Centrifugal chiller controller · BACnet points list

Trane Symbio 800 CenTraVac (Duplex) BACnet points list

Updated 28 October 2026

Short answer

Duplex CenTraVac chillers use the same object names and types as the simplex list, but different instance numbers, and add circuit 2 / compressor 2 points, for about 720 objects in total. Setpoints and commands are AV/BV/MV objects; status is AI/BI/MI. Most binary inputs are per-alarm diagnostic flags.

This page lists 717 BACnet objects for the Trane Symbio 800 CenTraVac (Duplex) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 CenTraVac (Duplex)
Equipment
Centrifugal chiller controller
Equipment type
Chillers
BACnet objects
717 (17 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009
Source document
Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025
Download CSV 717 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 CenTraVac (Duplex)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10104Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10111Chiller Running StateChiller on/off statusRead
BI 10104Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10106Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10151Actual Running CapacityActual running capacity in percentRead
BI 10116Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10126 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10103 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

Network setup

Watch out for

Trane Symbio 800 CenTraVac (Duplex) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

717 of 717 shown
Type
Access
Show
Trane Symbio 800 CenTraVac (Duplex) BACnet Points List
DescriptionStates
AI10100Active Chilled Water SetpointTemperatureRead
AI10101Chilled Water Setpoint StatusTemperatureRead
AI10102Active Base Loading SetpointPercentageRead
AI10103Hot Water Setpoint ActiveTemperatureRead
AI10104Calculated Chiller CapacityPower, CoolingRead
AI10105Active Cool/Heat Setpoint TemperatureTemperatureRead
AImin10106Evaporator Leaving Water TemperatureTemperatureRead
AI10107Evaporator Entering Water TemperatureTemperatureRead
AI10108Condenser Entering Water TemperatureTemperatureRead
AI10109Condenser Leaving Water TemperatureTemperatureRead
AI10110Evaporator Water Flow RateFlow, WaterRead
AI10111Evaporator Differential Water PressureDifferential PressureRead
AI10112Condenser Water Flow RateFlow, WaterRead
AI10113Condenser Differential Water PressureDifferential PressureRead
AI10114AFD Last Diagnostic Code Ckt1Read
AI10115Unit Source ID (Last Diagnostic Code)Read
AI10116Refrigerant MonitorConcentrationRead
AI10117Evaporator Refrigerant Pressure Circuit 1PressureRead
AI10118Condenser Refrigerant Pressure Circuit 1PressureRead
AI10119Differential Refrigerant Pressure Circuit 1Differential PressureRead
AI10120Low Side Oil Pressure - Compressor 1APressureRead
AI10121High Side Oil Pressure - Compressor 1APressureRead
AI10122Oil Differential Pressure Circuit 1Differential PressureRead
AI10123Oil Temperature - Compressor 1ATemperatureRead
AI10124Evaporator Saturated Refrigerant Temperature Circuit 1TemperatureRead
AI10125Condenser Saturated Refrigerant Temperature Circuit 1TemperatureRead
AI10126Refrigerant Discharge Temperature - Compressor 1ATemperatureRead
AI10127Inlet Guide Vane 1 Percent Open Circuit 1PercentageRead
AI10128Inlet Guide Vane 2 Percent Open Circuit 1PercentageRead
AI10129Purge Carbon Tank Temperature Circuit 1TemperatureRead
AI10130Purge Liquid Temperature Circuit 1TemperatureRead
AI10131Purge Refrigerant Compressor Suction Temperature Circuit 1TemperatureRead
AI10132Time Until Next Purge Run Circuit 1 (in seconds)Read
AI10133Purge Pumpout Chiller On % (7 Days) Circuit 1PercentageRead
AI10134Purge Pumpout Chiller Off % (7 Days) Circuit 1PercentageRead
AI10135Purge 24 Hour Pumpout Circuit 1 (in seconds)Read
AI10136Purge Pumpout - Life Circuit 1 (in seconds)Read
AI10137Refrigeration - Life Circuit 1 (in seconds)Read
AI10138Starts - Compressor 1ARead
AI10139Run Time - Compressor 1A (in seconds)Read
AI10140Phase AB Voltage - Compressor 1AVoltageRead
AI10141Phase BC Voltage - Compressor 1AVoltageRead
AI10142Phase CA Voltage - Compressor 1AVoltageRead
AI10143Starter Average Phase Volt Circuit 1VoltageRead
AI10144Line 1 Current - Compressor 1ACurrentRead
AI10145Line 2 Current - Compressor 1ACurrentRead
AI10146Line 3 Current - Compressor 1ACurrentRead
AI10147Average Line Current Circuit 1CurrentRead
AI10148Line 1 Current RLA - Compressor 1APercentageRead
AI10149Line 2 Current RLA - Compressor 1APercentageRead
AI10150Line 3 Current RLA - Compressor 1APercentageRead
AImin10151Actual Running CapacityPercentageRead
AI10153Starter Load Power Factor - Compressor 1ARead
AI10154Inboard Bearing Temperature Circuit 1TemperatureRead
AI10155Outboard Bearing Temperature Circuit 1TemperatureRead
AI10156Motor Winding Temperature 1 Circuit 1TemperatureRead
AI10157Motor Winding Temperature 2 Circuit 1TemperatureRead
AI10158Motor Winding Temperature 3 Circuit 1TemperatureRead
AI10159AFD Frequency Circuit 1Read
AI10160AFD Transistor Temperature Circuit 1TemperatureRead
AI10161Drive Average Line Current Circuit 1CurrentRead
AI10162Drive Line Frequency Circuit 1Read
AI10163Drive Motor Voltage Circuit 1VoltageRead
AI10164Drive Inverter Base Temperature Circuit 1TemperatureRead
AI10165Drive Rectifier Base Temperature Circuit 1TemperatureRead
AI10166Drive Output Power Circuit 1Power, ElectricalRead
AI10167Frequency Command Circuit 1Read
AI10168Outboard Bearing Pad Temperature #1 Ckt1TemperatureRead
AI10169Outboard Bearing Pad Temperature #2 Ckt1TemperatureRead
AI10170Outboard Bearing Pad Temperature #3 Ckt1TemperatureRead
AI10171Restart Inhibit Time Remaining Circuit 1Read
AI10172Chiller Design CapacityPower, CoolingRead
AI10173Entering Condenser Water PressurePressureRead
AI10174Entering Evaporator Water PressurePressureRead
AI10175Leaving Condenser Water PressurePressureRead
AI10176Leaving Evaporator Water PressurePressureRead
AI10177Condenser Approach Temperature Circuit 1Temperature, DeltaRead
AI10178Evaporator Approach Temperature Circuit 1Temperature, DeltaRead
AI10179Drive DC Bus Voltage Circuit 1VoltageRead
AI10180Drive Motor Average Current RLA Circuit 1PercentageRead
AI10182Active Demand Limit SetpointPercentageRead
AI10183Active Demand Limit SetpointPercentageRead
AI10184Demand Limit Setpoint StatusPercentageRead
AI10185Number of CircuitsRead
AI10186Number of Compressors Circuit 1Read
AI10187Number of Compressors Circuit 2Read
AI10188Low Side Oil Pressure - Compressor 2APressureRead
AI10189High Side Oil Pressure - Compressor 2APressureRead
AI10190Oil Differential Pressure Circuit 2Differential PressureRead
AI10191Oil Temperature - Compressor 2ATemperatureRead
AI10192Evaporator Saturated Refrigerant Temperature Circuit 2TemperatureRead
AI10193Condenser Saturated Refrigerant Temperature Circuit 2TemperatureRead
AI10194Refrigerant Discharge Temperature - Compressor 2ATemperatureRead
AI10195Inlet Guide Vane 1 Percent Open Circuit 2PercentageRead
AI10196Inlet Guide Vane 2 Percent Open Circuit 2PercentageRead
AI10197Purge Carbon Tank Temperature Circuit 2TemperatureRead
AI10198Purge Liquid Temperature Circuit 2TemperatureRead
AI10199Purge Refrigerant Compressor Suction Temperature Circuit 2TemperatureRead
AI10200Time Until Next Purge Run Circuit 2 (in seconds)Read
AI10201Refrigeration - Life Circuit 2 (in seconds)Read
AI10202Starts - Compressor 2ARead
AI10203Run Time - Compressor 2A (in seconds)Read
AI10204Starter Average Phase Volt Circuit 2VoltageRead
AI10205Line 1 Current - Compressor 2ACurrentRead
AI10206Line 2 Current - Compressor 2ACurrentRead
AI10207Line 3 Current - Compressor 2ACurrentRead
AI10208Average Line Current Circuit 2CurrentRead
AI10209Drive Average Line Current Circuit 2CurrentRead
AI10210Starter Load Power Factor - Compressor 2ARead
AI10211Inboard Bearing Temperature Circuit 2TemperatureRead
AI10212Outboard Bearing Temperature Circuit 2TemperatureRead
AI10213Motor Winding Temperature 1 Circuit 2TemperatureRead
AI10214Motor Winding Temperature 2 Circuit 2TemperatureRead
AI10215Motor Winding Temperature 3 Circuit 2TemperatureRead
AI10216AFD Transistor Temperature Circuit 2TemperatureRead
AI10217Heat Recovery Entering Water TempTemperatureRead
AI10218Heat Recovery Leaving Water TempTemperatureRead
AI10219Purge Pumpout Chiller On % (7 Days) Circuit 2PercentageRead
AI10220Purge Pumpout Chiller Off % (7 Days) Circuit 2PercentageRead
AI10221Purge 24 Hour Pumpout Circuit 2 (in seconds)Read
AI10222Phase AB Voltage - Compressor 2AVoltageRead
AI10223Phase BC Voltage - Compressor 2AVoltageRead
AI10224Phase CA Voltage - Compressor 2AVoltageRead
AI10225Purge Pumpout - Life Circuit 2 (in seconds)Read
AI10226Drive Motor Average Current RLA Circuit 2PercentageRead
AI10227Drive Inverter Base Temperature Circuit 2TemperatureRead
AI10228Drive Rectifier Base Temperature Circuit 2TemperatureRead
AI10229Outboard Bearing Pad Temperature #1 Ckt2TemperatureRead
AI10230Outboard Bearing Pad Temperature #2 Ckt2TemperatureRead
AI10231Outboard Bearing Pad Temperature #3 Ckt2TemperatureRead
AI10232Evaporator Refrigerant Pressure Circuit 2PressureRead
AI10233Condenser Refrigerant Pressure Circuit 2PressureRead
AI10234Differential Refrigerant Pressure Circuit 2Differential PressureRead
AI10235Restart Inhibit Time Remaining Circuit 2Read
AI10236AFD Frequency Circuit 2Read
AI10237Drive Line Frequency Circuit 2Read
AI10238Frequency Command Circuit 2Read
AI10239Drive DC Bus Voltage Circuit 2VoltageRead
AI10240Drive Output Power Circuit 2Power, ElectricalRead
AI10241Line 1 Current RLA - Compressor 2APercentageRead
AI10242Line 2 Current RLA - Compressor 2APercentageRead
AI10243Line 3 Current RLA - Compressor 2APercentageRead
AI10244Drive Current Line 1 Circuit 1CurrentRead
AI10245Drive Current Line 2 Circuit 1CurrentRead
AI10246Drive Current Line 3 Circuit 1CurrentRead
AI10247Drive Current Line 1 Circuit 2CurrentRead
AI10248Drive Current Line 2 Circuit 2CurrentRead
AI10249Drive Current Line 3 Circuit 2CurrentRead
AI10250Starter Input Power Consumption Ckt1Power, ElectricalRead
AI10251Starter Input Power Consumption Ckt2Power, ElectricalRead
AI10252Drive Motor Voltage Circuit 2VoltageRead
AI10253Chiller Control SignalPercentageRead
AI10254Head Pressure Control StatusPercentageRead
AI10255AFD Last Diagnostic Code Ckt2Read
AI10256Voltage L1-L2 Circuit 1VoltageRead
AI10257Voltage L1-L3 Circuit 1VoltageRead
AI10258Voltage L2-L3 Circuit 1VoltageRead
AI10259Voltage L1-L2 Circuit 2VoltageRead
AI10260Voltage L1-L3 Circuit 2VoltageRead
AI10261Voltage L2-L3 Circuit 2VoltageRead
AI10262Average Line Voltage Circuit 1VoltageRead
AI10263Average Line Voltage Circuit 2VoltageRead
AI10264Line Current L1 Circuit 1CurrentRead
AI10265Line Current L2 Circuit 1CurrentRead
AI10266Line Current L3 Circuit 1CurrentRead
AI10267Line Current L1 Circuit 2CurrentRead
AI10268Line Current L2 Circuit 2CurrentRead
AI10269Line Current L3 Circuit 2CurrentRead
AI10270Unit Average Line Current Circuit 1CurrentRead
AI10271Unit Average Line Current Circuit 2CurrentRead
AI10272Line Frequency Circuit 1Read
AI10273Line Frequency Circuit 2Read
AI10274Power Factor Circuit 1Read
AI10275Power Factor Circuit 2Read
AI10276Power Demand Circuit 1Power, ElectricalRead
AI10277Power Demand Circuit 2Power, ElectricalRead
AI10278Total Real PowerPower, ElectricalRead
AI10279Unit Power ConsumptionPower, ElectricalRead
AI10280Energy ConsumptionEnergy, ElectricalRead
AI10281Energy Consumption LifetimeEnergy, ElectricalRead
AI10282Condenser Approach Temperature Circuit 2Temperature, DeltaRead
AI10283Evaporator Approach Temperature Circuit 2Temperature, DeltaRead
AI10284Drive Input Voltage Calculated 1AVoltageRead
AI10285Drive Input Voltage Calculated 2AVoltageRead
AI10286Drive Heatsink Temperature Compressor 1ATemperatureRead
AI10287Drive Heatsink Temperature Compressor 2ATemperatureRead
AI10288Outdoor Air Temperature LocalTemperatureRead
AI10289Heat Recovery Differential Water PressurePressureRead
AI10290Heat Recovery Water Flow RateFlow, WaterRead
AI10291Heat Recovery Calculated CapacityPower, HeatingRead
AI10292Heat Recovery Entering Water PressurePressureRead
AI10293Heat Recovery Leaving Water PressurePressureRead
AI10294Heat Recovery Approach Temperature Circuit 1Temperature, DeltaRead
AI10295Heat Recovery Approach Temperature Circuit 2Temperature, DeltaRead
AI10296High Side Oil Gauge Pressure - Compressor 1APressureRead
AI10297Low Side Oil Gauge Pressure - Compressor 1APressureRead
AI10298High Side Oil Gauge Pressure - Compressor 2APressureRead
AI10299Low Side Oil Gauge Pressure - Compressor 2APressureRead
AI10300Condenser Refrigerant Gauge Pressure Circuit 1PressureRead
AI10301Condenser Refrigerant Gauge Pressure Circuit 2PressureRead
AI10302Entering Condenser Water Gauge PressurePressureRead
AI10303Entering Evaporator Water Gauge PressurePressureRead
AI10304Evaporator Refrigerant Gauge Pressure Circuit 1PressureRead
AI10305Evaporator Refrigerant Gauge Pressure Circuit 2PressureRead
AI10306Heat Recovery Entering Water Gauge PressurePressureRead
AI10307Heat Recovery Leaving Water Gauge PressurePressureRead
AI10308Leaving Condenser Water Gauge PressurePressureRead
AI10309Leaving Evaporator Water Gauge PressurePressureRead
AI10310Compressor Discharge Superheat Circuit 1Temperature, DeltaRead
AI10311Compressor Discharge Superheat Circuit 2Temperature, DeltaRead
AI10312Unit Load CommandPercentageRead
AI10313Drive Motor Current U RLA Circuit 1PercentageRead
AI10314Drive Motor Current V RLA Circuit 1PercentageRead
AI10315Drive Motor Current W RLA Circuit 1PercentageRead
AI10316Drive Motor Current U Circuit 1CurrentRead
AI10317Drive Motor Current V Circuit 1CurrentRead
AI10318Drive Motor Current W Circuit 1CurrentRead
AI10319Drive Motor Current U RLA Circuit 2PercentageRead
AI10320Drive Motor Current V RLA Circuit 2PercentageRead
AI10321Drive Motor Current W RLA Circuit 2PercentageRead
AI10322Drive Motor Current U Circuit 2CurrentRead
AI10323Drive Motor Current V Circuit 2CurrentRead
AI10324Drive Motor Current W Circuit 2CurrentRead
AI10325Active Cooling Differential to StartTemperature, DeltaRead
AI10326Active Cooling Differential to StopTemperature, DeltaRead
AI10327Active Heating Differential to StartTemperature, DeltaRead
AI10328Active Heating Differential to StopTemperature, DeltaRead
AVmin10100Chilled Water SetpointTemperatureWrite
AVmin10101Demand Limit SetpointPercentWrite
AV10102Hot Water SetpointTemperatureWrite
AV10103Base Loading SetpointPercentWrite
AV10104BAS Cooling Differential to StartTemperature, DeltaWrite
AV10105BAS Cooling Differential to StopTemperature, DeltaWrite
AV10106BAS Heating Differential to StartTemperature, DeltaWrite
AV10107BAS Heating Differential to StopTemperature, DeltaWrite
BI10101Manual Override ExistsRead0 = Off, 1 = On
BI10102Base Loading Request ActiveRead0 = Inactive, 1 = Active
BI10103Run EnabledRead0 = Run Not Enabled, 1 = Run Enabled
BImin10104Local Setpoint ControlRead0 = Remote Control, 1 = Local Control
BI10105Maximum CapacityRead0 = Off, 1 = On
BI10106Capacity LimitedRead0 = Not Limited, 1 = Limited
BI10107Head Relief RequestRead0 = Off, 1 = On
BI10108Purge Compressor Relay Circuit 1Read0 = Off, 1 = On
BI10109Pump Out Relay Circuit 1Read0 = Off, 1 = On
BI10110Purge Regenerating Valve Solenoid Circuit 1Read0 = Off, 1 = On
BImin10111Chiller Running StateRead0 = Off, 1 = On
BI10112Evaporator Water Pump RequestRead0 = Off, 1 = On
BI10113Evaporator Water Flow StatusRead0 = No Flow, 1 = Flow
BI10114Condenser Water Pump RequestRead0 = Off, 1 = On
BI10115Condenser Water Flow StatusRead0 = No Flow, 1 = Flow
BImin10116Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10117Diagnostic Shutdown PresentRead0 = Normal, 1 = In Alarm
BI10118Diagnostic: Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10119Diagnostic: Local Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10120Diagnostic Present: InformationRead0 = Normal, 1 = In Alarm
BI10121Diagnostic Present: AdvisoryRead0 = Normal, 1 = In Alarm
BI10122Diagnostic Present: CriticalRead0 = Normal, 1 = In Alarm
BI10123Diagnostic Present: Service RequiredRead0 = Normal, 1 = In Alarm
BI10124Compressor 1A StatusRead0 = Off, 1 = Running
BI10125Front Panel Auto StopRead0 = Stop, 1 = Auto
BI10126External Auto Stop Input StatusRead0 = Stop, 1 = Auto
BI10127Purge Compressor Relay Circuit 2Read0 = Off, 1 = On
BI10128Purge Regenerating Valve Solenoid Circuit 2Read0 = Off, 1 = On
BI10130Pump Out Relay Circuit 2Read0 = Off, 1 = On
BI10131Compressor 2A StatusRead0 = Off, 1 = Running
BI10132Emergency StopRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10133Circuit 1 Cooling AvailableRead0 = No, 1 = Yes
BI10134Circuit 2 Cooling AvailableRead0 = No, 1 = Yes
BI10135Circuit 1 Lockout Front PanelRead0 = Normal, 1 = Locked Out
BI10136Circuit 2 Lockout Front PanelRead0 = Normal, 1 = Locked Out
BI10137Circuit 1 Lockout ExternalRead0 = Normal, 1 = Locked Out
BI10138Circuit 2 Lockout ExternalRead0 = Normal, 1 = Locked Out
BI10139Circuit 1 Lockout ActiveRead0 = Normal, 1 = Locked Out
BI10140Circuit 2 Lockout ActiveRead0 = Normal, 1 = Locked Out
BI10141Diagnostic Shutdown Present: AFD/Starter Circuit 1Read0 = Normal, 1 = In Alarm
BI10142Diagnostic Shutdown Present: AFD/Starter Circuit 2Read0 = Normal, 1 = In Alarm
BI10143Heat Recovery Water Flow StatusRead0 = No Flow, 1 = Flow
BI11000Diagnostic: AFD Comm Loss: Main Processor Circuit 1Read0 = Normal, 1 = In Alarm
BI11001Diagnostic: AFD Comm Loss: Main Processor Circuit 2Read0 = Normal, 1 = In Alarm
BI11002Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11003Diagnostic: AFD Control Board Memory Error Type 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11004Diagnostic: AFD DPI Communication Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11005Diagnostic: AFD DPI Communication Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11006Diagnostic: AFD Fatal Software Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11007Diagnostic: AFD Fatal Software Error Circuit 2Read0 = Normal, 1 = In Alarm
BI11008Diagnostic: AFD General Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11009Diagnostic: AFD General Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11010Diagnostic: AFD Ground Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11011Diagnostic: AFD Ground Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11012Diagnostic: AFD High Bus Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11013Diagnostic: AFD High Bus Voltage Circuit 2Read0 = Normal, 1 = In Alarm
BI11014Diagnostic: AFD High Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11015Diagnostic: AFD High Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11016Diagnostic: AFD I/O Board Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11017Diagnostic: AFD I/O Board Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11018Diagnostic: AFD Instantaneous Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11019Diagnostic: AFD Instantaneous Current Overload Circuit 2Read0 = Normal, 1 = In Alarm
BI11020Diagnostic: AFD Interrupt Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11021Diagnostic: AFD Interrupt Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11022Diagnostic: AFD Motor Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11023Diagnostic: AFD Motor Current Overload Circuit 2Read0 = Normal, 1 = In Alarm
BI11024Diagnostic: AFD Motor Short Circuit 1Read0 = Normal, 1 = In Alarm
BI11025Diagnostic: AFD Motor Short Circuit 2Read0 = Normal, 1 = In Alarm
BI11026Diagnostic: AFD Output Phase Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11027Diagnostic: AFD Output Phase Loss Circuit 2Read0 = Normal, 1 = In Alarm
BI11028Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11029Diagnostic: AFD Power Intfc Controller Board Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11030Diagnostic: AFD Power Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11031Diagnostic: AFD Power Loss Circuit 2Read0 = Normal, 1 = In Alarm
BI11032Diagnostic: AFD Power Structure Board Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11033Diagnostic: AFD Power Structure Board Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11034Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11035Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11038Diagnostic: At Speed Input Opened Circuit 1Read0 = Normal, 1 = In Alarm
BI11039Diagnostic: At Speed Input Opened Circuit 2Read0 = Normal, 1 = In Alarm
BI11040Diagnostic: At Speed Input Shorted Circuit 1Read0 = Normal, 1 = In Alarm
BI11041Diagnostic: At Speed Input Shorted Circuit 2Read0 = Normal, 1 = In Alarm
BI11042Diagnostic: Check ClockRead0 = Normal, 1 = In Alarm
BI11043Diagnostic: Check Oil Filter Circuit 1Read0 = Normal, 1 = In Alarm
BI11044Diagnostic: Check Oil Filter Circuit 2Read0 = Normal, 1 = In Alarm
BI11045Diagnostic: Check Oil Heater Circuit 1Read0 = Normal, 1 = In Alarm
BI11046Diagnostic: Check Oil Heater Circuit 2Read0 = Normal, 1 = In Alarm
BI11047Comm Loss: Adaptive Frequency Drive Circuit 1Read0 = Normal, 1 = In Alarm
BI11048Comm Loss: Adaptive Frequency Drive Circuit 2Read0 = Normal, 1 = In Alarm
BI11049Comm Loss: AFD Speed Signal VDC Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11050Comm Loss: AFD Speed Signal VDC Output Circuit 2Read0 = Normal, 1 = In Alarm
BI11051Comm Loss: Compressor Motor % RLA Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11052Comm Loss: Compressor Motor % RLA Output Circuit 2Read0 = Normal, 1 = In Alarm
BI11053Comm Loss: Cond Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11054Comm Loss: Cond Head Press Cntrl OutputRead0 = Normal, 1 = In Alarm
BI11055Comm Loss: Cond High Pressure Cutout Circuit 1Read0 = Normal, 1 = In Alarm
BI11056Comm Loss: Cond High Pressure Cutout Circuit 2Read0 = Normal, 1 = In Alarm
BI11057Comm Loss: Cond Refrigerant Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11058Comm Loss: Cond Refrigerant Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11059Comm Loss: Cond Rfgt Pressure Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11060Comm Loss: Cond Rfgt Pressure Output Circuit 2Read0 = Normal, 1 = In Alarm
BI11061Comm Loss: Cond Saturated Rfgt Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11062Comm Loss: Cond Saturated Rfgt Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11063Comm Loss: Condenser Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11064Comm Loss: Condenser Entering Water TempRead0 = Normal, 1 = In Alarm
BI11065Comm Loss: Condenser Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11066Comm Loss: Condenser Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11067Comm Loss: Condenser Liquid Level Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11068Comm Loss: Condenser Liquid Level Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11069Comm Loss: Condenser Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11070Comm Loss: Condenser Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11071Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11072Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11073Comm Loss: Economizer Bypass Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11074Comm Loss: Economizer Bypass Valve Circuit 2Read0 = Normal, 1 = In Alarm
BI11075Comm Loss: Emergency StopRead0 = Normal, 1 = In Alarm
BI11076Comm Loss: Energy Meter 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11077Comm Loss: Energy Meter 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11078Comm Loss: Evap Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11079Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11080Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11081Comm Loss: Evap Refrigerant Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11082Comm Loss: Evap Refrigerant Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11083Comm Loss: Evap Sat Refrig Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11084Comm Loss: Evap Sat Refrig Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11085Comm Loss: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11086Comm Loss: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11087Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11088Comm Loss: Evaporator Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11089Comm Loss: Ext Base Loading CommandRead0 = Normal, 1 = In Alarm
BI11090Comm Loss: Ext Base Loading SetpointRead0 = Normal, 1 = In Alarm
BI11091Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11092Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11093Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11094Comm Loss: External Ckt Lockout Circuit 1Read0 = Normal, 1 = In Alarm
BI11095Comm Loss: External Ckt Lockout Circuit 2Read0 = Normal, 1 = In Alarm
BI11097Comm Loss: External Hot Water CommandRead0 = Normal, 1 = In Alarm
BI11098Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11099Comm Loss: Generator Fault Input Circuit 1Read0 = Normal, 1 = In Alarm
BI11100Comm Loss: Generator Fault Input Circuit 2Read0 = Normal, 1 = In Alarm
BI11101Comm Loss: Generator Speed Signal Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11102Comm Loss: Generator Speed Signal Output Circuit 2Read0 = Normal, 1 = In Alarm
BI11103Comm Loss: Generator Start/Stop Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11104Comm Loss: Generator Start/Stop Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11105Comm Loss: Generator Up To Speed Input Circuit 1Read0 = Normal, 1 = In Alarm
BI11106Comm Loss: Generator Up To Speed Input Circuit 2Read0 = Normal, 1 = In Alarm
BI11107Comm Loss: Heat Recovery Entering Water TempRead0 = Normal, 1 = In Alarm
BI11108Comm Loss: Heat Recovery Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11112Comm Loss: Ice Building RelayRead0 = Normal, 1 = In Alarm
BI11113Comm Loss: IGV First Stage Actuator Circuit 1Read0 = Normal, 1 = In Alarm
BI11114Comm Loss: IGV First Stage Actuator Circuit 2Read0 = Normal, 1 = In Alarm
BI11115Comm Loss: IGV Second Stage Actuator Circuit 1Read0 = Normal, 1 = In Alarm
BI11116Comm Loss: IGV Second Stage Actuator Circuit 2Read0 = Normal, 1 = In Alarm
BI11117Comm Loss: Inboard Bearing Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11118Comm Loss: Inboard Bearing Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11119Comm Loss: Motor Winding Temperature 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11120Comm Loss: Motor Winding Temperature 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11121Comm Loss: Motor Winding Temperature 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11122Comm Loss: Motor Winding Temperature 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11123Comm Loss: Motor Winding Temperature 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11124Comm Loss: Motor Winding Temperature 3 Circuit 2Read0 = Normal, 1 = In Alarm
BI11125Comm Loss: Oil Cooler Solenoid Circuit 1Read0 = Normal, 1 = In Alarm
BI11126Comm Loss: Oil Cooler Solenoid Circuit 2Read0 = Normal, 1 = In Alarm
BI11127Comm Loss: Oil Pump Discharge Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11128Comm Loss: Oil Pump Discharge Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11129Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11130Comm Loss: Oil Tank Heater 4E1 Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11131Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11132Comm Loss: Oil Tank Heater 4E2 Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11133Comm Loss: Oil Tank Heater Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11134Comm Loss: Oil Tank Heater Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11135Comm Loss: Oil Tank Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11136Comm Loss: Oil Tank Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11137Comm Loss: Oil Tank Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11138Comm Loss: Oil Tank Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11139Comm Loss: Oil Vent Line Circuit 1Read0 = Normal, 1 = In Alarm
BI11140Comm Loss: Oil Vent Line Circuit 2Read0 = Normal, 1 = In Alarm
BI11141Comm Loss: Oil/Refrigerant Pump Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11142Comm Loss: Oil/Refrigerant Pump Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11143Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11144Comm Loss: Outboard Bearing Pad Temp 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11145Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11146Comm Loss: Outboard Bearing Pad Temp 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11147Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11148Comm Loss: Outboard Bearing Pad Temp 3 Circuit 2Read0 = Normal, 1 = In Alarm
BI11149Comm Loss: Outboard Bearing Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11150Comm Loss: Outboard Bearing Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11151Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11152Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11153Comm Loss: Programmable Relay Board 2Read0 = Normal, 1 = In Alarm
BI11154Comm Loss: Purge Alarm Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11155Comm Loss: Purge Alarm Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11156Comm Loss: Purge Carbon Tank Heater Rly Circuit 1Read0 = Normal, 1 = In Alarm
BI11157Comm Loss: Purge Carbon Tank Heater Rly Circuit 2Read0 = Normal, 1 = In Alarm
BI11158Comm Loss: Purge Carbon Tank Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11159Comm Loss: Purge Carbon Tank Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11160Comm Loss: Purge Condensing Unit Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11161Comm Loss: Purge Condensing Unit Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11162Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11163Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11164Comm Loss: Purge Exhaust Solenoid Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11165Comm Loss: Purge Exhaust Solenoid Output Circuit 2Read0 = Normal, 1 = In Alarm
BI11166Comm Loss: Purge Liquid Level Switch Circuit 1Read0 = Normal, 1 = In Alarm
BI11167Comm Loss: Purge Liquid Level Switch Circuit 2Read0 = Normal, 1 = In Alarm
BI11168Comm Loss: Purge Liquid Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11169Comm Loss: Purge Liquid Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11170Comm Loss: Purge Pumpout Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11171Comm Loss: Purge Pumpout Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11172Comm Loss: Purge Pumpout Solenoid Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11173Comm Loss: Purge Pumpout Solenoid Output Circuit 2Read0 = Normal, 1 = In Alarm
BI11174Comm Loss: Purge Regen Solenoid Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11175Comm Loss: Purge Regen Solenoid Relay Circuit 2Read0 = Normal, 1 = In Alarm
BI11176Comm Loss: Refrigerant Monitor InputRead0 = Normal, 1 = In Alarm
BI11177Comm Loss: Starter Circuit 1Read0 = Normal, 1 = In Alarm
BI11178Comm Loss: Starter Circuit 2Read0 = Normal, 1 = In Alarm
BI11179Comm Loss: Starter Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11180Comm Loss: Starter Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11181Comm Loss: Unit Purge Alarm RelayRead0 = Normal, 1 = In Alarm
BI11182Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 1Read0 = Normal, 1 = In Alarm
BI11183Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 2Read0 = Normal, 1 = In Alarm
BI11184Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11185Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11186Diagnostic: Condenser Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11187Diagnostic: Condenser Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11188Diagnostic: Condenser Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11189Diagnostic: Condenser High Pressure Cutout Circuit 1Read0 = Normal, 1 = In Alarm
BI11190Diagnostic: Condenser High Pressure Cutout Circuit 2Read0 = Normal, 1 = In Alarm
BI11191Diagnostic: Condenser Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11192Diagnostic: Condenser Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11193Diagnostic: Condenser Liquid Level Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11194Diagnostic: Condenser Liquid Level Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11195Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 1Read0 = Normal, 1 = In Alarm
BI11196Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 2Read0 = Normal, 1 = In Alarm
BI11197Diagnostic: Condenser Water Flow LostRead0 = Normal, 1 = In Alarm
BI11198Diagnostic: Condenser Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11199Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 1Read0 = Normal, 1 = In Alarm
BI11200Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 2Read0 = Normal, 1 = In Alarm
BI11201Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11202Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11203Diagnostic: Differential Oil Pressure Overdue Circuit 1Read0 = Normal, 1 = In Alarm
BI11204Diagnostic: Differential Oil Pressure Overdue Circuit 2Read0 = Normal, 1 = In Alarm
BI11206Diagnostic: Emergency StopRead0 = Normal, 1 = In Alarm
BI11207Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11208Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11209Diagnostic: Evaporator Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11210Diagnostic: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11211Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11212Diagnostic: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11213Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11214Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1Read0 = Normal, 1 = In Alarm
BI11215Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 2Read0 = Normal, 1 = In Alarm
BI11216Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11217Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11218Diagnostic: Excessive Loss of CommunicationRead0 = Normal, 1 = In Alarm
BI11221Diagnostic: Extended Compressor Surge Circuit 1Read0 = Normal, 1 = In Alarm
BI11222Diagnostic: Extended Compressor Surge Circuit 2Read0 = Normal, 1 = In Alarm
BI11223Diagnostic: External Base Loading SetpointRead0 = Normal, 1 = In Alarm
BI11224Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11225Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11230Diagnostic: Generator Fault Relay Open Circuit 1Read0 = Normal, 1 = In Alarm
BI11231Diagnostic: Generator Fault Relay Open Circuit 2Read0 = Normal, 1 = In Alarm
BI11232Diagnostic: Generator Ready Signal Overdue Circuit 1Read0 = Normal, 1 = In Alarm
BI11233Diagnostic: Generator Ready Signal Overdue Circuit 2Read0 = Normal, 1 = In Alarm
BI11234Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11235Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11236Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11237Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11238Diagnostic: High Differential Refrigerant Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11239Diagnostic: High Differential Refrigerant Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11240Diagnostic: High Evaporator Refrigerant Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11241Diagnostic: High Evaporator Refrigerant Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11242Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11243Diagnostic: High Inboard Bearing Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11244Diagnostic: High Inboard Bearing Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11245Diagnostic: High Motor Winding Temperature 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11246Diagnostic: High Motor Winding Temperature 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11247Diagnostic: High Motor Winding Temperature 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11248Diagnostic: High Motor Winding Temperature 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11249Diagnostic: High Motor Winding Temperature 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11250Diagnostic: High Motor Winding Temperature 3 Circuit 2Read0 = Normal, 1 = In Alarm
BI11251Diagnostic: High Oil Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11252Diagnostic: High Oil Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11253Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11254Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11255Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11256Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11257Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11258Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 2Read0 = Normal, 1 = In Alarm
BI11259Diagnostic: High Outboard Bearing Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11260Diagnostic: High Outboard Bearing Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11261Diagnostic: High Vacuum Lockout Circuit 1Read0 = Normal, 1 = In Alarm
BI11262Diagnostic: High Vacuum Lockout Circuit 2Read0 = Normal, 1 = In Alarm
BI11266Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11267Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11268Diagnostic: Inboard Bearing Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11269Diagnostic: Inboard Bearing Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11270Diagnostic: Inverted Condenser Water TemperatureRead0 = Normal, 1 = In Alarm
BI11271Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11272Diagnostic: Loss of Economizer Bypass Valve Control Circuit 1Read0 = Normal, 1 = In Alarm
BI11273Diagnostic: Loss of Economizer Bypass Valve Control Circuit 2Read0 = Normal, 1 = In Alarm
BI11274Diagnostic: Low Differential Oil Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11275Diagnostic: Low Differential Oil Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11276Diagnostic: Low Evap Leaving Water Temp: Unit OffRead0 = Normal, 1 = In Alarm
BI11277Diagnostic: Low Evap Leaving Water Temp: Unit OnRead0 = Normal, 1 = In Alarm
BI11278Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11279Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11280Diagnostic: Low Evaporator Water FlowRead0 = Normal, 1 = In Alarm
BI11281Diagnostic: Low Oil Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11282Diagnostic: Low Oil Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11283Diagnostic: Momentary Power Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11284Diagnostic: Momentary Power Loss Circuit 2Read0 = Normal, 1 = In Alarm
BI11285Diagnostic: Motor Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11286Diagnostic: Motor Current Overload Circuit 2Read0 = Normal, 1 = In Alarm
BI11287Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11288Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11289Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11290Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11291Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11292Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11293Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11294Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11295Diagnostic: Oil Pressure Sensor Calibration Circuit 1Read0 = Normal, 1 = In Alarm
BI11296Diagnostic: Oil Pressure Sensor Calibration Circuit 2Read0 = Normal, 1 = In Alarm
BI11297Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1Read0 = Normal, 1 = In Alarm
BI11298Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 2Read0 = Normal, 1 = In Alarm
BI11299Diagnostic: Oil Tank Pressure Transducer Circuit 1Read0 = Normal, 1 = In Alarm
BI11300Diagnostic: Oil Tank Pressure Transducer Circuit 2Read0 = Normal, 1 = In Alarm
BI11301Diagnostic: Oil Tank Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11302Diagnostic: Oil Tank Temperature Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11303Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11304Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11305Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11306Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11307Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11308Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11309Diagnostic: Outboard Bearing Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11310Diagnostic: Outboard Bearing Temperature Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11311Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11312Diagnostic: Over Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11313Diagnostic: Over Voltage Circuit 2Read0 = Normal, 1 = In Alarm
BI11314Diagnostic: Phase Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11315Diagnostic: Phase Loss Circuit 2Read0 = Normal, 1 = In Alarm
BI11316Diagnostic: Phase Reversal Circuit 1Read0 = Normal, 1 = In Alarm
BI11317Diagnostic: Phase Reversal Circuit 2Read0 = Normal, 1 = In Alarm
BI11318Diagnostic: Power Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11319Diagnostic: Power Loss Circuit 2Read0 = Normal, 1 = In Alarm
BI11320Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1Read0 = Normal, 1 = In Alarm
BI11321Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 2Read0 = Normal, 1 = In Alarm
BI11322Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1Read0 = Normal, 1 = In Alarm
BI11323Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 2Read0 = Normal, 1 = In Alarm
BI11324Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1Read0 = Normal, 1 = In Alarm
BI11325Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 2Read0 = Normal, 1 = In Alarm
BI11326Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11327Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11328Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11329Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11330Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1Read0 = Normal, 1 = In Alarm
BI11331Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 2Read0 = Normal, 1 = In Alarm
BI11332Diagnostic: Purge Liquid Level Too High Continuously Circuit 1Read0 = Normal, 1 = In Alarm
BI11333Diagnostic: Purge Liquid Level Too High Continuously Circuit 2Read0 = Normal, 1 = In Alarm
BI11334Diagnostic: Purge Liquid Level Too High Warning Circuit 1Read0 = Normal, 1 = In Alarm
BI11335Diagnostic: Purge Liquid Level Too High Warning Circuit 2Read0 = Normal, 1 = In Alarm
BI11336Diagnostic: Purge Liquid Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11337Diagnostic: Purge Liquid Temperature Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11338Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1Read0 = Normal, 1 = In Alarm
BI11339Diagnostic: Purge Regen Cooldown Temp Too High Circuit 2Read0 = Normal, 1 = In Alarm
BI11341Diagnostic: Refrigerant Monitor InputRead0 = Normal, 1 = In Alarm
BI11342Diagnostic: Restart Inhibit Circuit 1Read0 = Normal, 1 = In Alarm
BI11343Diagnostic: Restart Inhibit Circuit 2Read0 = Normal, 1 = In Alarm
BI11344Diagnostic: Severe Current Unbalance Circuit 1Read0 = Normal, 1 = In Alarm
BI11345Diagnostic: Severe Current Unbalance Circuit 2Read0 = Normal, 1 = In Alarm
BI11346Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11347Diagnostic: Software Error 1004: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11348Diagnostic: Starter Comm Loss: Main Processor Circuit 1Read0 = Normal, 1 = In Alarm
BI11349Diagnostic: Starter Comm Loss: Main Processor Circuit 2Read0 = Normal, 1 = In Alarm
BI11350Diagnostic: Starter Contactor Interrupt Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11351Diagnostic: Starter Contactor Interrupt Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11352Diagnostic: Starter Did Not Fully Accelerate Circuit 1Read0 = Normal, 1 = In Alarm
BI11353Diagnostic: Starter Did Not Fully Accelerate Circuit 2Read0 = Normal, 1 = In Alarm
BI11354Diagnostic: Starter Did Not Transition Circuit 1Read0 = Normal, 1 = In Alarm
BI11355Diagnostic: Starter Did Not Transition Circuit 2Read0 = Normal, 1 = In Alarm
BI11356Diagnostic: Starter Dry Run Test Circuit 1Read0 = Normal, 1 = In Alarm
BI11357Diagnostic: Starter Dry Run Test Circuit 2Read0 = Normal, 1 = In Alarm
BI11358Diagnostic: Starter Failed to Arm/ Start Circuit 1Read0 = Normal, 1 = In Alarm
BI11359Diagnostic: Starter Failed to Arm/ Start Circuit 2Read0 = Normal, 1 = In Alarm
BI11360Diagnostic: Starter Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11361Diagnostic: Starter Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11362Diagnostic: Starter Fault Type I Circuit 1Read0 = Normal, 1 = In Alarm
BI11363Diagnostic: Starter Fault Type I Circuit 2Read0 = Normal, 1 = In Alarm
BI11364Diagnostic: Starter Fault Type II Circuit 1Read0 = Normal, 1 = In Alarm
BI11365Diagnostic: Starter Fault Type II Circuit 2Read0 = Normal, 1 = In Alarm
BI11366Diagnostic: Starter Fault Type III Circuit 1Read0 = Normal, 1 = In Alarm
BI11367Diagnostic: Starter Fault Type III Circuit 2Read0 = Normal, 1 = In Alarm
BI11368Diagnostic: Starter Module Memory Error Type 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11369Diagnostic: Starter Module Memory Error Type 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11370Diagnostic: Starter Module Memory Error Type 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11371Diagnostic: Starter Module Memory Error Type 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11372Diagnostic: Transition Complete Input Opened Circuit 1Read0 = Normal, 1 = In Alarm
BI11373Diagnostic: Transition Complete Input Opened Circuit 2Read0 = Normal, 1 = In Alarm
BI11374Diagnostic: Transition Complete Input Shorted Circuit 1Read0 = Normal, 1 = In Alarm
BI11375Diagnostic: Transition Complete Input Shorted Circuit 2Read0 = Normal, 1 = In Alarm
BI11376Diagnostic: Under Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11377Diagnostic: Under Voltage Circuit 2Read0 = Normal, 1 = In Alarm
BI11378Diagnostic: Unexpected Differential Oil Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11379Diagnostic: Unexpected Differential Oil Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11380Diagnostic: Unexpected Starter Shutdown Circuit 1Read0 = Normal, 1 = In Alarm
BI11381Diagnostic: Unexpected Starter Shutdown Circuit 2Read0 = Normal, 1 = In Alarm
BI11382Diagnostic: AFD Bus Over Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11383Diagnostic: AFD Bus Over Voltage Circuit 2Read0 = Normal, 1 = In Alarm
BI11384Diagnostic: AFD Bus Under Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11385Diagnostic: AFD Bus Under Voltage Circuit 2Read0 = Normal, 1 = In Alarm
BI11386Diagnostic: AFD Motor Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11387Diagnostic: AFD Motor Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11388Diagnostic: AFD Precharge Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11389Diagnostic: AFD Precharge Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11390Diagnostic: AFD Over Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11391Diagnostic: AFD Over Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11392Diagnostic: AFD Mains Phase Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11393Diagnostic: AFD Mains Phase Loss Circuit 2Read0 = Normal, 1 = In Alarm
BI11394Diagnostic: AFD Motor Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11395Diagnostic: AFD Motor Current Overload Circuit 2Read0 = Normal, 1 = In Alarm
BI11396Diagnostic: AFD Ground Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11397Diagnostic: AFD Ground Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11398Diagnostic: AFD Short Circuit Circuit 1Read0 = Normal, 1 = In Alarm
BI11399Diagnostic: AFD Short Circuit Circuit 2Read0 = Normal, 1 = In Alarm
BI11400Diagnostic: AFD Safe Stop Circuit 1Read0 = Normal, 1 = In Alarm
BI11401Diagnostic: AFD Safe Stop Circuit 2Read0 = Normal, 1 = In Alarm
BI11402Diagnostic: AFD Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11403Diagnostic: AFD Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11404Diagnostic: AFD Speed Configuration Mismatch Circuit 1Read0 = Normal, 1 = In Alarm
BI11405Diagnostic: AFD Speed Configuration Mismatch Circuit 2Read0 = Normal, 1 = In Alarm
BI11406Diagnostic: AFD General Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11407Diagnostic: AFD General Failure Circuit 2Read0 = Normal, 1 = In Alarm
BI11408Comm Loss: Heat Recovery Differential Water PressureRead0 = Normal, 1 = In Alarm
BI11409Comm Loss: Heat Recovery Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11410Comm Loss: Heat Recovery Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11411Comm Loss: Heat Recovery Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11412Comm Loss: External Diagnostic ResetRead0 = Normal, 1 = In Alarm
BI11413Diagnostic: Heat Recovery Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11414Diagnostic: Heat Recovery Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11415Diagnostic: Heat Recovery Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11416Diagnostic: Inverted Heat Recovery Water TemperatureRead0 = Normal, 1 = In Alarm
BI11417Comm Loss: Condenser Rfgt Valve Feedback Circuit 1Read0 = Normal, 1 = In Alarm
BI11418Comm Loss: Condenser Rfgt Valve Feedback Circuit 2Read0 = Normal, 1 = In Alarm
BI11419Comm Loss: Economizer Rfgt Valve Feedback Circuit 1Read0 = Normal, 1 = In Alarm
BI11420Comm Loss: Economizer Rfgt Valve Feedback Circuit 2Read0 = Normal, 1 = In Alarm
BI11421Comm Loss: Economizer Refrigerant Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11422Comm Loss: Economizer Refrigerant Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11423Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 1Read0 = Normal, 1 = In Alarm
BI11424Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 2Read0 = Normal, 1 = In Alarm
BI11425Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 1Read0 = Normal, 1 = In Alarm
BI11426Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 2Read0 = Normal, 1 = In Alarm
BI11427Diagnostic: Low Condenser Water FlowRead0 = Normal, 1 = In Alarm
BI11428Diagnostic: Low Heat Recovery Water FlowRead0 = Normal, 1 = In Alarm
BI11429Diagnostic: Economizer Refrigerant Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11430Diagnostic: Economizer Refrigerant Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11431Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11432Diagnostic: AFD Emergency Stop Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11433Diagnostic: AFD Drive Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11434Diagnostic: AFD Inverter Heatsink Over Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11435Diagnostic: AFD Emergency Stop Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11436Diagnostic: AFD Drive Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11437Comm Loss: Condenser Rfgt Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11438Comm Loss: Condenser Rfgt Valve Circuit 2Read0 = Normal, 1 = In Alarm
BI11439Comm Loss: Economizer Rfgt Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11440Comm Loss: Economizer Rfgt Valve Circuit 2Read0 = Normal, 1 = In Alarm
BV10100Base Loading RequestWrite0 = Off, 1 = On
BV10101Reset DiagnosticWrite0 = Normal, 1 = Reset
BV10102Evaporator Water Pump Request BASWrite0 = Auto, 1 = On
BV10103Condenser Water Pump Request BASWrite0 = Auto, 1 = On
BVmin10104Chiller Auto Stop Command BASWrite0 = Stop, 1 = Auto
BV10105Circuit 1 Lockout BASWrite0 = Normal, 1 = Locked Out
BV10106Circuit 2 Lockout BASWrite0 = Normal, 1 = Locked Out
BV10107Energy Consumption ResetWrite0 = Accumulating, 1 = Reset
MI10100Running ModeRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Chiller Setpoint SourceRead1 = BAS, 2 = External, 3 = Front Panel
MI10103Cooling TypeRead1 = Water Cooled
MI10104Refrigerant TypeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A
MI10105Manufacturing LocationRead1 = Field Applied, 2 = La Crosse, 15 = Taicang
MI10106Model Information [GEN2]Read1 = CVHF, 2 = CVGF, 3 = CVHS, 11 = CDHF, 12 = CVR, 13 = CVHH, 14 = CDHH, 20 = CVHM, 38 = CVHE, 39 = CVHG, 40 = CVHL, 43 = CDHG
MVmin10100Chiller Mode Command BASWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CenTraVac (Duplex) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 CenTraVac (Duplex)

How many BACnet points does the Trane Symbio 800 CenTraVac (Duplex) have?

This list has 717 BACnet objects: 227 analog inputs, 8 analog values, 466 binary inputs, 8 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 CenTraVac (Duplex) BACnet points are writable?

17 of the 717 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 CenTraVac (Duplex) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - CenTraVac (BAS-PTS009C-EN), revision 12/12/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 CenTraVac (Duplex)?

Start with BV 10104 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10111 Chiller Running State (Chiller on/off status); BI 10104 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10106 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10151 Actual Running Capacity (Actual running capacity in percent); BI 10116 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 CenTraVac (Duplex)?

BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10126 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10103 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

How do I check these points on the real Symbio 800 CenTraVac (Duplex)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025. Object names, instances and units are reproduced as published; descriptions are our own.