Water-cooled screw chiller controller · BACnet points list

Trane Symbio 800 RTHD (UC800) BACnet points list

Updated 28 October 2026

Short answer

A Symbio 800 list of about 245 objects for RTHD chillers marked UC800, with small instance numbers. About 170 are diagnostic binary inputs (BI 500 and up); the rest cover water temperatures and flows, refrigerant pressures, starter and drive data and heat recovery. The BAS writes setpoints (AV), base loading, heat recovery and reset (BV) and auto/stop and mode (MV).

This page lists 244 BACnet objects for the Trane Symbio 800 RTHD (UC800) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 RTHD (UC800)
Equipment
Water-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
244 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034
Source document
Symbio 800 Integration Points List BACnet - RTHD (UC800) · BAS-PTS034A-EN · rev. 12/6/2024
Download CSV 244 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 RTHD (UC800)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, current limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. The alarm-present flag gives a single summary alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1BAS Chiller Auto Stop CommandBMS auto/stop command (1 = Stop, 2 = Auto)Write
MV 2BAS Chiller Mode CommandCool/heat/ice mode commandWrite
AV 1BAS Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 2BAS Current Limit SetpointCurrent limit from the BMS, % RLAWrite
BI 4Chiller RunningChiller on/off statusRead
BI 2Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 13Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 4Actual Running CapacityActual running capacity in percentRead
BI 12Alarm PresentAny active alarm on the chillerRead

Enable & remote start

MV 1 BAS Chiller Auto Stop Command (1 = Stop, 2 = Auto; relinquish default Auto) is the BMS auto/stop. BI 1 Run Enable shows stop/auto. The document doesn't say how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Heartbeat & communication loss

No timeout or heartbeat is described. MI 3 BAS Communication Status (established/lost/never established/starting) and the diagnostic flags BI 510 BAS Communication Loss, BI 511 and BI 512 report the BAS link; the document doesn't say what the chiller does on loss.

Network setup

Watch out for

Trane Symbio 800 RTHD (UC800) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

244 of 244 shown
Type
Access
Show
Trane Symbio 800 RTHD (UC800) BACnet Points List
DescriptionStates
AI1Active Cool/Heat Setpoint TemperatureRead
AI2Active Current Limit SetpointRead
AI3Active Base Loading SetpointRead
AImin4Actual Running CapacityRead
AI5Evaporator Refrigerant PressureRead
AI6Evaporator Saturated Rfgt TempRead
AI7Condenser Refrigerant PressureRead
AI8Condenser Saturated Rfgt TempRead
AI9Local Atmospheric PressureRead
AI10Compressor StartsRead
AI11Compressor Running TimeRead
AI12Evaporator Entering Water TemperatureRead
AImin13Evaporator Leaving Water TemperatureRead
AI14Condenser Entering Water TemperatureRead
AI15Condenser Leaving Water TemperatureRead
AI16Compressor Oil PressureRead
AI17Discharge TemperatureRead
AI18Head Pressure Control CommandRead
AI19Starter Input Voltage ABRead
AI20Starter Input Voltage BCRead
AI21Starter Input Voltage CARead
AI22Starter Motor Current L1Read
AI23Starter Motor Current L2Read
AI24Starter Motor Current L3Read
AI25Starter Motor Current L1 % RLARead
AI26Starter Motor Current L2 % RLARead
AI27Starter Motor Current L3 % RLARead
AI28Number of CircuitsRead
AI29Number of Compressors— Ckt1Read
AI30Number of Compressors—Ckt2Read
AI31Chiller Design CapacityRead
AI32Frequency CommandRead
AI33AFD Output PowerRead
AI34Approx Evap Water FlowRead
AI35Evap Differential Wtr PressRead
AI36Approx Cond Water FlowRead
AI37Cond Differential Wtr PressRead
AI38EXV Position PercentRead
AI39Heat Recovery Entering Water TemperatureRead
AI40Heat Recovery Leaving Water TemperatureRead
AI41Heat Recovery Tank Water TempRead
AI42Evaporator Approach TemperatureRead
AI43Condenser Approach TemperatureRead
AI44Motor Winding Temperature 1Read
AI45Motor Winding Temperature 2Read
AVmin1BAS Chilled Water SetpointWrite
AVmin2BAS Current Limit SetpointWrite
AV3BAS Hot Water SetpointWrite
AV4BAS Base Loading SetpointWrite
AV5BAS Heat Recovery Water Tank Temperature SetpointWrite
BI1Run EnableRead0 = stop, 1 = auto
BImin2Local Setpoint ControlRead0 = no, 1 = yes
BI3Limit Mode Relay StatusRead0 = inactive, 1 = active
BImin4Chiller RunningRead0 = off, 1 = on
BI5Condenser Water Flow StatusRead0 = no flow, 1 = flow
BI6Head Relief Request RelayRead0 = off, 1 = on
BI7Active Base Loading CommandRead0 = auto, 1 = on
BI8Compressor Running StatusRead0 = off, 1 = running
BI9Evaporator Water Pump CommandRead0 = off, 1 = on
BI10Condenser Water Pump CommandRead0 = off, 1 = on
BI11Evaporator Water Flow StatusRead0 = no flow, 1 = flow
BImin12Alarm PresentRead0 = no, 1 = yes
BI13Shutdown Alarm PresentRead0 = no, 1 = yes
BI15Heat Recovery Water Flow StatusRead0 = no flow, 1 = flow
BI16Heat Recovery Control Active StatusRead0 = inactive, 1 = active
BI501Comm Loss: Ext Base Loading Command ChillerRead
BI502Comm Loss: Ext Base Loading Setpoint ChillerRead
BI503External Base Loading Setpoint ChillerRead
BI504Comm Loss: Evap Entering Water Temp ChillerRead
BI505Comm Loss: Evap Leaving Water Temp ChillerRead
BI506Comm Loss: Outdoor Air Temperature ChillerRead
BI508Outdoor Air Temperature Sensor ChillerRead
BI510BAS Communication LossRead
BI511BAS Failed to Establish CommunicationRead
BI512Comm Loss: Local BAS InterfaceRead
BI516LCI-C Software Mismatch: Use BAS ToolRead
BI517Comm Loss: Oil Loss Level Sensor Input ChillerRead
BI518Comm Loss: Cprsr Discharge Rfgt Temp ChillerRead
BI519Comm Loss: High Pressure Cutout Switch ChillerRead
BI520Comm Loss: Primary Oil Line SVRead
BI521Comm Loss: Oil Pressure ChillerRead
BI522Comm Loss: Oil Return Gas Pump Drain ChillerRead
BI523Comm Loss: Oil Return Gas Pump Fill ChillerRead
BI524Compressor Discharge Temperature Sensor ChillerRead
BI525High Cprsr Rfgt Discharge Temperature ChillerRead
BI526High Differential Refrigerant Pressure ChillerRead
BI527High Pressure Cutout ChillerRead
BI528High Refrigerant Pressure Ratio ChillerRead
BI529Loss of Oil at Compressor (Running) ChillerRead
BI530Loss of Oil at Compressor (Stopped) ChillerRead
BI531Low Differential Refrigerant Pressure ChillerRead
BI532Low Discharge Superheat ChillerRead
BI533Low Oil Flow ChillerRead
BI534No Differential Refrigerant Pressure ChillerRead
BI535Oil Flow Protection Fault ChillerRead
BI536Oil Pressure Transducer ChillerRead
BI537Comm Loss: Slide Valve Load ChillerRead
BI538Comm Loss: Slide Valve Unload ChillerRead
BI539Restart Inhibit ChillerRead
BI540Comm Loss: Condenser Rfgt Pressure ChillerRead
BI541Evaporator Rfgt Pressure Transducer ChillerRead
BI542Comm Loss: Condenser Water Flow SwitchRead
BI543Comm Loss: Condenser Water Pump Relay ChillerRead
BI544Condenser Water Flow Lost ChillerRead
BI545Condenser Water Flow Overdue ChillerRead
BI546Comm Loss: Condenser Entering Water Temp ChillerRead
BI547Comm Loss: Condenser Leaving Water Temp ChillerRead
BI548Condenser Entering Water Temp Sensor ChillerRead
BI549Condenser Leaving Water Temp Sensor ChillerRead
BI550Comm Loss: Evaporator Rfgt Liquid Level ChillerRead
BI551Evaporator Liquid Level Sensor ChillerRead
BI552High Evaporator Liquid Level ChillerRead
BI553Low Evaporator Liquid Level ChillerRead
BI554Low Evaporator Refrigerant Pressure ChillerRead
BI555Low Evaporator Refrigerant Temperature ChillerRead
BI556Low Evaporator Temp: Unit Off ChillerRead
BI557Comm Loss: Evaporator Water Flow Switch ChillerRead
BI558Comm Loss: Evaporator Water Pump Relay ChillerRead
BI559Evaporator Water Flow Lost ChillerRead
BI560Evaporator Water Flow Overdue ChillerRead
BI561High Evaporator Refrigerant Pressure ChillerRead
BI562High Evaporator Water Temperature ChillerRead
BI563Evap Water Flow (Entering Water Temp) ChillerRead
BI564Evaporator Entering Water Temp Sensor ChillerRead
BI565Evaporator Leaving Water Temp Sensor ChillerRead
BI566Low Evaporator Water Temp (Unit On) ChillerRead
BI567Low Evaporator Water Temp (Unit Off) ChillerRead
BI568Comm Loss: Electronic Expansion Valve 1 ChillerRead
BI569Comm Loss: Electronic Expansion Valve 2 ChillerRead
BI570Comm Loss: Evaporator Rfgt Pressure ChillerRead
BI571Evaporator Rfgt Pressure Transducer ChillerRead
BI572Comm Loss: Compressor % RLA Output ChillerRead
BI573Comm Loss: Cond Rfgt Pressure OutputRead
BI574Comm Loss: Cond Head Press Cntrl Output ChillerRead
BI575Comm Loss: Emergency Stop ChillerRead
BI576Comm Loss: Ext Chilled/Hot Water Setpoint ChillerRead
BI577Comm Loss: Ext Current Limit Setpoint ChillerRead
BI578Comm Loss: External Auto/Stop ChillerRead
BI579Comm Loss: External Hot Water Command ChillerRead
BI580Comm Loss: Op Status Programmable Relays ChillerRead
BI581Comm Loss: Refrigerant Monitor Input ChillerRead
BI582Emergency Stop ChillerRead
BI583External Chilled/Hot Water Setpoint ChillerRead
BI584External Current Limit Setpoint ChillerRead
BI585Refrigerant Monitor Input ChillerRead
BI586Comm Loss: External Ice Building Command Ice BuildingRead
BI587Comm Loss: Ice Building Status Relay Ice BuildingRead
BI588Comm Loss: SSS/AFD Fault ChillerRead
BI589Comm Loss: Starter ChillerRead
BI590Solid State Starter Fault ChillerRead
BI591Starter Failed to Arm/Start ChillerRead
BI592Unexpected Starter Shutdown ChillerRead
BI593At Speed Input Opened ChillerRead
BI594At Speed Input Shorted ChillerRead
BI595Compressor Did Not Accel: Transition ChillerRead
BI596Compressor Did Not Accelerate Fully ChillerRead
BI597Compressor Did Not Accelerate: Shutdown ChillerRead
BI598Starter Contactor Interrupt Failure ChillerRead
BI599Momentary Power Loss ChillerRead
BI600Motor Current Overload ChillerRead
BI601Over Voltage ChillerRead
BI602Phase Loss ChillerRead
BI603Phase Reversal ChillerRead
BI604Power Loss ChillerRead
BI605Severe Current Unbalance ChillerRead
BI606Starter Comm Loss: Main Processor ChillerRead
BI607Starter Did Not TransitionRead
BI608Starter Dry Run Test ChillerRead
BI609Starter Fault Type I ChillerRead
BI610Starter Fault Type II ChillerRead
BI611Starter Fault Type III ChillerRead
BI612Starter Module Memory Error Type 1 ChillerRead
BI613Starter Module Memory Error Type 2 ChillerRead
BI614Transition Complete Input OpenedRead
BI615Transition Complete Input ShortedRead
BI616Under Voltage ChillerRead
BI617Check ClockRead
BI619MP: Invalid Configuration PlatformRead
BI622MP: Reset Has Occurred PlatformRead
BI623AFD Drive Fault ChillerRead
BI624AFD Output Power Input ChillerRead
BI625Comm Loss: AFD Speed Signal Output ChillerRead
BI626Comm Loss: AFD Output Power Input ChillerRead
BI627Software Error 1001: Call Trane Service ChillerRead
BI628Low Evaporator Water FlowRead
BI629Comm Loss: Evap Diff Water PressureRead
BI630Comm Loss: Cond Diff Water PressureRead
BI631Evaporator Diff Water Pressure XdcrRead
BI632Condenser Diff Water Pressure Xdcr(a)Read
BI633Comm Loss: Adaptive Frequency DriveRead
BI634Comm Loss: External Heat Recovery SetpointRead
BI635Comm Loss: External Heat Recovery CommandRead
BI636Comm Loss: HR Entering Water Temp SensorRead
BI637Comm Loss: HR Leaving Water Temp SensorRead
BI638Comm Loss: Heat Recovery Tank Water TempRead
BI639Comm Loss: Heat Recovery Water Flow SwitchRead
BI640Comm Loss: Heat Recovery Water Pump RelayRead
BI641Ext Heat Recovery Temp Setpoint SensorRead
BI642Heat Recovery Entering Water Temperature SensorRead
BI643Heat Recovery Leaving Water Temperature SensorRead
BI644Heat Recovery Tank Water Temp SensorRead
BI645Heat Recovery Water Flow LostRead
BI646Heat Recovery Water Flow OverdueRead
BI647Unexpected Heat Recovery Water FlowRead
BI648Unexpected Condenser Water FlowRead
BI649Comm Loss: Economizer ValveRead
BI650Comm Loss: Economizer TemperatureRead
BI651Economizer Temperature SensorRead
BI652Comm Loss: Economizer PressureRead
BI653Economizer Pressure SensorRead
BI654Comm Loss: Economizer Bypass ValveRead
BI655AFD Bus Over VoltageRead
BI656AFD Bus Under VoltageRead
BI657AFD Comm Loss: Main ProcessorRead
BI658AFD Emergency Stop FaultRead
BI659AFD General FailureRead
BI660AFD Ground FaultRead
BI661AFD Instantaneous Current OverloadRead
BI662AFD Inverter Heatsink Over TempRead
BI663AFD Motor Current OverloadRead
BI664AFD Output Phase LossRead
BI665AFD Rated Current Out of RangeRead
BI666High Pressure CutoutRead
BI667AFD Interrupt FailureRead
BI668High Motor Winding TemperatureRead
BI669Motor Winding Temp Sensor - Cprsr1ARead
BI670Excessive Condenser PressureRead
BI671Comm Loss: Motor Winding Temperature 1Read
BI672Comm Loss: Motor Winding Temperature 2Read
BI673Comm Loss: Oil Return Purge ValveRead
BI674Comm Loss: Hot Gas Bypass ValveRead
BI675Comm Loss: Liquid Line Bypass ValveRead
BV1BAS Base Loading EnableWrite0 = auto, 1 = on
BV2BAS Diagnostic ResetWrite0 = false (no reset), 1 = true (can reset)
BV3BAS Heat Recovery CommandWrite0 = auto, 1 = on
MI1Chiller Running StatusRead1 = not running, 2 = starting, 3 = running, 4 = stopping, 5 = Chiller in service mode
MI2Chiller Mode CommandRead1 = cool, 2 = heat, 3 = ice, 4 = not used
MI3BAS Communication StatusRead1 = established, 2 = lost, 3 = never established, 4 = starting
MI4Refrigerant TypeRead5 = R-134A
MI7Manufacturing LocationRead3 = Pueblo, CO, USA, 4 = Charmes,France, 15 = Taicang, China
MI34Model InformationRead6 = RTH
MI35Cooling TypeRead1 = water cooled
MVmin1BAS Chiller Auto Stop CommandWrite1 = Stop, 2 = Auto
MVmin2BAS Chiller Mode CommandWrite1 = cool, 2 = heat, 3 = ice

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 RTHD (UC800) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 RTHD (UC800)

How many BACnet points does the Trane Symbio 800 RTHD (UC800) have?

This list has 244 BACnet objects: 45 analog inputs, 5 analog values, 182 binary inputs, 3 binary values, 7 multi-state inputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 RTHD (UC800) BACnet points are writable?

10 of the 244 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 RTHD (UC800) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - RTHD (UC800) (BAS-PTS034A-EN), revision 12/6/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS034A-EN_12062024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 RTHD (UC800)?

Start with MV 1 BAS Chiller Auto Stop Command (BMS auto/stop command (1 = Stop, 2 = Auto)); MV 2 BAS Chiller Mode Command (Cool/heat/ice mode command); AV 1 BAS Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 2 BAS Current Limit Setpoint (Current limit from the BMS, % RLA); BI 4 Chiller Running (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 13 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 4 Actual Running Capacity (Actual running capacity in percent); BI 12 Alarm Present (Any active alarm on the chiller).

How do I enable BMS control of the Trane Symbio 800 RTHD (UC800)?

MV 1 BAS Chiller Auto Stop Command (1 = Stop, 2 = Auto; relinquish default Auto) is the BMS auto/stop. BI 1 Run Enable shows stop/auto. The document doesn't say how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Does the Trane Symbio 800 RTHD (UC800) need a BACnet heartbeat or have a communication timeout?

No timeout or heartbeat is described. MI 3 BAS Communication Status (established/lost/never established/starting) and the diagnostic flags BI 510 BAS Communication Loss, BI 511 and BI 512 report the BAS link; the document doesn't say what the chiller does on loss.

How do I check these points on the real Symbio 800 RTHD (UC800)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - RTHD (UC800) · BAS-PTS034A-EN · rev. 12/6/2024. Object names, instances and units are reproduced as published; descriptions are our own.