Water-cooled screw chiller controller · BACnet points list

Trane Symbio 800 Series R RTHD BACnet points list

Updated 28 October 2026

Short answer

RTHD chillers with Symbio 800 publish about 275 BACnet objects; about 165 are diagnostic binary inputs. Water temperatures, flows, refrigerant and oil pressures, starter or drive currents and energy meter values are AIs. The BAS writes chilled and hot water setpoints, demand limit, base loading, mode, pump requests and auto/stop.

This page lists 275 BACnet objects for the Trane Symbio 800 Series R RTHD — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 Series R RTHD
Equipment
Water-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
275 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015
Source document
Symbio 800 Integration Points List BACnet - Series R Model RTHD · BAS-PTS015A-EN · rev. 11/15/2024
Download CSV 275 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 Series R RTHD

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10100Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10103Chiller Running StateChiller on/off statusRead
BI 10101Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10104Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10108Actual Running CapacityActual running capacity in percentRead
BI 10106Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10122 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10100 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Network setup

Watch out for

Trane Symbio 800 Series R RTHD BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

275 of 275 shown
Type
Access
Show
Trane Symbio 800 Series R RTHD BACnet Points List
DescriptionStates
AI10100Active Cool/Heat Setpoint TemperatureValue of the active Cool/Heat Setpoint actively being used by the chillerTemperatureRead
AI10101Active Demand Limit SetpointDemand limit setpoint value actively being used by the chillerPercentageRead
AI10102Active Base Loading Setpoint"active" Base Loading Setpoint resulting from arbitrationPercentageRead
AI10103Evaporator Entering Water TemperatureEvaporator Entering or Return water temperatureTemperatureRead
AImin10104Evaporator Leaving Water TemperatureTemperature of the water leaving the evaporatorTemperatureRead
AI10105Number of CircuitsNumber of refrigeration circuits in the chillerRead
AI10106Number of Compressors Circuit 1Number of compressors on circuit 1 of the chillerRead
AI10107Number of Compressors Circuit 2Number of compressors on circuit 2 of the chillerRead
AImin10108Actual Running CapacityMeasurement of the power being consumed by the ChillerPercentageRead
AI10109Evaporator Refrigerant Absolute Pressure Circuit 1Current absolute pressure of the refrigerant in the evaporator on circuit 1Pressure, FluidicRead
AI10110Condenser Refrigerant Absolute Pressure Circuit 1Current absolute pressure of the refrigerant in the condenser on circuit 1Pressure, FluidicRead
AI10111Evaporator Saturated Refrigerant Temperature Circuit 1Saturated refrigerant temperature of the evaporator on circuit 1TemperatureRead
AI10112Condenser Saturated Refrigerant Temperature Circuit 1Saturated refrigerant temperature of the condenser on circuit 1TemperatureRead
AI10113Refrigerant Discharge Temperature - Compressor 1ACurrent temperature of the refrigerant being discharged from Compressor 1ATemperatureRead
AI10114High Side Oil Absolute Pressure - Compressor 1APressure, FluidicRead
AI10115Starts - Compressor 1ANumber of starts of Compressor 1ARead
AI10116Run Time - Compressor 1ARun time of Compressor 1A, in secondsRead
AI10117Motor Winding Temperature 1 Circuit 1First temperaure sensor of the windings on motor 1ATemperatureRead
AI10118Motor Winding Temperature 2 Circuit 1Second temperaure sensor of the windings on motor 1ATemperatureRead
AI10119Condenser Entering Water TemperatureCurrent temperature of the water entering the condenserTemperatureRead
AI10120Condenser Leaving Water TemperatureCurrent temperature of the water leaving the condenserTemperatureRead
AI10121Starter Voltage Phase ABMeasurement of voltage in Phase ABVoltageRead
AI10122Starter Voltage Phase BCMeasurement of voltage in Phase BCVoltageRead
AI10123Starter Voltage Phase CAMeasurement of voltage in Phase CAVoltageRead
AI10124Line 1 Current - Compressor 1AWith Starter, Non Comm AFD, TR200 Modbus AFDCurrentRead
AI10125Line 2 Current - Compressor 1AWith Starter, Non Comm AFD, TR200 Modbus AFDCurrentRead
AI10126Line 3 Current - Compressor 1AWith Starter, Non Comm AFD, TR200 Modbus AFDCurrentRead
AI10127Line 1 Current - Compressor 1ACurrent L1 on Compressor 1A; with Local Comm AFDCurrentRead
AI10128Line 2 Current - Compressor 1ACurrent L2 on Compressor 1A; with Local Comm AFDCurrentRead
AI10129Line 3 Current - Compressor 1ACurrent L3 on Compressor 1A; with Local Comm AFDCurrentRead
AI10130Line 1 Current RLA - Compressor 1AWith Starter, Non Comm AFD, TR200 Modbus AFDPercentageRead
AI10131Line 2 Current RLA - Compressor 1AWith Starter, Non Comm AFD, TR200 Modbus AFDPercentageRead
AI10132Line 3 Current RLA - Compressor 1AWith Starter, Non Comm AFD, TR200 Modbus AFDPercentageRead
AI10133Line 1 Current RLA - Compressor 1AWith Local Comm AFDPercentageRead
AI10134Line 2 Current RLA - Compressor 1AWith Local Comm AFDPercentageRead
AI10135Line 3 Current RLA - Compressor 1AWith Local Comm AFDPercentageRead
AI10136Expansion Valve Position - Compressor 1APercent open of the exv valvePercentageRead
AI10137Drive Output Power Circuit 1Power output from the AFDPower, ElectricalRead
AI10138Chiller Design CapacityDesign capacity of chilllerPower, CoolingRead
AI10139Active Chilled Water SetpointValue of the active Chilled Water Setpoint actively beingTemperatureRead
AI10140Active Hot Water SetpointValue of the active Hot Water Setpoint actively beingTemperatureRead
AI10141Evaporator Water Flow RateFlow of water through the evaporatorFlow, FluidicRead
AI10142Condenser Water Flow RateFlow of water through the condenserFlow, FluidicRead
AI10143Condenser Differential Water PressureWater pressure differential of the condenserPressure, FluidicRead
AI10144Evaporator Differential Water PressureWater pressure differential of the evaporatorPressure, FluidicRead
AI10145Evaporator Refrigerant Pressure Circuit 1Current gauge pressure of the refrigerant in the evaporator on circuit 1Pressure, FluidicRead
AI10146Condenser Refrigerant Pressure Circuit 1Current gauge pressure of the refrigerant in the condenser on circuit 1Pressure, FluidicRead
AI10147Condenser Control OutputHead Pressure Control Output on the CondenserPercentageRead
AI10148High Side Oil Pressure - Compressor 1APressure, FluidicRead
AI10150Evaporator Approach Temperature Circuit 1Evaporator Approach Temperature on circuit 1Temperature, DeltaRead
AI10151Condenser Approach Temperature Circuit 1Condenser Approach Temperature on circuit 1Temperature, DeltaRead
AI10152Line Frequency Circuit 1Estimated input frequency at the AFDRead
AI10153Heat Recovery Entering Water TemperatureD the Entering Water Temp in Heat RecoveryTemperatureRead
AI10154Heat Recovery Leaving Water TemperatureD the Leaving Water Temp in Heat RecoveryTemperatureRead
AI10155Heat Recovery Tank Water TempWater Temp in the Heat Recovery TankTemperatureRead
AI10156Heat Recovery Water Tank Temperature Setpoint ActiveActive temperature setpoint for the heat recovery tankTemperatureRead
AI10157Chilled Water Setpoint StatusChilled Water Setpoint after arbitration and limitingTemperatureRead
AI10158Demand Limit Setpoint StatusPresently in use or "active" setting of the Demand LimitPercentageRead
AI10159Unit Source ID (Last Diagnostic Code)Last diagnostic of the chillerRead
AI10160Current L1Current phase A in amps for the chillerCurrentRead
AI10161Current L2Current phase B in amps for the chillerCurrentRead
AI10162Current L3Current phase C in amps for the chillerCurrentRead
AI10163Average CurrentAverage current in amps for the chillerCurrentRead
AI10164Voltage L1-L2Line voltage Vab for the chillerVoltageRead
AI10165Voltage L2-L3Line voltage Vbc for the chillerVoltageRead
AI10166Voltage L1-L3Line voltage Vca for the chillerVoltageRead
AI10167Average Voltage L-LAverage line voltage for the chillerVoltageRead
AI10168Line FrequencyLine frequency for the chillerRead
AI10169Power FactorUnit power factorRead
AVmin10100Chilled Water SetpointWritten by the BAS; goes through arbitration before useTemperatureWrite
AVmin10101Demand Limit SetpointWritten by the BAS; goes through arbitration before usePercentageWrite
AV10102Hot Water SetpointWritten by the BAS; goes through arbitration before useTemperatureWrite
AV10103Base Loading SetpointWritten by the BAS; goes through arbitration before usePercentageWrite
AV10104Heat Recovery Water Tank Temperature Setpoint BASWritten by the BAS; goes through arbitration before useTemperatureWrite
BI10100Run EnabledThat chiller is available to run or is currently runningRead0 = Run Not Enabled, 1 = Run Enabled
BImin10101Local Setpoint ControlWhich setpoint is used for control purposes, Remote (BAS) or LocalRead0 = Remote control, 1 = Local control
BI10102Limit Mode Relay StatusStatus of the chiller limit relayRead0 = Off, 1 = On
BImin10103Chiller Running StateThe chiller is onRead0 = Off, 1 = On
BI10104Base Loading Request Active"active" Base Loading Request resulting from arbitrationRead0 = Off, 1 = On
BI10105Evaporator Water Flow StatusFlow of water through evaporatorRead0 = No Flow, 1 = Flow
BImin10106Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10107Diagnostic Shutdown PresentChiller is shut down due to diagnosticsRead0 = Normal, 1 = In Alarm
BI10108Diagnostic: Manual Reset RequiredWhen a diagnostic exists that requires manual resetRead0 = Normal, 1 = In Alarm
BI10109Diagnostic: Local Manual Reset RequiredWhen a diagnostic exists that requires manual reset [Local only]Read0 = Normal, 1 = In Alarm
BI10110Diagnostic Present: InformationDiagnostic present with Information CategoryRead0 = Normal, 1 = In Alarm
BI10111Diagnostic Present: AdvisoryDiagnostic present with Warning CategoryRead0 = Normal, 1 = In Alarm
BI10112Diagnostic Present: CriticalDiagnostic present with Critical CategoryRead0 = Normal, 1 = In Alarm
BI10113Diagnostic Present: Service RequiredDiagnostic present with Service Required CategoryRead0 = Normal, 1 = In Alarm
BI10114Compressor 1A StatusRunning state fo Compressor 1ARead0 = Off, 1 = Running
BI10115Condenser Water Pump RequestThis provides a status of the Chillers Condenser Water Pump outputRead0 = Normal, 1 = In Alarm
BI10116Evaporator Water Pump RequestThis provides a status of the Chillers Evaporator Water Pump outputRead0 = Normal, 1 = In Alarm
BI10117Condenser Water Flow StatusWater flow through the condenserRead0 = Normal, 1 = In Alarm
BI10118Heat Recovery Water Flow StatusRead0 = Off, 1 = Running
BI10119Heat Recovery Control Active StatusHeat Recovery ActiveRead0 = Off, 1 = Running
BI10120Heat Recovery Request ActiveActive Heat Recovery CommandRead0 = Off, 1 = Running
BI10121Front Panel Auto StopAuto/stop status of the Front PanelRead0 = Stop, 1 = Auto
BI10122External Auto Stop Input StatusStatus of the externally-wired auto/stop inputRead0 = Stop, 1 = Auto
BI10123Head Relief RequestHead Relief Request RelayRead0 = Inactive, 1 = Active
BI10124Base Loading ActiveRead0 = Off, 1 = On
BI11000Comm Loss: Ext Base Loading CommandRead0 = Normal, 1 = In Alarm
BI11001Comm Loss: Ext Base Loading SetpointRead0 = Normal, 1 = In Alarm
BI11002Diagnostic: External Base Loading SetpointRead0 = Normal, 1 = In Alarm
BI11003Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11004Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11005Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11006Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11007Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11008Diagnostic: AFD Drive FaultRead0 = Normal, 1 = In Alarm
BI11009Comm Loss: Cprsr Discharge Rfgt TempRead0 = Normal, 1 = In Alarm
BI11010Comm Loss: Cond High Pressure CutoutRead0 = Normal, 1 = In Alarm
BI11011Comm Loss: Primary Oil Line Solenoid ValveRead0 = Normal, 1 = In Alarm
BI11012Comm Loss: Oil Loss Level Sensor InputRead0 = Normal, 1 = In Alarm
BI11013Comm Loss: Oil PressureRead0 = Normal, 1 = In Alarm
BI11014Comm Loss: Oil Return Gas Pump DrainRead0 = Normal, 1 = In Alarm
BI11015Comm Loss: Oil Return Gas Pump FillRead0 = Normal, 1 = In Alarm
BI11016Comm Loss: SSS/AFD FaultWith Non Comm AFDRead0 = Normal, 1 = In Alarm
BI11017Diagnostic: Cprsr Discharge Refrigerant Temp SensorRead0 = Normal, 1 = In Alarm
BI11018Diagnostic: High Cprsr Rfgt Discharge TemperatureRead0 = Normal, 1 = In Alarm
BI11019Diagnostic: High Differential Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11020Diagnostic: High Pressure CutoutRead0 = Normal, 1 = In Alarm
BI11021Diagnostic: High Refrigerant Pressure RatioRead0 = Normal, 1 = In Alarm
BI11022Diagnostic: Loss of Oil at Compressor (Running)Read0 = Normal, 1 = In Alarm
BI11023Diagnostic: Loss of Oil at Compressor (Stopped)Read0 = Normal, 1 = In Alarm
BI11024Diagnostic: Low Differential Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11025Diagnostic: Low Discharge SuperheatRead0 = Normal, 1 = In Alarm
BI11026Diagnostic: Low Oil FlowRead0 = Normal, 1 = In Alarm
BI11027Diagnostic: No Differential Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11028Diagnostic: Oil Flow Protection FaultRead0 = Normal, 1 = In Alarm
BI11029Diagnostic: Oil Pressure TransducerRead0 = Normal, 1 = In Alarm
BI11030Diagnostic: AFD Output Power InputRead0 = Normal, 1 = In Alarm
BI11031Comm Loss: AFD Output Power InputRead0 = Normal, 1 = In Alarm
BI11032Comm Loss: AFD Speed Signal OutputRead0 = Normal, 1 = In Alarm
BI11033Comm Loss: Adaptive Frequency DriveRead0 = Normal, 1 = In Alarm
BI11034Comm Loss: Economizer Bypass ValveRead0 = Normal, 1 = In Alarm
BI11035Comm Loss: Economizer PressureRead0 = Normal, 1 = In Alarm
BI11036Comm Loss: Economizer TemperatureRead0 = Normal, 1 = In Alarm
BI11037Comm Loss: Economizer ValveRead0 = Normal, 1 = In Alarm
BI11038Comm Loss: Hot Gas Bypass ValveRead0 = Normal, 1 = In Alarm
BI11039Comm Loss: Liquid Line Bypass ValveRead0 = Normal, 1 = In Alarm
BI11040Comm Loss: Oil Return Purge ValveRead0 = Normal, 1 = In Alarm
BI11041Comm Loss: Slide Valve LoadRead0 = Normal, 1 = In Alarm
BI11042Comm Loss: Slide Valve UnloadRead0 = Normal, 1 = In Alarm
BI11043Diagnostic: Economizer Pressure SensorRead0 = Normal, 1 = In Alarm
BI11044Diagnostic: Economizer Temperature SensorRead0 = Normal, 1 = In Alarm
BI11045Diagnostic: Restart InhibitRead0 = Normal, 1 = In Alarm
BI11046Comm Loss: Cond Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11047Diagnostic: Condenser Refrigerant Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11048Diagnostic: Excessive Condenser PressureRead0 = Normal, 1 = In Alarm
BI11049Comm Loss: Condenser Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11050Comm Loss: Condenser Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11051Comm Loss: Cond Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11052Diagnostic: Condenser Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11053Diagnostic: Condenser Water Flow LostRead0 = Normal, 1 = In Alarm
BI11054Diagnostic: Condenser Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11055Comm Loss: Condenser Entering Water TempRead0 = Normal, 1 = In Alarm
BI11056Comm Loss: Condenser Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11057Diagnostic: Condenser Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11058Diagnostic: Condenser Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11059Comm Loss: Evaporator Rfgt Liquid LevelRead0 = Normal, 1 = In Alarm
BI11060Diagnostic: Evaporator Liquid Level SensorRead0 = Normal, 1 = In Alarm
BI11061Diagnostic: High Evaporator Liquid LevelRead0 = Normal, 1 = In Alarm
BI11062Diagnostic: Low Evaporator Liquid LevelRead0 = Normal, 1 = In Alarm
BI11063Diagnostic: Low Evaporator Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11064Diagnostic: Low Evaporator Refrigerant TemperatureRead0 = Normal, 1 = In Alarm
BI11065Diagnostic: Low Evaporator Temp: Unit OffRead0 = Normal, 1 = In Alarm
BI11066Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11067Comm Loss: Evaporator Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11068Comm Loss: Evap Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11069Diagnostic: Evaporator Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11070Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11071Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11072Diagnostic: High Evaporator Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11073Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11074Diagnostic: Low Evaporator Water FlowRead0 = Normal, 1 = In Alarm
BI11075Diagnostic: Evap Water Flow (Entering Water Temp)Read0 = Normal, 1 = In Alarm
BI11076Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11077Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11078Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11079Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11080Comm Loss: Electronic Expansion Valve 1Read0 = Normal, 1 = In Alarm
BI11081Comm Loss: Electronic Expansion Valve 2Read0 = Normal, 1 = In Alarm
BI11082Comm Loss: Evaporator Rfgt PressureRead0 = Normal, 1 = In Alarm
BI11083Diagnostic: Evaporator Rfgt Pressure TransducerRead0 = Normal, 1 = In Alarm
BI11084Comm Loss: Compressor % RLA OutputRead0 = Normal, 1 = In Alarm
BI11085Comm Loss: Cond Head Press Cntrl OutputRead0 = Normal, 1 = In Alarm
BI11086Comm Loss: Cond Rfgt Pressure OutputRead0 = Normal, 1 = In Alarm
BI11087Comm Loss: Emergency StopRead0 = Normal, 1 = In Alarm
BI11088Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11089Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11090Comm Loss: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11091Comm Loss: External Hot Water CommandRead0 = Normal, 1 = In Alarm
BI11092Comm Loss: Op Status Programmable RelaysRead0 = Normal, 1 = In Alarm
BI11093Comm Loss: Refrigerant Monitor InputRead0 = Normal, 1 = In Alarm
BI11094Diagnostic: Emergency StopRead0 = Normal, 1 = In Alarm
BI11095Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11096Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11097Diagnostic: Refrigerant Monitor InputRead0 = Normal, 1 = In Alarm
BI11098Comm Loss: External Heat Recovery CommandRead0 = Normal, 1 = In Alarm
BI11099Comm Loss: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11100Comm Loss: HR Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11101Comm Loss: HR Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11102Comm Loss: Heat Recovery Tank Water TempRead0 = Normal, 1 = In Alarm
BI11103Comm Loss: Heat Recovery Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11104Comm Loss: Heat Recovery Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11105Diagnostic: Ext Heat Recovery Temp Setpoint SensorRead0 = Normal, 1 = In Alarm
BI11106Diagnostic: Heat Recovery Entering Water Temperature SensorRead0 = Normal, 1 = In Alarm
BI11107Diagnostic: Heat Recovery Leaving Water Temperature SensorRead0 = Normal, 1 = In Alarm
BI11108Diagnostic: Heat Recovery Tank Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11109Diagnostic: Heat Recovery Water Flow LostRead0 = Normal, 1 = In Alarm
BI11110Diagnostic: Heat Recovery Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11111Diagnostic: Unexpected Heat Recovery Water FlowRead0 = Normal, 1 = In Alarm
BI11112Diagnostic: Unexpected Condenser Water FlowRead0 = Normal, 1 = In Alarm
BI11113Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11114Comm Loss: Ice Building RelayRead0 = Normal, 1 = In Alarm
BI11115Comm Loss: SSS/AFD FaultWith Solid State StarterRead0 = Normal, 1 = In Alarm
BI11116Comm Loss: StarterRead0 = Normal, 1 = In Alarm
BI11117Diagnostic: Solid State Starter FaultRead0 = Normal, 1 = In Alarm
BI11118Diagnostic: Starter Failed to Arm/StartRead0 = Normal, 1 = In Alarm
BI11119Diagnostic: Unexpected Starter ShutdownRead0 = Normal, 1 = In Alarm
BI11120Diagnostic: AFD Bus Over VoltageRead0 = Normal, 1 = In Alarm
BI11121Diagnostic: AFD Bus Under VoltageRead0 = Normal, 1 = In Alarm
BI11122Diagnostic: AFD Comm Loss: Main ProcessorRead0 = Normal, 1 = In Alarm
BI11123Diagnostic: AFD Emergency Stop FaultRead0 = Normal, 1 = In Alarm
BI11124Diagnostic: AFD General FailureRead0 = Normal, 1 = In Alarm
BI11125Diagnostic: AFD Ground FaultRead0 = Normal, 1 = In Alarm
BI11126Diagnostic: AFD Instantaneous Current OverloadRead0 = Normal, 1 = In Alarm
BI11127Diagnostic: AFD Interrupt FailureRead0 = Normal, 1 = In Alarm
BI11128Diagnostic: AFD Inverter Heatsink Over TempRead0 = Normal, 1 = In Alarm
BI11129Diagnostic: AFD Motor Current OverloadRead0 = Normal, 1 = In Alarm
BI11130Diagnostic: AFD Output Phase LossRead0 = Normal, 1 = In Alarm
BI11131Diagnostic: AFD Rated Current Out of RangeRead0 = Normal, 1 = In Alarm
BI11132Diagnostic: At Speed Input OpenedRead0 = Normal, 1 = In Alarm
BI11133Diagnostic: At Speed Input ShortedRead0 = Normal, 1 = In Alarm
BI11134Comm Loss: Motor Winding Temperature 1Read0 = Normal, 1 = In Alarm
BI11135Comm Loss: Motor Winding Temperature 2Read0 = Normal, 1 = In Alarm
BI11136Diagnostic: Cprsr Did Not Accelerate: TransitionRead0 = Normal, 1 = In Alarm
BI11137Diagnostic: Compressor Did Not Accelerate FullyRead0 = Normal, 1 = In Alarm
BI11138Diagnostic: Compressor Did Not Accelerate: ShutdownRead0 = Normal, 1 = In Alarm
BI11139Diagnostic: High Motor Winding TemperatureRead0 = Normal, 1 = In Alarm
BI11140Diagnostic: High Pressure CutoutWith Local Comm AFDRead0 = Normal, 1 = In Alarm
BI11141Diagnostic: Momentary Power LossRead0 = Normal, 1 = In Alarm
BI11142Diagnostic: Motor Current OverloadRead0 = Normal, 1 = In Alarm
BI11143Diagnostic: Motor Winding Temp Sensor - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11144Diagnostic: Over VoltageRead0 = Normal, 1 = In Alarm
BI11145Diagnostic: Phase LossRead0 = Normal, 1 = In Alarm
BI11146Diagnostic: Phase ReversalRead0 = Normal, 1 = In Alarm
BI11147Diagnostic: Power LossRead0 = Normal, 1 = In Alarm
BI11148Diagnostic: Severe Current UnbalanceRead0 = Normal, 1 = In Alarm
BI11149Starter Comm Loss: Main ProcessorRead0 = Normal, 1 = In Alarm
BI11150Diagnostic: Starter Contactor Interrupt FailureRead0 = Normal, 1 = In Alarm
BI11151Diagnostic: Starter Did Not TransitionRead0 = Normal, 1 = In Alarm
BI11152Diagnostic: Starter Dry Run TestRead0 = Normal, 1 = In Alarm
BI11153Diagnostic: Starter Fault Type IRead0 = Normal, 1 = In Alarm
BI11154Diagnostic: Starter Fault Type IIRead0 = Normal, 1 = In Alarm
BI11155Diagnostic: Starter Fault Type IIIRead0 = Normal, 1 = In Alarm
BI11156Diagnostic: Starter Module Memory Error Type 1Read0 = Normal, 1 = In Alarm
BI11157Diagnostic: Starter Module Memory Error Type 2Read0 = Normal, 1 = In Alarm
BI11158Diagnostic: Transition Complete Input OpenedRead0 = Normal, 1 = In Alarm
BI11159Diagnostic: Transition Complete Input ShortedRead0 = Normal, 1 = In Alarm
BI11160Diagnostic: Under VoltageRead0 = Normal, 1 = In Alarm
BI11161Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11162Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BVmin10100Chiller Auto Stop Command BASCommand the chiller to start running if operating conditions are satisfiedWrite0 = Stop, 1 = Auto
BV10101Reset DiagnosticInitiate a request to reset any controller diagnosticsWrite0 = Normal, 1 = Reset
BV10102Base Loading RequestWrite0 = Normal, 1 = Reduce Noise
BV10103Heat Recovery Enable BASCommand the heat recovery to start running if operating conditions are satisfiedWrite0 = Off, 1 = On
BV10104Evaporator Water Pump Request BASLockout the Evaporator Water PumpWrite0 = Normal, 1 = Locked Out
BV10105Condenser Water Pump Request BASLockout the Condenser Water PumpWrite0 = Normal, 1 = Locked Out
MI10100Running ModeRunning state of the chillerRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre- Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeOperating mode of the chillerRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Refrigerant TypeChiller refrigerant typeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E)
MI10103Manufacture LocationLocation that the chiller was manufacturedRead1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey
MI10104Cooling TypeCooling Type of chillerRead1 = Water Cooled, 2 = Air Cooled
MI10105Model Information [GEN2]Model information of chillerRead1 = CVHF, 2 = CVGF, 3 = CVHS, 4 = RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTWE, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = ACXA, 35 = CMAF, 36 = ACRB Large, 37 = ACRB Small
MVmin10100Chiller Mode Command BASCommand the chiller ModeWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Series R RTHD and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 Series R RTHD

How many BACnet points does the Trane Symbio 800 Series R RTHD have?

This list has 275 BACnet objects: 69 analog inputs, 5 analog values, 188 binary inputs, 6 binary values, 6 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 Series R RTHD BACnet points are writable?

12 of the 275 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 Series R RTHD BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - Series R Model RTHD (BAS-PTS015A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS015A-EN_11152024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 Series R RTHD?

Start with BV 10100 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10104 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10108 Actual Running Capacity (Actual running capacity in percent); BI 10106 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 Series R RTHD?

BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10122 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10100 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

How do I check these points on the real Symbio 800 Series R RTHD?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - Series R Model RTHD · BAS-PTS015A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.