Rooftop unit / air handler controller · BACnet points list

Trane Symbio 800 IntelliPak BACnet points list

Updated 28 October 2026

Short answer

IntelliPak rooftops with Symbio 800 controls publish about 380 BACnet objects covering supply and exhaust fans, economizer, DX compressors, heat, energy recovery and power metering. Writable objects are AV/BV/MV setpoints and BAS commands, some with a heartbeat. Power meter points only appear when the meter option is installed.

This page lists 380 BACnet objects for the Trane Symbio 800 IntelliPak — 95 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 IntelliPak
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
380 (95 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
62000663-4-20-0006
Also known as
Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003
Source document
Symbio 800 Integration Points List BACnet/Modbus - IntelliPak · BAS-PTS003C-EN · rev. 12/17/2025
Download CSV 380 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 IntelliPak

Integration in brief

Schedule the unit with MV 10106 Occupancy Request and write the BAS setpoints you need: space, discharge air, duct static. MI 10119 Arbitration Method must read 'Full (Auto) Source' for BAS values to win over local ones. Sensor BAS points and the External setpoints AV 10183-10187 carry a 900 s heartbeat in the points list, so rewrite them periodically.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10106Occupancy RequestOccupancy command from the BMS scheduleWrite
MV 10104Heat Cool Mode RequestMode command from the BMSWrite
AV 10127Space Temperature Setpoint BASSpace setpoint from the BMSWrite
AV 10121Discharge Air Cooling Setpoint BASSupply air cooling setpoint from the BMSWrite
AV 10143Duct Static Pressure Setpoint BASDuct static setpoint on VAV unitsWrite
MI 10119Arbitration MethodMust read Full (Auto) for BAS values to be usedRead
MI 10103Occupancy StatusConfirms the occupancy in effectRead
BI 10226Supply Fan Output StatusSupply fan running (1 = on)Read
AI 10124Discharge Air TemperatureSupply air temperature in use (BAS or local sensor)Read
BI 10176Diagnostic PresentSummary alarmRead

Enable & remote start

The integration guide describes an arbitration method: with 'full/auto' the BMS value is used ahead of local or default values, and with 'local' BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active; the documents don't name a BACnet point to change it. BI 10211 Equipment Stop Status reports stop/auto; no BAS start/stop command is listed.

Heartbeat & communication loss

The points list gives a 900 s heartbeat for the sensor BAS values (AV 10111, 10113-10116, 10118, 10119) and the External setpoints (AV 10183-10187). The Symbio 800 integration guide doesn't describe what happens when it expires.

Sensors & values from the BMS

Write BMS values to the '... BAS' AVs (AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS, AV 10119 Space Humidity BAS, AV 10118 Space CO2 Concentration BAS, AV 10111 Discharge Air Temperature BAS). The '... Arbitrator' AVs show all sources in their priority array; the guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor. Direct capacity/fan/damper control uses the 'Setpoint External' AVs together with their 'Setpoint Enable External' BVs (e.g. AV 10187 with BV 10131).

Network setup

Watch out for

Trane Symbio 800 IntelliPak BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

380 of 380 shown
Type
Access
Show
Trane Symbio 800 IntelliPak BACnet Points List
DescriptionStates
AI10101Cooling Capacity StatusActual operating unit cooling capacity%Read
AI10102Heating Capacity Primary StatusUnit (primary) heating capacity%Read
AI10104Outdoor Air Relative Humidity LocalOutdoor air humidity value from sensor connected to the controller%Read
AI10105Outdoor Air Flow LocalCFMRead
AI10107Space Static Pressure LocalSpace statice pressure from a sensor connected to the controllerInches of WaterRead
AI10110Return Air Humidity LocalReturn air humidity value from sensor connected to the controller%Read
AI10111Outdoor Air Damper PositionPosition of the outside air damper as requested by the controller%Read
AI10112Exhaust Damper PositionUnit exhaust damper position%Read
AI10113Return Plenum Static PressureReturn plenum pressure value measured by a unit mounted sensorInches of WaterRead
AI10114Outdoor Air Minimum Flow Setpoint ActiveActive minimum outdoor air flow setpoint being used by the controllerCFMRead
AI10116Space Humidity ActiveActive space relative humidity being used by the controller%Read
AI10117Outdoor Air Dew Point°FRead
AI10118Outdoor Air Temperature ActiveActive outdoor air temperature currently being used by the controller°FRead
AI10120Outdoor Air Humidity ActiveActive outdoor air humidity value%Read
AI10121Discharge Air Cooling Setpoint ActiveDischarge air temperature cooling setpoint value resulting from any setpoint arbitration°FRead
AI10122Discharge Air Heating Setpoint ActiveDischarge air temperature heating setpoint value resulting from any setpoint arbitration°FRead
AI10123Duct Static Pressure Setpoint ActiveDuct static pressure control setpoint value resulting from any setpoint arbitrationInches of WaterRead
AImin10124Discharge Air TemperatureActual discharge air temperature being used by the controller°FRead
AI10125Mixed Air Temperature LocalMixed air temperature value from a sensor physically connected to the controller°FRead
AI10126Return Air TemperatureActual return air temperature being used by the controller°FRead
AI10128Space Static Pressure Setpoint ActiveActive space static pressure being used by the controllerInches of WaterRead
AI10135Space Dehumidification Setpoint ActiveActive (occupied) space dehumidification setpoint, considering all potential sources%Read
AI10152Exhaust Fan Speed StatusCommanded speed of the modulating exhaust fan%Read
AI10153Return Fan Speed StatusUnit commanded return fan speed%Read
AI10154Economizer Minimum Position Setpoint ActiveEconomizer minimum position setpoint value resulting from any setpoint arbitration%Read
AI10155Duct Static Pressure LocalDuct static pressure value from a sensor physically connected to the controllerInches of WaterRead
AI10156Outdoor Air Temperature LocalOutdoor air temperature value from a sensor physically connected to the controller°FRead
AI10157Dehumidification Control StatusStatus of the unit dehumidification capacity%Read
AI10161Condenser CapacityStatus of the unit condenser capacity, in percent%Read
AI10166Energy Recovery Leaving Exhaust Temperatue StatusEnergy recovery leaving exhaust temperature°FRead
AI10167Energy Recovery Outdoor Air Bypass Damper StatusEnergy recovery outdoor air bypass damper position%Read
AI10168Energy Recovery Exhaust Air Bypass Damper Position%Read
AI10172Reheat Capacity StatusUnit reheat capacity being requested by the controller, in percent%Read
AI10173Supply Fan Speed StatusCommanded speed of the supply fan, in percent%Read
AI10181Discharge Air Temperature LocalDischarge air temperature value from a sensor physically connected to the controller°FRead
AI10182Duct Static Pressure ActiveDuct static pressure value being used by the unitInches of WaterRead
AI10183Outdoor Air Enthalpy ActiveOutdoor air enthalpy value being utilized by the unitBTU/lbRead
AI10185Outdoor Air Flow ActiveActive outdoor air flow being used by the controllerCFMRead
AI10186Space Temperature ActiveActive space temperature being used by the controller°FRead
AI10187Space Static Pressure ActiveSpace static pressure value from a unit mounted sensorInches of WaterRead
AI10188Space CO2 Concentration ActiveActive space CO2 concentration being used by the controllerPPMRead
AI10190Space Temperature Cooling Setpoint Input(occupied) cooling temperature setpoint from the connected space sensor°FRead
AI10191Space Temperature Heating Setpoint Input(occupied) heating temperature setpoint from the connected space sensor°FRead
AI10197Heat TypeIdentifies the product heat typeRead
AI10198Cabinet StyleCabinet style of the unitRead
AI10199Cool TypeType of cooling in the unitRead
AI10200Preheat TypeType of preheat in the unitRead
AI10201Reheat TypeType of reheat in the unitRead
AI10202Supply Fan TypeType of supply fan in the unitRead
AI10203Exhaust Or Return Fan TypeType of exhaust fan or return fan in the unitRead
AI10204Exhaust Fan Speed Setpoint ActiveActive setpoint input to exhaust/relief fan control%Read
AI10206Number of CircuitsNumber of refrigeration circuits in the unitRead
AI10207Number of Compressors Circuit 1Number of compressors on DX circuit 1 of the unitRead
AI10208Number of Compressors Circuit 2Number of compressors on DX circuit 2 of the unitRead
AI10210Return Isolation Damper InputRequested position of the return isolation damper%Read
AI10213Space CO2 Concentration InputSpace CO2 concentration from a sensor connected to the controllerPPMRead
AI10214Space Dehumidification Unoccupied Setpoint ActiveActive unoccupied space dehumidification setpoint, considering all potential sources%Read
AI10215Space Humidity InputSpace relative humidity from a sensor connected to the controller%Read
AI10216Space Temp Cooling Setpoint Status(occupied) cooling temperature setpoint from the connected space sensor module°FRead
AI10217Space Temp Heating Setpoint Status(occupied) heating temperature setpoint from the connected space sensor module°FRead
AI10218Space Temperature Input°FRead
AI10221Space Temperature Setpoint ActiveActive space temperature setpoint being used by the controller°FRead
AI10222Supply Isolation Damper InputRequested position of the supply isolation damper, when present%Read
AI10224Average CurrentAmpsRead
AI10227Run Time - Compressor 1ARun time of Compressor 1ARead
AI10228Starts - Compressor 1ANumber of starts for Compressor 1ARead
AI10229Run Time - Compressor 1BRun time of Compressor 1BRead
AI10230Starts - Compressor 1BNumber of starts for Compressor 1BRead
AI10231Run Time - Compressor 1CRun time of Compressor 1CRead
AI10232Starts - Compressor 1CNumber of starts for Compressor 1CRead
AI10233Run Time - Compressor 2ARun time of Compressor 2ARead
AI10234Starts - Compressor 2ANumber of starts for Compressor 2ARead
AI10235Run Time - Compressor 2BRun time of Compressor 2BRead
AI10236Starts - Compressor 2BNumber of starts for Compressor 2BRead
AI10237Run Time - Compressor 2CRun time of Compressor 2CRead
AI10238Starts - Compressor 2CNumber of starts for Compressor 2CRead
AI10239Current L1AmpsRead
AI10240Current L2AmpsRead
AI10241Current L3AmpsRead
AI10242Current NeutralAmpsRead
AI10243Discharge Air Cooling Setpoint Status°FRead
AI10244Discharge Air Heating Setpoint Status°FRead
AI10246Discharge Gauge Pressure Circuit 1Refrigerant discharge gauge pressure for DX circuit 1PSIRead
AI10247Discharge Gauge Pressure Circuit 2Refrigerant discharge gauge pressure for DX circuit 2PSIRead
AI10249Energy Consumption LifetimeTotal energy consumption of the unit (for the lifetime of the unit)kWhRead
AI10250Evaporator Leaving Air TemperatureLeaving air temperature of the evaporator°FRead
AI10251Evaporator Leaving Air Temperature Evap ALeaving air temperature of evaporator A when a split evaporator is used°FRead
AI10252Evaporator Leaving Air Temperature Evap BLeaving air temperature of evaporator B when a split evaporator is used°FRead
AI10253Evaporator Leaving Air Temperature Setpoint ActiveEvaporator leaving air temperature setpoint value resulting from any setpoint arbitration°FRead
AI10254Final Filter Differential Pressure LocalStatus of the final filter differential pressure sensor input on the controllerInches of WaterRead
AI10255Line FrequencyLine frequency when the optional power monitoring option is includedRead
AI10256Mixed Air Temperature Evap AMixed air temperature associated with evaporator A°FRead
AI10257Mixed Air Temperature Evap BMixed air temperature associated with evaporator B°FRead
AI10258Power FactorReported power factor from the optional power monitoring option, when applicableRead
AI10259Prefilter Differential Pressure LocalInches of WaterRead
AI10262Suction Gauge Pressure Circuit 1Suction pressure for DX circuit 1, in PSIGPSIRead
AI10263Suction Gauge Pressure Circuit 2Suction pressure for DX circuit 2, in PSIGPSIRead
AI10268Total Apparent EnergyTotal apparent energy as reported by the optional power monitoring featurekWhRead
AI10269Energy ConsumptionTotal energy consumption of the unit (since last accumulation reset)kWhRead
AI10270Total Reactive EnergyTotal reactive energy as reported by the optional power monitoring featurekWhRead
AI10271Total Real PowerTotal real power as reported by the optional power monitoring featurekWRead
AI10272Total Apparent PowerTotal apparent power as reported by the optional power monitoring featurekWRead
AI10273Total Reactive PowerTotal reactive power as reported by the optional power monitoring featurekWRead
AI10274Unit Source IDIndividual diagnostics are reported with dedicated points, variables, registersRead
AI10275Voltage L1-L2Voltage between line/leg L1 and L2VoltsRead
AI10276Voltage L1-L3Voltage between line/leg L1 and L3VoltsRead
AI10277Voltage L1-NVoltage between line/leg L1 and NeutralVoltsRead
AI10278Voltage L2-L3Voltage between line/leg L2 and L3VoltsRead
AI10279Voltage L2-NVoltage between line/leg L2 and NeutralVoltsRead
AI10280Voltage L3-NVoltage between line/leg L3 and NeutralVoltsRead
AI10281Discharge Air Temperature Setpoint ActiveDischarge air temperature setpoint value resulting from any setpoint arbitration°FRead
AI10282Air Flow Percentage Circuit 1Requested condenser percentage for circuit 1%Read
AI10283Air Flow Percentage Circuit 2Requested condenser percentage for circuit 2%Read
AI10284Discharge Saturated Refrigeration Temperature Circuit 1Discharge saturated refrigerant temperature for DX circuit 2°FRead
AI10285Discharge Saturated Refrigeration Temperature Circuit 2Discharge saturated refrigerant temperature for DX circuit 2°FRead
AI10286Suction Saturated Refrigerant Temperature Circuit 1Suction saturated refrigerant temperature for DX circuit 1°FRead
AI10287Suction Saturated Refrigerant Temperature Circuit 2Suction saturated refrigerant temperature for DX circuit 2°FRead
AI10288Suction Temperature Evap 1ASuction temperature for evaporator 1A°FRead
AI10289Suction Temperature Evap 1BSuction temperature for evaporator 1B°FRead
AI10290Suction Temperature Evap 2ASuction temperature for evaporator 2A°FRead
AI10291Suction Temperature Evap 2BSuction temperature for evaporator 2B°FRead
AI10292Occupied Cooling SetpointActive occupied cooling setpoint being°FRead
AI10293Occupied Heating SetpointActive occupied heating setpoint being°FRead
AI10294Occupied Standby Cooling SetpointActive occupied standby cooling setpoint being°FRead
AI10295Occupied Standby Heating SetpointActive occupied standby heating setpoint being°FRead
AI10296Supply Fan Speed Setpoint ActiveActive setpoint input to supply fan control%Read
AI10297Discharge Air Temperature Maximum Cool Limit ActiveMaximum cooling setpoint allowed to be calculated by Space Temp Control°FRead
AI10298Discharge Air Temperature Minimum Heat Limit ActiveMinimum heating setpoint allowed to be calculated by Space Temp Control°FRead
AI10299Discharge Air Temperature Minimum Cool Limit ActiveMinimum cooling setpoint allowed to be calculated by Space Temp Control°FRead
AI10300Discharge Air Temperature Maximum Heat Limit ActiveMinimum heating setpoint allowed to be calculated by Space Temp Control°FRead
AI10303Energy Recovery Wheel Filter Differential PressureDifferntial pressure across the energy wheel filter while bypass dampers are closedInches of WaterRead
AI10304Average Current Meter 2Average current for the second power meterAmpsRead
AI10305Current L1 Meter 2Current for line/leg 1 for the second power meterAmpsRead
AI10306Current L2 Meter 2Current for line/leg 2 for the second power meterAmpsRead
AI10307Current L3 Meter 2Current for line/leg 3 for the second power meterAmpsRead
AI10308Current Neutral Meter 2Current for neutral for the second power meterAmpsRead
AI10309Energy Consumption Meter 2kWhRead
AI10310Energy Consumption Lifetime Meter 2Energy consumption for the second power meterkWhRead
AI10311Line Frequency Meter 2Line frequency for the second power meterRead
AI10312Power Factor Meter 2Power factor for the second power meterRead
AI10313Total Apparent Energy Meter 2Total apparent energy for the second power meterkWhRead
AI10314Total Apparent Power Meter 2Total apparent power for the second power meterkWRead
AI10315Total Reactive Energy Meter 2Total reactive energy for the second power meterkWhRead
AI10316Total Reactive Power Meter 2Total reactive power for the second power meterkWRead
AI10317Total Real Power Meter 2Total real power for the second power meterkWRead
AI10318Voltage L1-L2 Meter 2Voltage between line/leg L1 and L2 for the second power meterVoltsRead
AI10319Voltage L1-L3 Meter 2Voltage between line/leg L1 and L3 for the second power meterVoltsRead
AI10320Voltage L1-N Meter 2Voltage between line/leg L1 and Neutral for the second power meterVoltsRead
AI10321Voltage L2-L3 Meter 2Voltage between line/leg L2 and L3 for the second power meterVoltsRead
AI10322Voltage L2-N Meter 2Voltage between line/leg L2 and Neutral for the second power meterVoltsRead
AI10323Voltage L3-N Meter 2Voltage between line/leg L3 and Neutral for the second power meterVoltsRead
AI10324Run Time - Compressor 1A (Hours)Run time of Compressor 1A, in hoursRead
AI10325Run Time - Compressor 1B (Hours)Run time of Compressor 1B, in hoursRead
AI10326Run Time - Compressor 1C (Hours)Run time of Compressor 1C, in hoursRead
AI10327Run Time - Compressor 2A (Hours)Run time of Compressor 2A, in hoursRead
AI10328Run Time - Compressor 2B (Hours)Run time of Compressor 2B, in hoursRead
AI10329Run Time - Compressor 2C (Hours)Run time of Compressor 2C, in hoursRead
AI10330Discharge Pressure Circuit 1Refrigerant discharge absolute pressure for DX circuit 1PSIRead
AI10331Discharge Pressure Circuit 2Refrigerant discharge absolute pressure for DX circuit 2PSIRead
AI10332Suction Pressure Circuit 1Suction pressure for DX circuit 1, in PSIAPSIRead
AI10333Suction Pressure Circuit 2Suction pressure for DX circuit 2, in PSIAPSIRead
AI10334Space Dew PointCalculated space dew point from space humid active, space temp active°FRead
AI10335Space Dew Point Setpoint ActiveActive occupied space dew point setpoint°FRead
AI10336Space Dew Point Unocc Setpoint ActiveActive unoccupied space dew point setpoint°FRead
AI10337Heating Capacity Setpoint ActiveStatus of current heating capacity request%Read
AI10338Outdoor Air Damper Position Setpoint ActiveStatus of current outdoor air damper position request%Read
AI10339Return Fan Speed Setpoint ActiveStatus of current return fan speed request%Read
AI10340Cooling Capacity Setpoint ActiveStatus of current cooling capacity request%Read
AI10341Rfgt LFL Conc Alarm Threshold Sensor AInternal sensor % of refrigerant to trip alarm A%Read
AI10342Rfgt LFL Conc Alarm Threshold Sensor BInternal sensor % of refrigerant to trip alarm B%Read
AI10343Refrigerant LFL Concentration Sensor AActual refrigerant being measured by sensor A%Read
AI10344Refrigerant LFL Concentration Sensor BActual refrigerant being measured by sensor B%Read
AI10345Rfgt LFL Conc Alarm Threshold Sensor CInternal sensor % of refrigerant to trip alarm C%Read
AI10346Rfgt LFL Conc Alarm Threshold Sensor DInternal sensor % of refrigerant to trip alarm D%Read
AI10347Refrigerant LFL Concentration Sensor CActual refrigerant being measured by sensor C%Read
AI10348Refrigerant LFL Concentration Sensor DActual refrigerant being measured by sensor D%Read
AI10349Exhaust Fan 1 VFD PowerCurrent power being used by Exhaust Fan 1kWRead
AI10350Exhaust Fan 2 VFD PowerCurrent power being used by Exhaust Fan 2kWRead
AI10351Exhaust Fan 3 VFD PowerCurrent power being used by Exhaust Fan 3kWRead
AI10352Supply Fan 1 VFD PowerCurrent power being used by Supply Fan 1kWRead
AI10353Supply Fan 2 VFD PowerCurrent power being used by Supply Fan 2kWRead
AI10354Return Fan VFD PowerCurrent power being used by Return Fan 1kWRead
AI10355Return Air Enthalpy ActiveThe return air enthalpy value being utilized by the unitBTU/lbRead
AI10356Return Plenum Static Pressure Setpoint (Target)Lculated return plenum pressure tarInches of WaterRead
AV10101Discharge Air Temperature ArbitratorActual discharge air temperature being used by the controller°FWrite
AV10103Outdoor Air Temperature ArbitratorActual outdoor air temperature being used by the controller°FWrite
AV10104Outdoor Air Humidity ArbitratorActual outdoor air humidity being used by the controller%Write
AV10105Outdoor Air Flow ArbitratorActual outdoor air flow being used by the controllerCFMWrite
AV10106Space Temperature ArbitratorActual space temperature being used by the controller°FWrite
AV10107Space Static Pressure ArbitratorSpace static pressure value from a unit mounted sensorInches of WaterWrite
AV10108Space CO2 Concentration ArbitratorActual space CO2 concentration being used by the controllerPPMWrite
AV10109Space Humidity ArbitratorActual space relative humidity being used by the controller%Write
AV10111Discharge Air Temperature BASSend the discharge air temperature sensor value°FWrite
AV10113Outdoor Air Temperature BASSend the outdoor air temperature sensor value°FWrite
AV10114Space Temperature BASSend the space temperature value°FWrite
AV10115Outdoor Air Flow BASSend the outdoor air flow valueCFMWrite
AV10116Outdoor Air Humidity BASSend the outdoor air humidity sensor value%Write
AV10118Space CO2 Concentration BASSend the space CO2 concentration valuePPMWrite
AV10119Space Humidity BASSend the space relative humidity value%Write
AVmin10121Discharge Air Cooling Setpoint BASDischarge air temperature cooling setpoint value°FWrite
AV10122Discharge Air Heating Setpoint BASDischarge air temperature heating setpoint value°FWrite
AV10123Unoccupied Cooling SetpointDefine the cooling temperature setpoint used for control in unoccupied mode°FWrite
AV10124Unoccupied Heating SetpointDefine the heating temperature setpoint used for control in unoccupied mode°FWrite
AV10125Outdoor Air Minimum Flow Setpoint BASSend the requested minimum outdoor air flow setpointCFMWrite
AVmin10127Space Temperature Setpoint BASBAS-supplied space temperature setpoint value°FWrite
AV10128Space Static Pressure Setpoint BASSend the space static pressure valueInches of WaterWrite
AV10130Occupied OffsetDefine the difference between the occupied cooling and heating setpointsDelta °FWrite
AV10134Discharge Air Reheat Setpoint BASDischarge air temperature reheat setpoint value, for dehumidification control°FWrite
AV10135Space Dehumidification Setpoint BASDefine the (occupied) space dehumidification setpoint%Write
AV10136Supply Fan Speed SetpointBAS supplied supply fan speed setpoint value%Write
AV10137Exhaust Fan Speed SetpointBAS supplied exhaust fan speed setpoint value%Write
AV10139Cooling Capacity Enable%Write
AV10140Heat Primary Enable BAS%Write
AV10141Morning Warmup Setpoint BASNormally provided by the BMS, defines the space temperature below°FWrite
AV10142Occupied Standby OffsetDefine the difference between the occupied standby cooling and heating setpointsDelta °FWrite
AVmin10143Duct Static Pressure Setpoint BASDuct static pressure setpoint valueInches of WaterWrite
AV10144Economizer Minimum Position Setpoint BASEcominizer minimum position setpoint%Write
AV10147Cooling Setpoint High LimitOccupied cooling setpoint high limit for space comfort control applications°FWrite
AV10148Cooling Setpoint Low LimitOccupied cooling setpoint low limit for space comfort control applications°FWrite
AV10149Daytime Warmup Setpoint BASDefines the space temp below which daytime warmup will be enabled°FWrite
AV10150Economizer Outdoor Air Enable Setpoint BAS°FWrite
AV10152Heating Setpoint High LimitOccupied heating setpoint high limit for space comfort control applications°FWrite
AV10153Heating Setpoint Low LimitOccupied heating setpoint low limit for space comfort control applications°FWrite
AV10156Space Dehumidification Unoccupied Setpoint BASDefine the unoccupied space dehumidification setpoint%Write
AV10159Occupied Cooling Setpoint BASDefine the occupied cooling setpoint°FWrite
AV10160Occupied Heating Setpoint BASDefine the occupied heating setpoint°FWrite
AV10161Occupied Standby Cooling Setpoint BASDefine the occupied standby cooling setpoint°FWrite
AV10162Occupied Standby Heating Setpoint BASActive occupied standby heating setpoint being°FWrite
AV10163Demand Limit SetpointDemand limit the unit%Write
AV10164Evaporator Leaving Air Temperature Setpoint°FWrite
AV10165Pre Cool SetpointNormally provided by the BAS, defines the space temperature above°FWrite
AV10166Discharge Air Temperature Maximum Heat LimitDischarge air temperature maximum heat limit, above°FWrite
AV10167Discharge Air Temperature Minimum Cool LimitDischarge air temperature minimum cool limit, below°FWrite
AV10168Exhaust Enable Position SetpointIndicate the outdoor air damper position above%Write
AV10169Occupied Bypass TimeMinutesWrite
AV10170Economizer Outdoor Air Enthalpy Enable Setpoint BASBTU/lbWrite
AV10175Space CO2 High LimitDefine the CO2 high limit, for ventilation purposesPPMWrite
AV10176Space CO2 Low LimitDefine the CO2 low limitPPMWrite
AV10177Supply Fan Speed Setpoint External HeatSpecifies the supply fan speed setpoint during external heat modes of operation%Write
AV10178Discharge Air Temperature Maximum Cool LimitNormally used by BAS to limit space temperature control calculated cooling setpoint°FWrite
AV10179Discharge Air Temperature Minimum Heat LimitNormally used by BAS to limit space temperature control calculated heating setpoint°FWrite
AV10180Space Dew Point Setpoint BAS°FWrite
AV10181Space Dew Point Unocc Setpoint BAS°FWrite
AV10182Heating Capacity Setpoint ExternalRemote heating capacity request%Write
AV10183Outdoor Air Damper Position Setpoint ExternalRemote outdoor air damper position request%Write
AV10184Exhaust Fan Speed Setpoint ExternalRemote exhaust fan speed request%Write
AV10185Return Fan Speed Setpoint ExternalRemote rturn fan speed request%Write
AV10186Supply Fan Speed Setpoint ExternalRemote supply fan speed request%Write
AV10187Cooling Capacity Setpoint ExternalRemote cooling capacity request%Write
BI10001microSDWhen a micro SD card is presentRead0 = MicroSD card is not present, 1 = MicroSD card is present
BI10002USB Port 1When a USB device is present in port 1Read0 = USB device is not present, 1 = USB device is present
BI10003USB Port 2When a USB device is present in port 2Read0 = USB device is not present, 1 = USB device is present
BI10004USB Port 3When a USB device is present in port 3Read0 = USB device is not present, 1 = USB device is present
BI10005USB Port 4When a USB device is present in port 4Read0 = USB device is not present, 1 = USB device is present
BI10105FDD: Unit Economizing When It Should NotFDD: Indicates when the unit is economizing but should not beRead0 = Inactive, 1 = Active
BI10106FDD: Unit Not Economizing When it Should BeFDD: Indicates when the unit is not economizing but should beRead0 = Inactive, 1 = Active
BI10107FDD: Excessive Outdoor AirFDD: Indicates an excessive outdoor air conditionRead0 = Inactive, 1 = Active
BI10108FDD: Outdoor Air Damper Not ModulatingRead0 = Inactive, 1 = Active
BI10111Compressor 1A StatusOperating status of compressor 1ARead0 = Off, 1 = Running
BI10112Compressor 1B StatusOperating status of compressor 1BRead0 = Off, 1 = Running
BI10113Compressor 1C StatusOperating status of compressor 1CRead0 = Off, 1 = Running
BI10114Compressor 2A StatusOperating status of compressor 2ARead0 = Off, 1 = Running
BI10115Compressor 2B StatusOperating status of compressor 2BRead0 = Off, 1 = Running
BI10116Compressor 2C StatusOperating status of compressor 2CRead0 = Off, 1 = Running
BI10132FDD: Outdoor Air Temperature Sensor FailureFDD: Indicates when the outdoor air temperature sensor has failedRead0 = Inactive, 1 = Active
BI10140Unit Running StateThe unit is off or onRead0 = Off, 1 = Running
BI10143VAV Box CommandRead0 = Auto, 1 = Open
BI10144Alarm Relay Output StatusState of the alarm output of the controllerRead0 = De-energized, 1 =Energized
BI10149Return Fan Output StatusState of the return fanRead0 = Off, 1 = On
BI10154Supply Fan Configuration StatusSupply fan configurationRead0 = Cycling, 1 =Continuouos
BI10155Rapid Restart StatusActive status of the Rapid Restart eventRead0 = Inactive, 1 = Active
BI10161Morning Warmup ActiveActive status of the Morning Warmup eventRead0 = Inactive, 1 = Active
BI10162Daytime Warmup ActiveActive status of the Daytime Warmup eventRead0 = Inactive, 1 = Active
BI10164Coil Frost Protection Status Circuit 1Status of evaporator frost protection function for circuit 1Read0 = Inactive, 1 = Active
BI10165Coil Frost Protection Status Circuit 2Status of evaporator frost protection function for circuit 2Read0 = Inactive, 1 = Active
BI10166Energy Recovery StatusStatus of the energy recovery device (Wheel)Read0 = Inactive, 1 = Active
BI10167Energy Recovery Preheat StatusStatus of the energy recovery preheatRead0 = Inactive, 1 = Active
BI10168Energy Recovery Frost Avoidance StatusStatus of the Recovery Frost Avoidance functionRead0 = Inactive, 1 = Active
BI10170Condensate Overflow InputStatus of the condensate overflow inputRead0 = Normal, 1 = Overflow
BI10172Occupancy InputStatus of the occupancy input (see below)Read0 = Occupied, 1 =Unoccupied
BI10173Precool ActiveWhen the pre-cool mode is activeRead0 = Inactive, 1 = Active
BI10174Supply Air Tempering StatusOr not the supply air tempering feature is enabledRead0 = Disable, 1 = Enable
BI10175Timed Override Timer Is ActiveOr not the timed override timer is activeRead0 = Inactive, 1 = Active
BImin10176Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10201Changeover InputStatus of the (heat/cool) changeover inputRead0 = Heating, 1 = Cooling
BI10202Condenser Fan Circuit 1 Relay 1 StatusStatus of condenser fan circuit 1, relay 1Read0 = Off, 1 = On
BI10203Condenser Fan Circuit 1 Relay 2 StatusStatus of condenser fan circuit 1, relay 2Read0 = Off, 1 = On
BI10204Condenser Fan Circuit 1 Relay 3 StatusStatus of condenser fan circuit 1, relay 3Read0 = Off, 1 = On
BI10205Condenser Fan Circuit 1 Relay 4 StatusStatus of condenser fan circuit 1, relay 4Read0 = Off, 1 = On
BI10206Condenser Fan Circuit 2 Relay 1 StatusStatus of condenser fan circuit 2, relay 1Read0 = Off, 1 = On
BI10207Condenser Fan Circuit 2 Relay 2 StatusStatus of condenser fan circuit 2, relay 2Read0 = Off, 1 = On
BI10208Condenser Fan Circuit 2 Relay 3 StatusStatus of condenser fan circuit 2, relay 3Read0 = Off, 1 = On
BI10209Condenser Fan Circuit 2 Relay 4 StatusStatus of condenser fan circuit 2, relay 4Read0 = Off, 1 = On
BI10210Emergency StopStatus of the emergency stop function of the unitRead0 = Auto, 1 =Emergency Stop - Manual Reset Required
BI10211Equipment Stop StatusStatus of the externally-wired auto/stop inputRead0 = Stop, 1 = Auto
BI10212Supply Fan Bypass StatusStatus of the supply fan bypass from the variable frequency drive (VFD)Read0 = Inactive, 1 = Active
BI10213Ventilation Mode A LocalWhen the controller is actively in the Ventilation Override Mode ARead0 = Inactive, 1 = Active
BI10214Ventilation Mode B LocalWhen the controller is actively in the Ventilation Override Mode BRead0 = Inactive, 1 = Active
BI10215Ventilation Mode C LocalWhen the controller is actively in the Ventilation Override Mode CRead0 = Inactive, 1 = Active
BI10216Ventilation Mode D LocalWhen the controller is actively in the Ventilation Override Mode DRead0 = Inactive, 1 = Active
BI10217Ventilation Mode E LocalWhen the controller is actively in the Ventilation Override Mode ERead0 = Inactive, 1 = Active
BI10218Diagnostic: Manual Reset RequiredWhen a diagnostic exists that requires manual resetRead0 = Normal, 1 = In Alarm
BI10219Economizer Airside StatusStatus of airside economizingRead0 = Inactive, 1 = Active
BI10221Exhaust Fan Output StatusStatus of the exhaust fan output on the controllerRead0 = Off, 1 = On
BI10222Heat Output 1 StatusCommanded state of heating output 1Read0 = Off, 1 = On
BI10223Heat Output 2 StatusCommanded state of heating output 2Read0 = Off, 1 = On
BI10224Heat Output 3 StatusCommanded state of heating output 3Read0 = Off, 1 = On
BI10225Heat Output 4 StatusCommanded state of heating output 4Read0 = Off, 1 = On
BImin10226Supply Fan Output StatusStatus of the supply fan output of the controllerRead0 = Off, 1 = On
BI10603Diagnostic: Discharge Air High Temperature DetectedWhen a discharge air high temperature diagnostic is presentRead0 = No, 1 = Yes
BI10605Diagnostic: Loss of Charge Lockout Ckt1When a loss of charge lockout diagnostic exists for DX circuit 1Read0 = No, 1 = Yes
BI10606Diagnostic: Loss of Charge Lockout Ckt2When a loss of charge lockout diagnostic exists for DX circuit 2Read0 = No, 1 = Yes
BI10608Diagnostic: Morning Warmup Mode Exceeded 120 MinutesWhen the morning warmup mode has exceeded 120 consectutive minutesRead0 = No, 1 = Yes
BI10609Diagnostic: Pre Cool Mode Exceeded 120 MinutesWhen the pre-cool mode has exceeded 120 consective minutesRead0 = No, 1 = Yes
BI10611Diagnostic: Return Air High Temperature DetectedWhen a return air high temperature diagnostic is presentRead0 = No, 1 = Yes
BI10614Diagnostic: Condensate Overflow LockoutWhen a condensate overflow lockout diagnostic is presentRead0 = No, 1 = Yes
BI10615Diagnostic: High Condensate Level DetectedWhen a high condensate level is detectedRead0 = No, 1 = Yes
BI10616Supply Fan Speed Control EnabledSupply fan speed is controlled via Supply Fan Speed SetpointRead0 = Disabled, 1 = Enabled
BI10617Supply Fan Speed LimitedRead0 = Not Limited, 1 = Limited
BI10618Exhaust Fan Speed Control EnabledExhaust fan speed is controlled via Exhaust Fan Speed SetpointRead0 = Disabled, 1 = Enabled
BI10619Diagnostic Shutdown PresentUnit is shut down due to diagnosticsRead0 = Normal, 1 = In Alarm
BI10620Diagnostic: Local Manual Reset RequiredDiagnostic Reset required [Local only]Read0 = Normal, 1 = In Alarm
BI10622Exhaust Fan Bypass StatusStatus of the exhaust fan bypass from the variable frequency drive (VFD)Read0 = Inactive, 1 = Active
BI10623Return Fan Bypass StatusStatus of the return fan bypass from the variable frequency drive (VFD)Read0 = Inactive, 1 = Active
BI10624Heating Capacity Control EnabledStatus of heating capacity enabledRead0 = Disabled, 1 = Enabled
BI10625Outdoor Air Damper Control EnabledStatus of ourdoor air damper enabledRead0 = Disabled, 1 = Enabled
BI10626Return Fan Speed Control EnabledStatus of return fan speed enabledRead0 = Disabled, 1 = Enabled
BI10627Cooling Capacity Control EnabledStatus of cooling capacity enabledRead0 = Disabled, 1 = Enabled
BI10628Final Filter Differential Press Setpoint ExceededWhen the Final Filter Differential Pressure Setpoint has been exceededRead0 = Inactive, 1 = Active
BI10629Pre Evap Filter Differential Pressure Setpoint ExceededWhen the Pre Evaporator Filter Differential Pressure Setpoint has been exceededRead0 = Inactive, 1 = Active
BI10630Energy Wheel Filter Differential Pressure Setpoint ExceededWhen the Energy Wheel Filter Differential Pressure Setpoint has been exceededRead0 = Inactive, 1 = Active
BI10631Refrigerant Mitigation ActiveUnit is in active mitigation modeRead0 = Inactive, 1 = Active
BV10103Heat Lockout CommandCommand the unit to prevent heating operation (Trane external heat option)Write0 = Normal, 1 = Locked Out
BV10104Supply Fan Configuration CommandCommand the unit supply fan configuration as either cycling or continuousWrite0 = Cycling, 1 = Continuous
BV10106Dehumidification Enable CommandDisable unit dehumidificationWrite0 = Disable, 1 = Auto
BV10110Reset DiagnosticInitiate a request to reset any remote controller diagnosticsWrite0 = Normal, 1 = Reset
BV10111Daytime Warmup Enable CommandEnable daytime warmupWrite0 = Disable, 1 = Enable
BV10112Morning Warmup Enable CommandEnable morning warmupWrite0 = Disable, 1 = Enable
BV10113Occupancy Input BASProvide the requested occupancy state to the unitWrite0 = Occupied, 1 =Unoccupied
BV10115Cooling Lockout BASNormally used by the BAS as a command toWrite0 = Normal, 1 = Locked Out
BV10116Demand Limit Request BASWrite0 = Not Limited, 1 = Limited
BV10117Energy Consumption ResetReset the energy consumption accumulated totalWrite0 = Accumulating, 1 = Reset
BV10118Pre Cool Enable CommandEnable pre- coolWrite0 = Disabled, 1 = Enabled
BV10119Supply Air Tempering EnableEnable the supply (discharge) air tempering feature of the unitWrite0 = Disable, 1 = Enable
BV10120Rapid Restart EnableEnables/Disables rapid restart operationWrite0 = Disable, 1 = Enable
BV10121Rapid Restart Economizer EnableEnables/Disables economizer evaluation during rapid restart operationWrite0 = Disable, 1 = Enable
BV10122Supply Fan Speed Setpoint EnableEnables Supply Fan Speed Setpoint controlWrite0 = Disable, 1 = Enable
BV10123Exhaust Fan Speed Setpoint EnableEnables Exhaust Fan Speed Setpoint controlWrite0 = Disable, 1 = Enable
BV10124Supply Fan CompensationWrite0 = Disable, 1 = Enable
BV10125Energy Consumption Reset Meter 2Reset the energy consumption accumulated total for second power meterWrite0 = Accumulating, 1 = Reset
BV10126Heating Capacity Setpoint Enable ExternalEnables Heating Capacity Setpoint controlWrite0 = Disable, 1 = Enable
BV10127Outdoor Air Damper Position Setpoint Enable ExternalEnables Outdoor Air Damper Position Setpoint controlWrite0 = Disable, 1 = Enable
BV10128Exhaust Fan Speed Setpoint Enable ExternalEnables Exhust Fan Speed Setpoint controlWrite0 = Disable, 1 = Enable
BV10129Return Fan Speed Setpoint Enable ExternalEnables Return Fan Speed Setpoint controlWrite0 = Disable, 1 = Enable
BV10130Supply Fan Speed Setpoint Enable ExternalEnables Supply Fan Speed Setpoint controlWrite0 = Disable, 1 = Enable
BV10131Cooling Capacity Setpoint Enable ExternalEnables Cooling Capacity Setpoint controlWrite0 = Disable, 1 = Enable
MI10101Heat Cool Mode StatusCurrent heat cool mode of the controllerRead1 = Auto, 2 = Heat, 3 = Morning Warm- up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MI10102Ventilation Override StatusWhich of the 5 preprogrammed ventilation override modes is operational, when applicableRead1 = Inactive, 2 = Mode A Active, 3 = Mode B Active, 4 = Mode C Active, 5 = Mode D Active, 6 = Mode E Active
MImin10103Occupancy StatusActive occupancy mode of the controllerRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MI10105Cooling Reset Type StatusType of cooling reset used by the controllerRead1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air
MI10106Heating Reset Type StatusType of heating reset used, when applicableRead1 = None, 2 = Outdoor Air, 3 = Zone
MI10107Trane Unit TypeEquipment type according to the manufacturer's classificationRead6 = Rooftop
MI10108Economizer TypeGeneral description of the type of economizer systemRead1 = None, 3 = Modulation Economizer, 8 = Airside Economizer and TRAQ Damper/ Sensor
MI10109Condenser TypeGeneral description of the equipment condenser systemRead2 = Air Cooled Condenser
MI10117Refrigerant TypeType of refrigerant used in the equipmentRead7 = R-410A, 17 = R-454B
MI10118System Mode Switch LocalStatus of the system mode switch connected to the controllerRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MImin10119Arbitration MethodRead1 = Full (Auto) Source, 2 = Local Source, 3 = Default Source
MI10120Timed Override Request ActiveStatus of the timed override request (see above)Read1 = Idle, 2 = On, 3 = Cancel
MI10121Electrical Service TypeElectrical service type used for the unitRead1 = A+N, 2 = A+B, 3 = A+B+N, 4 = A+B+C, 5 = A+B+C+N
MI10132Economizer Decision MethodMethod of enabling airside economizingRead1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy
MI10144Economizer System StatusStatus of enabling economizingRead1 = Disabled, 2 = Enabled, 3 = Not Present
MI10145Model Information [GEN2]Type of equipmentRead27 = IPAK
MI10146Electrical Service Type Meter 2Electrical service type used for the second power connection on the unitRead1 = A+N, 2 = A+B, 3 = A+B+N, 4 = A+B+C, 5 = A+B+C+N
MI10147Emergency Override BAS - ActiveStatus of emergency overrideRead1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV10102Emergency Override BASCommand the unit into an emergency mode of operationWrite1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV10103Economizer Airside Enable BASEnable airside economizingWrite1 = Disabled, 2 = Enabled, 3 = Auto
MVmin10104Heat Cool Mode RequestCommand the unit into a heat/cool mode, including additional possible control modesWrite1 = Auto, 2 = Heat, 3 = Morning Warm- up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MVmin10106Occupancy RequestCommand the unit into an occupancy modeWrite1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV10110Timed Override RequestRequest a temporary timed override during unoccupiedWrite1 = Idle, 2 = On, 3 = Cancel
MV10111Dehumidification MethodSelect how the unit determines when to dehumidifyWrite1 = Relative Humidity, 2 = Dew Point

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 IntelliPak and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 IntelliPak

How many BACnet points does the Trane Symbio 800 IntelliPak have?

This list has 380 BACnet objects: 184 analog inputs, 65 analog values, 83 binary inputs, 24 binary values, 18 multi-state inputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 IntelliPak BACnet points are writable?

95 of the 380 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane Symbio 800 IntelliPak BACnet documentation?

The source is Symbio 800 Integration Points List BACnet/Modbus - IntelliPak (BAS-PTS003C-EN), revision 12/17/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS003C-EN_12172025.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 IntelliPak?

Start with MV 10106 Occupancy Request (Occupancy command from the BMS schedule); MV 10104 Heat Cool Mode Request (Mode command from the BMS); AV 10127 Space Temperature Setpoint BAS (Space setpoint from the BMS); AV 10121 Discharge Air Cooling Setpoint BAS (Supply air cooling setpoint from the BMS); AV 10143 Duct Static Pressure Setpoint BAS (Duct static setpoint on VAV units); MI 10119 Arbitration Method (Must read Full (Auto) for BAS values to be used); MI 10103 Occupancy Status (Confirms the occupancy in effect); BI 10226 Supply Fan Output Status (Supply fan running (1 = on)); AI 10124 Discharge Air Temperature (Supply air temperature in use (BAS or local sensor)); BI 10176 Diagnostic Present (Summary alarm).

How do I enable BMS control of the Trane Symbio 800 IntelliPak?

The integration guide describes an arbitration method: with 'full/auto' the BMS value is used ahead of local or default values, and with 'local' BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active; the documents don't name a BACnet point to change it. BI 10211 Equipment Stop Status reports stop/auto; no BAS start/stop command is listed.

Does the Trane Symbio 800 IntelliPak need a BACnet heartbeat or have a communication timeout?

The points list gives a 900 s heartbeat for the sensor BAS values (AV 10111, 10113-10116, 10118, 10119) and the External setpoints (AV 10183-10187). The Symbio 800 integration guide doesn't describe what happens when it expires.

Can the BMS supply sensor values to the Trane Symbio 800 IntelliPak?

Write BMS values to the '... BAS' AVs (AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS, AV 10119 Space Humidity BAS, AV 10118 Space CO2 Concentration BAS, AV 10111 Discharge Air Temperature BAS). The '... Arbitrator' AVs show all sources in their priority array; the guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor. Direct capacity/fan/damper control uses the 'Setpoint External' AVs together with their 'Setpoint Enable External' BVs (e.g. AV 10187 with BV 10131).

How do I check these points on the real Symbio 800 IntelliPak?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists