Centrifugal chiller controller · BACnet points list

Trane Symbio 800 CenTraVac (Simplex) BACnet points list

Updated 28 October 2026

Short answer

Simplex CenTraVac chillers controlled by a Symbio 800 publish their operating data as AI/BI/MI objects, plus a short list of AV/BV/MV objects for setpoints and commands (chilled water setpoint, demand limit, auto/stop, mode). Most of the list is diagnostic binary inputs, one per alarm condition. Many points depend on options such as base loading, heat recovery or a unit-mounted drive.

This page lists 546 BACnet objects for the Trane Symbio 800 CenTraVac (Simplex) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 CenTraVac (Simplex)
Equipment
Centrifugal chiller controller
Equipment type
Chillers
BACnet objects
546 (15 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009
Source document
Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025
Download CSV 546 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 CenTraVac (Simplex)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10104Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10113Chiller Running StateChiller on/off statusRead
BI 10105Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10107Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10158Actual Running CapacityActual running capacity in percentRead
BI 10118Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10128 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10104 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10105 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

Network setup

Watch out for

Trane Symbio 800 CenTraVac (Simplex) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

546 of 546 shown
Type
Access
Show
Trane Symbio 800 CenTraVac (Simplex) BACnet Points List
DescriptionStates
AI10100Active Chilled Water SetpointTemperatureRead
AI10101Chilled Water Setpoint StatusTemperatureRead
AI10102Active Base Loading SetpointPercentRead
AI10103Active Hot Water SetpointTemperatureRead
AI10104Calculated Chiller CapacityPower, CoolingRead
AI10105Total Demand DistortionPercentRead
AI10106Active Cool/Heat Setpoint TemperatureTemperatureRead
AImin10107Evaporator Leaving Water TemperatureTemperatureRead
AI10108Evaporator Entering Water TemperatureTemperatureRead
AI10109Condenser Entering Water TemperatureTemperatureRead
AI10110Condenser Leaving Water TemperatureTemperatureRead
AI10111Evaporator Water Flow RateFlow, waterRead
AI10112Evaporator Differential Water PressureDifferential PressureRead
AI10113Condenser Water Flow RateFlow, waterRead
AI10114Condenser Differential Water PressureDifferential PressureRead
AI10115Heat Recovery Entering Water TemperatureTemperatureRead
AI10116Heat Recovery Leaving Water TemperatureTemperatureRead
AI10117AFD Last Diagnostic Code Ckt1Read
AI10118Unit Source ID (Last Diagnostic Code)Read
AI10119Drive Input Voltage CalculatedVoltageRead
AI10120Number of CircuitsRead
AI10121Number of Compressors Circuit 1Read
AI10122Number of Compressors Circuit 2Read
AI10123Refrigerant MonitorConcentrationRead
AI10124Evaporator Refrigerant Pressure Circuit 1PressureRead
AI10125Condenser Refrigerant Pressure Circuit 1PressureRead
AI10126Differential Refrigerant Pressure Circuit 1Differential PressureRead
AI10127Low Side Oil Pressure - Compressor 1APressureRead
AI10128High Side Oil Pressure - Compressor 1APressureRead
AI10129Oil Differential Pressure Circuit 1Differential PressureRead
AI10130Oil Temperature - Compressor 1ATemperatureRead
AI10131Evaporator Saturated Refrigerant Temperature Circuit 1TemperatureRead
AI10132Condenser Saturated Refrigerant Temperature Circuit 1TemperatureRead
AI10133Refrigerant Discharge Temperature - Compressor 1ATemperatureRead
AI10134Inlet Guide Vane 1 Percent Open Circuit 1PercentRead
AI10135Inlet Guide Vane 2 Percent Open Circuit 1PercentRead
AI10136Purge Carbon Tank Temperature Circuit 1TemperatureRead
AI10137Purge Liquid Temperature Circuit 1TemperatureRead
AI10138Purge Refrigerant Compressor Suction Temperature Circuit 1TemperatureRead
AI10139Time Until Next Purge Run Circuit 1 (in seconds)Read
AI10140Purge Pumpout Chiller On % (7 Days) Circuit 1PercentRead
AI10141Purge Pumpout Chiller Off % (7 Days) Circuit 1PercentRead
AI10142Purge 24 Hour Pumpout Circuit 1 (in seconds)Read
AI10143Purge Pumpout - Life Circuit 1 (in seconds)Read
AI10144Refrigeration - Life Circuit 1 (in seconds)Read
AI10145Starts - Compressor 1ARead
AI10146Run Time - Compressor 1A (in seconds)Read
AI10147Phase AB Voltage - Compressor 1AVoltageRead
AI10148Phase BC Voltage - Compressor 1AVoltageRead
AI10149Phase CA Voltage - Compressor 1AVoltageRead
AI10150Starter Average Phase Volt Circuit 1VoltageRead
AI10151Line 1 Current - Compressor 1ACurrentRead
AI10152Line 2 Current - Compressor 1ACurrentRead
AI10153Line 3 Current - Compressor 1ACurrentRead
AI10154Average Line Current Circuit 1CurrentRead
AI10155Line 1 Current RLA - Compressor 1APercentRead
AI10156Line 2 Current RLA - Compressor 1APercentRead
AI10157Line 3 Current RLA - Compressor 1APercentRead
AImin10158Actual Running CapacityPercentRead
AI10159Unit Power ConsumptionPower, ElectricalRead
AI10160Starter Load Power Factor - Compressor 1ARead
AI10161Inboard Bearing Temperature Circuit 1TemperatureRead
AI10162Outboard Bearing Temperature Circuit 1TemperatureRead
AI10163Motor Winding Temperature 1 Circuit 1TemperatureRead
AI10164Motor Winding Temperature 2 Circuit 1TemperatureRead
AI10165Motor Winding Temperature 3 Circuit 1TemperatureRead
AI10166AFD Frequency Circuit 1Read
AI10167AFD Transistor Temperature Circuit 1TemperatureRead
AI10168Drive Average Line Current Circuit 1CurrentRead
AI10169Drive Current Line 1 Circuit 1CurrentRead
AI10170Drive Current Line 2 Circuit 1CurrentRead
AI10171Drive Current Line 3 Circuit 1CurrentRead
AI10172Drive Line Frequency Circuit 1Read
AI10173Drive Frequency StatusRead
AI10174Drive Inverter Base Temperature Circuit 1TemperatureRead
AI10175Drive Rectifier Base Temperature Circuit 1TemperatureRead
AI10176Drive Output Power Circuit 1CurrentRead
AI10177Drive Motor Current U RLA Circuit 1PercentRead
AI10178Drive Motor Current V RLA Circuit 1PercentRead
AI10179Drive Motor Current W RLA Circuit 1PercentRead
AI10180Drive Motor Current U Circuit 1CurrentRead
AI10181Drive Motor Current V Circuit 1CurrentRead
AI10182Drive Motor Current W Circuit 1CurrentRead
AI10183Drive Motor Voltage UV Circuit 1VoltageRead
AI10184Drive Motor Voltage VW Circuit 1VoltageRead
AI10185Drive Motor Voltage WU Circuit 1VoltageRead
AI10186Drive Motor Average Voltage Circuit 1VoltageRead
AI10187Drive Motor Average Current RLA Circuit 1PercentRead
AI10188Lube Differential PressureDifferential PressureRead
AI10189Lube Pump Suction PressurePressureRead
AI10190Lube Pump Discharge PressurePressureRead
AI10191Motor Coolant TemperatureTemperatureRead
AI10192AFD % RLA RipplePercentRead
AI10193AFD Inverter Module Temperature UTemperatureRead
AI10194AFD Inverter Module Temperature VTemperatureRead
AI10195AFD Inverter Module Temperature WTemperatureRead
AI10196Outboard Bearing Pad Temperature #1 Ckt1TemperatureRead
AI10197Outboard Bearing Pad Temperature #2 Ckt1TemperatureRead
AI10198Outboard Bearing Pad Temperature #3 Ckt1TemperatureRead
AI10199Condenser Control OutputPercentRead
AI10200Restart Inhibit Time RemainingRead
AI10201Chiller Design CapacityPower, CoolingRead
AI10202Entering Condenser Water PressurePressureRead
AI10203Entering Evaporator Water PressurePressureRead
AI10204Leaving Condenser Water PressurePressureRead
AI10205Leaving Evaporator Water PressurePressureRead
AI10206Condenser Approach Temperature Circuit 1Temperature, DeltaRead
AI10207Evaporator Approach Temperature Circuit 1Temperature, DeltaRead
AI10208Drive DC Bus Voltage Circuit 1VoltageRead
AI10209Active Demand Limit SetpointPercentRead
AI10210Demand Limit Setpoint StatusPercentRead
AI10211Drive Heatsink Temperature Compressor 1ATemperatureRead
AI10212Heat Recovery Differential Water PressureDifferential PressureRead
AI10213Heat Recovery Water Flow RateFlow, waterRead
AI10214Heat Recovery Calculated CapacityPower, HeatingRead
AI10215Heat Recovery Entering Water PressurePressureRead
AI10216Heat Recovery Leaving Water PressurePressureRead
AI10217Voltage L1-L2VoltageRead
AI10218Voltage L2-L3VoltageRead
AI10219Voltage L1-L3VoltageRead
AI10220Chiller Average Line VoltageVoltageRead
AI10221Current L1CurrentRead
AI10222Current L2CurrentRead
AI10223Current L3CurrentRead
AI10224Unit Average Line CurrentCurrentRead
AI10225Line FrequencyRead
AI10226Power FactorRead
AI10227Unit Power DemandRead
AI10228Energy ConsumptionEnergy, ElectricalRead
AI10229Energy Consumption LifetimeEnergy, ElectricalRead
AI10230Outdoor Air Temperature LocalTemperatureRead
AI10231Heat Recovery Approach Temperature Circuit 1Temperature, DeltaRead
AI10232High Side Oil Gauge Pressure - Compressor 1APressureRead
AI10233Low Side Oil Gauge Pressure - Compressor 1APressureRead
AI10234Condenser Refrigerant Gauge Pressure Circuit 1PressureRead
AI10235Entering Condenser Water Gauge PressurePressureRead
AI10236Entering Evaporator Water Gauge PressurePressureRead
AI10237Evaporator Refrigerant Gauge Pressure Circuit 1PressureRead
AI10238Heat Recovery Entering Water Gauge PressurePressureRead
AI10239Heat Recovery Leaving Water Gauge PressurePressureRead
AI10240Leaving Condenser Water Gauge PressurePressureRead
AI10241Leaving Evaporator Water Gauge PressurePressureRead
AI10242Lube Pump Suction Gauge PressurePressureRead
AI10243Lube Pump Discharge Gauge PressurePressureRead
AI10244Active Cooling Differential to StartTemperature, DeltaRead
AI10245Active Cooling Differential to StopTemperature, DeltaRead
AI10246Active Heating Differential to StartTemperature, DeltaRead
AI10247Active Heating Differential to StopTemperature, DeltaRead
AI10248Calculated Heating CapacityPower, HeatingRead
AI10249Discharge Superheat Compressor 1ATemperature, DeltaRead
AVmin10100Chilled Water SetpointTemperatureWrite
AVmin10101Demand Limit SetpointPercentWrite
AV10102Hot Water SetpointTemperatureWrite
AV10103Base Loading SetpointPercentWrite
AV10104BAS Cooling Differential to StartTemperature, DeltaWrite
AV10105BAS Cooling Differential to StopTemperature, DeltaWrite
AV10106BAS Heating Differential to StartTemperature, DeltaWrite
AV10107BAS Heating Differential to StopTemperature, DeltaWrite
BI10100Base Loading Request ActiveRead0 = Off, 1 = On
BI10101Emergency StopRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10102Manual Override ExistsRead0 = Off, 1 = On
BI10103Base Loading ActiveRead0 = Inactive, 1 = Active
BI10104Run EnabledRead0 = Run Not Enabled, 1 = Run Enabled
BImin10105Local Setpoint ControlRead0 = Remote Control, 1 = Local Control
BI10106Maximum CapacityRead0 = Off, 1 = On
BI10107Evaporator Leaving Water TemperatureRead0 = Not Limited, 1 = Limited
BI10108Head Relief RequestRead0 = Off, 1 = On
BI10109Hot Gas Bypass ActiveRead0 = Inactive, 1 = Active
BI10110Purge Compressor Relay Circuit 1Read0 = Off, 1 = On
BI10111Pump Out Relay Circuit 1Read0 = Off, 1 = On
BI10112Purge Regenerating Valve Solenoid Circuit 1Read0 = Off, 1 = On
BImin10113Chiller Running StateRead0 = Off, 1 = On
BI10114Evaporator Water Pump RequestRead0 = Off, 1 = On
BI10115Evaporator Water Flow StatusRead0 = No Flow, 1 = Flow
BI10116Condenser Water Pump RequestRead0 = Off, 1 = On
BI10117Condenser Water Flow StatusRead0 = No Flow, 1 = Flow
BImin10118Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10119Diagnostic Shutdown PresentRead0 = Normal, 1 = In Alarm
BI10120Diagnostic: Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10121Diagnostic: Local Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10122Diagnostic Present: InformationRead0 = Normal, 1 = In Alarm
BI10123Diagnostic Present: AdvisoryRead0 = Normal, 1 = In Alarm
BI10124Diagnostic Present: CriticalRead0 = Normal, 1 = In Alarm
BI10125Diagnostic Present: Service RequiredRead0 = Normal, 1 = In Alarm
BI10126Compressor 1A StatusRead0 = Off, 1 = Running
BI10127Front Panel Auto StopRead0 = Stop, 1 = Auto
BI10128External Auto Stop Input StatusRead0 = Stop, 1 = Auto
BI10129Heat Recovery Water Flow StatusRead0 = No Flow, 1 = Flow
BI10130AFD Shutdown Diagnostic Present Circuit 1Read0 = Normal, 1 = In Alarm
BI11000Diagnostic: AFD AD Calibration Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11001Diagnostic: AFD AHD Frequency Out of Range Circuit 1Read0 = Normal, 1 = In Alarm
BI11002Diagnostic: AFD AHD Sync Signal Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11003Diagnostic: AFD Bump Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11004Diagnostic: AFD Bus Over Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11005Diagnostic: AFD Bus Ripple Too High Circuit 1Read0 = Normal, 1 = In Alarm
BI11006Diagnostic: AFD Bus Under Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11007Evaporator Leaving Water TemperatureRead0 = Normal, 1 = In Alarm
BI11008Diagnostic: AFD Comm Loss: Main Processor Circuit 1Read0 = Normal, 1 = In Alarm
BI11009Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11010Diagnostic: AFD Current Sensor Self Test Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11011Diagnostic: AFD Desaturation Detected Circuit 1Read0 = Normal, 1 = In Alarm
BI11012Diagnostic: AFD DPI Communication Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11013Diagnostic: AFD Drive Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11014Diagnostic: AFD DSP Board ID Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11015Diagnostic: AFD DSP Board Initialization Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11016Diagnostic: AFD DSP Board Low Voltage Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11017Diagnostic: AFD DSP Board Over Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11018Diagnostic: AFD Emergency Stop Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11019Diagnostic: AFD Estimated Junction Over Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11020Diagnostic: AFD Excessive AHD Inhibit Circuit 1Read0 = Normal, 1 = In Alarm
BI11021Diagnostic: AFD External Fault Input Circuit 1Read0 = Normal, 1 = In Alarm
BI11022Diagnostic: AFD Fatal Software Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11023Diagnostic: AFD Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11024Diagnostic: AFD Gate Drive Board Over Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11025Diagnostic: AFD Gate Drive Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11026Diagnostic: AFD Gate Drive Low Voltage Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11027Diagnostic: AFD Gate Drive Module Comm Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11028Diagnostic: AFD Gate Kill Active Circuit 1Read0 = Normal, 1 = In Alarm
BI11029Diagnostic: AFD General Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11030Diagnostic: AFD General Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11031Diagnostic: AFD Ground Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11032Diagnostic: AFD Ground Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11033Diagnostic: AFD High Bus Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11034Diagnostic: AFD High Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11035Diagnostic: AFD I/O Board Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11036Diagnostic: AFD IGBT Self Test Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11037Diagnostic: AFD IMC 24V Detection Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11038Diagnostic: AFD Input Transformer or Filter High Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11039Diagnostic: AFD Instantaneous Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11040Diagnostic: AFD Interrupt Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11041Diagnostic: AFD Invalid Drive Command Circuit 1Read0 = Normal, 1 = In Alarm
BI11042Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11043Diagnostic: AFD Loss of AHD Sync Signal Circuit 1Read0 = Normal, 1 = In Alarm
BI11044Diagnostic: AFD Low Rotor Flux Feedback Circuit 1Read0 = Normal, 1 = In Alarm
BI11045Diagnostic: AFD Mains Phase Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11046Diagnostic: AFD Motor Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11047Diagnostic: AFD Motor Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11048Diagnostic: AFD Motor Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11049Diagnostic: AFD Motor Short Circuit 1Read0 = Normal, 1 = In Alarm
BI11050Diagnostic: AFD Non-Volatile Memory Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11051Diagnostic: AFD Output Phase Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11052Diagnostic: AFD Over Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11053Diagnostic: AFD Overspeed Circuit 1Read0 = Normal, 1 = In Alarm
BI11054Diagnostic: AFD Panel Interlock Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11055Diagnostic: AFD Panel Interlock Warning Circuit 1Read0 = Normal, 1 = In Alarm
BI11056Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11057Diagnostic: AFD Power Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11058Diagnostic: AFD Power Structure Board Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11059Diagnostic: AFD Precharge Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11060Diagnostic: AFD Rectifier Heatsink Over Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11061Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11062Diagnostic: AFD Safe Stop Circuit 1Read0 = Normal, 1 = In Alarm
BI11063Diagnostic: AFD Short Circuit Circuit 1Read0 = Normal, 1 = In Alarm
BI11064Diagnostic: AFD Speed Configuration Mismatch Circuit 1Read0 = Normal, 1 = In Alarm
BI11065Diagnostic: AFD Start Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11066Diagnostic: AFD Temperature Sensor Warning Circuit 1Read0 = Normal, 1 = In Alarm
BI11067Diagnostic: AFD Watchdog Timer Overflow Circuit 1Read0 = Normal, 1 = In Alarm
BI11068Diagnostic: At Speed Input Opened Circuit 1Read0 = Normal, 1 = In Alarm
BI11069Diagnostic: At Speed Input Shorted Circuit 1Read0 = Normal, 1 = In Alarm
BI11070Diagnostic: Bearing Lube Flow First Stage Sensor InputRead0 = Normal, 1 = In Alarm
BI11071Diagnostic: Bearing Lube Flow Second Stage Sensor InputRead0 = Normal, 1 = In Alarm
BI11072Diagnostic: Brg Lube Flow Overdue First Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11073Diagnostic: Brg Lube Flow Overdue Second Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11075Diagnostic: Check Lube Filter Circuit 1Read0 = Normal, 1 = In Alarm
BI11076Diagnostic: Check Oil Filter Circuit 1Read0 = Normal, 1 = In Alarm
BI11077Diagnostic: Check Oil Heater Circuit 1Read0 = Normal, 1 = In Alarm
BI11078Comm Loss: Adaptive Frequency Drive Circuit 1Read0 = Normal, 1 = In Alarm
BI11079Comm Loss: AFD Speed Signal VDC Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11080Comm Loss: Bearing Lube Flow First StageRead0 = Normal, 1 = In Alarm
BI11081Comm Loss: Bearing Lube Flow Second StageRead0 = Normal, 1 = In Alarm
BI11082Comm Loss: Compressor Motor % RLA Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11083Comm Loss: Cond Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11084Comm Loss: Cond Head Press Cntrl OutputRead0 = Normal, 1 = In Alarm
BI11085Comm Loss: Cond High Pressure CutoutRead0 = Normal, 1 = In Alarm
BI11086Comm Loss: Cond Lubrication Source ValveRead0 = Normal, 1 = In Alarm
BI11087Comm Loss: Cond Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11088Comm Loss: Cond Rfgt Pressure OutputRead0 = Normal, 1 = In Alarm
BI11089Comm Loss: Cond Saturated Rfgt TempRead0 = Normal, 1 = In Alarm
BI11090Comm Loss: Condenser Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11091Comm Loss: Condenser Entering Water TempRead0 = Normal, 1 = In Alarm
BI11092Comm Loss: Condenser Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11093Comm Loss: Condenser Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11094Comm Loss: Condenser Liquid Level SensorRead0 = Normal, 1 = In Alarm
BI11096Comm Loss: Condenser Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11097Comm Loss: Condenser Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11098Comm Loss: Cprsr Discharge Rfgt TempRead0 = Normal, 1 = In Alarm
BI11099Comm Loss: Economizer Bypass ValveRead0 = Normal, 1 = In Alarm
BI11102Comm Loss: Emergency StopRead0 = Normal, 1 = In Alarm
BI11103Comm Loss: Energy Meter Circuit 1Read0 = Normal, 1 = In Alarm
BI11104Comm Loss: Evap Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11105Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11106Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11107Comm Loss: Evap Lube Source Valve RelayRead0 = Normal, 1 = In Alarm
BI11108Comm Loss: Evap Saturated Rfgt TempRead0 = Normal, 1 = In Alarm
BI11109Comm Loss: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11110Comm Loss: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11111Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11112Comm Loss: Evaporator Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11113Comm Loss: Ext Base Loading CommandRead0 = Normal, 1 = In Alarm
BI11114Comm Loss: Ext Base Loading SetpointRead0 = Normal, 1 = In Alarm
BI11115Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11116Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11117Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11118Comm Loss: External Free Cooling CommandRead0 = Normal, 1 = In Alarm
BI11119Comm Loss: External Hot Water CommandRead0 = Normal, 1 = In Alarm
BI11120Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11121Comm Loss: Free Cool Actrs Closed InputRead0 = Normal, 1 = In Alarm
BI11122Comm Loss: Free Cool Gas Line Actr RelayRead0 = Normal, 1 = In Alarm
BI11123Comm Loss: Free Cool Liq Line Actr RelayRead0 = Normal, 1 = In Alarm
BI11124Comm Loss: Free Cooling Auxiliary RelayRead0 = Normal, 1 = In Alarm
BI11125Comm Loss: Generator Fault InputRead0 = Normal, 1 = In Alarm
BI11126Comm Loss: Generator Speed Signal OutputRead0 = Normal, 1 = In Alarm
BI11127Comm Loss: Generator Start/Stop RelayRead0 = Normal, 1 = In Alarm
BI11128Comm Loss: Generator Up To Speed InputRead0 = Normal, 1 = In Alarm
BI11129Comm Loss: Heat Recovery Differential Water PressureRead0 = Normal, 1 = In Alarm
BI11130Comm Loss: Heat Recovery Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11131Comm Loss: Heat Recovery Entering Water TempRead0 = Normal, 1 = In Alarm
BI11132Comm Loss: Heat Recovery Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11133Comm Loss: Heat Recovery Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11134Comm Loss: Heat Recovery Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11135Comm Loss: High Lift Unload Valve RelayRead0 = Normal, 1 = In Alarm
BI11136Comm Loss: Hot Gas Bypass Actr Closed InRead0 = Normal, 1 = In Alarm
BI11137Comm Loss: Hot Gas Bypass Load RelayRead0 = Normal, 1 = In Alarm
BI11138Comm Loss: Hot Gas Bypass Unload RelayRead0 = Normal, 1 = In Alarm
BI11139Comm Loss: Ice Building RelayRead0 = Normal, 1 = In Alarm
BI11140Comm Loss: IGV First Stage Actuator Circuit 1Read0 = Normal, 1 = In Alarm
BI11141Comm Loss: IGV Second Stage Actuator Circuit 1Read0 = Normal, 1 = In Alarm
BI11142Comm Loss: Inboard Bearing Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11143Comm Loss: Lube Pump Discharge PressureRead0 = Normal, 1 = In Alarm
BI11144Comm Loss: Lube Pump Suction PressureRead0 = Normal, 1 = In Alarm
BI11145Comm Loss: Lube/Refrigerant Pump RelayRead0 = Normal, 1 = In Alarm
BI11146Comm Loss: Motor Coolant TemperatureRead0 = Normal, 1 = In Alarm
BI11147Comm Loss: Motor Temp/OverloadRead0 = Normal, 1 = In Alarm
BI11148Comm Loss: Motor Temperature CutoutRead0 = Normal, 1 = In Alarm
BI11149Comm Loss: Motor Winding Temperature 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11150Comm Loss: Motor Winding Temperature 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11151Comm Loss: Motor Winding Temperature 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11152Comm Loss: Oil Cooler Solenoid Circuit 1Read0 = Normal, 1 = In Alarm
BI11153Comm Loss: Oil Diff Pressure Switch Circuit 1Read0 = Normal, 1 = In Alarm
BI11154Comm Loss: Oil Pressure Status Circuit 1Read0 = Normal, 1 = In Alarm
BI11155Comm Loss: Oil Pump Discharge Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11156Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11157Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11158Comm Loss: Oil Tank Heater Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11159Comm Loss: Oil Tank Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11160Comm Loss: Oil Tank Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11161Comm Loss: Oil Vent Line Circuit 1Read0 = Normal, 1 = In Alarm
BI11162Comm Loss: Oil/Refrigerant Pump Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11163Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11164Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11165Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11166Comm Loss: Outboard Bearing Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11167Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11168Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11169Comm Loss: Programmable Relay Board 2Read0 = Normal, 1 = In Alarm
BI11170Comm Loss: Purge Alarm Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11171Comm Loss: Purge Carbon Tank Heater Rly Circuit 1Read0 = Normal, 1 = In Alarm
BI11172Comm Loss: Purge Carbon Tank Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11173Comm Loss: Purge Condensing Unit Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11174Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11175Comm Loss: Purge Exhaust Solenoid Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11176Comm Loss: Purge Liquid Level Switch Circuit 1Read0 = Normal, 1 = In Alarm
BI11177Comm Loss: Purge Pumpout Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11178Comm Loss: Purge Pumpout Solenoid Output Circuit 1Read0 = Normal, 1 = In Alarm
BI11179Comm Loss: Purge Regen Solenoid Relay Circuit 1Read0 = Normal, 1 = In Alarm
BI11180Comm Loss: Refrigerant Monitor InputRead0 = Normal, 1 = In Alarm
BI11181Comm Loss: Starter Circuit 1Read0 = Normal, 1 = In Alarm
BI11182Comm Loss: Starter Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11183Comm Loss: Vibration Sensor InputRead0 = Normal, 1 = In Alarm
BI11184Diagnostic: Compressor Did Not Accelerate: Shutdown Compressor 1ARead0 = Normal, 1 = In Alarm
BI11185Diagnostic: Cond Saturated Refrigerant Temp SensorRead0 = Normal, 1 = In Alarm
BI11186Diagnostic: Condenser Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11187Diagnostic: Condenser Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11188Diagnostic: Condenser Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11189Diagnostic: Condenser High Pressure CutoutRead0 = Normal, 1 = In Alarm
BI11190Diagnostic: Condenser Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11191Diagnostic: Condenser Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11192Diagnostic: Condenser Liquid Level SensorRead0 = Normal, 1 = In Alarm
BI11193Diagnostic: Condenser Refrigerant Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11195Diagnostic: Condenser Water Flow LostRead0 = Normal, 1 = In Alarm
BI11196Diagnostic: Condenser Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11197Diagnostic: Cprsr Did Not Accelerate: TransitionRead0 = Normal, 1 = In Alarm
BI11198Diagnostic: Cprsr Discharge Refrigerant Temp SensorRead0 = Normal, 1 = In Alarm
BI11199Diagnostic: Differential Lube Pressure Overdue Circuit 1Read0 = Normal, 1 = In Alarm
BI11200Diagnostic: Differential Oil Pressure Overdue Circuit 1Read0 = Normal, 1 = In Alarm
BI11202Diagnostic: Emergency StopRead0 = Normal, 1 = In Alarm
BI11203Diagnostic: Evap Rfgt Temp Deviate From SelectionRead0 = Normal, 1 = In Alarm
BI11204Diagnostic: Evap Saturated Refrigerant Temp SensorRead0 = Normal, 1 = In Alarm
BI11205Diagnostic: Evaporator Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11206Diagnostic: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11207Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11208Diagnostic: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11209Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11210Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11211Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11212Diagnostic: Excessive Loss of CommunicationRead0 = Normal, 1 = In Alarm
BI11213Diagnostic: Extended Compressor Surge Compressor 1ARead0 = Normal, 1 = In Alarm
BI11214Diagnostic: External Base Loading SetpointRead0 = Normal, 1 = In Alarm
BI11215Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11216Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11217Diagnostic: Free Cooling Actrs Not Open During FCRead0 = Normal, 1 = In Alarm
BI11218Diagnostic: Free Cooling Actuators Not ClosedRead0 = Normal, 1 = In Alarm
BI11219Diagnostic: Free Cooling Actuators Not OpenRead0 = Normal, 1 = In Alarm
BI11220Diagnostic: Free Cooling Actuators Unexpectedly OpenRead0 = Normal, 1 = In Alarm
BI11221Diagnostic: Generator Fault Relay OpenRead0 = Normal, 1 = In Alarm
BI11222Diagnostic: Generator Ready Signal OverdueRead0 = Normal, 1 = In Alarm
BI11223Diagnostic: Heat Recovery Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11224Diagnostic: Heat Recovery Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11225Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11226Diagnostic: Heat Recovery Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11227Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11228Diagnostic: High Condenser PressureRead0 = Normal, 1 = In Alarm
BI11229Diagnostic: High Cprsr Rfgt Discharge TemperatureRead0 = Normal, 1 = In Alarm
BI11230Diagnostic: High Differential Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11231Diagnostic: High Evaporator Refrigerant TemperatureRead0 = Normal, 1 = In Alarm
BI11232Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11233Diagnostic: High Inboard Bearing Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11234Diagnostic: High Motor Coolant Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11235Diagnostic: High Motor Winding Temperature 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11236Diagnostic: High Motor Winding Temperature 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11237Diagnostic: High Motor Winding Temperature 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11238Diagnostic: High Oil Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11239Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11240Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11241Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11242Diagnostic: High Outboard Bearing Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11243Diagnostic: High Vacuum Lockout Circuit 1Read0 = Normal, 1 = In Alarm
BI11244Diagnostic: Hot Gas Bypass Valve Closure OverdueRead0 = Normal, 1 = In Alarm
BI11245Diagnostic: Hot Gas Bypass Valve Opening OverdueRead0 = Normal, 1 = In Alarm
BI11246Diagnostic: Hot Gas Bypass Valve Unexpectedly OpenRead0 = Normal, 1 = In Alarm
BI11247Diagnostic: HPC/High AFD Heat Sink Water PressureRead0 = Normal, 1 = In Alarm
BI11248Diagnostic: Inboard Bearing Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11249Diagnostic: Inverted Condenser Approach TemperatureRead0 = Normal, 1 = In Alarm
BI11250Diagnostic: Inverted Condenser Water TemperatureRead0 = Normal, 1 = In Alarm
BI11251Diagnostic: Inverted Evaporator Approach TemperatureRead0 = Normal, 1 = In Alarm
BI11252Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11253Diagnostic: Loss of Economizer Bypass Valve ControlRead0 = Normal, 1 = In Alarm
BI11254Diagnostic: Low Bearing Lube Flow First Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11255Diagnostic: Low Bearing Lube Flow Second Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11256Diagnostic: Low Brg Lube Flow Lockout First Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11257Diagnostic: Low Brg Lube Flow Lockout Second Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11258Diagnostic: Low Differential Lube Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11259Diagnostic: Low Differential Oil Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11260Diagnostic: Low Evap Leaving Water Temp: Unit OffRead0 = Normal, 1 = In Alarm
BI11261Diagnostic: Low Evap Leaving Water Temp: Unit OnRead0 = Normal, 1 = In Alarm
BI11262Diagnostic: Low Evaporator Refrigerant TemperatureRead0 = Normal, 1 = In Alarm
BI11263Diagnostic: Low Evaporator Water FlowRead0 = Normal, 1 = In Alarm
BI11264Diagnostic: Low Oil Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11265Diagnostic: Lube Pressure Sensor Calibration Circuit 1Read0 = Normal, 1 = In Alarm
BI11266Diagnostic: Lube Pump Disch Pressure Xdcr Circuit 1Read0 = Normal, 1 = In Alarm
BI11267Diagnostic: Lube Pump Override: Low Diff Press Circuit 1Read0 = Normal, 1 = In Alarm
BI11268Diagnostic: Lube Pump Override: Low Flow 1st Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11269Diagnostic: Lube Pump Override: Low Flow 2nd Stage Circuit 1Read0 = Normal, 1 = In Alarm
BI11270Diagnostic: Lube Pump Suction Pressure Xdcr Circuit 1Read0 = Normal, 1 = In Alarm
BI11271Diagnostic: Momentary Power LossRead0 = Normal, 1 = In Alarm
BI11272Diagnostic: Motor Coolant Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11273Diagnostic: Motor Current Overload Circuit 1Read0 = Normal, 1 = In Alarm
BI11274Diagnostic: Motor Temperature Cutout Tripped Circuit 1Read0 = Normal, 1 = In Alarm
BI11275Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11276Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11277Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11278Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11279Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11280Diagnostic: Oil Pressure Sensor Calibration Circuit 1Read0 = Normal, 1 = In Alarm
BI11281Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1Read0 = Normal, 1 = In Alarm
BI11282Diagnostic: Oil Tank Pressure Transducer Circuit 1Read0 = Normal, 1 = In Alarm
BI11283Diagnostic: Oil Tank Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11284Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11285Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11286Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11287Diagnostic: Outboard Bearing Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11288Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11289Diagnostic: Over Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11290Diagnostic: Phase Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11291Diagnostic: Phase Reversal Circuit 1Read0 = Normal, 1 = In Alarm
BI11292Diagnostic: Power Loss Circuit 1Read0 = Normal, 1 = In Alarm
BI11293Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1Read0 = Normal, 1 = In Alarm
BI11294Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1Read0 = Normal, 1 = In Alarm
BI11295Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1Read0 = Normal, 1 = In Alarm
BI11296Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11297Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11298Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1Read0 = Normal, 1 = In Alarm
BI11299Diagnostic: Purge Liquid Level Too High Continuously Circuit 1Read0 = Normal, 1 = In Alarm
BI11300Diagnostic: Purge Liquid Level Too High Warning Circuit 1Read0 = Normal, 1 = In Alarm
BI11301Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1Read0 = Normal, 1 = In Alarm
BI11302Diagnostic: Refrigerant Monitor InputRead0 = Normal, 1 = In Alarm
BI11303Diagnostic: Restart InhibitRead0 = Normal, 1 = In Alarm
BI11304Diagnostic: Severe Current Unbalance Circuit 1Read0 = Normal, 1 = In Alarm
BI11305Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11306Diagnostic: Software Error 1004: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11307Diagnostic: Starter Comm Loss: Main Processor Circuit 1Read0 = Normal, 1 = In Alarm
BI11308Diagnostic: Starter Contactor Interrupt Failure Circuit 1Read0 = Normal, 1 = In Alarm
BI11309Diagnostic: Starter Did Not Fully Accelerate Circuit 1Read0 = Normal, 1 = In Alarm
BI11310Diagnostic: Starter Did Not Transition Circuit 1Read0 = Normal, 1 = In Alarm
BI11311Diagnostic: Starter Dry Run Test Circuit 1Read0 = Normal, 1 = In Alarm
BI11312Diagnostic: Starter Failed to Arm/Start Circuit 1Read0 = Normal, 1 = In Alarm
BI11313Diagnostic: Starter Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11314Diagnostic: Starter Fault Type I Circuit 1Read0 = Normal, 1 = In Alarm
BI11315Diagnostic: Starter Fault Type II Circuit 1Read0 = Normal, 1 = In Alarm
BI11316Diagnostic: Starter Fault Type III Circuit 1Read0 = Normal, 1 = In Alarm
BI11317Diagnostic: Starter Module Memory Error Type 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11318Diagnostic: Starter Module Memory Error Type 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11319Diagnostic: Transition Complete Input Opened Circuit 1Read0 = Normal, 1 = In Alarm
BI11320Diagnostic: Transition Complete Input Shorted Circuit 1Read0 = Normal, 1 = In Alarm
BI11321Diagnostic: Under Voltage Circuit 1Read0 = Normal, 1 = In Alarm
BI11322Diagnostic: Unexpected Differential Lube Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11323Diagnostic: Unexpected Differential Oil Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11324Diagnostic: Unexpected Starter Shutdown Circuit 1Read0 = Normal, 1 = In Alarm
BI11325Diagnostic: Vibration Sensor InputRead0 = Normal, 1 = In Alarm
BI11326Comm Loss: Evap Refrigerant Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11327Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1Read0 = Normal, 1 = In Alarm
BI11328Diagnostic: Inverted Heat Recovery Approach Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11329Comm Loss: Sporlan Automatic Econ Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11330Comm Loss: Sporlan Automatic Cond Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11331Comm Loss: Trane IGV Cond Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11332Comm Loss: Trane IGV Econ Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11333Diagnostic: External Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11334Diagnostic: External Chilled Water SetpointRead0 = Normal, 1 = In Alarm
BI11335Comm Loss: External Hot Wtr SetpointRead0 = Normal, 1 = In Alarm
BI11336Comm Loss: External Chilled Wtr SetpointRead0 = Normal, 1 = In Alarm
BI11337Comm Loss: Motor Cooling Vent Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11338Diagnostic: Motor Cooling Vent Valve Position Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11339Comm Loss: Oil Heat Exchanger Vent Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11340Diagnostic: Oil Heat Exchanger Vent Valve Position Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11341Diagnostic: High Evaporator Refrigerant TemperatureRead0 = Normal, 1 = In Alarm
BI11342Diagnostic: Low Condenser Water FlowRead0 = Normal, 1 = In Alarm
BI11343Diagnostic: Low Heat Recovery Water FlowRead0 = Normal, 1 = In Alarm
BI11344Comm Loss: External Diagnostic ResetRead0 = Normal, 1 = In Alarm
BI11345Diagnostic: Economizer Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11346Diagnostic: Motor Cooling Pressure Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11347Comm Loss: Motor Cooling Valve Circuit 1Read0 = Normal, 1 = In Alarm
BI11348Comm Loss: Motor Cooling Pressure Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BV10100Base Loading RequestWrite0 = Off, 1 = On
BV10101Reset DiagnosticWrite0 = Normal, 1 = Reset
BV10102Evaporator Water Pump Request BASWrite0 = Auto, 1 = On
BV10103Condenser Water Pump Request BASWrite0 = Auto, 1 = On
BVmin10104Chiller Auto Stop Command BASWrite0 = Stop, 1 = Auto
BV10105Energy Consumption ResetWrite0 = Accumulating, 1 = Reset
MI10100Running ModeRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Chiller Setpoint SourceRead1 = BAS, 2 = External, 3 = Front Panel
MI10103Model Information [GEN2]Read1 = CVHF, 2 = CVGF, 3 = CVHS, 11 = CDHF, 12 = CVR, 13 = CVHH, 14 = CDHH, 20 = CVHM, 38 = CVHE, 39 = CVHG, 40 = CVHL, 43 = CDHG, 72 =CVZA, 73 =CVXA
MI10104Cooling TypeRead1 = Water Cooled
MI10105Refrigerant TypeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A
MI10106Manufacturing LocationRead1 = Field Applied, 2 = La Crosse, 15 = Taicang
MVmin10100Chiller Mode Command BASWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CenTraVac (Simplex) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 CenTraVac (Simplex)

How many BACnet points does the Trane Symbio 800 CenTraVac (Simplex) have?

This list has 546 BACnet objects: 150 analog inputs, 8 analog values, 374 binary inputs, 6 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 CenTraVac (Simplex) BACnet points are writable?

15 of the 546 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 CenTraVac (Simplex) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - CenTraVac (BAS-PTS009C-EN), revision 12/12/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 CenTraVac (Simplex)?

Start with BV 10104 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10113 Chiller Running State (Chiller on/off status); BI 10105 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10107 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10158 Actual Running Capacity (Actual running capacity in percent); BI 10118 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 CenTraVac (Simplex)?

BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10128 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10104 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10105 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

How do I check these points on the real Symbio 800 CenTraVac (Simplex)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025. Object names, instances and units are reproduced as published; descriptions are our own.