Air-cooled chiller controller · BACnet points list
Trane Symbio 800 Ascend ACS / ACX BACnet points list
Updated 28 October 2026
Ascend ACS/ACX chillers expose about 400 BACnet objects through the Symbio 800. Status values are AI/BI/MI, and the BAS writes a small set of AV/BV/MV objects for chilled and hot water setpoints, demand limit, mode, circuit lockouts and auto/stop. Most binary inputs are individual diagnostic flags.
This page lists 397 BACnet objects for the Trane Symbio 800 Ascend ACS / ACX — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 Ascend ACS / ACX
- Equipment
- Air-cooled chiller controller
- Equipment type
- Chillers
- BACnet objects
- 397 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011
BMS integration notes: Trane Symbio 800 Ascend ACS / ACX
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10107 | BAS Chiller Auto Stop Command | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10110 | Chiller Running State | Chiller on/off status | Read |
| BI 10104 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10101 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10116 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10126 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10107 BAS Chiller Auto Stop Command (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10130 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 Ascend ACS / ACX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Cool/Heat Setpoint Temperature | Temperature | Read | ||
| AImin | 10101 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10102 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AI | 10103 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10104 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10105 | Outdoor Air Temperature | Temperature | Read | ||
| AI | 10106 | Evaporator Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10107 | Condenser Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10108 | Differential Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10109 | Evaporator Saturated Rfgt Temp Circuit 1 | Temperature | Read | ||
| AI | 10110 | Condenser Saturated Rfgt Temp Circuit 1 | Temperature | Read | ||
| AI | 10111 | Evaporator Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10112 | Condenser Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10113 | Differential Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10114 | Evaporator Saturated Rfgt Temp Circuit 2 | Temperature | Read | ||
| AI | 10115 | Condenser Saturated Rfgt Temp Circuit 2 | Temperature | Read | ||
| AImin | 10116 | Actual Running Capacity | Percentage | Read | ||
| AI | 10117 | Active Heat Recovery Setpoint | Temperature | Read | ||
| AI | 10118 | Active Hot Water Setpoint | Temperature | Read | ||
| AI | 10119 | Air Flow Circuit 1 | Percentage | Read | ||
| AI | 10120 | Air Flow Circuit 2 | Percentage | Read | ||
| AI | 10121 | Starts Cprsr1A | Read | |||
| AI | 10122 | Running Time Cprsr1A | Read | |||
| AI | 10123 | Starts Cprsr2A | Read | |||
| AI | 10124 | Running Time Cprsr2A | Read | |||
| AI | 10125 | Heat Recovery Entering Water Temp | Temperature | Read | ||
| AI | 10126 | Heat Recovery Leaving Water Temp | Temperature | Read | ||
| AI | 10127 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10128 | Starts Cprsr1B | Read | |||
| AI | 10129 | Running Time Cprsr1B | Read | |||
| AI | 10130 | Starts Cprsr2B | Read | |||
| AI | 10131 | Running Time Cprsr2B | Read | |||
| AI | 10132 | Number Of Circuits | Read | |||
| AI | 10133 | Number of Compressors for Circuit 1 | Read | |||
| AI | 10134 | Number of Compressors for Circuit 2 | Read | |||
| AI | 10135 | Free Cooling Capacity | Percentage | Read | ||
| AI | 10136 | Free Cooling Entering Water Temperature | Temperature | Read | ||
| AI | 10137 | Free Cooling Entering Glycol Temperature | Temperature | Read | ||
| AI | 10138 | Free Cooling Leaving Glycol Temperature | Temperature | Read | ||
| AI | 10139 | Energy Consumption NonReset | Power, Electrical | Read | ||
| AI | 10140 | Energy Consumption Resettable | Power, Electrical | Read | ||
| AI | 10141 | Starts Cprsr1C | Read | |||
| AI | 10142 | Running Time Cprsr1C | Read | |||
| AI | 10143 | Starts Cprsr2C | Read | |||
| AI | 10144 | Running Time Cprsr2C | Read | |||
| AI | 10145 | Estimated Discharge Temperature Circuit 1 | Temperature | Read | ||
| AI | 10146 | Estimated Discharge Temperature Circuit 2 | Temperature | Read | ||
| AI | 10147 | Compressor Discharge Temperature Circuit 1 | Temperature | Read | ||
| AI | 10148 | Compressor Discharge Temperature Circuit 2 | Temperature | Read | ||
| AI | 10149 | Free Cooling Glycol Pressure | Pressure, Fluidic | Read | ||
| AI | 10150 | Last Logged Diagnostic | Read | |||
| AI | 10151 | Unit Load Command | Percentage | Read | ||
| AI | 10152 | Average Line Current | Current | Read | ||
| AI | 10153 | Average Line Voltage | Voltage | Read | ||
| AI | 10154 | Current L1 | Current | Read | ||
| AI | 10155 | Current L2 | Current | Read | ||
| AI | 10156 | Current L3 | Current | Read | ||
| AI | 10157 | Voltage L1-L2 | Voltage | Read | ||
| AI | 10158 | Voltage L2-L3 | Voltage | Read | ||
| AI | 10159 | Voltage L1-L3 | Voltage | Read | ||
| AI | 10160 | Total Real Power | Power, Electrical | Read | ||
| AI | 10161 | Line Frequency | Read | |||
| AI | 10162 | Power Factor | Read | |||
| AI | 10163 | Heat Recovery Valve Position | Percentage | Read | ||
| AI | 10164 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10165 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10166 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10167 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10168 | Free Cooling Glycol Absolute Pressure | Pressure, Fluidic | Read | ||
| AI | 10169 | Supplemental Heater Status | Percentage | Read | ||
| AI | 10170 | Evaporator Approach Temperature Circuit 1 (Cooling Mode Only) | Temperature | Read | ||
| AI | 10171 | Evaporator Approach Temperature Circuit 2 (Cooling Mode Only) | Temperature | Read | ||
| AI | 10172 | Condenser Approach Temperature Circuit 1 (Heating Mode Only) | Temperature | Read | ||
| AI | 10173 | Condenser Approach Temperature Circuit 2 (Heating Mode Only) | Temperature | Read | ||
| AI | 10174 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10175 | Chilled Water Setpoint Status | Temperature | Read | ||
| AI | 10176 | Hot Water Setpoint Status | Temperature | Read | ||
| AI | 10177 | Demand Limit Setpoint Status | Percentage | Read | ||
| AI | 10178 | Active Demand Limit Setpoint | Percentage | Read | ||
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percentage | Write | ||
| AV | 10102 | BAS Hot Water Setpoint | Temperature | Write | ||
| AV | 10103 | BAS Heat Recovery Setpoint | Temperature | Write | ||
| AV | 10104 | Evaporator Water Pump Speed Setpoint | Percentage | Write | ||
| BI | 10100 | Limit Mode Relay Status | Read | 0 = Auto, 1 = On | ||
| BI | 10101 | Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | ||
| BI | 10102 | Manual Override Exists | Read | 0 = Off, 1 = On | ||
| BI | 10103 | Run Enable | Read | 0 = Run Not Enabled, 1 = Run Enabled | ||
| BImin | 10104 | Local Setpoint Control | Read | 0 = Remote control, 1 = Local control | ||
| BI | 10105 | Maximum Capacity Relay | Read | 0 = Off, 1 = On | ||
| BI | 10106 | Running Status Cprsr1A | Read | 0 = Off, 1 = Running | ||
| BI | 10107 | Running Status Cprsr2A | Read | 0 = Off, 1 = Running | ||
| BI | 10108 | Running Status Cprsr1B | Read | 0 = Off, 1 = Running | ||
| BI | 10109 | Running Status Cprsr2B | Read | 0 = Off, 1 = Running | ||
| BImin | 10110 | Chiller Running State | Read | 0 = Off, 1 = On | ||
| BI | 10111 | Running Status Cprsr1C | Read | 0 = Off, 1 = Running | ||
| BI | 10112 | Running Status Cprsr2C | Read | 0 = Off, 1 = Running | ||
| BI | 10113 | Free Cooling Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10114 | Heat Recovery Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10115 | Front Panel Auto/Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10116 | Circuit Manual Reset Indicator (CMR) Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10117 | Circuit Manual Reset Indicator (CMR) Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10118 | Circuit Auto Reset Indicator (CAR) Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10119 | Circuit Auto Reset Indicator (CAR) Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10120 | Evaporator Water Pump Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10121 | Evaporator Water Flow Status | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10122 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10123 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10124 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10125 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BImin | 10126 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10127 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10128 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10129 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10130 | External Auto Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10131 | Noise Reduction Request Active | Read | 0 = Off, 1 = On | ||
| BI | 10132 | Heat Recovery Request Active | Read | 0 = Off, 1 = On | ||
| BI | 10133 | Evaporator Water Pump Status | Read | 0 = Off, 1 = On | ||
| BI | 10134 | Circuit 1 Defrost Delay Status | Read | 0 = Off, 1 = On | ||
| BI | 10135 | Circuit 2 Defrost Delay Status | Read | 0 = Off, 1 = On | ||
| BI | 10136 | In Defrost | Read | 0 = Not in Defrost, 1 = Defrost | ||
| BI | 10137 | Circuit 1 Defrost Status | Read | 0 = Inactive, 1 = Active | ||
| BI | 10138 | Circuit 2 Defrost Status | Read | 0 = Inactive, 1 = Active | ||
| BI | 10139 | Circuit 1 Running Status | Read | 0 = Off, 1 = On | ||
| BI | 10140 | Circuit 2 Running Status | Read | 0 = Off, 1 = On | ||
| BI | 10141 | Low Ambient Lockout Status | Read | 0 = No Lockout, 1 = Lockout Present | ||
| BI | 10142 | Circuit 1 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10143 | Circuit 2 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10144 | Circuit 1 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10145 | Circuit 2 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10146 | Circuit 1 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10147 | Circuit 2 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 11000 | Comm Loss: Percent Capacity Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Comm Loss: Supplemental Heater Relay 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Comm Loss: Supplemental Heater Relay 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Comm Loss: Supplemental Heater Relay 3 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Comm Loss: Supplemental Heater Relay 4 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Comm Loss: Energy Meter | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Comm Loss: Phase Protection Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: Energy Meter Write Command Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: Phase Protection Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Diagnostic: Pumpdown Terminated By Time - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Diagnostic: Pumpdown Terminated By Time - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Comm Loss: Discharge Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Comm Loss: Discharge Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Comm Loss: Discharge Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Comm Loss: Discharge Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Comm Loss: External Circuit 2 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Comm Loss: External Circuit 1 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Comm Loss: Reversing Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Comm Loss: Reversing Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Comm Loss: Suction Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Comm Loss: Suction Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Comm Loss: Suction Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Comm Loss: Suction Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Diagnostic: Discharge Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: Discharge Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: Discharge Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Diagnostic: Discharge Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Diagnostic: Suction Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: Suction Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: Suction Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: Suction Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Comm Loss: Sump Heater - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Comm Loss: Sump Heater - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Diagnostic: High Compressor Pressure Differential - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Diagnostic: High Compressor Pressure Differential - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: High Discharge Refrigerant Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Diagnostic: High Discharge Refrigerant Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Diagnostic: High Discharge Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Diagnostic: High Discharge Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Diagnostic: High Discharge Temperature Lockout - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Diagnostic: High Discharge Temperature Lockout - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Diagnostic: Loss of Charge - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Diagnostic: Loss of Charge - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: Low Discharge Saturated Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Diagnostic: Low Discharge Saturated Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Diagnostic: Low Refrigerant Pressure Ratio - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Diagnostic: Low Refrigerant Pressure Ratio - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Diagnostic: Low Refrigerant Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Diagnostic: Low Refrigerant Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Diagnostic: Low Suction Refrigerant Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Diagnostic: Low Suction Refrigerant Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Diagnostic: Low Suction Superheat - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Diagnostic: Low Suction Superheat - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Diagnostic: Suction Temperature Too High - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Diagnostic: Suction Temperature Too High - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Diagnostic: Very Low Suction Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Diagnostic: Very Low Suction Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Compressor 1C Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Compressor 1B Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Compressor 1A Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Diagnostic: Compressor 1A Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Diagnostic: Compressor 1B Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Diagnostic: Compressor 1C Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Diagnostic: Compressor 1C Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Diagnostic: Compressor 1B Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Diagnostic: Compressor 1A Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Diagnostic: Starts/Hours Modified 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Diagnostic: Starts/Hours Modified 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Diagnostic: Starts/Hours Modified 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Compressor 2C Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Compressor 2B Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Compressor 2A Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Diagnostic: Compressor 2A Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Diagnostic: Compressor 2B Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Diagnostic: Compressor 2C Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Diagnostic: Compressor 2C Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Diagnostic: Compressor 2B Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Diagnostic: Compressor 2A Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Diagnostic: Starts/Hours Modified 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Diagnostic: Starts/Hours Modified 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Diagnostic: Starts/Hours Modified 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: High Pressure Cutout Switch - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: High Pressure Cutout Switch - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Diagnostic: High Pressure Cutout - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Diagnostic: High Pressure Cutout - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Shared V Coil Isolating Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Shared V Coil Isolating Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Dynamic Receiver Fill Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Dynamic Receiver Fill Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Hot Gas Bypass Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: Hot Gas Bypass Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: Liquid Line Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Comm Loss: Liquid Line Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Comm Loss: Liquid Line Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: Liquid Line Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Diagnostic: Liquid Line Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Diagnostic: Liquid Line Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Diagnostic: Liquid Line Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Diagnostic: Liquid Line Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss:Evaporator Antifreeze Heater | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss:Heat Recovery Antifreeze Heater | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Diagnostic: Evaporator Water Flow Lost Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Diagnostic: High Suction Rfgt Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Diagnostic: Inverted Water Temp (Heating) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Diagnostic: Low Evaporator Water Temp (Unit On) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Cooling EXV - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Cooling EXV - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Electronic Expansion Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Electronic Expansion Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Heating EXV - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Heating EXV - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Auxiliary Setpoint Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Ext Noise Reduction Request | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Diagnostic: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Condenser Fan Enable - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Condenser Fan Enable - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Cond Fan Enbl Shared Ckt 1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Condenser Fan Fault - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Condenser Fan Fault - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Fan Board 1 Relay 1 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Fan Board 1 Relay 1 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Fan Board 1 Relay 2 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Fan Board 1 Relay 2 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Fan Board 1 Relay 3 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Comm Loss: Fan Board 1 Relay 3 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Comm Loss: Fan Board 1 Relay 4 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Comm Loss: Fan Board 1 Relay 4 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Comm Loss: Fan Board 2 Relay 1 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Fan Board 2 Relay 1 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Fan Board 2 Relay 2 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Fan Board 2 Relay 2 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Fan Board 2 Relay 3 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Fan Board 2 Relay 3 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Fan Board 2 Relay 4 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Fan Board 2 Relay 4 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Comm Loss: Fan Inverter Speed Command - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Comm Loss: Fan Inverter Speed Command - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Fan Speed Select Board Relay 1 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Fan Speed Select Board Relay 2 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Fan Speed Select Board Relay 3 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Fan Speed Select Board Relay 4 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Diagnostic: Condenser Fan Fault - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Diagnostic: Condenser Fan Fault - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Comm Loss: FC Entering Glycol Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Comm Loss: FC Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Comm Loss: FC Leaving Glycol Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Comm Loss: Free Cooling Glycol Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Comm Loss: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Comm Loss: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Comm Loss: Free Cooling Pump | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Comm Loss: Free Cooling Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Diagnostic: Free Cooling Entering Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Diagnostic: Free Cooling Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Diagnostic: Free Cooling Glycol Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Diagnostic: Free Cooling Glycol Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Diagnostic: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Diagnostic: Free Cooling Glycol Temperature Equalization Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Diagnostic: Free Cooling Leaving Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Diagnostic: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: Low Glycol Pressure Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: Low Glycol Temp Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Comm Loss: External Heat Recovery Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Comm Loss: External Heat Recovery Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Comm Loss: HR Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Comm Loss: HR Leaving Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Comm Loss: Heat Recovery Three Way Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: External Heat Recovery Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: No Heat Recovery | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Restart Inhibit Invoked - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Restart Inhibit Invoked - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Restart Inhibit Invoked - 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Restart Inhibit Invoked - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Restart Inhibit Invoked - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: Restart Inhibit Invoked - 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Comm Loss: Energy Meter Pulse Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Comm Loss: Run Command Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Comm Loss: Run Command Compressor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Comm Loss: Run Command Compressor 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Comm Loss: Run Command Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Comm Loss: Run Command Compressor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Comm Loss: Run Command Compressor 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Comm Loss: Evap Pump Inv1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Comm Loss: Evap Pump Inv1 Freq Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Comm Loss: Evap Pump Inv1 Run Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Comm Loss: Evaporator Pump 2 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Comm Loss: Evaporator Water Pump 1 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Comm Loss: Evaporator Water Pump 2 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Comm Loss: Evaporator Pump 1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Evap Pump 1 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: Evap Pump 2 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: Evaporator Pump 1 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Evaporator Pump 2 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Evaporator Water Flow Lost - Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: Evaporator Water Flow Lost - Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: Evaporator Water Flow Overdue - Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: Evaporator Water Flow Overdue - Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Comm Loss: SLHX Entering Refrigerant Temp - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Comm Loss: SLHX Entering Refrigerant Temp - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Comm Loss: SLHX Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Comm Loss: SLHX Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: SLHX Entering Temp Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: SLHX Entering Temp Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Chiller Service Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: Evap Water Pump 1 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: Evap Water Pump 2 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Mfr Maintenance Recommended - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: Mfr Maintenance Recommended - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: Mfr Maintenance Recommended - 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: Mfr Maintenance Recommended - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: Mfr Maintenance Recommended - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: Mfr Maintenance Recommended - 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: Evaporator Water Flow Too Low | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Comm Loss: Evap Water Pump Inverter Speed | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Energy Meter Write Value Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Reset Diagnostic | Write | 0 = Normal, 1 = Reset | ||
| BV | 10101 | BAS Noise Reduction Request | Write | 0 = Normal, 1 = Reduce Noise | ||
| BV | 10102 | BAS Heat Recovery Command | Write | 0 = Off, 1 = On | ||
| BV | 10103 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| BV | 10104 | BAS Circuit 1 Lockout | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10105 | BAS Circuit 2 Lockout | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10106 | BAS Free Cooling Auto Stop Command | Write | 0 = Stop, 1 = Auto | ||
| BVmin | 10107 | BAS Chiller Auto Stop Command | Write | 0 = Stop, 1 = Auto | ||
| BV | 10108 | Evaporator Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BV | 10109 | Defrost Delay Request BAS | Write | 0 = Off, 1 = On | ||
| MI | 10100 | Running Mode | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | ||
| MI | 10101 | Operating Mode | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10102 | Chiller Setpoint Source | Read | 1 = BAS, 2 = External, 3 = Front Panel | ||
| MI | 10103 | Refrigerant Type | Read | 1 = R-11, 2 = R-12, 3= R-22, 4= R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234z(E), 17 = R-454B, 18 = R-515B | ||
| MI | 10104 | Cooling Type | Read | 1 = Water Cooled, 2 = Air Cooled | ||
| MI | 10105 | Manufacture Location | Read | 1 = Field Applied, 2= La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey | ||
| MI | 10107 | Front Panel Chiller Mode Command | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10108 | Model Information [GEN2] | Read | 1 = CVHF, 2 = CVGF, 3= CVHS, 4= RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTW, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = ACXA, 35 = CMAF, 36 = ACRB (375 to 550 tons), 37 = ACRB (150 to 300 tons) | ||
| MI | 10109 | Circuit 1 Status | Read | 1 = Available, 2 = Heat Recovery, 3 = Cooling, 4 = Heating, 5 = Defrost, 6 = Not Available | ||
| MI | 10110 | Circuit 2 Status | Read | 1 = Available, 2 = Heat Recovery, 3 = Cooling, 4 = Heating, 5 = Defrost, 6 = Not Available | ||
| MVmin | 10100 | Chiller Mode Command BAS | BAS Chiller Mode Command | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the actual engineering unit follows the controller's display-unit setting.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Ascend ACS / ACX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 Ascend ACS / ACX
How many BACnet points does the Trane Symbio 800 Ascend ACS / ACX have?
This list has 397 BACnet objects: 79 analog inputs, 5 analog values, 292 binary inputs, 10 binary values, 10 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 Ascend ACS / ACX BACnet points are writable?
16 of the 397 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 Ascend ACS / ACX BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX (BAS-PTS011A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS011A-EN_11152024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 Ascend ACS / ACX?
Start with BV 10107 BAS Chiller Auto Stop Command (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10110 Chiller Running State (Chiller on/off status); BI 10104 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10101 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10116 Actual Running Capacity (Actual running capacity in percent); BI 10126 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 Ascend ACS / ACX?
BV 10107 BAS Chiller Auto Stop Command (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10130 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 Ascend ACS / ACX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013
Source: Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.