Centrifugal chiller controller · BACnet points list
Trane Symbio 800 CenTraVac (Duplex) BACnet points list
Updated 28 October 2026
Duplex CenTraVac chillers use the same object names and types as the simplex list, but different instance numbers, and add circuit 2 / compressor 2 points, for about 720 objects in total. Setpoints and commands are AV/BV/MV objects; status is AI/BI/MI. Most binary inputs are per-alarm diagnostic flags.
This page lists 717 BACnet objects for the Trane Symbio 800 CenTraVac (Duplex) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 CenTraVac (Duplex)
- Equipment
- Centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 717 (17 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009
BMS integration notes: Trane Symbio 800 CenTraVac (Duplex)
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10104 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10111 | Chiller Running State | Chiller on/off status | Read |
| BI 10104 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10106 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10151 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10116 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10126 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10103 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 CenTraVac (Duplex) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10101 | Chilled Water Setpoint Status | Temperature | Read | ||
| AI | 10102 | Active Base Loading Setpoint | Percentage | Read | ||
| AI | 10103 | Hot Water Setpoint Active | Temperature | Read | ||
| AI | 10104 | Calculated Chiller Capacity | Power, Cooling | Read | ||
| AI | 10105 | Active Cool/Heat Setpoint Temperature | Temperature | Read | ||
| AImin | 10106 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10107 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AI | 10108 | Condenser Entering Water Temperature | Temperature | Read | ||
| AI | 10109 | Condenser Leaving Water Temperature | Temperature | Read | ||
| AI | 10110 | Evaporator Water Flow Rate | Flow, Water | Read | ||
| AI | 10111 | Evaporator Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10112 | Condenser Water Flow Rate | Flow, Water | Read | ||
| AI | 10113 | Condenser Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10114 | AFD Last Diagnostic Code Ckt1 | Read | |||
| AI | 10115 | Unit Source ID (Last Diagnostic Code) | Read | |||
| AI | 10116 | Refrigerant Monitor | Concentration | Read | ||
| AI | 10117 | Evaporator Refrigerant Pressure Circuit 1 | Pressure | Read | ||
| AI | 10118 | Condenser Refrigerant Pressure Circuit 1 | Pressure | Read | ||
| AI | 10119 | Differential Refrigerant Pressure Circuit 1 | Differential Pressure | Read | ||
| AI | 10120 | Low Side Oil Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10121 | High Side Oil Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10122 | Oil Differential Pressure Circuit 1 | Differential Pressure | Read | ||
| AI | 10123 | Oil Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10124 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10125 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10126 | Refrigerant Discharge Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10127 | Inlet Guide Vane 1 Percent Open Circuit 1 | Percentage | Read | ||
| AI | 10128 | Inlet Guide Vane 2 Percent Open Circuit 1 | Percentage | Read | ||
| AI | 10129 | Purge Carbon Tank Temperature Circuit 1 | Temperature | Read | ||
| AI | 10130 | Purge Liquid Temperature Circuit 1 | Temperature | Read | ||
| AI | 10131 | Purge Refrigerant Compressor Suction Temperature Circuit 1 | Temperature | Read | ||
| AI | 10132 | Time Until Next Purge Run Circuit 1 (in seconds) | Read | |||
| AI | 10133 | Purge Pumpout Chiller On % (7 Days) Circuit 1 | Percentage | Read | ||
| AI | 10134 | Purge Pumpout Chiller Off % (7 Days) Circuit 1 | Percentage | Read | ||
| AI | 10135 | Purge 24 Hour Pumpout Circuit 1 (in seconds) | Read | |||
| AI | 10136 | Purge Pumpout - Life Circuit 1 (in seconds) | Read | |||
| AI | 10137 | Refrigeration - Life Circuit 1 (in seconds) | Read | |||
| AI | 10138 | Starts - Compressor 1A | Read | |||
| AI | 10139 | Run Time - Compressor 1A (in seconds) | Read | |||
| AI | 10140 | Phase AB Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10141 | Phase BC Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10142 | Phase CA Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10143 | Starter Average Phase Volt Circuit 1 | Voltage | Read | ||
| AI | 10144 | Line 1 Current - Compressor 1A | Current | Read | ||
| AI | 10145 | Line 2 Current - Compressor 1A | Current | Read | ||
| AI | 10146 | Line 3 Current - Compressor 1A | Current | Read | ||
| AI | 10147 | Average Line Current Circuit 1 | Current | Read | ||
| AI | 10148 | Line 1 Current RLA - Compressor 1A | Percentage | Read | ||
| AI | 10149 | Line 2 Current RLA - Compressor 1A | Percentage | Read | ||
| AI | 10150 | Line 3 Current RLA - Compressor 1A | Percentage | Read | ||
| AImin | 10151 | Actual Running Capacity | Percentage | Read | ||
| AI | 10153 | Starter Load Power Factor - Compressor 1A | Read | |||
| AI | 10154 | Inboard Bearing Temperature Circuit 1 | Temperature | Read | ||
| AI | 10155 | Outboard Bearing Temperature Circuit 1 | Temperature | Read | ||
| AI | 10156 | Motor Winding Temperature 1 Circuit 1 | Temperature | Read | ||
| AI | 10157 | Motor Winding Temperature 2 Circuit 1 | Temperature | Read | ||
| AI | 10158 | Motor Winding Temperature 3 Circuit 1 | Temperature | Read | ||
| AI | 10159 | AFD Frequency Circuit 1 | Read | |||
| AI | 10160 | AFD Transistor Temperature Circuit 1 | Temperature | Read | ||
| AI | 10161 | Drive Average Line Current Circuit 1 | Current | Read | ||
| AI | 10162 | Drive Line Frequency Circuit 1 | Read | |||
| AI | 10163 | Drive Motor Voltage Circuit 1 | Voltage | Read | ||
| AI | 10164 | Drive Inverter Base Temperature Circuit 1 | Temperature | Read | ||
| AI | 10165 | Drive Rectifier Base Temperature Circuit 1 | Temperature | Read | ||
| AI | 10166 | Drive Output Power Circuit 1 | Power, Electrical | Read | ||
| AI | 10167 | Frequency Command Circuit 1 | Read | |||
| AI | 10168 | Outboard Bearing Pad Temperature #1 Ckt1 | Temperature | Read | ||
| AI | 10169 | Outboard Bearing Pad Temperature #2 Ckt1 | Temperature | Read | ||
| AI | 10170 | Outboard Bearing Pad Temperature #3 Ckt1 | Temperature | Read | ||
| AI | 10171 | Restart Inhibit Time Remaining Circuit 1 | Read | |||
| AI | 10172 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10173 | Entering Condenser Water Pressure | Pressure | Read | ||
| AI | 10174 | Entering Evaporator Water Pressure | Pressure | Read | ||
| AI | 10175 | Leaving Condenser Water Pressure | Pressure | Read | ||
| AI | 10176 | Leaving Evaporator Water Pressure | Pressure | Read | ||
| AI | 10177 | Condenser Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10178 | Evaporator Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10179 | Drive DC Bus Voltage Circuit 1 | Voltage | Read | ||
| AI | 10180 | Drive Motor Average Current RLA Circuit 1 | Percentage | Read | ||
| AI | 10182 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10183 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10184 | Demand Limit Setpoint Status | Percentage | Read | ||
| AI | 10185 | Number of Circuits | Read | |||
| AI | 10186 | Number of Compressors Circuit 1 | Read | |||
| AI | 10187 | Number of Compressors Circuit 2 | Read | |||
| AI | 10188 | Low Side Oil Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10189 | High Side Oil Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10190 | Oil Differential Pressure Circuit 2 | Differential Pressure | Read | ||
| AI | 10191 | Oil Temperature - Compressor 2A | Temperature | Read | ||
| AI | 10192 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature | Read | ||
| AI | 10193 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature | Read | ||
| AI | 10194 | Refrigerant Discharge Temperature - Compressor 2A | Temperature | Read | ||
| AI | 10195 | Inlet Guide Vane 1 Percent Open Circuit 2 | Percentage | Read | ||
| AI | 10196 | Inlet Guide Vane 2 Percent Open Circuit 2 | Percentage | Read | ||
| AI | 10197 | Purge Carbon Tank Temperature Circuit 2 | Temperature | Read | ||
| AI | 10198 | Purge Liquid Temperature Circuit 2 | Temperature | Read | ||
| AI | 10199 | Purge Refrigerant Compressor Suction Temperature Circuit 2 | Temperature | Read | ||
| AI | 10200 | Time Until Next Purge Run Circuit 2 (in seconds) | Read | |||
| AI | 10201 | Refrigeration - Life Circuit 2 (in seconds) | Read | |||
| AI | 10202 | Starts - Compressor 2A | Read | |||
| AI | 10203 | Run Time - Compressor 2A (in seconds) | Read | |||
| AI | 10204 | Starter Average Phase Volt Circuit 2 | Voltage | Read | ||
| AI | 10205 | Line 1 Current - Compressor 2A | Current | Read | ||
| AI | 10206 | Line 2 Current - Compressor 2A | Current | Read | ||
| AI | 10207 | Line 3 Current - Compressor 2A | Current | Read | ||
| AI | 10208 | Average Line Current Circuit 2 | Current | Read | ||
| AI | 10209 | Drive Average Line Current Circuit 2 | Current | Read | ||
| AI | 10210 | Starter Load Power Factor - Compressor 2A | Read | |||
| AI | 10211 | Inboard Bearing Temperature Circuit 2 | Temperature | Read | ||
| AI | 10212 | Outboard Bearing Temperature Circuit 2 | Temperature | Read | ||
| AI | 10213 | Motor Winding Temperature 1 Circuit 2 | Temperature | Read | ||
| AI | 10214 | Motor Winding Temperature 2 Circuit 2 | Temperature | Read | ||
| AI | 10215 | Motor Winding Temperature 3 Circuit 2 | Temperature | Read | ||
| AI | 10216 | AFD Transistor Temperature Circuit 2 | Temperature | Read | ||
| AI | 10217 | Heat Recovery Entering Water Temp | Temperature | Read | ||
| AI | 10218 | Heat Recovery Leaving Water Temp | Temperature | Read | ||
| AI | 10219 | Purge Pumpout Chiller On % (7 Days) Circuit 2 | Percentage | Read | ||
| AI | 10220 | Purge Pumpout Chiller Off % (7 Days) Circuit 2 | Percentage | Read | ||
| AI | 10221 | Purge 24 Hour Pumpout Circuit 2 (in seconds) | Read | |||
| AI | 10222 | Phase AB Voltage - Compressor 2A | Voltage | Read | ||
| AI | 10223 | Phase BC Voltage - Compressor 2A | Voltage | Read | ||
| AI | 10224 | Phase CA Voltage - Compressor 2A | Voltage | Read | ||
| AI | 10225 | Purge Pumpout - Life Circuit 2 (in seconds) | Read | |||
| AI | 10226 | Drive Motor Average Current RLA Circuit 2 | Percentage | Read | ||
| AI | 10227 | Drive Inverter Base Temperature Circuit 2 | Temperature | Read | ||
| AI | 10228 | Drive Rectifier Base Temperature Circuit 2 | Temperature | Read | ||
| AI | 10229 | Outboard Bearing Pad Temperature #1 Ckt2 | Temperature | Read | ||
| AI | 10230 | Outboard Bearing Pad Temperature #2 Ckt2 | Temperature | Read | ||
| AI | 10231 | Outboard Bearing Pad Temperature #3 Ckt2 | Temperature | Read | ||
| AI | 10232 | Evaporator Refrigerant Pressure Circuit 2 | Pressure | Read | ||
| AI | 10233 | Condenser Refrigerant Pressure Circuit 2 | Pressure | Read | ||
| AI | 10234 | Differential Refrigerant Pressure Circuit 2 | Differential Pressure | Read | ||
| AI | 10235 | Restart Inhibit Time Remaining Circuit 2 | Read | |||
| AI | 10236 | AFD Frequency Circuit 2 | Read | |||
| AI | 10237 | Drive Line Frequency Circuit 2 | Read | |||
| AI | 10238 | Frequency Command Circuit 2 | Read | |||
| AI | 10239 | Drive DC Bus Voltage Circuit 2 | Voltage | Read | ||
| AI | 10240 | Drive Output Power Circuit 2 | Power, Electrical | Read | ||
| AI | 10241 | Line 1 Current RLA - Compressor 2A | Percentage | Read | ||
| AI | 10242 | Line 2 Current RLA - Compressor 2A | Percentage | Read | ||
| AI | 10243 | Line 3 Current RLA - Compressor 2A | Percentage | Read | ||
| AI | 10244 | Drive Current Line 1 Circuit 1 | Current | Read | ||
| AI | 10245 | Drive Current Line 2 Circuit 1 | Current | Read | ||
| AI | 10246 | Drive Current Line 3 Circuit 1 | Current | Read | ||
| AI | 10247 | Drive Current Line 1 Circuit 2 | Current | Read | ||
| AI | 10248 | Drive Current Line 2 Circuit 2 | Current | Read | ||
| AI | 10249 | Drive Current Line 3 Circuit 2 | Current | Read | ||
| AI | 10250 | Starter Input Power Consumption Ckt1 | Power, Electrical | Read | ||
| AI | 10251 | Starter Input Power Consumption Ckt2 | Power, Electrical | Read | ||
| AI | 10252 | Drive Motor Voltage Circuit 2 | Voltage | Read | ||
| AI | 10253 | Chiller Control Signal | Percentage | Read | ||
| AI | 10254 | Head Pressure Control Status | Percentage | Read | ||
| AI | 10255 | AFD Last Diagnostic Code Ckt2 | Read | |||
| AI | 10256 | Voltage L1-L2 Circuit 1 | Voltage | Read | ||
| AI | 10257 | Voltage L1-L3 Circuit 1 | Voltage | Read | ||
| AI | 10258 | Voltage L2-L3 Circuit 1 | Voltage | Read | ||
| AI | 10259 | Voltage L1-L2 Circuit 2 | Voltage | Read | ||
| AI | 10260 | Voltage L1-L3 Circuit 2 | Voltage | Read | ||
| AI | 10261 | Voltage L2-L3 Circuit 2 | Voltage | Read | ||
| AI | 10262 | Average Line Voltage Circuit 1 | Voltage | Read | ||
| AI | 10263 | Average Line Voltage Circuit 2 | Voltage | Read | ||
| AI | 10264 | Line Current L1 Circuit 1 | Current | Read | ||
| AI | 10265 | Line Current L2 Circuit 1 | Current | Read | ||
| AI | 10266 | Line Current L3 Circuit 1 | Current | Read | ||
| AI | 10267 | Line Current L1 Circuit 2 | Current | Read | ||
| AI | 10268 | Line Current L2 Circuit 2 | Current | Read | ||
| AI | 10269 | Line Current L3 Circuit 2 | Current | Read | ||
| AI | 10270 | Unit Average Line Current Circuit 1 | Current | Read | ||
| AI | 10271 | Unit Average Line Current Circuit 2 | Current | Read | ||
| AI | 10272 | Line Frequency Circuit 1 | Read | |||
| AI | 10273 | Line Frequency Circuit 2 | Read | |||
| AI | 10274 | Power Factor Circuit 1 | Read | |||
| AI | 10275 | Power Factor Circuit 2 | Read | |||
| AI | 10276 | Power Demand Circuit 1 | Power, Electrical | Read | ||
| AI | 10277 | Power Demand Circuit 2 | Power, Electrical | Read | ||
| AI | 10278 | Total Real Power | Power, Electrical | Read | ||
| AI | 10279 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10280 | Energy Consumption | Energy, Electrical | Read | ||
| AI | 10281 | Energy Consumption Lifetime | Energy, Electrical | Read | ||
| AI | 10282 | Condenser Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10283 | Evaporator Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10284 | Drive Input Voltage Calculated 1A | Voltage | Read | ||
| AI | 10285 | Drive Input Voltage Calculated 2A | Voltage | Read | ||
| AI | 10286 | Drive Heatsink Temperature Compressor 1A | Temperature | Read | ||
| AI | 10287 | Drive Heatsink Temperature Compressor 2A | Temperature | Read | ||
| AI | 10288 | Outdoor Air Temperature Local | Temperature | Read | ||
| AI | 10289 | Heat Recovery Differential Water Pressure | Pressure | Read | ||
| AI | 10290 | Heat Recovery Water Flow Rate | Flow, Water | Read | ||
| AI | 10291 | Heat Recovery Calculated Capacity | Power, Heating | Read | ||
| AI | 10292 | Heat Recovery Entering Water Pressure | Pressure | Read | ||
| AI | 10293 | Heat Recovery Leaving Water Pressure | Pressure | Read | ||
| AI | 10294 | Heat Recovery Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10295 | Heat Recovery Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10296 | High Side Oil Gauge Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10297 | Low Side Oil Gauge Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10298 | High Side Oil Gauge Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10299 | Low Side Oil Gauge Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10300 | Condenser Refrigerant Gauge Pressure Circuit 1 | Pressure | Read | ||
| AI | 10301 | Condenser Refrigerant Gauge Pressure Circuit 2 | Pressure | Read | ||
| AI | 10302 | Entering Condenser Water Gauge Pressure | Pressure | Read | ||
| AI | 10303 | Entering Evaporator Water Gauge Pressure | Pressure | Read | ||
| AI | 10304 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Pressure | Read | ||
| AI | 10305 | Evaporator Refrigerant Gauge Pressure Circuit 2 | Pressure | Read | ||
| AI | 10306 | Heat Recovery Entering Water Gauge Pressure | Pressure | Read | ||
| AI | 10307 | Heat Recovery Leaving Water Gauge Pressure | Pressure | Read | ||
| AI | 10308 | Leaving Condenser Water Gauge Pressure | Pressure | Read | ||
| AI | 10309 | Leaving Evaporator Water Gauge Pressure | Pressure | Read | ||
| AI | 10310 | Compressor Discharge Superheat Circuit 1 | Temperature, Delta | Read | ||
| AI | 10311 | Compressor Discharge Superheat Circuit 2 | Temperature, Delta | Read | ||
| AI | 10312 | Unit Load Command | Percentage | Read | ||
| AI | 10313 | Drive Motor Current U RLA Circuit 1 | Percentage | Read | ||
| AI | 10314 | Drive Motor Current V RLA Circuit 1 | Percentage | Read | ||
| AI | 10315 | Drive Motor Current W RLA Circuit 1 | Percentage | Read | ||
| AI | 10316 | Drive Motor Current U Circuit 1 | Current | Read | ||
| AI | 10317 | Drive Motor Current V Circuit 1 | Current | Read | ||
| AI | 10318 | Drive Motor Current W Circuit 1 | Current | Read | ||
| AI | 10319 | Drive Motor Current U RLA Circuit 2 | Percentage | Read | ||
| AI | 10320 | Drive Motor Current V RLA Circuit 2 | Percentage | Read | ||
| AI | 10321 | Drive Motor Current W RLA Circuit 2 | Percentage | Read | ||
| AI | 10322 | Drive Motor Current U Circuit 2 | Current | Read | ||
| AI | 10323 | Drive Motor Current V Circuit 2 | Current | Read | ||
| AI | 10324 | Drive Motor Current W Circuit 2 | Current | Read | ||
| AI | 10325 | Active Cooling Differential to Start | Temperature, Delta | Read | ||
| AI | 10326 | Active Cooling Differential to Stop | Temperature, Delta | Read | ||
| AI | 10327 | Active Heating Differential to Start | Temperature, Delta | Read | ||
| AI | 10328 | Active Heating Differential to Stop | Temperature, Delta | Read | ||
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percent | Write | ||
| AV | 10102 | Hot Water Setpoint | Temperature | Write | ||
| AV | 10103 | Base Loading Setpoint | Percent | Write | ||
| AV | 10104 | BAS Cooling Differential to Start | Temperature, Delta | Write | ||
| AV | 10105 | BAS Cooling Differential to Stop | Temperature, Delta | Write | ||
| AV | 10106 | BAS Heating Differential to Start | Temperature, Delta | Write | ||
| AV | 10107 | BAS Heating Differential to Stop | Temperature, Delta | Write | ||
| BI | 10101 | Manual Override Exists | Read | 0 = Off, 1 = On | ||
| BI | 10102 | Base Loading Request Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10103 | Run Enabled | Read | 0 = Run Not Enabled, 1 = Run Enabled | ||
| BImin | 10104 | Local Setpoint Control | Read | 0 = Remote Control, 1 = Local Control | ||
| BI | 10105 | Maximum Capacity | Read | 0 = Off, 1 = On | ||
| BI | 10106 | Capacity Limited | Read | 0 = Not Limited, 1 = Limited | ||
| BI | 10107 | Head Relief Request | Read | 0 = Off, 1 = On | ||
| BI | 10108 | Purge Compressor Relay Circuit 1 | Read | 0 = Off, 1 = On | ||
| BI | 10109 | Pump Out Relay Circuit 1 | Read | 0 = Off, 1 = On | ||
| BI | 10110 | Purge Regenerating Valve Solenoid Circuit 1 | Read | 0 = Off, 1 = On | ||
| BImin | 10111 | Chiller Running State | Read | 0 = Off, 1 = On | ||
| BI | 10112 | Evaporator Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10113 | Evaporator Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 10114 | Condenser Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10115 | Condenser Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BImin | 10116 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10117 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10118 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10119 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10120 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10121 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10122 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10123 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10124 | Compressor 1A Status | Read | 0 = Off, 1 = Running | ||
| BI | 10125 | Front Panel Auto Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10126 | External Auto Stop Input Status | Read | 0 = Stop, 1 = Auto | ||
| BI | 10127 | Purge Compressor Relay Circuit 2 | Read | 0 = Off, 1 = On | ||
| BI | 10128 | Purge Regenerating Valve Solenoid Circuit 2 | Read | 0 = Off, 1 = On | ||
| BI | 10130 | Pump Out Relay Circuit 2 | Read | 0 = Off, 1 = On | ||
| BI | 10131 | Compressor 2A Status | Read | 0 = Off, 1 = Running | ||
| BI | 10132 | Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | ||
| BI | 10133 | Circuit 1 Cooling Available | Read | 0 = No, 1 = Yes | ||
| BI | 10134 | Circuit 2 Cooling Available | Read | 0 = No, 1 = Yes | ||
| BI | 10135 | Circuit 1 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10136 | Circuit 2 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10137 | Circuit 1 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10138 | Circuit 2 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10139 | Circuit 1 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10140 | Circuit 2 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10141 | Diagnostic Shutdown Present: AFD/Starter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10142 | Diagnostic Shutdown Present: AFD/Starter Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10143 | Heat Recovery Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 11000 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Diagnostic: AFD Comm Loss: Main Processor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Diagnostic: AFD DPI Communication Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Diagnostic: AFD DPI Communication Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Diagnostic: AFD Fatal Software Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Diagnostic: AFD Fatal Software Error Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: AFD General Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: AFD General Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Diagnostic: AFD Ground Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Diagnostic: AFD High Bus Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Diagnostic: AFD High Bus Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Diagnostic: AFD High Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Diagnostic: AFD High Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Diagnostic: AFD I/O Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Diagnostic: AFD I/O Board Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Diagnostic: AFD Instantaneous Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Diagnostic: AFD Instantaneous Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Diagnostic: AFD Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Diagnostic: AFD Interrupt Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Diagnostic: AFD Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Diagnostic: AFD Motor Short Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Diagnostic: AFD Motor Short Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Diagnostic: AFD Output Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: AFD Output Phase Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Diagnostic: AFD Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: AFD Power Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: AFD Power Structure Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: AFD Power Structure Board Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: At Speed Input Opened Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Diagnostic: At Speed Input Opened Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Diagnostic: At Speed Input Shorted Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Diagnostic: At Speed Input Shorted Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Diagnostic: Check Oil Filter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Diagnostic: Check Oil Filter Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Diagnostic: Check Oil Heater Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: Check Oil Heater Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Comm Loss: Adaptive Frequency Drive Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Comm Loss: AFD Speed Signal VDC Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Comm Loss: AFD Speed Signal VDC Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Comm Loss: Compressor Motor % RLA Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Comm Loss: Compressor Motor % RLA Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Comm Loss: Cond Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Comm Loss: Cond Head Press Cntrl Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Comm Loss: Cond High Pressure Cutout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Comm Loss: Cond High Pressure Cutout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Comm Loss: Cond Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Comm Loss: Cond Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Comm Loss: Cond Rfgt Pressure Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Cond Rfgt Pressure Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Cond Saturated Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Cond Saturated Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Comm Loss: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Comm Loss: Condenser Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Comm Loss: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Comm Loss: Condenser Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Comm Loss: Condenser Liquid Level Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Comm Loss: Condenser Liquid Level Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Comm Loss: Condenser Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Comm Loss: Condenser Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Economizer Bypass Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Economizer Bypass Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Comm Loss: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Comm Loss: Energy Meter 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Comm Loss: Energy Meter 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Comm Loss: Evap Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Comm Loss: Evap Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Comm Loss: Evap Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Comm Loss: Evap Sat Refrig Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: Evap Sat Refrig Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Comm Loss: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Evaporator Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Ext Base Loading Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Ext Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: External Ckt Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Comm Loss: External Ckt Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Comm Loss: Generator Fault Input Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Comm Loss: Generator Fault Input Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Comm Loss: Generator Speed Signal Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss: Generator Speed Signal Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Generator Start/Stop Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Generator Start/Stop Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Generator Up To Speed Input Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Generator Up To Speed Input Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Comm Loss: Heat Recovery Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Comm Loss: Heat Recovery Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Ice Building Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: IGV First Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: IGV First Stage Actuator Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Comm Loss: IGV Second Stage Actuator Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Comm Loss: Inboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Inboard Bearing Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Motor Winding Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Motor Winding Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Motor Winding Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Oil Cooler Solenoid Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Oil Cooler Solenoid Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Oil Pump Discharge Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: Oil Pump Discharge Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Comm Loss: Oil Tank Heater Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Oil Tank Heater Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: Oil Tank Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Oil Tank Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Oil Tank Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Oil Tank Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Oil Vent Line Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Oil Vent Line Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Comm Loss: Outboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Outboard Bearing Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Purge Alarm Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Purge Alarm Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Comm Loss: Purge Carbon Tank Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Purge Carbon Tank Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Purge Condensing Unit Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Purge Condensing Unit Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Comm Loss: Purge Exhaust Solenoid Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Comm Loss: Purge Exhaust Solenoid Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Comm Loss: Purge Liquid Level Switch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Comm Loss: Purge Liquid Level Switch Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Comm Loss: Purge Liquid Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Comm Loss: Purge Liquid Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Comm Loss: Purge Pumpout Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Comm Loss: Purge Pumpout Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Comm Loss: Purge Pumpout Solenoid Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Comm Loss: Purge Pumpout Solenoid Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Comm Loss: Purge Regen Solenoid Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Comm Loss: Purge Regen Solenoid Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Comm Loss: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Comm Loss: Starter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Comm Loss: Starter Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Comm Loss: Starter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Comm Loss: Starter Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Comm Loss: Unit Purge Alarm Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: Condenser Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: Condenser Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Diagnostic: Condenser High Pressure Cutout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Diagnostic: Condenser High Pressure Cutout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Condenser Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Condenser Liquid Level Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: Condenser Liquid Level Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Condenser Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Condenser Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: Differential Oil Pressure Overdue Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: Differential Oil Pressure Overdue Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Diagnostic: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Excessive Loss of Communication | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Extended Compressor Surge Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Extended Compressor Surge Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: External Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: Generator Fault Relay Open Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: Generator Fault Relay Open Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Generator Ready Signal Overdue Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: Generator Ready Signal Overdue Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: High Differential Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: High Differential Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Diagnostic: High Inboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Diagnostic: High Inboard Bearing Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: High Motor Winding Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Diagnostic: High Motor Winding Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Diagnostic: High Motor Winding Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: High Oil Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Diagnostic: High Oil Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Diagnostic: High Outboard Bearing Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Diagnostic: High Outboard Bearing Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Diagnostic: High Vacuum Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Diagnostic: High Vacuum Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Diagnostic: Inboard Bearing Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Diagnostic: Inboard Bearing Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Diagnostic: Inverted Condenser Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Diagnostic: Loss of Economizer Bypass Valve Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: Loss of Economizer Bypass Valve Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Diagnostic: Low Differential Oil Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: Low Differential Oil Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Diagnostic: Low Evaporator Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Diagnostic: Low Oil Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: Low Oil Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: Momentary Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Diagnostic: Momentary Power Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11293 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11294 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11295 | Diagnostic: Oil Pressure Sensor Calibration Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11296 | Diagnostic: Oil Pressure Sensor Calibration Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11297 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11298 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11299 | Diagnostic: Oil Tank Pressure Transducer Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11300 | Diagnostic: Oil Tank Pressure Transducer Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11301 | Diagnostic: Oil Tank Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11302 | Diagnostic: Oil Tank Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11303 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11304 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11305 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11306 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11307 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11308 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11309 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11310 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11311 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11312 | Diagnostic: Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11313 | Diagnostic: Over Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11314 | Diagnostic: Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11315 | Diagnostic: Phase Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11316 | Diagnostic: Phase Reversal Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11317 | Diagnostic: Phase Reversal Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11318 | Diagnostic: Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11319 | Diagnostic: Power Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11320 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11321 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11322 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11323 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11324 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11325 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11326 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11327 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11328 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11329 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11330 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11331 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11332 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11333 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11334 | Diagnostic: Purge Liquid Level Too High Warning Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11335 | Diagnostic: Purge Liquid Level Too High Warning Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11336 | Diagnostic: Purge Liquid Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11337 | Diagnostic: Purge Liquid Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11338 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11339 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11341 | Diagnostic: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11342 | Diagnostic: Restart Inhibit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11343 | Diagnostic: Restart Inhibit Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11344 | Diagnostic: Severe Current Unbalance Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11345 | Diagnostic: Severe Current Unbalance Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11346 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11347 | Diagnostic: Software Error 1004: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11348 | Diagnostic: Starter Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11349 | Diagnostic: Starter Comm Loss: Main Processor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11350 | Diagnostic: Starter Contactor Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11351 | Diagnostic: Starter Contactor Interrupt Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11352 | Diagnostic: Starter Did Not Fully Accelerate Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11353 | Diagnostic: Starter Did Not Fully Accelerate Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11354 | Diagnostic: Starter Did Not Transition Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11355 | Diagnostic: Starter Did Not Transition Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11356 | Diagnostic: Starter Dry Run Test Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11357 | Diagnostic: Starter Dry Run Test Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11358 | Diagnostic: Starter Failed to Arm/ Start Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11359 | Diagnostic: Starter Failed to Arm/ Start Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11360 | Diagnostic: Starter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11361 | Diagnostic: Starter Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11362 | Diagnostic: Starter Fault Type I Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11363 | Diagnostic: Starter Fault Type I Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11364 | Diagnostic: Starter Fault Type II Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11365 | Diagnostic: Starter Fault Type II Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11366 | Diagnostic: Starter Fault Type III Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11367 | Diagnostic: Starter Fault Type III Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11368 | Diagnostic: Starter Module Memory Error Type 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11369 | Diagnostic: Starter Module Memory Error Type 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11370 | Diagnostic: Starter Module Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11371 | Diagnostic: Starter Module Memory Error Type 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11372 | Diagnostic: Transition Complete Input Opened Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11373 | Diagnostic: Transition Complete Input Opened Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11374 | Diagnostic: Transition Complete Input Shorted Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11375 | Diagnostic: Transition Complete Input Shorted Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11376 | Diagnostic: Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11377 | Diagnostic: Under Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11378 | Diagnostic: Unexpected Differential Oil Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11379 | Diagnostic: Unexpected Differential Oil Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11380 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11381 | Diagnostic: Unexpected Starter Shutdown Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11382 | Diagnostic: AFD Bus Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11383 | Diagnostic: AFD Bus Over Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11384 | Diagnostic: AFD Bus Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11385 | Diagnostic: AFD Bus Under Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11386 | Diagnostic: AFD Motor Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11387 | Diagnostic: AFD Motor Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11388 | Diagnostic: AFD Precharge Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11389 | Diagnostic: AFD Precharge Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11390 | Diagnostic: AFD Over Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11391 | Diagnostic: AFD Over Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11392 | Diagnostic: AFD Mains Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11393 | Diagnostic: AFD Mains Phase Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11394 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11395 | Diagnostic: AFD Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11396 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11397 | Diagnostic: AFD Ground Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11398 | Diagnostic: AFD Short Circuit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11399 | Diagnostic: AFD Short Circuit Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11400 | Diagnostic: AFD Safe Stop Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11401 | Diagnostic: AFD Safe Stop Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11402 | Diagnostic: AFD Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11403 | Diagnostic: AFD Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11404 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11405 | Diagnostic: AFD Speed Configuration Mismatch Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11406 | Diagnostic: AFD General Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11407 | Diagnostic: AFD General Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11408 | Comm Loss: Heat Recovery Differential Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11409 | Comm Loss: Heat Recovery Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11410 | Comm Loss: Heat Recovery Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11411 | Comm Loss: Heat Recovery Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11412 | Comm Loss: External Diagnostic Reset | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11413 | Diagnostic: Heat Recovery Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11414 | Diagnostic: Heat Recovery Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11415 | Diagnostic: Heat Recovery Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11416 | Diagnostic: Inverted Heat Recovery Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11417 | Comm Loss: Condenser Rfgt Valve Feedback Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11418 | Comm Loss: Condenser Rfgt Valve Feedback Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11419 | Comm Loss: Economizer Rfgt Valve Feedback Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11420 | Comm Loss: Economizer Rfgt Valve Feedback Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11421 | Comm Loss: Economizer Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11422 | Comm Loss: Economizer Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11423 | Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11424 | Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11425 | Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11426 | Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11427 | Diagnostic: Low Condenser Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11428 | Diagnostic: Low Heat Recovery Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11429 | Diagnostic: Economizer Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11430 | Diagnostic: Economizer Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11431 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11432 | Diagnostic: AFD Emergency Stop Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11433 | Diagnostic: AFD Drive Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11434 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11435 | Diagnostic: AFD Emergency Stop Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11436 | Diagnostic: AFD Drive Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11437 | Comm Loss: Condenser Rfgt Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11438 | Comm Loss: Condenser Rfgt Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11439 | Comm Loss: Economizer Rfgt Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11440 | Comm Loss: Economizer Rfgt Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Base Loading Request | Write | 0 = Off, 1 = On | ||
| BV | 10101 | Reset Diagnostic | Write | 0 = Normal, 1 = Reset | ||
| BV | 10102 | Evaporator Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BV | 10103 | Condenser Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BVmin | 10104 | Chiller Auto Stop Command BAS | Write | 0 = Stop, 1 = Auto | ||
| BV | 10105 | Circuit 1 Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10106 | Circuit 2 Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10107 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| MI | 10100 | Running Mode | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | ||
| MI | 10101 | Operating Mode | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10102 | Chiller Setpoint Source | Read | 1 = BAS, 2 = External, 3 = Front Panel | ||
| MI | 10103 | Cooling Type | Read | 1 = Water Cooled | ||
| MI | 10104 | Refrigerant Type | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A | ||
| MI | 10105 | Manufacturing Location | Read | 1 = Field Applied, 2 = La Crosse, 15 = Taicang | ||
| MI | 10106 | Model Information [GEN2] | Read | 1 = CVHF, 2 = CVGF, 3 = CVHS, 11 = CDHF, 12 = CVR, 13 = CVHH, 14 = CDHH, 20 = CVHM, 38 = CVHE, 39 = CVHG, 40 = CVHL, 43 = CDHG | ||
| MVmin | 10100 | Chiller Mode Command BAS | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the communicated engineering unit follows the factory-configured unit system (I-P or SI), not the web UI display setting.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- Same document as the simplex list; this is the duplex table only.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CenTraVac (Duplex) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 CenTraVac (Duplex)
How many BACnet points does the Trane Symbio 800 CenTraVac (Duplex) have?
This list has 717 BACnet objects: 227 analog inputs, 8 analog values, 466 binary inputs, 8 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 CenTraVac (Duplex) BACnet points are writable?
17 of the 717 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 CenTraVac (Duplex) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - CenTraVac (BAS-PTS009C-EN), revision 12/12/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 CenTraVac (Duplex)?
Start with BV 10104 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10111 Chiller Running State (Chiller on/off status); BI 10104 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10106 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10151 Actual Running Capacity (Actual running capacity in percent); BI 10116 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 CenTraVac (Duplex)?
BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10126 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10103 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 CenTraVac (Duplex)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013
Source: Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025. Object names, instances and units are reproduced as published; descriptions are our own.