Water-cooled screw chiller controller · BACnet points list

Trane Symbio 800 RTWD (CH530) BACnet points list

Updated 28 October 2026

Short answer

A two-page Symbio 800 list for RTWD chillers marked CH530 that contains analog inputs only: 47 AIs with small instance numbers. They cover active setpoint and current limit, evaporator and condenser water temperatures, refrigerant and oil pressures, compressor starts and run times, line voltages and currents. No command, setpoint or binary status objects are listed.

This page lists 47 BACnet objects for the Trane Symbio 800 RTWD (CH530) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 RTWD (CH530)
Equipment
Water-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
47 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035
Source document
Symbio 800 Integration Points List BACnet - RTWD (CH530) · BAS-PTS035A-EN · rev. 12/6/2024
Download CSV 47 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 RTWD (CH530)

Integration in brief

This list has only analog inputs, so the BMS can monitor the chiller but has no start/stop, setpoint or alarm object here. Map the active setpoint, entering and leaving water temperatures and running capacity. For control or alarms, check whether the controller on site matches another Trane RTWD list.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Active Cool/Heat Setpoint TemperatureChilled or hot water setpoint in useRead
AI 2Active Current Limit SetpointCurrent limit in use, %Read
AI 44Evaporator Entering Water TempEntering (return) chilled water temperatureRead
AI 45Evaporator Leaving Water TempLeaving chilled water temperatureRead
AI 5Actual Running CapacityActual running capacity in percentRead

Network setup

Watch out for

Trane Symbio 800 RTWD (CH530) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

47 of 47 shown
Type
Analog
Show
Trane Symbio 800 RTWD (CH530) BACnet Points List
DescriptionStates
AImin1Active Cool/Heat Setpoint TemperatureActive chiller water or hot water setpointTemperatureRead
AImin2Active Current Limit SetpointActive capacity current limit setpointPercentRead
AImin5Actual Running CapacityLevel of capacity that the chiller is currently running atPercentRead
AI7Suction Pressure- Ckt 1Circuit 1 suction pressurePressureRead
AI10Suction Pressure- Ckt 2Circuit 2 suction pressurePressureRead
AI12Evaporator Saturated Refrigerant Temperature- Ckt 1Circuit 2 evaporator refrigerant temperatureTemperatureRead
AI14Evaporator Saturated Refrigerant Temperature- Ckt 2Circuit 2 evaporator refrigerant temperatureTemperatureRead
AI16Condenser Refrigerant Pressure- Ckt 1Circuit 1 condenser refrigerant pressurePressureRead
AI18Condenser Refrigerant Pressure- Ckt 2Circuit 2 condenser refrigerant pressurePressureRead
AI20Condenser Saturated Refrigerant Temperature- Ckt 1Circuit 1 condenser refrigerant temperatureTemperatureRead
AI22Condenser Saturated Refrigerant Temperature- Ckt 2Circuit 2 condenser refrigerant temperatureTemperatureRead
AI24Unit Power ConsumptionThe power being consumed by the chillerPowerRead
AI25Local Atmospheric PressurePressureRead
AI26Starts- Compressor 1ANumber of starts for compressor 1ARead
AI28Starts- Compressor 2ANumber of starts for compressor 2ARead
AI34Run Time- Compressor 1ATotal run time of compressor 1ATimeRead
AI36Run Time- Compressor 2ATotal run time of compressor 2ATimeRead
AImin44Evaporator Entering Water TempTemperature of the water entering the evaporatorTemperatureRead
AImin45Evaporator Leaving Water TempTemperature of the water leaving the evaporatorTemperatureRead
AI46Condenser Entering Water TempTemperature of the water entering the condenserTemperatureRead
AI47Condenser Leaving Water TempTemperature of the water leaving the condenserTemperatureRead
AI48High Side Oil Pressure- Compressor 1APressure of the oil at the high side of compressor 1APressureRead
AI50High Side Oil Pressure- Compressor 2APressure of the oil at the high side of compressor 2APressureRead
AI57Outdoor Air TemperatureTemperatureRead
AI58Condenser Control OutputPercentage of condenser water flow being requested by the chillerPercentRead
AI59Phase AB Voltage- Compressor 1APhase AB voltage, compressor 1AVoltageRead
AI60Phase BC Voltage- Compressor 1APhase BC voltage, compressor 1AVoltageRead
AI61Phase CA Voltage- Compressor 1APhase CA voltage, compressor 1AVoltageRead
AI65Phase AB Voltage- Compressor 2APhase AB voltage, compressor 2AVoltageRead
AI66Phase BC Voltage- Compressor 2APhase BC voltage, compressor 2AVoltageRead
AI67Phase CA Voltage- Compressor 2APhase CA voltage, compressor 2AVoltageRead
AI71Line 1 Current (in Amps)- Compressor 1ACurrentRead
AI72Line 2 Current (in Amps)- Compressor 1ACurrentRead
AI73Line 3 Current (in Amps)- Compressor 1ACurrentRead
AI77Line 1 Current (in Amps)- Compressor 2ACurrentRead
AI78Line 2 Current (in Amps)- Compressor 2ACurrentRead
AI79Line 3 Current (in Amps)- Compressor 2ACurrentRead
AI83Line 1 Current (%RLA)- Compressor 1APercentRead
AI84Line 2 Current (%RLA)- Compressor 1APercentRead
AI85Line 3 Current (%RLA)- Compressor 1APercentRead
AI89Line 1 Current (%RLA)- Compressor 2APercentRead
AI90Line 2 Current (%RLA)- Compressor 2APercentRead
AI91Line 3 Current (%RLA)- Compressor 2APercentRead
AI95Number of CircuitsRead
AI96Number of Compressors, Ckt 1Read
AI97Number of Compressors, Ckt 2Read
AI98Chiller Design CapacityDesign Capacity of the ChillerRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 RTWD (CH530) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 RTWD (CH530)

How many BACnet points does the Trane Symbio 800 RTWD (CH530) have?

This list has 47 BACnet objects: 47 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 RTWD (CH530) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 RTWD (CH530) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - RTWD (CH530) (BAS-PTS035A-EN), revision 12/6/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS035A-EN_12062024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 RTWD (CH530)?

Start with AI 1 Active Cool/Heat Setpoint Temperature (Chilled or hot water setpoint in use); AI 2 Active Current Limit Setpoint (Current limit in use, %); AI 44 Evaporator Entering Water Temp (Entering (return) chilled water temperature); AI 45 Evaporator Leaving Water Temp (Leaving chilled water temperature); AI 5 Actual Running Capacity (Actual running capacity in percent).

How do I check these points on the real Symbio 800 RTWD (CH530)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - RTWD (CH530) · BAS-PTS035A-EN · rev. 12/6/2024. Object names, instances and units are reproduced as published; descriptions are our own.