uses its local value; set Out_of_Service to False (BCI2 Service Tool Points screens or Tracer TU) on each output the BMS will write.

Does the Trane BCI2-R (ReliaTel) need a BACnet heartbeat or have a communication timeout?

The BAS sensor outputs with a 900 s refresh rate (AO 10, 11, 14, 15, 18, 25) must be rewritten within that time. If not, the BCI2-R puts the object in fault and the unit falls back to its own sensor. At power-up these objects start in fault until the first write. Setpoint and command outputs have no refresh limit.

Can the BMS supply sensor values to the Trane BCI2-R (ReliaTel)?

Write BMS sensor values to the '... BAS' AOs (AO 11 Space Temperature BAS, AO 14 Outdoor Air Temperature BAS, AO 15 Outdoor Air Humidity BAS, AO 18 Space CO2 Concentration BAS, AO 25 Space Humidity BAS, AO 10 Space Static Pressure BAS) with the object in service, and keep refreshing them. The matching '... Active' AIs show the value in use.

How do I check these points on the real BCI2-R (ReliaTel)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide: BACnet Communication Interface for ReliaTel Controllers (BCI2-R) · BAS-SVP053A-EN · rev. April 2022. Object names, instances and units are reproduced as published; descriptions are our own.