Air-cooled screw chiller controller · BACnet points list

Trane Symbio 800 Sintesis RTAF BACnet points list

Updated 28 October 2026

Short answer

Sintesis RTAF chillers with Symbio 800 publish about 830 BACnet objects, each also mapped to a Modbus register in the same table. About 540 are per-alarm diagnostic binary inputs; the rest cover water temperatures, refrigerant circuits, compressors, condenser fans, free cooling and heat recovery. The BAS writes chilled water setpoint, demand limit, mode, lockouts and auto/stop.

This page lists 826 BACnet objects for the Trane Symbio 800 Sintesis RTAF — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 Sintesis RTAF
Equipment
Air-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
826 (23 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013
Source document
Symbio 800 Integration Points List BACnet/Modbus - Sintesis Model RTAF · BAS-PTS013B-EN · rev. 04/07/2026
Download CSV 826 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 Sintesis RTAF

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10100Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10104Chiller Running StateChiller on/off statusRead
BI 10102Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10107Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10113Actual Running CapacityActual running capacity in percentRead
BI 10110Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10122 External Auto Stop Status reports the hardwired external auto/stop input, and BI 10101 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10102 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10107 Chiller Setpoint Source shows BAS, External or Front Panel.

Heartbeat & communication loss

No timeout or heartbeat is described. The list includes the diagnostic flags BI 11232 'Diagnostic: BAS Communication Lost', BI 11233 'Diagnostic: BAS Failed to Establish Communication' and BI 11125 'Comm Loss: Local BAS Interface'; the document doesn't say what timeout sets them or what the chiller does when they are set.

Network setup

Watch out for

Trane Symbio 800 Sintesis RTAF BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

826 of 826 shown
Type
Access
Show
Trane Symbio 800 Sintesis RTAF BACnet Points List
DescriptionStates
AI10100Active Cool/Heat Setpoint TemperatureValue of the active Cool/Heat Setpoint actively being used by the chillerTemperatureRead
AI10101External Chilled Water SetpointExternal Chilled Water Setpoint value actively being used by the chillerTemperatureRead
AI10102Front Panel Chilled Water SetpointValue of Front Panel Chilled Water setpointTemperatureRead
AI10103Active Demand Limit SetpointDemand limit setpoint value actively being used by the chillerPercentageRead
AI10104External Demand Limit SetpointStatus of the External Demand Limit SetpointPercentageRead
AI10105Front Panel Demand Limit SetpointPercentageRead
AI10106Evaporator Entering Water TemperatureCurrent temperature of the water entering the evaporatorTemperatureRead
AImin10107Evaporator Leaving Water TemperatureCurrent temperature of the water leaving the evaporatorTemperatureRead
AI10108Outdoor Air TemperatureCurrent temperature of the outdoor airTemperatureRead
AI10109Number of CircuitsNumber of refrigeration circuits in the chillerRead
AI10110Unit Source IDLast diagnostic of the chillerRead
AI10111Number of Compressors Circuit 1Number of compressors on circuit 1 of the chillerRead
AI10112Number of Compressors Circuit 2Number of compressors on circuit 2 of the chillerRead
AImin10113Actual Running CapacityMeasurement of the power being consumed by the chillerPercentageRead
AI10114Air Flow Percentage Circuit 1Approximate air flow percentage of circuit 1PercentageRead
AI10115Evaporator Refrigerant Pressure Circuit 1Current absolute pressure of the refrigerant in the evaporator on circuit 1Pressure, FluidicRead
AI10116Condenser Refrigerant Pressure Circuit 1Current absolute pressure of the refrigerant in the condenser on circuit 1Pressure, FluidicRead
AI10117Differential Refrigerant Pressure Circuit 1Pressure difference between the suction and discharge lines on circuit 1Pressure, FluidicRead
AI10118Evaporator Saturated Refrigerant Temperature Circuit 1Saturated refrigerant temperature of the evaporator on circuit 1TemperatureRead
AI10119Condenser Saturated Refrigerant Temperature Circuit 1Saturated refrigerant temperature of the condenser on circuit 1TemperatureRead
AI10120Sub Cooled Liquid Temperature Circuit 1Sub cooled liquid temperature on circuit 1TemperatureRead
AI10121Refrigerant Discharge Temperature - Compressor 1ACurrent temperature of the refrigerant being discharged from Compressor 1ATemperatureRead
AI10122Oil Pressure - Compressor 1AOil absolute pressure on the Compressor 1APressure, FluidicRead
AI10123Starts - Compressor 1ANumber of starts of Compressor 1ARead
AI10124Run Time - Compressor 1A (in seconds)Run time of Compressor 1A (in seconds)Read
AI10125Air Flow Percentage Circuit 2Approximate air flow percentage of circuit 2PercentageRead
AI10126Evaporator Refrigerant Pressure Circuit 2Current absolute pressure of the refrigerant in the evaporator on circuit 2Pressure, FluidicRead
AI10127Condenser Refrigerant Pressure Circuit 2Current absolute pressure of the refrigerant in the condenser on circuit 2Pressure, FluidicRead
AI10128Differential Refrigerant Pressure Circuit 2Pressure difference between the suction and discharge lines on circuit 2Pressure, FluidicRead
AI10129Evaporator Saturated Refrigerant Temperature Circuit 2Saturated refrigerant temperature of the evaporator on circuit 2TemperatureRead
AI10130Condenser Saturated Refrigerant Temperature Circuit 2Saturated refrigerant temperature of the condenser on circuit 2TemperatureRead
AI10131Sub Cooled Liquid Temperature Circuit 2Sub cooled liquid temperature on circuit 2TemperatureRead
AI10132Refrigerant Discharge Temperature - Compressor 2ACurrent temperature of the refrigerant being discharged from Compressor 2ATemperatureRead
AI10133Oil Pressure - Compressor 2AOil absolute pressure on the Compressor 2APressure, FluidicRead
AI10134Refrigerant Discharge Temperature - Compressor 1BCurrent temperature of the refrigerant being discharged from Compressor 1BTemperatureRead
AI10135Oil Pressure - Compressor 1BOil absolute pressure on the Compressor 1BPressure, FluidicRead
AI10136Starts - Compressor 1BNumber of starts of Compressor 1BRead
AI10137Run Time - Compressor 1B (in seconds)Run time of Compressor 1B (in seconds)Read
AI10138Starts - Compressor 2ANumber of starts of Compressor 2ARead
AI10139Run Time - Compressor 2A (in seconds)Run time of Compressor 2A (in seconds)Read
AI10140Refrigerant Discharge Temperature - Compressor 2BCurrent temperature of the refrigerant being discharged from Compressor 2BTemperatureRead
AI10141Oil Pressure - Compressor 2BOil absolute pressure on the Compressor 2BPressure, FluidicRead
AI10142Starts - Compressor 2BNumber of starts of Compressor 2BRead
AI10143Run Time - Compressor 2B (in seconds)Run time of Compressor 2B (in seconds)Read
AI10144Free Cooling Capacity Status% capacity of the free cooling being usedPercentageRead
AI10145Free Cooling Entering Water Temperature ActiveEntering water temperature of the free cooling circuitTemperatureRead
AI10146Free Cooling Entering Glycol TemperatureEntering glycol water temperature of the free cooling circuitTemperatureRead
AI10147Free Cooling Leaving Glycol TemperatureLeaving glycol water temperature of the free cooling circuitTemperatureRead
AI10148Free Cooling Glycol PressureGlycol absolute pressure of the free cooling circuitPressure, FluidicRead
AI10149Drive Motor Average Current RLA Compressor 1AAverage current at AFD for Compressor 1A in terms of % RLAPercentageRead
AI10150Drive Motor Average Current RLA Compressor 2AAverage current at AFD for Compressor 2A in terms of % RLAPercentageRead
AI10151Heat Recovery Entering Water TemperatureTemperatureRead
AI10152Heat Recovery Leaving Water TemperatureTemperatureRead
AI10153Evaporator Shell Refrigerant Pressure Circuit 1Measurement of evaporator shell refrigerant absolute pressure in circuit 1Pressure, FluidicRead
AI10154Evaporator Shell Refrigerant Pressure Circuit 2Measurement of evaporator shell refrigerant absolute pressure in circuit 2Pressure, FluidicRead
AI10155Phase AB Voltage - Compressor 1AMeasurement of voltage in Phase AB for Compressor 1AVoltageRead
AI10156Phase AB Voltage - Compressor 1BMeasurement of voltage in Phase AB for Compressor 1BVoltageRead
AI10157Phase AB Voltage - Compressor 2AMeasurement of voltage in Phase AB for Compressor 2AVoltageRead
AI10158Phase AB Voltage - Compressor 2BMeasurement of voltage in Phase AB for Compressor 2BVoltageRead
AI10159Oil Temperature - Compressor 1AMeasurement of oil temperature in Compressor 1ATemperatureRead
AI10160Oil Temperature - Compressor 1BMeasurement of oil temperature in Compressor 1BTemperatureRead
AI10161Oil Temperature - Compressor 2AMeasurement of oil temperature in Compressor 2ATemperatureRead
AI10162Oil Temperature - Compressor 2BMeasurement of oil temperature in Compressor 2BTemperatureRead
AI10163Oil Supply Temperature Circuit 1Measurement of oil supply temperature in circuit 1TemperatureRead
AI10164Oil Supply Temperature Circuit 2Measurement of oil supply temperature in circuit 2TemperatureRead
AI10165Unit Power ConsumptionMeasurement of the power being consumed by the chillerPower, ElectricalRead
AI10166Energy Consumption LifetimeTotal energy consumption of the chiller (for the lifetime of the chiller)Power, ElectricalRead
AI10167Energy ConsumptionTotal energy consumption of the chiller (since last accumulation reset)Power, ElectricalRead
AI10168Evaporator Differential Water PressureDifferential water pressure of the evaporatorPressure, FluidicRead
AI10169System Chilled Water Differential Water PressureDifferential water pressure of the chilled water systemPressure, FluidicRead
AI10170Evaporator Differential Water Pressure Setpoint StatusStatus of differential water pressure setpoint of the evaporatorPressure, FluidicRead
AI10171Line 1 Current - Compressor 1AMeasurement of Line 1 current for Compressor 1A in terms of AmpsCurrentRead
AI10172Line 2 Current - Compressor 1AMeasurement of Line 2 current for Compressor 1A in terms of AmpsCurrentRead
AI10173Line 3 Current - Compressor 1AMeasurement of Line 3 current for Compressor 1A in terms of AmpsCurrentRead
AI10174Line 1 Current RLA - Compressor 1APercentageRead
AI10175Line 2 Current RLA - Compressor 1APercentageRead
AI10176Line 3 Current RLA - Compressor 1APercentageRead
AI10177Line 1 Current - Compressor 1BMeasurement of Line 1 current for Compressor 1B in terms of AmpsCurrentRead
AI10178Line 2 Current - Compressor 1BMeasurement of Line 2 current for Compressor 1B in terms of AmpsCurrentRead
AI10179Line 3 Current - Compressor 1BMeasurement of Line 3 current for Compressor 1B in terms of AmpsCurrentRead
AI10180Line 1 Current RLA - Compressor 1BPercentageRead
AI10181Line 2 Current RLA - Compressor 1BPercentageRead
AI10182Line 3 Current RLA - Compressor 1BPercentageRead
AI10183Line 1 Current - Compressor 2AMeasurement of Line 1 current for Compressor 2A in terms of AmpsCurrentRead
AI10184Line 2 Current - Compressor 2AMeasurement of Line 2 current for Compressor 2A in terms of AmpsCurrentRead
AI10185Line 3 Current - Compressor 2AMeasurement of Line 3 current for Compressor 2A in terms of AmpsCurrentRead
AI10186Line 1 Current RLA - Compressor 2APercentageRead
AI10187Line 2 Current RLA - Compressor 2APercentageRead
AI10188Line 3 Current RLA - Compressor 2APercentageRead
AI10189Line 1 Current - Compressor 2BMeasurement of Line 1 current for Compressor 2B in terms of AmpsCurrentRead
AI10190Line 2 Current - Compressor 2BMeasurement of Line 2 current for Compressor 2B in terms of AmpsCurrentRead
AI10191Line 3 Current - Compressor 2BMeasurement of Line 3 current for Compressor 2B in terms of AmpsCurrentRead
AI10192Line 1 Current RLA - Compressor 2BPercentageRead
AI10193Line 2 Current RLA - Compressor 2BPercentageRead
AI10194Line 3 Current RLA - Compressor 2BPercentageRead
AI10195Drive Motor Current U Compressor 1ACurrentRead
AI10196Drive Motor Current V Compressor 1ACurrentRead
AI10197Drive Motor Current W Compressor 1ACurrentRead
AI10198Drive Motor Current U RLA Compressor 1APercentageRead
AI10199Drive Motor Current V RLA Compressor 1APercentageRead
AI10200Drive Motor Current W RLA Compressor 1APercentageRead
AI10201Drive Motor Average Voltage Compressor 1AAverage voltage line to line at AFD for Compressor 1AVoltageRead
AI10202Drive Motor Average Voltage Compressor 2AAverage voltage line to line at AFD for Compressor 2AVoltageRead
AI10203Drive Motor Current U Compressor 2ACurrentRead
AI10204Drive Motor Current V Compressor 2ACurrentRead
AI10205Drive Motor Current W Compressor 2ACurrentRead
AI10206Drive Motor Current U RLA Compressor 2APercentageRead
AI10207Drive Motor Current V RLA Compressor 2APercentageRead
AI10208Drive Motor Current W RLA Compressor 2APercentageRead
AI10209Drive Motor Average Current RLA Compressor 1BAverage current at AFD for Compressor 1B in terms of % RLAPercentageRead
AI10210Drive Motor Average Current RLA Compressor 2BAverage current at AFD for Compressor 2B in terms of % RLAPercentageRead
AI10211Demand Limit Setpoint StatusStatus of demand limit setpoint value actively being used by the chillerPercentageRead
AI10212Chiller Design CapacityDesign capacity of chillerPower, CoolingRead
AI10213Chilled Water Setpoint StatusStatus of chilled water setpoint value actively being used by the chillerTemperatureRead
AI10214Evaporator Approach Temperature Circuit 1Approach temperature of the evaporator of circuit 1TemperatureRead
AI10215Evaporator Approach Temperature Circuit 2Approach temperature of the evaporator of circuit 2TemperatureRead
AI10216Unit Load CommandTotal unit load command in percentage %PercentageRead
AI10217Chilled Water Pump 1 Run HoursRun time of chilled water pump 1Read
AI10218Chilled Water Pump 2 Run HoursRun time of chilled water pump 2Read
AI10219Active Chilled Water Pump Service Interval SetpointActive Chilled Water Pump Service Interval HoursRead
AI10220Evaporator Refrigerant Gauge Pressure Circuit 1Evaporator Refrigerant Gauge Pressure Ckt1Pressure, FluidicRead
AI10221Condenser Refrigerant Gauge Pressure Circuit 1Condenser Refrigerant Gauge Pressure Ckt1Pressure, FluidicRead
AI10222Evaporator Refrigerant Gauge Pressure Circuit 2Evaporator Refrigerant Gauge Pressure Ckt2Pressure, FluidicRead
AI10223Condenser Refrigerant Gauge Pressure Circuit 2Condenser Refrigerant Gauge Pressure Ckt2Pressure, FluidicRead
AI10224Oil Gauge Pressure - Compressor 1AOil Gauge Pressure Cprsr1APressure, FluidicRead
AI10225Oil Gauge Pressure - Compressor 2AOil Gauge Pressure Cprsr2APressure, FluidicRead
AI10226Oil Gauge Pressure - Compressor 1BOil Gauge Pressure Cprsr1BPressure, FluidicRead
AI10227Oil Gauge Pressure - Compressor 2BOil Gauge Pressure Cprsr2BPressure, FluidicRead
AI10228Free Cooling Glycol Gauge PressurePressure, FluidicRead
AI10229Evaporator Shell Refrigerant Gauge Pressure Circuit 1Evaporator Shell Refrigerant Gauge Pressure Ckt1Pressure, FluidicRead
AI10230Evaporator Shell Refrigerant Gauge Pressure Circuit 2Evaporator Shell Refrigerant Gauge Pressure Ckt2Pressure, FluidicRead
AI10231Active Heat Recovery SetpointTemperatureRead
AI10232Active Rapid Start Target Load CommandPercentageRead
AI10233Free Cooling Valve Position StatusFree Cooling Valve Percent OpenPercentageRead
AI10234Free Cooling Bypass Valve Position StatusFree Cooling Bypass Valve Percent OpenPercentageRead
AI10235Free Cooling Target OffsetTemperature, DeltaRead
AI10236Free Cooling Pump Override Time RemainingRead
AVmin10100Chilled Water SetpointWritten by the BAS; goes through arbitration before useTemperatureWrite
AVmin10101Demand Limit SetpointWritten by the BAS; goes through arbitration before usePercentageWrite
AV10102Heat Recovery Leaving Water Temperature Setpoint BASWritten by the BAS; goes through arbitration before useTemperatureWrite
AV10103Evaporator Water Pump Speed SetpointPercentageWrite
AV10104Rapid Start Target Load Command BASPercentageWrite
BI10101Run EnableThat chiller is available to run or is currently runningRead0 = Run Not Enabled, 1 = Run Enabled
BImin10102Local Setpoint ControlWhich setpoint is used for control purposes, Remote (BAS) or LocalRead0 = Remote control, 1 = Local control
BI10103Limit Mode Relay StatusStatus of the chiller limit relayRead0 = Off, 1 = On
BImin10104Chiller Running StateThe chiller is onRead0 = Off, 1 = On
BI10105Maximum CapacityStatus of the maximum capacity relayRead0 = Off, 1 = On
BI10106Manual Override ExistsD a manual override is presentRead0 = Off, 1 = On
BI10107Emergency StopStatus of the emergency stop function of the chillerRead0 = Auto, 1 = Emergency Stop-Manual Reset Required
BI10108Evaporator Water Flow StatusFlow of water through evaporatorRead0 = No Flow, 1 = Flow
BI10109Front Panel Auto StopAuto/stop status of the Front PanelRead0 = Stop, 1 = Auto
BImin10110Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10111Diagnostic Shutdown PresentChiller is shut down due to diagnosticsRead0 = Normal, 1 = In Alarm
BI10112Diagnostic: Manual Reset RequiredWhen a diagnostic exists that requires manual resetRead0 = Normal, 1 = In Alarm
BI10113Diagnostic: Local Manual Reset RequiredWhen a diagnostic exists that requires manual reset (local only)Read0 = Normal, 1 = In Alarm
BI10114Diagnostic Present: InformationDiagnostic present with Information CategoryRead0 = Normal, 1 = In Alarm
BI10115Diagnostic Present: AdvisoryDiagnostic present with Warning CategoryRead0 = Normal, 1 = In Alarm
BI10116Diagnostic Present: CriticalDiagnostic present with Critical CategoryRead0 = Normal, 1 = In Alarm
BI10117Diagnostic Present: Service RequiredDiagnostic present with Service Required CategoryRead0 = Normal, 1 = In Alarm
BI10118Compressor 1A Running StatusRunning state of Compressor 1ARead0 = Off, 1 = Running
BI10119Compressor 1BRunning StatusRunning state of Compressor 1BRead0 = Off, 1 = Running
BI10120Compressor 2A Running StatusRunning state of Compressor 2ARead0 = Off, 1 = Running
BI10121Compressor 2B Running StatusRunning state of Compressor 2BRead0 = Off, 1 = Running
BI10122External Auto Stop StatusStatus of the externally-wired auto/stop inputRead0 = Stop, 1 = Auto
BI10123Free Cooling ActiveD the free cooling mode is activeRead0 = Normal, 1 = Active
BI10124Evaporator Water Pump RequestRequest from the chiller to turn on the Evaporator Water PumpRead0 = Off, 1 = On
BI10125Heat Recovery Control Active StatusActive control state of Heat RecoveryRead0 = Normal, 1 = Active
BI10126Heat Recovery Ckt1 Active StatusActive state of Heat Recovery circuit 1Read0 = Normal, 1 = Active
BI10127Heat Recovery Ckt2 Active StatusActive state of Heat Recovery circuit 2Read0 = Normal, 1 = Active
BI10128Alarm - Latching UnitLatching alarm is presentRead0 = Normal, 1 = In Alarm
BI10129Alarm - NonLatching UnitNon-latching alarm is presentRead0 = Normal, 1 = In Alarm
BI10130Alarm - Ckt 1Latching and/or non-latching alarm present on circuit 1Read0 = Normal, 1 = In Alarm
BI10131Alarm - Ckt 2Latching and/or non-latching alarm present on circuit 2Read0 = Normal, 1 = In Alarm
BI10132Alarm - General Latching UnitLatching alarm is presentRead0 = Normal, 1 = In Alarm
BI10133Alarm - General Non Latching UnitAt least one non-latching alarm is presentRead0 = Normal, 1 = In Alarm
BI10134Alarm - General Latching Ckt1Latching alarm is presentRead0 = Normal, 1 = In Alarm
BI10135Alarm - General Latching Ckt2Latching alarm is presentRead0 = Normal, 1 = In Alarm
BI10136Alarm - General Non Latching Ckt1At least one non-latching alarm is presentRead0 = Normal, 1 = In Alarm
BI10137Alarm - General Non Latching Ckt2At least one non-latching alarm is presentRead0 = Normal, 1 = In Alarm
BI10138Noise Reduction Request ActiveNoise Reduction activeRead0 = Off, 1 = On
BI10139Heat Recovery Water Flow StatusFlow of water through heat recoveryRead0 = No, 1 = Flow
BI10140Heat Recovery Water Pump CommandStatus of heat recovery pump commandRead0 = Off, 1 = On
BI10141Circuit 1 Running StatusRunning state of circuit 1Read0 = Off, 1 = Running
BI10142Circuit 2 Running StatusRunning state of circuit 2Read0 = Off, 1 = Running
BI10143Emergency Stop Input StatusStatus of the emergency stop function of the chillerRead0 = Inactive, 1 = Active
BI10144Evaporator Water Pump StatusEvaporator Water Pump effective run command statusRead0 = Off, 1 = On
BI10145Active Heat Recovery CommandRead0 = Off, 1 = On
BI10146Active Rapid Start RequestRead0 = Off, 1 = On
BI10147Fan 1 circuit 1 running stateFan 5M40-111 running stateRead0 = Off, 1 = On
BI10148Fan 2 circuit 1 running stateFan 5M40-112 running stateRead0 = Off, 1 = On
BI10149Fan 3 circuit 1 running stateFan 5M40-113 running stateRead0 = Off, 1 = On
BI10150Fan 4 circuit 1 running stateFan 5M40-114 running stateRead0 = Off, 1 = On
BI10151Fan 5 circuit 1 running stateFan 5M40-115 running stateRead0 = Off, 1 = On
BI10152Fan 6 circuit 1 running stateFan 5M40-116 running stateRead0 = Off, 1 = On
BI10153Fan 7 circuit 1 running stateFan 5M40-117 running stateRead0 = Off, 1 = On
BI10154Fan 8 circuit 1 running stateFan 5M40-118 running stateRead0 = Off, 1 = On
BI10155Fan 9 circuit 1 running stateFan 5M40-119 running stateRead0 = Off, 1 = On
BI10156Fan 10 circuit 1 running stateFan 5M40-120 running stateRead0 = Off, 1 = On
BI10157Fan 11 circuit 1 running stateFan 5M40-121 running stateRead0 = Off, 1 = On
BI10158Fan 12 circuit 1 running stateFan 5M40-1221 running stateRead0 = Off, 1 = On
BI10159Fan 13 circuit 1 running stateFan 5M40-123 running stateRead0 = Off, 1 = On
BI10160Fan 14 circuit 1 running stateFan 5M40-124 running stateRead0 = Off, 1 = On
BI10161Fan 15 circuit 1 running stateFan 5M40-1251 running stateRead0 = Off, 1 = On
BI10162Fan 16 circuit 1 running stateFan 5M40-126 running stateRead0 = Off, 1 = On
BI10163Fan 1 circuit 2 running stateFan 5M40-211 running stateRead0 = Off, 1 = On
BI10164Fan 2 circuit 2 running stateFan 5M40-212 running stateRead0 = Off, 1 = On
BI10165Fan 3 circuit 2 running stateFan 5M40-213 running stateRead0 = Off, 1 = On
BI10166Fan 4 circuit 2 running stateFan 5M40-214 running stateRead0 = Off, 1 = On
BI10167Fan 5 circuit 2 running stateFan 5M40-215 running stateRead0 = Off, 1 = On
BI10168Fan 6 circuit 2 running stateFan 5M40-216 running stateRead0 = Off, 1 = On
BI10169Fan 7 circuit 2 running stateFan 5M40-217 running stateRead0 = Off, 1 = On
BI10170Fan 8 circuit 2 running stateFan 5M40-218 running stateRead0 = Off, 1 = On
BI10171Fan 9 circuit 2 running stateFan 5M40-219 running stateRead0 = Off, 1 = On
BI10172Fan 10 circuit 2 running stateFan 5M40-220 running stateRead0 = Off, 1 = On
BI10173Fan 11 circuit 2 running stateFan 5M40-221 running stateRead0 = Off, 1 = On
BI10174Fan 12 circuit 2 running stateFan 5M40-222 running stateRead0 = Off, 1 = On
BI10175Fan 13 circuit 2 running stateFan 5M40-223 running stateRead0 = Off, 1 = On
BI10176Fan 14 circuit 2 running stateFan 5M40-224 running stateRead0 = Off, 1 = On
BI10177Fan 15 circuit 2 running stateFan 5M40-225 running stateRead0 = Off, 1 = On
BI10178Fan 16 circuit 2 running stateFan 5M40-226 running stateRead0 = Off, 1 = On
BI10179Fan 1 circuit 1 faultFan 5M40-111 faultRead0 = Off, 1 = On
BI10180Fan 2 circuit 1 faultFan 5M40-112 faultRead0 = Off, 1 = On
BI10181Fan 3 circuit 1 faultFan 5M40-113 faultRead0 = Off, 1 = On
BI10182Fan 4 circuit 1 faultFan 5M40-114 faultRead0 = Off, 1 = On
BI10183Fan 5 circuit 1 faultFan 5M40-115 faultRead0 = Off, 1 = On
BI10184Fan 6 circuit 1 faultFan 5M40-116 faultRead0 = Off, 1 = On
BI10185Fan 7 circuit 1 faultFan 5M40-117 faultRead0 = Off, 1 = On
BI10186Fan 8 circuit 1 faultFan 5M40-118 faultRead0 = Off, 1 = On
BI10187Fan 9 circuit 1 faultFan 5M40-119 faultRead0 = Off, 1 = On
BI10188Fan 10 circuit 1 faultFan 5M40-120 faultRead0 = Off, 1 = On
BI10189Fan 11 circuit 1 faultFan 5M40-1211 faultRead0 = Off, 1 = On
BI10190Fan 12 circuit 1 faultFan 5M40-122 faultRead0 = Off, 1 = On
BI10191Fan 13 circuit 1 faultFan 5M40-123 faultRead0 = Off, 1 = On
BI10192Fan 14 circuit 1 faultFan 5M40-124 faultRead0 = Off, 1 = On
BI10193Fan 15 circuit 1 faultFan 5M40-125 faultRead0 = Off, 1 = On
BI10194Fan 16 circuit 1 faultFan 5M40-126 faultRead0 = Off, 1 = On
BI10195Fan 1 circuit 2 faultFan 5M40-211 faultRead0 = Off, 1 = On
BI10196Fan 2 circuit 2 faultFan 5M40-212 faultRead0 = Off, 1 = On
BI10197Fan 3 circuit 2 faultFan 5M40-213 faultRead0 = Off, 1 = On
BI10198Fan 4 circuit 2 faultFan 5M40-214 faultRead0 = Off, 1 = On
BI10199Fan 5 circuit 2 faultFan 5M40-215 faultRead0 = Off, 1 = On
BI10200Fan 6 circuit 2 faultFan 5M40-216 faultRead0 = Off, 1 = On
BI10201Fan 7 circuit 2 faultFan 5M40-217 faultRead0 = Off, 1 = On
BI10202Fan 8 circuit 2 faultFan 5M40-218 faultRead0 = Off, 1 = On
BI10203Fan 9 circuit 2 faultFan 5M40-219 faultRead0 = Off, 1 = On
BI10204Fan 10 circuit 2 faultFan 5M40-220 faultRead0 = Off, 1 = On
BI10205Fan 11 circuit 2 faultFan 5M40-221 faultRead0 = Off, 1 = On
BI10206Fan 12 circuit 2 faultFan 5M40-222 faultRead0 = Off, 1 = On
BI10207Fan 13 circuit 2 faultFan 5M40-223 faultRead0 = Off, 1 = On
BI10208Fan 14 circuit 2 faultFan 5M40-224 faultRead0 = Off, 1 = On
BI10209Fan 15 circuit 2 faultFan 5M40-225 faultRead0 = Off, 1 = On
BI10210Fan 16 circuit 2 faultFan 5M40-226 faultRead0 = Off, 1 = On
BI10211Free Cooling Pump Command StatusFree Cooling Pump CommandRead0 = Off, 1 = On
BI10212Free Cooling Front Panel Command StatusFront Panel Free Cooling CommandRead0 = Off, 1 = On
BI10213Free Cooling Glycol Flow StatusRead0 = Off, 1 = On
BI11000Comm Loss: %RLA Indication Output(Vdc)Read0 = Normal, 1 = In Alarm
BI11001Comm Loss: AFD Fault Input 1ARead0 = Normal, 1 = In Alarm
BI11002Comm Loss: AFD Fault Input 1BRead0 = Normal, 1 = In Alarm
BI11003Comm Loss: AFD Fault Input 2ARead0 = Normal, 1 = In Alarm
BI11004Comm Loss: AFD Fault Input 2BRead0 = Normal, 1 = In Alarm
BI11005Comm Loss: AFD Run Command - 1ARead0 = Normal, 1 = In Alarm
BI11006Comm Loss: AFD Run Command - 2ARead0 = Normal, 1 = In Alarm
BI11007Comm Loss: AFD Speed Command 1ARead0 = Normal, 1 = In Alarm
BI11008Comm Loss: AFD Speed Command 1BRead0 = Normal, 1 = In Alarm
BI11009Comm Loss: AFD Speed Command 2ARead0 = Normal, 1 = In Alarm
BI11010Comm Loss: AFD Speed Command 2BRead0 = Normal, 1 = In Alarm
BI11011Comm Loss: Auxiliary Setpoint CommandRead0 = Normal, 1 = In Alarm
BI11012Comm Loss: Chiller Bypass Valve OutputRead0 = Normal, 1 = In Alarm
BI11013Comm Loss: Cond Fan Enbl Shared Ckt 1&2Read0 = Normal, 1 = In Alarm
BI11014Comm Loss: Cond Rfgt Tank Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11015Comm Loss: Cond Rfgt Tank Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11016Comm Loss: Condenser Fan Enable - Ckt1Read0 = Normal, 1 = In Alarm
BI11017Comm Loss: Condenser Fan Enable - Ckt2Read0 = Normal, 1 = In Alarm
BI11018Comm Loss: Condenser Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11019Comm Loss: Condenser Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11020Comm Loss: Cprsr Disch Rfgt Temp - 1ARead0 = Normal, 1 = In Alarm
BI11021Comm Loss: Cprsr Disch Rfgt Temp - 1BRead0 = Normal, 1 = In Alarm
BI11022Comm Loss: Cprsr Disch Rfgt Temp - 2ARead0 = Normal, 1 = In Alarm
BI11023Comm Loss: Cprsr Disch Rfgt Temp - 2BRead0 = Normal, 1 = In Alarm
BI11024Comm Loss: Economizer Disch Press - 1ARead0 = Normal, 1 = In Alarm
BI11025Comm Loss: Economizer Disch Press - 1BRead0 = Normal, 1 = In Alarm
BI11026Comm Loss: Economizer Disch Press - 2ARead0 = Normal, 1 = In Alarm
BI11027Comm Loss: Economizer Disch Press - 2BRead0 = Normal, 1 = In Alarm
BI11028Comm Loss: Economizer Disch Temp - 1ARead0 = Normal, 1 = In Alarm
BI11029Comm Loss: Economizer Disch Temp - 1BRead0 = Normal, 1 = In Alarm
BI11030Comm Loss: Economizer Disch Temp - 2ARead0 = Normal, 1 = In Alarm
BI11031Comm Loss: Economizer Disch Temp - 2BRead0 = Normal, 1 = In Alarm
BI11032Comm Loss: Economizer Valve - 1ARead0 = Normal, 1 = In Alarm
BI11033Comm Loss: Economizer Valve - 1BRead0 = Normal, 1 = In Alarm
BI11034Comm Loss: Economizer Valve - 2ARead0 = Normal, 1 = In Alarm
BI11035Comm Loss: Economizer Valve - 2BRead0 = Normal, 1 = In Alarm
BI11036Comm Loss: Electronic Expansion Valve - Ckt1Read0 = Normal, 1 = In Alarm
BI11037Comm Loss: Electronic Expansion Valve - Ckt2Read0 = Normal, 1 = In Alarm
BI11038Comm Loss: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11039Comm Loss: Energy MeterRead0 = Normal, 1 = In Alarm
BI11040Comm Loss: Energy Meter Pulse InputRead0 = Normal, 1 = In Alarm
BI11041Comm Loss: Evap Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11042Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11043Comm Loss: Evap Iso Valve Close Switch - Ckt1Read0 = Normal, 1 = In Alarm
BI11044Comm Loss: Evap Iso Valve Close Switch - Ckt2Read0 = Normal, 1 = In Alarm
BI11045Comm Loss: Evap Iso Valve Open Switch - Ckt1Read0 = Normal, 1 = In Alarm
BI11046Comm Loss: Evap Iso Valve Open Switch - Ckt2Read0 = Normal, 1 = In Alarm
BI11047Comm Loss: Evap Isolation Valve Relay - Ckt1Read0 = Normal, 1 = In Alarm
BI11048Comm Loss: Evap Isolation Valve Relay - Ckt2Read0 = Normal, 1 = In Alarm
BI11049Comm Loss: Evap Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11050Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11051Comm Loss: Evap Pump Inv1 Fault InputRead0 = Normal, 1 = In Alarm
BI11052Comm Loss: Evap Pump Inv1 Run CommandRead0 = Normal, 1 = In Alarm
BI11053Comm Loss: Evap Rfgt Pool Temp - Ckt1Read0 = Normal, 1 = In Alarm
BI11054Comm Loss: Evap Rfgt Pool Temp - Ckt2Read0 = Normal, 1 = In Alarm
BI11055Comm Loss: Evap Shell Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11056Comm Loss: Evap Shell Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11057Comm Loss: Evap Water Pump Inv Freq InputRead0 = Normal, 1 = In Alarm
BI11058Comm Loss: Evap Water Pump Inverter SpeedRead0 = Normal, 1 = In Alarm
BI11059Comm Loss: Evaporator Pump 1 Fault InputRead0 = Normal, 1 = In Alarm
BI11060Comm Loss: Evaporator Pump 2 Fault InputRead0 = Normal, 1 = In Alarm
BI11061Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11062Comm Loss: Evaporator Water Pump 1 RelayRead0 = Normal, 1 = In Alarm
BI11063Comm Loss: Evaporator Water Pump 2 RelayRead0 = Normal, 1 = In Alarm
BI11064Comm Loss: Evaporator Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11065Comm Loss: Ext Chilled Water SetpointRead0 = Normal, 1 = In Alarm
BI11066Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11067Comm Loss: Ext Noise Reduction RequestRead0 = Normal, 1 = In Alarm
BI11068Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11069Comm Loss: External Ckt Lockout - Ckt1Read0 = Normal, 1 = In Alarm
BI11070Comm Loss: External Ckt Lockout - Ckt2Read0 = Normal, 1 = In Alarm
BI11071Comm Loss: External Heat Recovery Ckt LockoutRead0 = Normal, 1 = In Alarm
BI11072Comm Loss: External Heat Recovery CommandRead0 = Normal, 1 = In Alarm
BI11073Comm Loss: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11074Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11075Comm Loss: Fan Board 1 Relay 1 - Ckt1Read0 = Normal, 1 = In Alarm
BI11076Comm Loss: Fan Board 1 Relay 1 - Ckt2Read0 = Normal, 1 = In Alarm
BI11077Comm Loss: Fan Board 1 Relay 2 - Ckt1Read0 = Normal, 1 = In Alarm
BI11078Comm Loss: Fan Board 1 Relay 2 - Ckt2Read0 = Normal, 1 = In Alarm
BI11079Comm Loss: Fan Board 1 Relay 3 - Ckt1Read0 = Normal, 1 = In Alarm
BI11080Comm Loss: Fan Board 1 Relay 3 - Ckt2Read0 = Normal, 1 = In Alarm
BI11081Comm Loss: Fan Board 1 Relay 4 - Ckt1Read0 = Normal, 1 = In Alarm
BI11082Comm Loss: Fan Board 1 Relay 4 - Ckt2Read0 = Normal, 1 = In Alarm
BI11083Comm Loss: Fan Board 2 Relay 1 - Ckt1Read0 = Normal, 1 = In Alarm
BI11084Comm Loss: Fan Board 2 Relay 1 - Ckt2Read0 = Normal, 1 = In Alarm
BI11085Comm Loss: Fan Board 2 Relay 2 - Ckt1Read0 = Normal, 1 = In Alarm
BI11086Comm Loss: Fan Board 2 Relay 2 - Ckt2Read0 = Normal, 1 = In Alarm
BI11087Comm Loss: Fan Board 2 Relay 3 - Ckt1Read0 = Normal, 1 = In Alarm
BI11088Comm Loss: Fan Board 2 Relay 3 - Ckt2Read0 = Normal, 1 = In Alarm
BI11089Comm Loss: Fan Board 2 Relay 4 - Ckt1Read0 = Normal, 1 = In Alarm
BI11090Comm Loss: Fan Board 2 Relay 4 - Ckt2Read0 = Normal, 1 = In Alarm
BI11091Comm Loss: Fan Inv Spd Cmd, Shrd Ckt1&2Read0 = Normal, 1 = In Alarm
BI11092Comm Loss: Fan Inverter Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11093Comm Loss: Fan Inverter Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11094Comm Loss: Fan Inverter Speed Command - Ckt1Read0 = Normal, 1 = In Alarm
BI11095Comm Loss: Fan Inverter Speed Command - Ckt2Read0 = Normal, 1 = In Alarm
BI11096Comm Loss: Free Cooling Bypass ValveRead0 = Normal, 1 = In Alarm
BI11097Comm Loss: Free Cooling Entering Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11098Comm Loss: Free Cooling Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11099Comm Loss: Free Cooling Glycol Flow SwitchRead0 = Normal, 1 = In Alarm
BI11100Comm Loss: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11101Comm Loss: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11102Comm Loss: Free Cooling Leaving Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11103Comm Loss: Free Cooling PumpRead0 = Normal, 1 = In Alarm
BI11104Comm Loss: Free Cooling ValveRead0 = Normal, 1 = In Alarm
BI11105Comm Loss: Heat Recovery Mode Valve Command – Ckt1Read0 = Normal, 1 = In Alarm
BI11106Comm Loss: Heat Recovery Mode Valve Command – Ckt2Read0 = Normal, 1 = In Alarm
BI11107Comm Loss: Heat Recovery Water Flow Cmd - Ckt1Read0 = Normal, 1 = In Alarm
BI11108Comm Loss: Heat Recovery Water Flow Cmd - Ckt2Read0 = Normal, 1 = In Alarm
BI11109Comm Loss: Heat Recovery Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11110Comm Loss: High Pressure Cutout Sw - 1ARead0 = Normal, 1 = In Alarm
BI11111Comm Loss: High Pressure Cutout Sw - 1BRead0 = Normal, 1 = In Alarm
BI11112Comm Loss: High Pressure Cutout Sw - 2ARead0 = Normal, 1 = In Alarm
BI11113Comm Loss: High Pressure Cutout Sw - 2BRead0 = Normal, 1 = In Alarm
BI11114Comm Loss: High Pressure Cutout Switch - Ckt1Read0 = Normal, 1 = In Alarm
BI11115Comm Loss: High Pressure Cutout Switch - Ckt2Read0 = Normal, 1 = In Alarm
BI11116Comm Loss: Hot Gas Bypass Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11117Comm Loss: Hot Gas Bypass Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11118Comm Loss: HR Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11119Comm Loss: HR Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11120Comm Loss: External Rapid Start CommandRead0 = Normal, 1 = In Alarm
BI11121Comm Loss: Liquid Line Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11122Comm Loss: Liquid Line Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11123Comm Loss: Liquid Line Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11124Comm Loss: Liquid Line Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11125Comm Loss: Local BAS InterfaceRead0 = Normal, 1 = In Alarm
BI11126Comm Loss: Mains Voltage DetectionRead0 = Normal, 1 = In Alarm
BI11127Comm Loss: Motor RLA Input - 1ARead0 = Normal, 1 = In Alarm
BI11128Comm Loss: Motor RLA Input - 1BRead0 = Normal, 1 = In Alarm
BI11129Comm Loss: Motor RLA Input - 2ARead0 = Normal, 1 = In Alarm
BI11130Comm Loss: Motor RLA Input - 2BRead0 = Normal, 1 = In Alarm
BI11131Comm Loss: Motor Winding Tstat Cprsr1ARead0 = Normal, 1 = In Alarm
BI11132Comm Loss: Motor Winding Tstat Cprsr2ARead0 = Normal, 1 = In Alarm
BI11133Comm Loss: Off-cycle Freeze Prot RelayRead0 = Normal, 1 = In Alarm
BI11134Comm Loss: Oil Loss Level Sensor Input - Ckt1Read0 = Normal, 1 = In Alarm
BI11135Comm Loss: Oil Loss Level Sensor Input - Ckt2Read0 = Normal, 1 = In Alarm
BI11136Comm Loss: Oil Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11137Comm Loss: Oil Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11138Comm Loss: Oil Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11139Comm Loss: Oil Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11140Comm Loss: Oil Return Purge Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11141Comm Loss: Oil Return Purge Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11142Comm Loss: Oil Return Solenoid Valve - 1ARead0 = Normal, 1 = In Alarm
BI11143Comm Loss: Oil Return Solenoid Valve - 1BRead0 = Normal, 1 = In Alarm
BI11144Comm Loss: Oil Return Solenoid Valve - 2ARead0 = Normal, 1 = In Alarm
BI11145Comm Loss: Oil Return Solenoid Valve - 2BRead0 = Normal, 1 = In Alarm
BI11146Comm Loss: Oil Supply Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11147Comm Loss: Oil Supply Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11148Comm Loss: Oil Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11149Comm Loss: Oil Temperature - 1BRead0 = Normal, 1 = In Alarm
BI11150Comm Loss: Oil Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11151Comm Loss: Oil Temperature - 2BRead0 = Normal, 1 = In Alarm
BI11152Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11153Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11154Comm Loss: Programmable Relay Board 2Read0 = Normal, 1 = In Alarm
BI11155Comm Loss: Slide Valve Load - 1ARead0 = Normal, 1 = In Alarm
BI11156Comm Loss: Slide Valve Load - 1BRead0 = Normal, 1 = In Alarm
BI11157Comm Loss: Slide Valve Load - 2ARead0 = Normal, 1 = In Alarm
BI11158Comm Loss: Slide Valve Load - 2BRead0 = Normal, 1 = In Alarm
BI11159Comm Loss: Slide Valve Unload - 1ARead0 = Normal, 1 = In Alarm
BI11160Comm Loss: Slide Valve Unload - 1BRead0 = Normal, 1 = In Alarm
BI11161Comm Loss: Slide Valve Unload - 2ARead0 = Normal, 1 = In Alarm
BI11162Comm Loss: Slide Valve Unload - 2BRead0 = Normal, 1 = In Alarm
BI11163Comm Loss: Starter 1ARead0 = Normal, 1 = In Alarm
BI11164Comm Loss: Starter 1BRead0 = Normal, 1 = In Alarm
BI11165Comm Loss: Starter 2ARead0 = Normal, 1 = In Alarm
BI11166Comm Loss: Starter 2BRead0 = Normal, 1 = In Alarm
BI11167Comm Loss: Step Load - 1ARead0 = Normal, 1 = In Alarm
BI11168Comm Loss: Step Load - 1BRead0 = Normal, 1 = In Alarm
BI11169Comm Loss: Step Load - 2ARead0 = Normal, 1 = In Alarm
BI11170Comm Loss: Step Load - 2BRead0 = Normal, 1 = In Alarm
BI11171Comm Loss: Suction Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11172Comm Loss: Suction Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11173Comm Loss: Suction Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11174Comm Loss: Suction Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11175Comm Loss: Suction Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11176Comm Loss: Suction Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11177Comm Loss: Var Vi Valve – Cprsr1ARead0 = Normal, 1 = In Alarm
BI11178Comm Loss: Var Vi Valve – Cprsr2ARead0 = Normal, 1 = In Alarm
BI11179Comm Loss: Water System Diff PressureRead0 = Normal, 1 = In Alarm
BI11180Comm Loss: Winding Temp 1, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11181Comm Loss: Winding Temp 1, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11182Comm Loss: Winding Temp 2, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11183Comm Loss: Winding Temp 2, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11184Diagnostic: AFD %RLA Feedback - 1ARead0 = Normal, 1 = In Alarm
BI11185Diagnostic: AFD %RLA Feedback - 1BRead0 = Normal, 1 = In Alarm
BI11186Diagnostic: AFD %RLA Feedback - 2ARead0 = Normal, 1 = In Alarm
BI11187Diagnostic: AFD %RLA Feedback - 2BRead0 = Normal, 1 = In Alarm
BI11188Diagnostic: AFD Bump Complete - 1ARead0 = Normal, 1 = In Alarm
BI11189Diagnostic: AFD Bump Complete - 2ARead0 = Normal, 1 = In Alarm
BI11190Diagnostic: AFD Bump Current High - 1ARead0 = Normal, 1 = In Alarm
BI11191Diagnostic: AFD Bump Current High - 2ARead0 = Normal, 1 = In Alarm
BI11192Diagnostic: AFD Comm Loss – 1ARead0 = Normal, 1 = In Alarm
BI11193Diagnostic: AFD Comm Loss – 1BRead0 = Normal, 1 = In Alarm
BI11194Diagnostic: AFD Comm Loss – 2ARead0 = Normal, 1 = In Alarm
BI11195Diagnostic: AFD Comm Loss – 2BRead0 = Normal, 1 = In Alarm
BI11196Diagnostic: AFD Failure to Arm or Start - 1ARead0 = Normal, 1 = In Alarm
BI11197Diagnostic: AFD Failure to Arm or Start - 1BRead0 = Normal, 1 = In Alarm
BI11198Diagnostic: AFD Failure to Arm or Start - 2ARead0 = Normal, 1 = In Alarm
BI11199Diagnostic: AFD Failure to Arm or Start - 2BRead0 = Normal, 1 = In Alarm
BI11200Diagnostic: AFD Fault - 1ARead0 = Normal, 1 = In Alarm
BI11201Diagnostic: AFD Fault - 1BRead0 = Normal, 1 = In Alarm
BI11202Diagnostic: AFD Fault - 2ARead0 = Normal, 1 = In Alarm
BI11203Diagnostic: AFD Fault - 2BRead0 = Normal, 1 = In Alarm
BI11204Diagnostic: AFD Fault Mains - 1ARead0 = Normal, 1 = In Alarm
BI11205Diagnostic: AFD Fault Mains - 1BRead0 = Normal, 1 = In Alarm
BI11206Diagnostic: AFD Fault Mains - 2ARead0 = Normal, 1 = In Alarm
BI11207Diagnostic: AFD Fault Mains - 2BRead0 = Normal, 1 = In Alarm
BI11208Diagnostic: AFD Harmonic Filter Over Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11209Diagnostic: AFD Harmonic Filter Over Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11210Diagnostic: AFD High Pressure Cutout - 1ARead0 = Normal, 1 = In Alarm
BI11211Diagnostic: AFD High Pressure Cutout - 2ARead0 = Normal, 1 = In Alarm
BI11212Diagnostic: AFD Interrupt Failure - 1ARead0 = Normal, 1 = In Alarm
BI11213Diagnostic: AFD Interrupt Failure - 1BRead0 = Normal, 1 = In Alarm
BI11214Diagnostic: AFD Interrupt Failure - 2ARead0 = Normal, 1 = In Alarm
BI11215Diagnostic: AFD Interrupt Failure - 2BRead0 = Normal, 1 = In Alarm
BI11216Diagnostic: AFD Motor Current Overload - 1ARead0 = Normal, 1 = In Alarm
BI11217Diagnostic: AFD Motor Current Overload - 1BRead0 = Normal, 1 = In Alarm
BI11218Diagnostic: AFD Motor Current Overload - 2ARead0 = Normal, 1 = In Alarm
BI11219Diagnostic: AFD Motor Current Overload - 2BRead0 = Normal, 1 = In Alarm
BI11220Diagnostic: AFD Motor Fault - 1ARead0 = Normal, 1 = In Alarm
BI11221Diagnostic: AFD Motor Fault - 2ARead0 = Normal, 1 = In Alarm
BI11222Diagnostic: AFD Motor Speed Too High - 1ARead0 = Normal, 1 = In Alarm
BI11223Diagnostic: AFD Motor Speed Too High - 2ARead0 = Normal, 1 = In Alarm
BI11224Diagnostic: AFD Motor Speed Too Low - 1ARead0 = Normal, 1 = In Alarm
BI11225Diagnostic: AFD Motor Speed Too Low - 2ARead0 = Normal, 1 = In Alarm
BI11226Diagnostic: AFD Pump Out Speed Low - 1ARead0 = Normal, 1 = In Alarm
BI11227Diagnostic: AFD Pump Out Speed Low - 2ARead0 = Normal, 1 = In Alarm
BI11228Diagnostic: AFD Unexpected Shutdown - 1ARead0 = Normal, 1 = In Alarm
BI11229Diagnostic: AFD Unexpected Shutdown - 2ARead0 = Normal, 1 = In Alarm
BI11230Diagnostic: AFD Unhandled Fault - 1ARead0 = Normal, 1 = In Alarm
BI11231Diagnostic: AFD Unhandled Fault - 2ARead0 = Normal, 1 = In Alarm
BI11232Diagnostic: BAS Communication LostRead0 = Normal, 1 = In Alarm
BI11233Diagnostic: BAS Failed to Establish CommunicationRead0 = Normal, 1 = In Alarm
BI11234Diagnostic: Check ClockRead0 = Normal, 1 = In Alarm
BI11235Diagnostic: Chiller Service RecommendedRead0 = Normal, 1 = In Alarm
BI11236Diagnostic: Compressor Speed Too High - Thrust Load - Cprs1ARead0 = Normal, 1 = In Alarm
BI11237Diagnostic: Compressor Speed Too High - Thrust Load - Cprs1BRead0 = Normal, 1 = In Alarm
BI11238Diagnostic: Compressor Speed Too High - Thrust Load - Cprs2ARead0 = Normal, 1 = In Alarm
BI11239Diagnostic: Compressor Speed Too High - Thrust Load - Cprs2BRead0 = Normal, 1 = In Alarm
BI11240Diagnostic: Compressor Speed Too Low - Discharge Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11241Diagnostic: Compressor Speed Too Low - Discharge Temperature - 1BRead0 = Normal, 1 = In Alarm
BI11242Diagnostic: Compressor Speed Too Low - Discharge Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11243Diagnostic: Compressor Speed Too Low - Discharge Temperature - 2BRead0 = Normal, 1 = In Alarm
BI11244Diagnostic: Compressor Speed Too Low - Oil Viscosity - 1ARead0 = Normal, 1 = In Alarm
BI11245Diagnostic: Compressor Speed Too Low - Oil Viscosity - 1BRead0 = Normal, 1 = In Alarm
BI11246Diagnostic: Compressor Speed Too Low - Oil Viscosity - 2ARead0 = Normal, 1 = In Alarm
BI11247Diagnostic: Compressor Speed Too Low - Oil Viscosity - 2BRead0 = Normal, 1 = In Alarm
BI11248Diagnostic: Condenser Rfgt Pressure Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11249Diagnostic: Condenser Rfgt Pressure Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11250Diagnostic: Cprsr Did Not Accel: Shutdown - 1ARead0 = Normal, 1 = In Alarm
BI11251Diagnostic: Cprsr Did Not Accel: Shutdown - 1BRead0 = Normal, 1 = In Alarm
BI11252Diagnostic: Cprsr Did Not Accel: Shutdown - 2ARead0 = Normal, 1 = In Alarm
BI11253Diagnostic: Cprsr Did Not Accel: Shutdown - 2BRead0 = Normal, 1 = In Alarm
BI11254Diagnostic: Cprsr Did Not Accel: Transition - 1ARead0 = Normal, 1 = In Alarm
BI11255Diagnostic: Cprsr Did Not Accel: Transition - 1BRead0 = Normal, 1 = In Alarm
BI11256Diagnostic: Cprsr Did Not Accel: Transition - 2ARead0 = Normal, 1 = In Alarm
BI11257Diagnostic: Cprsr Did Not Accel: Transition - 2BRead0 = Normal, 1 = In Alarm
BI11258Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11259Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11260Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11261Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11262Diagnostic: Economizer Disch Press Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11263Diagnostic: Economizer Disch Press Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11264Diagnostic: Economizer Disch Press Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11265Diagnostic: Economizer Disch Press Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11266Diagnostic: Economizer Disch Temp Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11267Diagnostic: Economizer Disch Temp Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11268Diagnostic: Economizer Disch Temp Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11269Diagnostic: Economizer Disch Temp Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11270Diagnostic: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11271Diagnostic: Energy Meter Write Command FailureRead0 = Normal, 1 = In Alarm
BI11272Diagnostic: Evap Iso Valve Illegal Switch State - Ckt1Read0 = Normal, 1 = In Alarm
BI11273Diagnostic: Evap Iso Valve Illegal Switch State - Ckt2Read0 = Normal, 1 = In Alarm
BI11274Diagnostic: Evap Isolation Valve Closed Switch Failure - Ckt1Read0 = Normal, 1 = In Alarm
BI11275Diagnostic: Evap Isolation Valve Closed Switch Failure - Ckt2Read0 = Normal, 1 = In Alarm
BI11276Diagnostic: Evap Isolation Valve Failed To Close - Ckt1Read0 = Normal, 1 = In Alarm
BI11277Diagnostic: Evap Isolation Valve Failed To Close - Ckt2Read0 = Normal, 1 = In Alarm
BI11278Diagnostic: Evap Isolation Valve Failed To Open - Ckt1Read0 = Normal, 1 = In Alarm
BI11279Diagnostic: Evap Isolation Valve Failed To Open - Ckt2Read0 = Normal, 1 = In Alarm
BI11280Diagnostic: Evap Isolation Valve Open Switch Failure - Ckt1Read0 = Normal, 1 = In Alarm
BI11281Diagnostic: Evap Isolation Valve Open Switch Failure - Ckt2Read0 = Normal, 1 = In Alarm
BI11282Diagnostic: Evap Pump 1 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11283Diagnostic: Evap Pump 2 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11284Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11285Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11286Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1Read0 = Normal, 1 = In Alarm
BI11287Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2Read0 = Normal, 1 = In Alarm
BI11288Diagnostic: Evap Water Pump 1 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11289Diagnostic: Evap Water Pump 2 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11290Diagnostic: Evaporator Approach Error - Ckt1Read0 = Normal, 1 = In Alarm
BI11291Diagnostic: Evaporator Approach Error - Ckt2Read0 = Normal, 1 = In Alarm
BI11292Diagnostic: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11293Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11294Diagnostic: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11295Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11296Diagnostic: Evaporator Pump 1 FaultRead0 = Normal, 1 = In Alarm
BI11297Diagnostic: Evaporator Pump 2 FaultRead0 = Normal, 1 = In Alarm
BI11298Diagnostic: Evaporator Shell Rfgt Pressure Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11299Diagnostic: Evaporator Shell Rfgt Pressure Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11300Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11301Diagnostic: Evaporator Water Flow Lost - Pump1Read0 = Normal, 1 = In Alarm
BI11302Diagnostic: Evaporator Water Flow Lost - Pump2Read0 = Normal, 1 = In Alarm
BI11303Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11304Diagnostic: Evaporator Water Flow Overdue - Pump1Read0 = Normal, 1 = In Alarm
BI11305Diagnostic: Evaporator Water Flow Overdue - Pump2Read0 = Normal, 1 = In Alarm
BI11306Diagnostic: Excessive Condenser Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11307Diagnostic: Excessive Condenser Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11308Diagnostic: External Chilled Water SetpointRead0 = Normal, 1 = In Alarm
BI11309Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11310Diagnostic: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11311Diagnostic: EXV Pressure Equalization Failed - Ckt1Read0 = Normal, 1 = In Alarm
BI11312Diagnostic: EXV Pressure Equalization Failed - Ckt2Read0 = Normal, 1 = In Alarm
BI11313Diagnostic: Fan Inverter Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11314Diagnostic: Fan Inverter Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11315Diagnostic: Free Cooling Entering Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11316Diagnostic: Free Cooling Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11317Diagnostic: Free Cooling Glycol Flow LostRead0 = Normal, 1 = In Alarm
BI11318Diagnostic: Free Cooling Glycol Flow OverdueRead0 = Normal, 1 = In Alarm
BI11319Diagnostic: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11320Diagnostic: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11321Diagnostic: Free Cooling Glycol Temperature Equalization OverdueRead0 = Normal, 1 = In Alarm
BI11322Diagnostic: Free Cooling Leaving Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11323Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11324Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11325Diagnostic: Heat Recovery Water Flow LostRead0 = Normal, 1 = In Alarm
BI11326Diagnostic: Heat Recovery Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11327Diagnostic: High Cprsr Rfgt Discharge Temp - 1ARead0 = Normal, 1 = In Alarm
BI11328Diagnostic: High Cprsr Rfgt Discharge Temp - 1BRead0 = Normal, 1 = In Alarm
BI11329Diagnostic: High Cprsr Rfgt Discharge Temp - 2ARead0 = Normal, 1 = In Alarm
BI11330Diagnostic: High Cprsr Rfgt Discharge Temp - 2BRead0 = Normal, 1 = In Alarm
BI11331Diagnostic: High Differential Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11332Diagnostic: High Differential Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11333Diagnostic: High Differential Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11334Diagnostic: High Differential Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11335Diagnostic: High Differential Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11336Diagnostic: High Evap Shell Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11337Diagnostic: High Evap Shell Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11338Diagnostic: High Evaporator Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11339Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11340Diagnostic: High Motor Winding Temperature - 1A - Ckt1Read0 = Normal, 1 = In Alarm
BI11341Diagnostic: High Motor Winding Temperature - 1A - Ckt2Read0 = Normal, 1 = In Alarm
BI11342Diagnostic: High Motor Winding Temperature - 2A - Ckt1Read0 = Normal, 1 = In Alarm
BI11343Diagnostic: High Motor Winding Temperature - 2A - Ckt2Read0 = Normal, 1 = In Alarm
BI11344Diagnostic: High Oil Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11345Diagnostic: High Oil Temperature - 1BRead0 = Normal, 1 = In Alarm
BI11346Diagnostic: High Oil Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11347Diagnostic: High Oil Temperature - 2BRead0 = Normal, 1 = In Alarm
BI11348Diagnostic: High Pressure Cutout - 1ARead0 = Normal, 1 = In Alarm
BI11349Diagnostic: High Pressure Cutout - 1BRead0 = Normal, 1 = In Alarm
BI11350Diagnostic: High Pressure Cutout - 2ARead0 = Normal, 1 = In Alarm
BI11351Diagnostic: High Pressure Cutout - 2BRead0 = Normal, 1 = In Alarm
BI11352Diagnostic: High Pressure Cutout - Ckt1Read0 = Normal, 1 = In Alarm
BI11353Diagnostic: High Pressure Cutout - Ckt2Read0 = Normal, 1 = In Alarm
BI11354Diagnostic: High Refrigerant Pressure RatioRead0 = Normal, 1 = In Alarm
BI11355Diagnostic: High Refrigerant Pressure Ratio - 1ARead0 = Normal, 1 = In Alarm
BI11356Diagnostic: High Refrigerant Pressure Ratio - 1BRead0 = Normal, 1 = In Alarm
BI11357Diagnostic: High Refrigerant Pressure Ratio - 2ARead0 = Normal, 1 = In Alarm
BI11358Diagnostic: High Refrigerant Pressure Ratio - 2BRead0 = Normal, 1 = In Alarm
BI11359Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11360Diagnostic: LCI-C Software Mismatch: Use BAS ToolRead0 = Normal, 1 = In Alarm
BI11361Diagnostic: Liquid Line Pressure Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11362Diagnostic: Liquid Line Pressure Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11363Diagnostic: Liquid Line Temp Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11364Diagnostic: Liquid Line Temp Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11365Diagnostic: Loss of Oil at Compressor (Running) - Ckt1Read0 = Normal, 1 = In Alarm
BI11366Diagnostic: Loss of Oil at Compressor (Running) - Ckt2Read0 = Normal, 1 = In Alarm
BI11367Diagnostic: Loss of Oil at Compressor (Stopped) - Ckt1Read0 = Normal, 1 = In Alarm
BI11368Diagnostic: Loss of Oil at Compressor (Stopped) - Ckt2Read0 = Normal, 1 = In Alarm
BI11369Diagnostic: Loss of Oil for Compressor (Running) - Ckt1Read0 = Normal, 1 = In Alarm
BI11370Diagnostic: Loss of Oil for Compressor (Running) - Ckt2Read0 = Normal, 1 = In Alarm
BI11371Diagnostic: Loss of Oil for Compressor (Stopped) - Ckt1Read0 = Normal, 1 = In Alarm
BI11372Diagnostic: Loss of Oil for Compressor (Stopped) - Ckt2Read0 = Normal, 1 = In Alarm
BI11373Diagnostic: Low Differential Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11374Diagnostic: Low Differential Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11375Diagnostic: Low Differential Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11376Diagnostic: Low Differential Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11377Diagnostic: Low Discharge Superheat - 1ARead0 = Normal, 1 = In Alarm
BI11378Diagnostic: Low Discharge Superheat - 1BRead0 = Normal, 1 = In Alarm
BI11379Diagnostic: Low Discharge Superheat - 2ARead0 = Normal, 1 = In Alarm
BI11380Diagnostic: Low Discharge Superheat - 2BRead0 = Normal, 1 = In Alarm
BI11381Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffRead0 = Normal, 1 = In Alarm
BI11382Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffRead0 = Normal, 1 = In Alarm
BI11383Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11384Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11385Diagnostic: Low Glycol Pressure Free CoolingRead0 = Normal, 1 = In Alarm
BI11386Diagnostic: Low Glycol Temp Free CoolingRead0 = Normal, 1 = In Alarm
BI11387Diagnostic: Low Oil Flow - 1ARead0 = Normal, 1 = In Alarm
BI11388Diagnostic: Low Oil Flow - 1BRead0 = Normal, 1 = In Alarm
BI11389Diagnostic: Low Oil Flow - 2ARead0 = Normal, 1 = In Alarm
BI11390Diagnostic: Low Oil Flow - 2BRead0 = Normal, 1 = In Alarm
BI11391Diagnostic: Low Refrigerant Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11392Diagnostic: Low Refrigerant Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11393Diagnostic: Low Suction Refrigerant Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11394Diagnostic: Low Suction Refrigerant Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11395Diagnostic: Main Power LossRead0 = Normal, 1 = In Alarm
BI11396Diagnostic: Mfr Maintenance Recommended - 1ARead0 = Normal, 1 = In Alarm
BI11397Diagnostic: Mfr Maintenance Recommended - 1BRead0 = Normal, 1 = In Alarm
BI11398Diagnostic: Mfr Maintenance Recommended - 2ARead0 = Normal, 1 = In Alarm
BI11399Diagnostic: Mfr Maintenance Recommended - 2BRead0 = Normal, 1 = In Alarm
BI11400Diagnostic: Momentary Power Loss - Ckt1Read0 = Normal, 1 = In Alarm
BI11401Diagnostic: Momentary Power Loss - Ckt2Read0 = Normal, 1 = In Alarm
BI11402Diagnostic: Motor Current Overload - 1ARead0 = Normal, 1 = In Alarm
BI11403Diagnostic: Motor Current Overload - 1BRead0 = Normal, 1 = In Alarm
BI11404Diagnostic: Motor Current Overload - 2ARead0 = Normal, 1 = In Alarm
BI11405Diagnostic: Motor Current Overload - 2BRead0 = Normal, 1 = In Alarm
BI11406Diagnostic: Motor Winding Temp Sensor - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11407Diagnostic: Motor Winding Temp Sensor - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11408Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11409Diagnostic: MP: Non-Volatile Block Test ErrorRead0 = Normal, 1 = In Alarm
BI11410Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11411Diagnostic: No Differential Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11412Diagnostic: No Differential Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11413Diagnostic: No Differential Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11414Diagnostic: No Differential Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11415Diagnostic: Oil Analysis Recommended - Ckt1Read0 = Normal, 1 = In Alarm
BI11416Diagnostic: Oil Analysis Recommended - Ckt2Read0 = Normal, 1 = In Alarm
BI11417Diagnostic: Oil Filter Change Recommended - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11418Diagnostic: Oil Filter Change Recommended - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11419Diagnostic: Oil Flow Protection Fault - 1ARead0 = Normal, 1 = In Alarm
BI11420Diagnostic: Oil Flow Protection Fault - 1BRead0 = Normal, 1 = In Alarm
BI11421Diagnostic: Oil Flow Protection Fault - 2ARead0 = Normal, 1 = In Alarm
BI11422Diagnostic: Oil Flow Protection Fault - 2BRead0 = Normal, 1 = In Alarm
BI11423Diagnostic: Oil Pressure Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11424Diagnostic: Oil Pressure Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11425Diagnostic: Oil Pressure Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11426Diagnostic: Oil Pressure Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11427Diagnostic: Oil Supply Temperature Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11428Diagnostic: Oil Supply Temperature Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11429Diagnostic: Oil Temperature Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11430Diagnostic: Oil Temperature Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11431Diagnostic: Oil Temperature Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11432Diagnostic: Oil Temperature Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11433Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11434Diagnostic: Over VoltageRead0 = Normal, 1 = In Alarm
BI11435Diagnostic: Phase Loss - 1ARead0 = Normal, 1 = In Alarm
BI11436Diagnostic: Phase Loss - 1BRead0 = Normal, 1 = In Alarm
BI11437Diagnostic: Phase Loss - 2ARead0 = Normal, 1 = In Alarm
BI11438Diagnostic: Phase Loss - 2BRead0 = Normal, 1 = In Alarm
BI11439Diagnostic: Phase Reversal - 1ARead0 = Normal, 1 = In Alarm
BI11440Diagnostic: Phase Reversal - 1BRead0 = Normal, 1 = In Alarm
BI11441Diagnostic: Phase Reversal - 2ARead0 = Normal, 1 = In Alarm
BI11442Diagnostic: Phase Reversal - 2BRead0 = Normal, 1 = In Alarm
BI11443Diagnostic: Power Loss - 1ARead0 = Normal, 1 = In Alarm
BI11444Diagnostic: Power Loss - 1BRead0 = Normal, 1 = In Alarm
BI11445Diagnostic: Power Loss - 2ARead0 = Normal, 1 = In Alarm
BI11446Diagnostic: Power Loss - 2BRead0 = Normal, 1 = In Alarm
BI11447Diagnostic: Pumpdown Terminated By Time - Ckt1Read0 = Normal, 1 = In Alarm
BI11448Diagnostic: Pumpdown Terminated By Time - Ckt2Read0 = Normal, 1 = In Alarm
BI11449Diagnostic: Restart Inhibit Invoked - 1ARead0 = Normal, 1 = In Alarm
BI11450Diagnostic: Restart Inhibit Invoked - 1BRead0 = Normal, 1 = In Alarm
BI11451Diagnostic: Restart Inhibit Invoked - 2ARead0 = Normal, 1 = In Alarm
BI11452Diagnostic: Restart Inhibit Invoked - 2BRead0 = Normal, 1 = In Alarm
BI11453Diagnostic: Severe Current Imbalance - 1ARead0 = Normal, 1 = In Alarm
BI11454Diagnostic: Severe Current Imbalance - 1BRead0 = Normal, 1 = In Alarm
BI11455Diagnostic: Severe Current Imbalance - 2ARead0 = Normal, 1 = In Alarm
BI11456Diagnostic: Severe Current Imbalance - 2BRead0 = Normal, 1 = In Alarm
BI11457Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11458Diagnostic: Software Error 1002: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11459Diagnostic: Software Error 1003: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11460Diagnostic: Starter Comm Loss: Main Processor - 1ARead0 = Normal, 1 = In Alarm
BI11461Diagnostic: Starter Comm Loss: Main Processor - 1BRead0 = Normal, 1 = In Alarm
BI11462Diagnostic: Starter Comm Loss: Main Processor - 2ARead0 = Normal, 1 = In Alarm
BI11463Diagnostic: Starter Comm Loss: Main Processor - 2BRead0 = Normal, 1 = In Alarm
BI11464Diagnostic: Starter Contactor Interrupt Failure - 1ARead0 = Normal, 1 = In Alarm
BI11465Diagnostic: Starter Contactor Interrupt Failure - 1BRead0 = Normal, 1 = In Alarm
BI11466Diagnostic: Starter Contactor Interrupt Failure - 2ARead0 = Normal, 1 = In Alarm
BI11467Diagnostic: Starter Contactor Interrupt Failure - 2BRead0 = Normal, 1 = In Alarm
BI11468Diagnostic: Starter Did Not Fully Accelerate - Ckt1Read0 = Normal, 1 = In Alarm
BI11469Diagnostic: Starter Did Not Fully Accelerate - Ckt2Read0 = Normal, 1 = In Alarm
BI11470Diagnostic: Starter Did Not Transition - 1ARead0 = Normal, 1 = In Alarm
BI11471Diagnostic: Starter Did Not Transition - 1BRead0 = Normal, 1 = In Alarm
BI11472Diagnostic: Starter Did Not Transition - 2ARead0 = Normal, 1 = In Alarm
BI11473Diagnostic: Starter Did Not Transition - 2BRead0 = Normal, 1 = In Alarm
BI11474Diagnostic: Starter Dry Run Test - 1ARead0 = Normal, 1 = In Alarm
BI11475Diagnostic: Starter Dry Run Test - 1BRead0 = Normal, 1 = In Alarm
BI11476Diagnostic: Starter Dry Run Test - 2ARead0 = Normal, 1 = In Alarm
BI11477Diagnostic: Starter Dry Run Test - 2BRead0 = Normal, 1 = In Alarm
BI11478Diagnostic: Starter Failed to Arm/Start - 1ARead0 = Normal, 1 = In Alarm
BI11479Diagnostic: Starter Failed to Arm/Start - 1BRead0 = Normal, 1 = In Alarm
BI11480Diagnostic: Starter Failed to Arm/Start - 2ARead0 = Normal, 1 = In Alarm
BI11481Diagnostic: Starter Failed to Arm/Start - 2BRead0 = Normal, 1 = In Alarm
BI11482Diagnostic: Starter Fault Type I - 1ARead0 = Normal, 1 = In Alarm
BI11483Diagnostic: Starter Fault Type I - 1BRead0 = Normal, 1 = In Alarm
BI11484Diagnostic: Starter Fault Type I - 2ARead0 = Normal, 1 = In Alarm
BI11485Diagnostic: Starter Fault Type I - 2BRead0 = Normal, 1 = In Alarm
BI11486Diagnostic: Starter Fault Type II - 1ARead0 = Normal, 1 = In Alarm
BI11487Diagnostic: Starter Fault Type II - 1BRead0 = Normal, 1 = In Alarm
BI11488Diagnostic: Starter Fault Type II - 2ARead0 = Normal, 1 = In Alarm
BI11489Diagnostic: Starter Fault Type II - 2BRead0 = Normal, 1 = In Alarm
BI11490Diagnostic: Starter Fault Type III - 1ARead0 = Normal, 1 = In Alarm
BI11491Diagnostic: Starter Fault Type III - 1BRead0 = Normal, 1 = In Alarm
BI11492Diagnostic: Starter Fault Type III - 2ARead0 = Normal, 1 = In Alarm
BI11493Diagnostic: Starter Fault Type III - 2BRead0 = Normal, 1 = In Alarm
BI11494Diagnostic: Starter Module Memory Error Type 1 - 1ARead0 = Normal, 1 = In Alarm
BI11495Diagnostic: Starter Module Memory Error Type 1 - 1BRead0 = Normal, 1 = In Alarm
BI11496Diagnostic: Starter Module Memory Error Type 1 - 2ARead0 = Normal, 1 = In Alarm
BI11497Diagnostic: Starter Module Memory Error Type 1 - 2BRead0 = Normal, 1 = In Alarm
BI11498Diagnostic: Starter Module Memory Error Type 2 - 1ARead0 = Normal, 1 = In Alarm
BI11499Diagnostic: Starter Module Memory Error Type 2 - 1BRead0 = Normal, 1 = In Alarm
BI11500Diagnostic: Starter Module Memory Error Type 2 - 2ARead0 = Normal, 1 = In Alarm
BI11501Diagnostic: Starter Module Memory Error Type 2 - 2BRead0 = Normal, 1 = In Alarm
BI11502Diagnostic: Starts/Hours Modified 1ARead0 = Normal, 1 = In Alarm
BI11503Diagnostic: Starts/Hours Modified 1BRead0 = Normal, 1 = In Alarm
BI11504Diagnostic: Starts/Hours Modified 2ARead0 = Normal, 1 = In Alarm
BI11505Diagnostic: Starts/Hours Modified 2BRead0 = Normal, 1 = In Alarm
BI11506Diagnostic: Suction Pressure Transducer - Ckt1Read0 = Normal, 1 = In Alarm
BI11507Diagnostic: Suction Pressure Transducer - Ckt2Read0 = Normal, 1 = In Alarm
BI11508Diagnostic: Suction Refrigerant Pressure Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11509Diagnostic: Suction Refrigerant Pressure Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11510Diagnostic: Suction Refrigerant Pressure Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11511Diagnostic: Suction Refrigerant Pressure Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11512Diagnostic: Transition Complete Input Opened - 1ARead0 = Normal, 1 = In Alarm
BI11513Diagnostic: Transition Complete Input Opened - 1BRead0 = Normal, 1 = In Alarm
BI11514Diagnostic: Transition Complete Input Opened - 2ARead0 = Normal, 1 = In Alarm
BI11515Diagnostic: Transition Complete Input Opened - 2BRead0 = Normal, 1 = In Alarm
BI11516Diagnostic: Transition Complete Input Shorted - 1ARead0 = Normal, 1 = In Alarm
BI11517Diagnostic: Transition Complete Input Shorted - 1BRead0 = Normal, 1 = In Alarm
BI11518Diagnostic: Transition Complete Input Shorted - 2ARead0 = Normal, 1 = In Alarm
BI11519Diagnostic: Transition Complete Input Shorted - 2BRead0 = Normal, 1 = In Alarm
BI11520Diagnostic: Under VoltageRead0 = Normal, 1 = In Alarm
BI11521Diagnostic: Unexpected Starter Shutdown - 1ARead0 = Normal, 1 = In Alarm
BI11522Diagnostic: Unexpected Starter Shutdown - 1BRead0 = Normal, 1 = In Alarm
BI11523Diagnostic: Unexpected Starter Shutdown - 2ARead0 = Normal, 1 = In Alarm
BI11524Diagnostic: Unexpected Starter Shutdown - 2BRead0 = Normal, 1 = In Alarm
BI11525Diagnostic: Very Low Discharge Superheat - 1ARead0 = Normal, 1 = In Alarm
BI11526Diagnostic: Very Low Discharge Superheat - 2ARead0 = Normal, 1 = In Alarm
BI11527Diagnostic: Very Low Evap Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11528Diagnostic: Very Low Evap Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11529Diagnostic: Very Low Evap Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11530Diagnostic: Very Low Evap Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11531Diagnostic: Water System Differential PressureRead0 = Normal, 1 = In Alarm
BI11532Comm Loss: Fan Control ModuleRead0 = Normal, 1 = In Alarm
BI11533Comm Loss: Condenser Fan Circuit 1Read0 = Normal, 1 = In Alarm
BI11534Comm Loss: Condenser Fan Shared CircuitRead0 = Normal, 1 = In Alarm
BI11535Comm Loss: Condenser Fan Circuit 2Read0 = Normal, 1 = In Alarm
BI11536Diagnostic: Drive 1A configuration may be not completeRead0 = Normal, 1 = In Alarm
BI11537Diagnostic: Drive 1B configuration may be not completeRead0 = Normal, 1 = In Alarm
BI11538Diagnostic: Drive 2A configuration may be not completeRead0 = Normal, 1 = In Alarm
BI11539Diagnostic: Drive 2B configuration may be not completeRead0 = Normal, 1 = In Alarm
BI11540Comm Loss: Refrigerant Leak DetectorRead0 = Normal, 1 = In Alarm
BI11541Diagnostic: Refrigerant Leakage DetectedRead0 = Normal, 1 = In Alarm
BI11542Comm Loss: Evap Water Pump Inlet PressureRead0 = Normal, 1 = In Alarm
BI11543Diagnostic: Low Evaporator Water PressureRead0 = Normal, 1 = In Alarm
BI11544Diagnostic: Evaporator Water Pump Inlet Pressure TransducerRead0 = Normal, 1 = In Alarm
BVmin10100Chiller Auto Stop Command BASCommand the chiller to start running if operating conditions are satisfiedWrite0 = Stop, 1 = Auto
BV10101Reset DiagnosticInitiate a request to reset any controller diagnosticsWrite0 = Normal, 1 = Reset
BV10102Noise Reduction Request BASWrite0 = Normal, 1 = Locked Out
BV10103Circuit 1 Lockout BASLockout the Circuit-1 CompressorWrite0 = Normal, 1 = Locked Out
BV10104Circuit 2 Lockout BASLockout the Circuit-2 CompressorWrite0 = Normal, 1 = Locked Out
BV10105Compressor 1A Lockout BASLockout the Compressor 1AWrite0 = Normal, 1 = Locked Out
BV10106Compressor 1B Lockout BASLockout the Compressor 1BWrite0 = Normal, 1 = Locked Out
BV10107Compressor 2A Lockout BASLockout the Compressor 2AWrite0 = Normal, 1 = Locked Out
BV10108Compressor 2B Lockout BASLockout the Compressor 2BWrite0 = Normal, 1 = Locked Out
BV10109Free Cooling Auto Stop Command BASCommand the chiller to allow free cooling mode if conditions are satisfiedWrite0 = Stop, 1 = Auto
BV10110Energy Consumption ResetReset the energy consumption accumulated totalWrite0 = Accumulating, 1 = Reset
BV10111Heat Recovery Enable BASCommand the heat recovery to start running if operating conditions are satisfiedWrite0 = Off, 1 = On
BV10112Heat Recovery Lockout Circuit 1 BASLockout the heat recovery Circuit 1Write0 = Normal, 1 = Locked Out
BV10113Heat Recovery Lockout Circuit 2 BASLockout the heat recovery Circuit 2Write0 = Normal, 1 = Locked Out
BV10114Evaporator Water Pump Request BASBAS Evaporator Water Pump Auto On RequestWrite0 = Auto, 1 = On
BV10115Rapid Start Request BASWrite0 = Off, 1 = On
BV10116Free Cooling Compressor LockoutWrite0 = Normal, 1 = Locked Out
MI10100Running ModeRunning state of the chillerRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre- Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeOperating mode of the chillerRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Front Panel Chiller Mode CommandChiller Mode Command in Front PanelRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10103Refrigerant TypeChiller refrigerant typeRead5 = R-134a, 13 = R-513A, 16 = R-1234ze(E)
MI10104Cooling TypeCooling Type of chillerRead2 = Air Cooled
MI10105Model Information [GEN2]Model information of chillerRead5 = RTAF
MI10106Manufacture LocationLocation that the chiller was manufacturedRead3 = Pueblo, 4 = Charmes
MI10107Chiller Setpoint SourceSelected setpoint source for control purposeRead1 = BAS, 2 = External, 3 = Front Panel
MVmin10100Chiller Mode Command BASCommand the chiller ModeWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Sintesis RTAF and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 Sintesis RTAF

How many BACnet points does the Trane Symbio 800 Sintesis RTAF have?

This list has 826 BACnet objects: 137 analog inputs, 5 analog values, 658 binary inputs, 17 binary values, 8 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 Sintesis RTAF BACnet points are writable?

23 of the 826 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 Sintesis RTAF BACnet documentation?

The source is Symbio 800 Integration Points List BACnet/Modbus - Sintesis Model RTAF (BAS-PTS013B-EN), revision 04/07/2026, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS013B-EN_04072026.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 Sintesis RTAF?

Start with BV 10100 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10104 Chiller Running State (Chiller on/off status); BI 10102 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10107 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10113 Actual Running Capacity (Actual running capacity in percent); BI 10110 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 Sintesis RTAF?

BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10122 External Auto Stop Status reports the hardwired external auto/stop input, and BI 10101 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10102 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10107 Chiller Setpoint Source shows BAS, External or Front Panel.

Does the Trane Symbio 800 Sintesis RTAF need a BACnet heartbeat or have a communication timeout?

No timeout or heartbeat is described. The list includes the diagnostic flags BI 11232 'Diagnostic: BAS Communication Lost', BI 11233 'Diagnostic: BAS Failed to Establish Communication' and BI 11125 'Comm Loss: Local BAS Interface'; the document doesn't say what timeout sets them or what the chiller does when they are set.

How do I check these points on the real Symbio 800 Sintesis RTAF?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet/Modbus - Sintesis Model RTAF · BAS-PTS013B-EN · rev. 04/07/2026. Object names, instances and units are reproduced as published; descriptions are our own.