Air-cooled chiller controller · BACnet points list

Trane Symbio 800 Ascend ACS / ACX BACnet points list

Updated 28 October 2026

Short answer

Ascend ACS/ACX chillers expose about 400 BACnet objects through the Symbio 800. Status values are AI/BI/MI, and the BAS writes a small set of AV/BV/MV objects for chilled and hot water setpoints, demand limit, mode, circuit lockouts and auto/stop. Most binary inputs are individual diagnostic flags.

This page lists 397 BACnet objects for the Trane Symbio 800 Ascend ACS / ACX — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 Ascend ACS / ACX
Equipment
Air-cooled chiller controller
Equipment type
Chillers
BACnet objects
397 (16 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011
Source document
Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 11/15/2024
Download CSV 397 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 Ascend ACS / ACX

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10107BAS Chiller Auto Stop CommandBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10110Chiller Running StateChiller on/off statusRead
BI 10104Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10101Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10116Actual Running CapacityActual running capacity in percentRead
BI 10126Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10107 BAS Chiller Auto Stop Command (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10130 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

Network setup

Watch out for

Trane Symbio 800 Ascend ACS / ACX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

397 of 397 shown
Type
Access
Show
Trane Symbio 800 Ascend ACS / ACX BACnet Points List
DescriptionStates
AI10100Active Cool/Heat Setpoint TemperatureTemperatureRead
AImin10101Evaporator Leaving Water TemperatureTemperatureRead
AI10102Evaporator Entering Water TemperatureTemperatureRead
AI10103Active Demand Limit SetpointPercentageRead
AI10104Unit Power ConsumptionPower, ElectricalRead
AI10105Outdoor Air TemperatureTemperatureRead
AI10106Evaporator Refrigerant Pressure Circuit 1Pressure, FluidicRead
AI10107Condenser Refrigerant Pressure Circuit 1Pressure, FluidicRead
AI10108Differential Refrigerant Pressure Circuit 1Pressure, FluidicRead
AI10109Evaporator Saturated Rfgt Temp Circuit 1TemperatureRead
AI10110Condenser Saturated Rfgt Temp Circuit 1TemperatureRead
AI10111Evaporator Refrigerant Pressure Circuit 2Pressure, FluidicRead
AI10112Condenser Refrigerant Pressure Circuit 2Pressure, FluidicRead
AI10113Differential Refrigerant Pressure Circuit 2Pressure, FluidicRead
AI10114Evaporator Saturated Rfgt Temp Circuit 2TemperatureRead
AI10115Condenser Saturated Rfgt Temp Circuit 2TemperatureRead
AImin10116Actual Running CapacityPercentageRead
AI10117Active Heat Recovery SetpointTemperatureRead
AI10118Active Hot Water SetpointTemperatureRead
AI10119Air Flow Circuit 1PercentageRead
AI10120Air Flow Circuit 2PercentageRead
AI10121Starts Cprsr1ARead
AI10122Running Time Cprsr1ARead
AI10123Starts Cprsr2ARead
AI10124Running Time Cprsr2ARead
AI10125Heat Recovery Entering Water TempTemperatureRead
AI10126Heat Recovery Leaving Water TempTemperatureRead
AI10127Chiller Design CapacityPower, CoolingRead
AI10128Starts Cprsr1BRead
AI10129Running Time Cprsr1BRead
AI10130Starts Cprsr2BRead
AI10131Running Time Cprsr2BRead
AI10132Number Of CircuitsRead
AI10133Number of Compressors for Circuit 1Read
AI10134Number of Compressors for Circuit 2Read
AI10135Free Cooling CapacityPercentageRead
AI10136Free Cooling Entering Water TemperatureTemperatureRead
AI10137Free Cooling Entering Glycol TemperatureTemperatureRead
AI10138Free Cooling Leaving Glycol TemperatureTemperatureRead
AI10139Energy Consumption NonResetPower, ElectricalRead
AI10140Energy Consumption ResettablePower, ElectricalRead
AI10141Starts Cprsr1CRead
AI10142Running Time Cprsr1CRead
AI10143Starts Cprsr2CRead
AI10144Running Time Cprsr2CRead
AI10145Estimated Discharge Temperature Circuit 1TemperatureRead
AI10146Estimated Discharge Temperature Circuit 2TemperatureRead
AI10147Compressor Discharge Temperature Circuit 1TemperatureRead
AI10148Compressor Discharge Temperature Circuit 2TemperatureRead
AI10149Free Cooling Glycol PressurePressure, FluidicRead
AI10150Last Logged DiagnosticRead
AI10151Unit Load CommandPercentageRead
AI10152Average Line CurrentCurrentRead
AI10153Average Line VoltageVoltageRead
AI10154Current L1CurrentRead
AI10155Current L2CurrentRead
AI10156Current L3CurrentRead
AI10157Voltage L1-L2VoltageRead
AI10158Voltage L2-L3VoltageRead
AI10159Voltage L1-L3VoltageRead
AI10160Total Real PowerPower, ElectricalRead
AI10161Line FrequencyRead
AI10162Power FactorRead
AI10163Heat Recovery Valve PositionPercentageRead
AI10164Evaporator Refrigerant Absolute Pressure Circuit 1Pressure, FluidicRead
AI10165Condenser Refrigerant Absolute Pressure Circuit 1Pressure, FluidicRead
AI10166Evaporator Refrigerant Absolute Pressure Circuit 2Pressure, FluidicRead
AI10167Condenser Refrigerant Absolute Pressure Circuit 2Pressure, FluidicRead
AI10168Free Cooling Glycol Absolute PressurePressure, FluidicRead
AI10169Supplemental Heater StatusPercentageRead
AI10170Evaporator Approach Temperature Circuit 1 (Cooling Mode Only)TemperatureRead
AI10171Evaporator Approach Temperature Circuit 2 (Cooling Mode Only)TemperatureRead
AI10172Condenser Approach Temperature Circuit 1 (Heating Mode Only)TemperatureRead
AI10173Condenser Approach Temperature Circuit 2 (Heating Mode Only)TemperatureRead
AI10174Active Chilled Water SetpointTemperatureRead
AI10175Chilled Water Setpoint StatusTemperatureRead
AI10176Hot Water Setpoint StatusTemperatureRead
AI10177Demand Limit Setpoint StatusPercentageRead
AI10178Active Demand Limit SetpointPercentageRead
AVmin10100Chilled Water SetpointTemperatureWrite
AVmin10101Demand Limit SetpointPercentageWrite
AV10102BAS Hot Water SetpointTemperatureWrite
AV10103BAS Heat Recovery SetpointTemperatureWrite
AV10104Evaporator Water Pump Speed SetpointPercentageWrite
BI10100Limit Mode Relay StatusRead0 = Auto, 1 = On
BI10101Emergency StopRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10102Manual Override ExistsRead0 = Off, 1 = On
BI10103Run EnableRead0 = Run Not Enabled, 1 = Run Enabled
BImin10104Local Setpoint ControlRead0 = Remote control, 1 = Local control
BI10105Maximum Capacity RelayRead0 = Off, 1 = On
BI10106Running Status Cprsr1ARead0 = Off, 1 = Running
BI10107Running Status Cprsr2ARead0 = Off, 1 = Running
BI10108Running Status Cprsr1BRead0 = Off, 1 = Running
BI10109Running Status Cprsr2BRead0 = Off, 1 = Running
BImin10110Chiller Running StateRead0 = Off, 1 = On
BI10111Running Status Cprsr1CRead0 = Off, 1 = Running
BI10112Running Status Cprsr2CRead0 = Off, 1 = Running
BI10113Free Cooling ActiveRead0 = Inactive, 1 = Active
BI10114Heat Recovery ActiveRead0 = Inactive, 1 = Active
BI10115Front Panel Auto/StopRead0 = Stop, 1 = Auto
BI10116Circuit Manual Reset Indicator (CMR) Circuit 1Read0 = Normal, 1 = In Alarm
BI10117Circuit Manual Reset Indicator (CMR) Circuit 2Read0 = Normal, 1 = In Alarm
BI10118Circuit Auto Reset Indicator (CAR) Circuit 1Read0 = Normal, 1 = In Alarm
BI10119Circuit Auto Reset Indicator (CAR) Circuit 2Read0 = Normal, 1 = In Alarm
BI10120Evaporator Water Pump CommandRead0 = Normal, 1 = In Alarm
BI10121Evaporator Water Flow StatusRead0 = Normal, 1 = In Alarm
BI10122Diagnostic Present: InformationRead0 = Normal, 1 = In Alarm
BI10123Diagnostic Present: AdvisoryRead0 = Normal, 1 = In Alarm
BI10124Diagnostic Present: CriticalRead0 = Normal, 1 = In Alarm
BI10125Diagnostic Present: Service RequiredRead0 = Normal, 1 = In Alarm
BImin10126Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10127Diagnostic Shutdown PresentRead0 = Normal, 1 = In Alarm
BI10128Diagnostic: Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10129Diagnostic: Local Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10130External Auto StopRead0 = Stop, 1 = Auto
BI10131Noise Reduction Request ActiveRead0 = Off, 1 = On
BI10132Heat Recovery Request ActiveRead0 = Off, 1 = On
BI10133Evaporator Water Pump StatusRead0 = Off, 1 = On
BI10134Circuit 1 Defrost Delay StatusRead0 = Off, 1 = On
BI10135Circuit 2 Defrost Delay StatusRead0 = Off, 1 = On
BI10136In DefrostRead0 = Not in Defrost, 1 = Defrost
BI10137Circuit 1 Defrost StatusRead0 = Inactive, 1 = Active
BI10138Circuit 2 Defrost StatusRead0 = Inactive, 1 = Active
BI10139Circuit 1 Running StatusRead0 = Off, 1 = On
BI10140Circuit 2 Running StatusRead0 = Off, 1 = On
BI10141Low Ambient Lockout StatusRead0 = No Lockout, 1 = Lockout Present
BI10142Circuit 1 Lockout Front PanelRead0 = Normal, 1 = Locked Out
BI10143Circuit 2 Lockout Front PanelRead0 = Normal, 1 = Locked Out
BI10144Circuit 1 Lockout ExternalRead0 = Normal, 1 = Locked Out
BI10145Circuit 2 Lockout ExternalRead0 = Normal, 1 = Locked Out
BI10146Circuit 1 Lockout ActiveRead0 = Normal, 1 = Locked Out
BI10147Circuit 2 Lockout ActiveRead0 = Normal, 1 = Locked Out
BI11000Comm Loss: Percent Capacity OutputRead0 = Normal, 1 = In Alarm
BI11001Comm Loss: Supplemental Heater Relay 1Read0 = Normal, 1 = In Alarm
BI11002Comm Loss: Supplemental Heater Relay 2Read0 = Normal, 1 = In Alarm
BI11003Comm Loss: Supplemental Heater Relay 3Read0 = Normal, 1 = In Alarm
BI11004Comm Loss: Supplemental Heater Relay 4Read0 = Normal, 1 = In Alarm
BI11005Comm Loss: Energy MeterRead0 = Normal, 1 = In Alarm
BI11006Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11007Comm Loss: Phase Protection Fault InputRead0 = Normal, 1 = In Alarm
BI11008Diagnostic: Energy Meter Write Command FailureRead0 = Normal, 1 = In Alarm
BI11009Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11010Diagnostic: Phase Protection FaultRead0 = Normal, 1 = In Alarm
BI11011Diagnostic: Software Error 1003: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11012Diagnostic: Pumpdown Terminated By Time - Circuit 2Read0 = Normal, 1 = In Alarm
BI11013Diagnostic: Pumpdown Terminated By Time - Circuit 1Read0 = Normal, 1 = In Alarm
BI11014Comm Loss: Discharge Pressure Transducer - Circuit 2Read0 = Normal, 1 = In Alarm
BI11015Comm Loss: Discharge Pressure Transducer - Circuit 1Read0 = Normal, 1 = In Alarm
BI11016Comm Loss: Discharge Temperature Sensor - Circuit 2Read0 = Normal, 1 = In Alarm
BI11017Comm Loss: Discharge Temperature Sensor - Circuit 1Read0 = Normal, 1 = In Alarm
BI11018Comm Loss: External Circuit 2 LockoutRead0 = Normal, 1 = In Alarm
BI11019Comm Loss: External Circuit 1 LockoutRead0 = Normal, 1 = In Alarm
BI11020Comm Loss: Reversing Valve - Circuit 1Read0 = Normal, 1 = In Alarm
BI11021Comm Loss: Reversing Valve - Circuit 2Read0 = Normal, 1 = In Alarm
BI11022Comm Loss: Suction Pressure Transducer - Circuit 2Read0 = Normal, 1 = In Alarm
BI11023Comm Loss: Suction Pressure Transducer - Circuit 1Read0 = Normal, 1 = In Alarm
BI11024Comm Loss: Suction Temperature - Circuit 2Read0 = Normal, 1 = In Alarm
BI11025Comm Loss: Suction Temperature - Circuit 1Read0 = Normal, 1 = In Alarm
BI11026Diagnostic: Discharge Pressure Transducer - Circuit 2Read0 = Normal, 1 = In Alarm
BI11027Diagnostic: Discharge Pressure Transducer - Circuit 1Read0 = Normal, 1 = In Alarm
BI11028Diagnostic: Discharge Temperature Sensor - Circuit 1Read0 = Normal, 1 = In Alarm
BI11029Diagnostic: Discharge Temperature Sensor - Circuit 2Read0 = Normal, 1 = In Alarm
BI11030Diagnostic: Suction Pressure Transducer - Circuit 2Read0 = Normal, 1 = In Alarm
BI11031Diagnostic: Suction Pressure Transducer - Circuit 1Read0 = Normal, 1 = In Alarm
BI11032Diagnostic: Suction Temperature Sensor - Circuit 2Read0 = Normal, 1 = In Alarm
BI11033Diagnostic: Suction Temperature Sensor - Circuit 1Read0 = Normal, 1 = In Alarm
BI11034Comm Loss: Sump Heater - Circuit 1Read0 = Normal, 1 = In Alarm
BI11035Comm Loss: Sump Heater - Circuit 2Read0 = Normal, 1 = In Alarm
BI11036Diagnostic: High Compressor Pressure Differential - Circuit 2Read0 = Normal, 1 = In Alarm
BI11037Diagnostic: High Compressor Pressure Differential - Circuit 1Read0 = Normal, 1 = In Alarm
BI11038Diagnostic: High Discharge Refrigerant Pressure - Circuit 2Read0 = Normal, 1 = In Alarm
BI11039Diagnostic: High Discharge Refrigerant Pressure - Circuit 1Read0 = Normal, 1 = In Alarm
BI11040Diagnostic: High Discharge Temperature - Circuit 2Read0 = Normal, 1 = In Alarm
BI11041Diagnostic: High Discharge Temperature - Circuit 1Read0 = Normal, 1 = In Alarm
BI11042Diagnostic: High Discharge Temperature Lockout - Circuit 2Read0 = Normal, 1 = In Alarm
BI11043Diagnostic: High Discharge Temperature Lockout - Circuit 1Read0 = Normal, 1 = In Alarm
BI11044Diagnostic: Loss of Charge - Circuit 2Read0 = Normal, 1 = In Alarm
BI11045Diagnostic: Loss of Charge - Circuit 1Read0 = Normal, 1 = In Alarm
BI11046Diagnostic: Low Discharge Saturated Temperature - Circuit 2Read0 = Normal, 1 = In Alarm
BI11047Diagnostic: Low Discharge Saturated Temperature - Circuit 1Read0 = Normal, 1 = In Alarm
BI11048Diagnostic: Low Refrigerant Pressure Ratio - Circuit 1Read0 = Normal, 1 = In Alarm
BI11049Diagnostic: Low Refrigerant Pressure Ratio - Circuit 2Read0 = Normal, 1 = In Alarm
BI11050Diagnostic: Low Refrigerant Temperature - Circuit 2Read0 = Normal, 1 = In Alarm
BI11051Diagnostic: Low Refrigerant Temperature - Circuit 1Read0 = Normal, 1 = In Alarm
BI11052Diagnostic: Low Suction Refrigerant Pressure - Circuit 2Read0 = Normal, 1 = In Alarm
BI11053Diagnostic: Low Suction Refrigerant Pressure - Circuit 1Read0 = Normal, 1 = In Alarm
BI11054Diagnostic: Low Suction Superheat - Circuit 2Read0 = Normal, 1 = In Alarm
BI11055Diagnostic: Low Suction Superheat - Circuit 1Read0 = Normal, 1 = In Alarm
BI11056Diagnostic: Suction Temperature Too High - Circuit 2Read0 = Normal, 1 = In Alarm
BI11057Diagnostic: Suction Temperature Too High - Circuit 1Read0 = Normal, 1 = In Alarm
BI11058Diagnostic: Very Low Suction Pressure - Circuit 1Read0 = Normal, 1 = In Alarm
BI11059Diagnostic: Very Low Suction Pressure - Circuit 2Read0 = Normal, 1 = In Alarm
BI11060Comm Loss: Compressor 1C Fault InputRead0 = Normal, 1 = In Alarm
BI11061Comm Loss: Compressor 1B Fault InputRead0 = Normal, 1 = In Alarm
BI11062Comm Loss: Compressor 1A Fault InputRead0 = Normal, 1 = In Alarm
BI11063Diagnostic: Compressor 1A FaultRead0 = Normal, 1 = In Alarm
BI11064Diagnostic: Compressor 1B FaultRead0 = Normal, 1 = In Alarm
BI11065Diagnostic: Compressor 1C FaultRead0 = Normal, 1 = In Alarm
BI11066Diagnostic: Compressor 1C Fault LockoutRead0 = Normal, 1 = In Alarm
BI11067Diagnostic: Compressor 1B Fault LockoutRead0 = Normal, 1 = In Alarm
BI11068Diagnostic: Compressor 1A Fault LockoutRead0 = Normal, 1 = In Alarm
BI11069Diagnostic: Starts/Hours Modified 1ARead0 = Normal, 1 = In Alarm
BI11070Diagnostic: Starts/Hours Modified 1BRead0 = Normal, 1 = In Alarm
BI11071Diagnostic: Starts/Hours Modified 1CRead0 = Normal, 1 = In Alarm
BI11072Comm Loss: Compressor 2C Fault InputRead0 = Normal, 1 = In Alarm
BI11073Comm Loss: Compressor 2B Fault InputRead0 = Normal, 1 = In Alarm
BI11074Comm Loss: Compressor 2A Fault InputRead0 = Normal, 1 = In Alarm
BI11075Diagnostic: Compressor 2A FaultRead0 = Normal, 1 = In Alarm
BI11076Diagnostic: Compressor 2B FaultRead0 = Normal, 1 = In Alarm
BI11077Diagnostic: Compressor 2C FaultRead0 = Normal, 1 = In Alarm
BI11078Diagnostic: Compressor 2C Fault LockoutRead0 = Normal, 1 = In Alarm
BI11079Diagnostic: Compressor 2B Fault LockoutRead0 = Normal, 1 = In Alarm
BI11080Diagnostic: Compressor 2A Fault LockoutRead0 = Normal, 1 = In Alarm
BI11081Diagnostic: Starts/Hours Modified 2BRead0 = Normal, 1 = In Alarm
BI11082Diagnostic: Starts/Hours Modified 2CRead0 = Normal, 1 = In Alarm
BI11083Diagnostic: Starts/Hours Modified 2ARead0 = Normal, 1 = In Alarm
BI11084Comm Loss: High Pressure Cutout Switch - Circuit 2Read0 = Normal, 1 = In Alarm
BI11085Comm Loss: High Pressure Cutout Switch - Circuit 1Read0 = Normal, 1 = In Alarm
BI11086Diagnostic: High Pressure Cutout - Circuit 2Read0 = Normal, 1 = In Alarm
BI11087Diagnostic: High Pressure Cutout - Circuit 1Read0 = Normal, 1 = In Alarm
BI11088Comm Loss: Shared V Coil Isolating Valve - Circuit 1Read0 = Normal, 1 = In Alarm
BI11089Comm Loss: Shared V Coil Isolating Valve - Circuit 2Read0 = Normal, 1 = In Alarm
BI11090Comm Loss: Dynamic Receiver Fill Valve - Circuit 1Read0 = Normal, 1 = In Alarm
BI11091Comm Loss: Dynamic Receiver Fill Valve - Circuit 2Read0 = Normal, 1 = In Alarm
BI11092Comm Loss: Hot Gas Bypass Valve - Circuit 1Read0 = Normal, 1 = In Alarm
BI11093Comm Loss: Hot Gas Bypass Valve - Circuit 2Read0 = Normal, 1 = In Alarm
BI11094Comm Loss: Liquid Line Pressure - Circuit 1Read0 = Normal, 1 = In Alarm
BI11095Comm Loss: Liquid Line Pressure - Circuit 2Read0 = Normal, 1 = In Alarm
BI11096Comm Loss: Liquid Line Temperature - Circuit 1Read0 = Normal, 1 = In Alarm
BI11097Comm Loss: Liquid Line Temperature - Circuit 2Read0 = Normal, 1 = In Alarm
BI11098Diagnostic: Liquid Line Pressure Transducer - Circuit 1Read0 = Normal, 1 = In Alarm
BI11099Diagnostic: Liquid Line Pressure Transducer - Circuit 2Read0 = Normal, 1 = In Alarm
BI11100Diagnostic: Liquid Line Temperature Sensor - Circuit 1Read0 = Normal, 1 = In Alarm
BI11101Diagnostic: Liquid Line Temperature Sensor - Circuit 2Read0 = Normal, 1 = In Alarm
BI11102Comm Loss:Evaporator Antifreeze HeaterRead0 = Normal, 1 = In Alarm
BI11103Comm Loss:Heat Recovery Antifreeze HeaterRead0 = Normal, 1 = In Alarm
BI11104Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11105Diagnostic: Evaporator Water Flow Lost LockoutRead0 = Normal, 1 = In Alarm
BI11106Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11107Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11108Diagnostic: High Suction Rfgt PressureRead0 = Normal, 1 = In Alarm
BI11109Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11110Diagnostic: Inverted Water Temp (Heating)Read0 = Normal, 1 = In Alarm
BI11111Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11112Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11113Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11114Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11115Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11116Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11117Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11118Comm Loss: Cooling EXV - Circuit 1Read0 = Normal, 1 = In Alarm
BI11119Comm Loss: Cooling EXV - Circuit 2Read0 = Normal, 1 = In Alarm
BI11120Comm Loss: Electronic Expansion Valve - Circuit 2Read0 = Normal, 1 = In Alarm
BI11121Comm Loss: Electronic Expansion Valve - Circuit 1Read0 = Normal, 1 = In Alarm
BI11122Comm Loss: Heating EXV - Circuit 1Read0 = Normal, 1 = In Alarm
BI11123Comm Loss: Heating EXV - Circuit 2Read0 = Normal, 1 = In Alarm
BI11124Comm Loss: Auxiliary Setpoint CommandRead0 = Normal, 1 = In Alarm
BI11125Comm Loss: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11126Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11127Comm Loss: Ext Noise Reduction RequestRead0 = Normal, 1 = In Alarm
BI11128Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11129Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11130Comm Loss: External Hot Water CommandRead0 = Normal, 1 = In Alarm
BI11131Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11132Comm Loss: Programmable Relay Board 2Read0 = Normal, 1 = In Alarm
BI11133Diagnostic: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11134Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11135Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11136Comm Loss: Condenser Fan Enable - Circuit 2Read0 = Normal, 1 = In Alarm
BI11137Comm Loss: Condenser Fan Enable - Circuit 1Read0 = Normal, 1 = In Alarm
BI11138Comm Loss: Cond Fan Enbl Shared Ckt 1&2Read0 = Normal, 1 = In Alarm
BI11139Comm Loss: Condenser Fan Fault - Circuit 1Read0 = Normal, 1 = In Alarm
BI11140Comm Loss: Condenser Fan Fault - Circuit 2Read0 = Normal, 1 = In Alarm
BI11141Comm Loss: Fan Board 1 Relay 1 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11142Comm Loss: Fan Board 1 Relay 1 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11143Comm Loss: Fan Board 1 Relay 2 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11144Comm Loss: Fan Board 1 Relay 2 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11145Comm Loss: Fan Board 1 Relay 3 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11146Comm Loss: Fan Board 1 Relay 3 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11147Comm Loss: Fan Board 1 Relay 4 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11148Comm Loss: Fan Board 1 Relay 4 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11149Comm Loss: Fan Board 2 Relay 1 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11150Comm Loss: Fan Board 2 Relay 1 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11151Comm Loss: Fan Board 2 Relay 2 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11152Comm Loss: Fan Board 2 Relay 2 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11153Comm Loss: Fan Board 2 Relay 3 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11154Comm Loss: Fan Board 2 Relay 3 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11155Comm Loss: Fan Board 2 Relay 4 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11156Comm Loss: Fan Board 2 Relay 4 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11157Comm Loss: Fan Inverter Speed Command - Circuit 2Read0 = Normal, 1 = In Alarm
BI11158Comm Loss: Fan Inverter Speed Command - Circuit 1Read0 = Normal, 1 = In Alarm
BI11159Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1&2Read0 = Normal, 1 = In Alarm
BI11160Comm Loss: Fan Speed Select Board Relay 1 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11161Comm Loss: Fan Speed Select Board Relay 2 - Circuit 1Read0 = Normal, 1 = In Alarm
BI11162Comm Loss: Fan Speed Select Board Relay 3 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11163Comm Loss: Fan Speed Select Board Relay 4 - Circuit 2Read0 = Normal, 1 = In Alarm
BI11164Diagnostic: Condenser Fan Fault - Circuit 1Read0 = Normal, 1 = In Alarm
BI11165Diagnostic: Condenser Fan Fault - Circuit 2Read0 = Normal, 1 = In Alarm
BI11166Comm Loss: FC Entering Glycol TempRead0 = Normal, 1 = In Alarm
BI11167Comm Loss: FC Entering Water TempRead0 = Normal, 1 = In Alarm
BI11168Comm Loss: FC Leaving Glycol TempRead0 = Normal, 1 = In Alarm
BI11169Comm Loss: Free Cooling Glycol Flow SwitchRead0 = Normal, 1 = In Alarm
BI11170Comm Loss: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11171Comm Loss: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11172Comm Loss: Free Cooling PumpRead0 = Normal, 1 = In Alarm
BI11173Comm Loss: Free Cooling ValveRead0 = Normal, 1 = In Alarm
BI11174Diagnostic: Free Cooling Entering Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11175Diagnostic: Free Cooling Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11176Diagnostic: Free Cooling Glycol Flow LostRead0 = Normal, 1 = In Alarm
BI11177Diagnostic: Free Cooling Glycol Flow OverdueRead0 = Normal, 1 = In Alarm
BI11178Diagnostic: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11179Diagnostic: Free Cooling Glycol Temperature Equalization OverdueRead0 = Normal, 1 = In Alarm
BI11180Diagnostic: Free Cooling Leaving Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11181Diagnostic: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11182Diagnostic: Low Glycol Pressure Free CoolingRead0 = Normal, 1 = In Alarm
BI11183Diagnostic: Low Glycol Temp Free CoolingRead0 = Normal, 1 = In Alarm
BI11184Comm Loss: External Heat Recovery CommandRead0 = Normal, 1 = In Alarm
BI11185Comm Loss: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11186Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11187Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 2Read0 = Normal, 1 = In Alarm
BI11188Comm Loss: HR Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11189Comm Loss: HR Leaving Water TemperatureRead0 = Normal, 1 = In Alarm
BI11190Comm Loss: Heat Recovery Three Way ValveRead0 = Normal, 1 = In Alarm
BI11191Diagnostic: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11192Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11193Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11194Diagnostic: No Heat RecoveryRead0 = Normal, 1 = In Alarm
BI11195Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11196Diagnostic: Restart Inhibit Invoked - 1ARead0 = Normal, 1 = In Alarm
BI11197Diagnostic: Restart Inhibit Invoked - 1BRead0 = Normal, 1 = In Alarm
BI11198Diagnostic: Restart Inhibit Invoked - 1CRead0 = Normal, 1 = In Alarm
BI11199Diagnostic: Restart Inhibit Invoked - 2ARead0 = Normal, 1 = In Alarm
BI11200Diagnostic: Restart Inhibit Invoked - 2BRead0 = Normal, 1 = In Alarm
BI11201Diagnostic: Restart Inhibit Invoked - 2CRead0 = Normal, 1 = In Alarm
BI11202Comm Loss: Energy Meter Pulse InputRead0 = Normal, 1 = In Alarm
BI11203Comm Loss: Run Command Compressor 1ARead0 = Normal, 1 = In Alarm
BI11204Comm Loss: Run Command Compressor 1BRead0 = Normal, 1 = In Alarm
BI11205Comm Loss: Run Command Compressor 1CRead0 = Normal, 1 = In Alarm
BI11206Comm Loss: Run Command Compressor 2ARead0 = Normal, 1 = In Alarm
BI11207Comm Loss: Run Command Compressor 2BRead0 = Normal, 1 = In Alarm
BI11208Comm Loss: Run Command Compressor 2CRead0 = Normal, 1 = In Alarm
BI11209Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11210Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11211Comm Loss: Evap Pump Inv1 Fault InputRead0 = Normal, 1 = In Alarm
BI11212Comm Loss: Evap Pump Inv1 Freq FeedbackRead0 = Normal, 1 = In Alarm
BI11213Comm Loss: Evap Pump Inv1 Run CommandRead0 = Normal, 1 = In Alarm
BI11214Comm Loss: Evaporator Pump 2 Fault InputRead0 = Normal, 1 = In Alarm
BI11215Comm Loss: Evaporator Water Pump 1 RelayRead0 = Normal, 1 = In Alarm
BI11216Comm Loss: Evaporator Water Pump 2 RelayRead0 = Normal, 1 = In Alarm
BI11217Comm Loss: Evaporator Pump 1 Fault InputRead0 = Normal, 1 = In Alarm
BI11218Diagnostic: Evap Pump 1 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11219Diagnostic: Evap Pump 2 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11220Diagnostic: Evaporator Pump 1 FaultRead0 = Normal, 1 = In Alarm
BI11221Diagnostic: Evaporator Pump 2 FaultRead0 = Normal, 1 = In Alarm
BI11222Diagnostic: Evaporator Water Flow Lost - Pump1Read0 = Normal, 1 = In Alarm
BI11223Diagnostic: Evaporator Water Flow Lost - Pump2Read0 = Normal, 1 = In Alarm
BI11224Diagnostic: Evaporator Water Flow Overdue - Pump1Read0 = Normal, 1 = In Alarm
BI11225Diagnostic: Evaporator Water Flow Overdue - Pump2Read0 = Normal, 1 = In Alarm
BI11226Comm Loss: SLHX Entering Refrigerant Temp - Circuit 1Read0 = Normal, 1 = In Alarm
BI11227Comm Loss: SLHX Entering Refrigerant Temp - Circuit 2Read0 = Normal, 1 = In Alarm
BI11228Comm Loss: SLHX Valve - Circuit 1Read0 = Normal, 1 = In Alarm
BI11229Comm Loss: SLHX Valve - Circuit 2Read0 = Normal, 1 = In Alarm
BI11230Diagnostic: SLHX Entering Temp Sensor - Circuit 1Read0 = Normal, 1 = In Alarm
BI11231Diagnostic: SLHX Entering Temp Sensor - Circuit 2Read0 = Normal, 1 = In Alarm
BI11232Diagnostic: Chiller Service RecommendedRead0 = Normal, 1 = In Alarm
BI11233Diagnostic: Evap Water Pump 1 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11234Diagnostic: Evap Water Pump 2 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11235Diagnostic: Mfr Maintenance Recommended - 1ARead0 = Normal, 1 = In Alarm
BI11236Diagnostic: Mfr Maintenance Recommended - 1BRead0 = Normal, 1 = In Alarm
BI11237Diagnostic: Mfr Maintenance Recommended - 1CRead0 = Normal, 1 = In Alarm
BI11238Diagnostic: Mfr Maintenance Recommended - 2ARead0 = Normal, 1 = In Alarm
BI11239Diagnostic: Mfr Maintenance Recommended - 2BRead0 = Normal, 1 = In Alarm
BI11240Diagnostic: Mfr Maintenance Recommended - 2CRead0 = Normal, 1 = In Alarm
BI11241Diagnostic: Evaporator Water Flow Too LowRead0 = Normal, 1 = In Alarm
BI11242Comm Loss: Evap Water Pump Inverter SpeedRead0 = Normal, 1 = In Alarm
BI11243Energy Meter Write Value FailureRead0 = Normal, 1 = In Alarm
BV10100Reset DiagnosticWrite0 = Normal, 1 = Reset
BV10101BAS Noise Reduction RequestWrite0 = Normal, 1 = Reduce Noise
BV10102BAS Heat Recovery CommandWrite0 = Off, 1 = On
BV10103Energy Consumption ResetWrite0 = Accumulating, 1 = Reset
BV10104BAS Circuit 1 LockoutWrite0 = Normal, 1 = Locked Out
BV10105BAS Circuit 2 LockoutWrite0 = Normal, 1 = Locked Out
BV10106BAS Free Cooling Auto Stop CommandWrite0 = Stop, 1 = Auto
BVmin10107BAS Chiller Auto Stop CommandWrite0 = Stop, 1 = Auto
BV10108Evaporator Water Pump Request BASWrite0 = Auto, 1 = On
BV10109Defrost Delay Request BASWrite0 = Off, 1 = On
MI10100Running ModeRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Chiller Setpoint SourceRead1 = BAS, 2 = External, 3 = Front Panel
MI10103Refrigerant TypeRead1 = R-11, 2 = R-12, 3= R-22, 4= R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234z(E), 17 = R-454B, 18 = R-515B
MI10104Cooling TypeRead1 = Water Cooled, 2 = Air Cooled
MI10105Manufacture LocationRead1 = Field Applied, 2= La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey
MI10107Front Panel Chiller Mode CommandRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10108Model Information [GEN2]Read1 = CVHF, 2 = CVGF, 3= CVHS, 4= RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTW, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = ACXA, 35 = CMAF, 36 = ACRB (375 to 550 tons), 37 = ACRB (150 to 300 tons)
MI10109Circuit 1 StatusRead1 = Available, 2 = Heat Recovery, 3 = Cooling, 4 = Heating, 5 = Defrost, 6 = Not Available
MI10110Circuit 2 StatusRead1 = Available, 2 = Heat Recovery, 3 = Cooling, 4 = Heating, 5 = Defrost, 6 = Not Available
MVmin10100Chiller Mode Command BASBAS Chiller Mode CommandWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Ascend ACS / ACX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 Ascend ACS / ACX

How many BACnet points does the Trane Symbio 800 Ascend ACS / ACX have?

This list has 397 BACnet objects: 79 analog inputs, 5 analog values, 292 binary inputs, 10 binary values, 10 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 Ascend ACS / ACX BACnet points are writable?

16 of the 397 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 Ascend ACS / ACX BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX (BAS-PTS011A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS011A-EN_11152024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 Ascend ACS / ACX?

Start with BV 10107 BAS Chiller Auto Stop Command (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10110 Chiller Running State (Chiller on/off status); BI 10104 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10101 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10116 Actual Running Capacity (Actual running capacity in percent); BI 10126 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 Ascend ACS / ACX?

BV 10107 BAS Chiller Auto Stop Command (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10130 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

How do I check these points on the real Symbio 800 Ascend ACS / ACX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.