Air-cooled screw chiller controller · BACnet points list

Trane Symbio 800 RTAC (UC800) BACnet points list

Updated 28 October 2026

Short answer

A Symbio 800 list of about 335 objects for RTAC chillers marked UC800, with small instance numbers. About 240 are diagnostic binary inputs (BI 500 and up); the rest are temperatures, pressures, motor currents and run data. The BAS writes chilled water setpoint and current limit (AV), auto/stop and mode (MV) and diagnostic reset (BV).

This page lists 335 BACnet objects for the Trane Symbio 800 RTAC (UC800) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 RTAC (UC800)
Equipment
Air-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
335 (5 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032
Source document
Symbio 800 Integration Points List BACnet - RTAC (UC800) · BAS-PTS032A-EN · rev. 12/6/2024
Download CSV 335 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 RTAC (UC800)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, current limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. The alarm-present flag gives a single summary alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1BAS Chiller Auto Stop CommandBMS auto/stop command (1 = Stop, 2 = Auto)Write
MV 2BAS Chiller Mode CommandCool/ice mode commandWrite
AV 1BAS Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 2BAS Current Limit SetpointCurrent limit from the BMS, % RLAWrite
BI 4Chiller Running IndicatorChiller on/off statusRead
BI 2Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 45Evaporator Leaving Water TempLeaving chilled water temperatureRead
AI 5Actual Running CapacityActual running capacity in percentRead
BI 23Alarm PresentAny active alarm on the chillerRead

Enable & remote start

MV 1 BAS Chiller Auto Stop Command (1 = Stop, 2 = Auto; relinquish default Auto) is the BMS auto/stop. BI 1 Run Enabled shows stop/auto. The document doesn't say how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Heartbeat & communication loss

No timeout or heartbeat is described. BI 742 'Comm Loss: Local BAS Interface' is a diagnostic flag; the document doesn't say what the chiller does when it is set.

Network setup

Watch out for

Trane Symbio 800 RTAC (UC800) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

335 of 335 shown
Type
Access
Show
Trane Symbio 800 RTAC (UC800) BACnet Points List
DescriptionStates
AI1Active Chilled Water SetpointRead
AI2Active Current Limit SetpointRead
AImin5Actual Running CapacityRead
AI6Evaporator Refrigerant Pressure - Ckt1Read
AI9Evaporator Refrigerant Pressure - Ckt 2Read
AI12Evaporator Saturated Refrigerant Temperature- Ckt 1Read
AI14Evaporator Saturated Refrigerant Temperature- Ckt 2Read
AI16Condenser Refrigerant Pressure - Ckt 1Read
AI18Condenser Refrigerant Pressure - Ckt 2Read
AI20Condenser Saturated Refrigerant Temperature - Ckt 1Read
AI22Condenser Saturated Refrigerant Temperature - Ckt 2Read
AI25Local Atmospheric PressureRead
AI26Starts- Compressor 1ARead
AI27Starts- Compressor 1BRead
AI28Starts- Compressor 2ARead
AI29Starts- Compressor 2BRead
AI34Run Time- Compressor 1ARead
AI35Run Time- Compressor 1BRead
AI36Run Time- Compressor 2ARead
AI37Run Time- Compressor 2BRead
AI42Airflow Percentage- Circuit 1Read
AI43Airflow Percentage- Circuit 2Read
AI44Evaporator Entering Water TempRead
AImin45Evaporator Leaving Water TempRead
AI48High Side Oil Pressure - Compressor 1ARead
AI49High Side Oil Pressure - Compressor 1BRead
AI50High Side Oil Pressure - Compressor 2ARead
AI51High Side Oil Pressure - Compressor 2BRead
AI52Oil Temp - Compressor 1ARead
AI53Oil Temp - Compressor 1BRead
AI54Oil Temp - Compressor 2ARead
AI55Oil Temp - Compressor 2BRead
AI57Outdoor Air TemperatureRead
AI59Motor Voltage AB Starter 1ARead
AI60Motor Voltage AB Starter 1BRead
AI61Motor Voltage AB Starter 2ARead
AI71Motor Current L1 Starter 1ARead
AI72Motor Current L2 Starter 1ARead
AI73Motor Current L3 Starter 1ARead
AI74Motor Current L1 Starter 1BRead
AI75Motor Current L2 Starter 1BRead
AI76Motor Current L3 Starter 1BRead
AI77Motor Current L1 Starter 2ARead
AI78Motor Current L2 Starter 2ARead
AI79Motor Current L3 Starter 2ARead
AI80Motor Current L1 Starter 2BRead
AI81Motor Current L2 Starter 2BRead
AI82Motor Current L3 Starter 2BRead
AI83Motor Current L1 % RLA Starter 1ARead
AI84Motor Current L2 % RLA Starter 1ARead
AI85Motor Current L3 % RLA Starter 1ARead
AI86Motor Current L1 % RLA Starter 1BRead
AI87Motor Current L2 % RLA Starter 1BRead
AI88Motor Current L3 % RLA Starter 1BRead
AI89Motor Current L1 % RLA Starter 2ARead
AI90Motor Current L2 % RLA Starter 2ARead
AI91Motor Current L3 % RLA Starter 2ARead
AI92Motor Current L1 % RLA Starter 2BRead
AI93Motor Current L2 % RLA Starter 2BRead
AI94Motor Current L3 % RLA Starter 2BRead
AI95Number of CircuitsRead
AI96Number of Compressors, Ckt 1Read
AI97Number of Compressors, Ckt 2Read
AI98Chiller Design CapacityRead
AI100Output Power AFD 1ARead
AI101Output Power AFD 2ARead
AI102Discharge Temperature Cprsr 1ARead
AI103Discharge Temperature Cprsr 2ARead
AI106Frequency Command Cprsr 1ARead
AI107Frequency Command Cprsr 2ARead
AI108Average Motor Current % RLA AFD 1ARead
AI109Average Motor Current % RLA AFD 2ARead
AVmin1BAS Chilled Water SetpointWrite
AVmin2BAS Current Limit SetpointWrite
BI1Run EnabledRead0 = Stop, 1 = Auto
BImin2Local Setpoint ControlRead0 = Remote, 1 = Local
BI3Chiller Limit Mode IndicatorRead0 = Not limited, 1 = Limited
BImin4Chiller Running IndicatorRead0 = Off, 1 = On
BI6Maximum CapacityRead0 = Off, 1 = On
BI9Compressor 1A RunningRead0 = Off, 1 = Running
BI10Compressor 1B RunningRead0 = Off, 1 = Running
BI11Compressor 2A RunningRead0 = Off, 1 = Running
BI12Compressor 2B RunningRead0 = Off, 1 = Running
BI17Evaporator Water Pump CommandRead0 = Off, 1 = On
BI22Evaporator Water Flow StatusRead0 = No flow, 1 = Flow
BImin23Alarm PresentRead0 = No alarm, 1 = Alarm
BI24Shutdown Alarm PresentRead0 = No alarm, 1 = Alarm
BI500AFD Fault – 1ARead
BI502AFD Fault–2ARead
BI504AFD Motor Current Overload – 1ARead
BI506AFD Motor Current Overload – 2ARead
BI508AFD Interrupt Failure – 1ARead
BI510AFD Interrupt Failure – 2ARead
BI512Starter Did Not Transition - 1ARead
BI513Starter Did Not Transition - 1BRead
BI514Starter Did Not Transition - 2ARead
BI515Starter Did Not Transition - 2BRead
BI516Phase Reversal - 1ARead
BI517Phase Reversal - 1BRead
BI518Phase Reversal - 2ARead
BI519Phase Reversal - 2BRead
BI520Starter Dry Run Test - 1ARead
BI521Starter Dry Run Test- 1BRead
BI522Starter Dry Run Test - 2ARead
BI523Starter Dry Run Test - 2BRead
BI524Phase Loss - 1ARead
BI525Phase Loss - 1BRead
BI526Phase Loss-2ARead
BI527Phase Loss-2BRead
BI528Power Loss - 1ARead
BI529Power Loss - 1BRead
BI530Power Loss - 2ARead
BI531Power Loss - 2BRead
BI532Severe CurrentPhase UnbalanceImbalance - Cprsr 1ARead
BI533Severe CurrentPhase UnbalanceImbalance - Cprsr 1BRead
BI534Severe CurrentPhase UnbalanceImbalance - Cprsr 2ARead
BI535Severe CurrentPhase UnbalanceImbalance - Cprsr 2BRead
BI536Starter Fault Type I – 1ARead
BI537Starter Fault Type I – 1BRead
BI538Starter Fault Type I – 2ARead
BI539Starter Fault Type I –2BRead
BI540Starter Fault Type II – 1ARead
BI541Starter Fault Type II –1BRead
BI542Starter Fault Type II –2ARead
BI543Starter Fault Type II – 2BRead
BI544Starter Fault Type III – 1ARead
BI545Starter Fault Type III –1BRead
BI546Starter Fault Type III –2ARead
BI547Starter Fault Type III –2BRead
BI548Transition Complete Input Shorted –1ARead
BI549Transition Complete Input Shorted –1BRead
BI550Transition Complete Input Shorted –2ARead
BI551Transition Complete Input Shorted –2BRead
BI552Transition Complete Input Opened –1ARead
BI553Transition Complete Input Opened –1BRead
BI554Transition Complete Input Opened –2ARead
BI555Transition Complete Input Opened –2BRead
BI556Motor Current Overload Trip - Cprsr 1ARead
BI557Motor Current Overload Trip - Cprsr 1BRead
BI558Motor Current Overload Trip - Cprsr 2ARead
BI559Motor Current Overload Trip - Cprsr 2BRead
BI560Starter Contactor Interrupt Failure - 1ARead
BI561Starter Contactor Interrupt Failure - 1BRead
BI562Starter Contactor Interrupt Failure - 2ARead
BI563Starter Contactor Interrupt Failure - 2BRead
BI564Over VoltageRead
BI565Under VoltageRead
BI566MP: Reset Has OccurredRead
BI567Low Evaporator Rfgt Temperature - Ckt1Read
BI568Low Evaporator Rfgt Temperature - Ckt2Read
BI569Low Oil Flow - Cprsr 1ARead
BI570Low Oil Flow - Cprsr 1BRead
BI571Low Oil Flow- Cprsr 2ARead
BI572Low Oil Flow - Cprsr 2BRead
BI573Low Differential Rfgt Pressure - Ckt1Read
BI574Low Differential Rfgt Pressure - Ckt2Read
BI575High Differential Rfgt Pressure - Ckt1Read
BI576High Differential Rfgt Pressure - Ckt2Read
BI577High Oil Temperature – 1ARead
BI578High Oil Temperature –1BRead
BI579High Oil Temperature –2ARead
BI580High Oil Temperature – 2BRead
BI581Oil Temperature Sensor – 1ARead
BI582Oil Temperature Sensor – 1BRead
BI583Oil Temperature Sensor–2ARead
BI584Oil Temperature Sensor–2BRead
BI585Evaporator Liquid Level Sensor– Ckt1Read
BI586Evaporator Liquid Level Sensor– Ckt2Read
BI587Condenser Fan VFD Fault - Ckt 1 Dr 1Read
BI588Condenser Fan VFD Fault - Ckt1 Dr 2Read
BI589Condenser Fan VFD Fault - Ckt2 Dr 1Read
BI590Condenser Fan VFD Fault - Ckt2 Dr 2Read
BI593Low Evaporator Liquid Level – Ckt1Read
BI594Low Evaporator Liquid Level – Ckt2Read
BI595High Evaporator Liquid Level – Ckt1Read
BI596High Evaporator Liquid Level – Ckt2Read
BI597Evaporator Rfgt Drain – Circuit 1Read
BI598Evaporator Rfgt Drain – Circuit 2Read
BI599External Chilled Water SetpointRead
BI600External Current Limit SetpointRead
BI601Evap Water Flow (Entering Water Temp)Read
BI602Evaporator Entering Water Temp SensorRead
BI603Evaporator Leaving Water Temp SensorRead
BI604Condenser Rfgt Pressure Transducer - Ckt1Read
BI605Condenser Rfgt Pressure Transducer - Ckt2Read
BI606Suction Refrigerant Pressure Sensor- 1ARead
BI607Suction Refrigerant Pressure Sensor - 1BRead
BI608Suction Refrigerant Pressure Sensor - 2ARead
BI609Suction Refrigerant Pressure Sensor - 2BRead
BI610Intermediate Oil Press Xdcr - Cprsr 1ARead
BI611Intermediate Oil Press Xdcr - Cprsr 1BRead
BI612Intermediate Oil Press Xdcr - Cprsr 2ARead
BI613Intermediate Oil Press Xdcr - Cprsr 2BRead
BI614Oil Flow Protection Fault - 1ARead
BI615Oil Flow Protection Fault - 1BRead
BI616Oil Flow Protection Fault - 2ARead
BI617Oil Flow Protection Fault - 2BRead
BI618Low Suction Rfgt Pressure – Ckt 1Read
BI620Low Suction Rfgt Pressure – Ckt 2Read
BI622Very Low Evaporator Rfgt Pressure - Ckt1Read
BI623Very Low Evaporator Rfgt Pressure - Ckt2Read
BI624Pumpdown Terminated - Ckt1Read
BI625Pumpdown Terminated - Ckt2Read
BI626Low Evaporator Water Temp (Unit Off)Read
BI627Low Evaporator Temp (Unit Off) - Ckt1Read
BI628Low Evaporator Temp (Unit Off) - Ckt2Read
BI629Low Evap Leaving Water Temp: Unit OnRead
BI630Evaporator Water Flow OverdueRead
BI631Evaporator Water Flow LostRead
BI632High Evaporator Refrigerant PressureRead
BI633High Evaporator Water TemperatureRead
BI634High Pressure Cutout - Cprsr 1ARead
BI635High Pressure Cutout - Cprsr 1BRead
BI636High Pressure Cutout - Cprsr 2ARead
BI637High Pressure Cutout - Cprsr 2BRead
BI638Emergency StopRead
BI639Outdoor Air Temperature SensorRead
BI640Starter Panel Thermostat Cutout - 2ARead
BI641Starter Panel Thermostat Cutout - 1BRead
BI642Starter Panel Thermostat Cutout - 2BRead
BI643Starter Module Memory Error Type 1 - 1ARead
BI644Starter Module Memory Error Type 1 - 1BRead
BI645Starter Module Memory Error Type 1 - 2ARead
BI646Starter Module Memory Error Type 1 - 2BRead
BI647Starter Module Memory Error Type 2 - 1ARead
BI648Starter Module Memory Error Type 2 - 1BRead
BI649Starter Module Memory Error Type 2 - 2ARead
BI650Starter Module Memory Error Type 2 - 2BRead
BI651MP: Invalid ConfigurationRead
BI652MP Application Memory CRC ErrorRead
BI653MP: Non-Volatile Memory ReformattedRead
BI654Check ClockRead
BI655MP: Could not Store Starts and HoursRead
BI656MP: Non-Volatile Block Test ErrorRead
BI657Starter Failed to Arm/Start - 1ARead
BI658Starter Failed to Arm/Start - 1BRead
BI659Starter Failed to Arm/Start - 2ARead
BI660Starter Failed to Arm/Start - 2BRead
BI661Software Error 1001: Call Trane ServiceRead
BI662Software Error 1002: Call Trane ServiceRead
BI663Software Error 1003: Call Trane ServiceRead
BI664Excessive IPC Comm LossRead
BI665Comm Loss: Slide Valve Unload - 1ARead
BI666Comm Loss: Slide Valve Load - 1ARead
BI667Comm Loss: Slide Valve Unload - 1BRead
BI668Comm Loss: Slide Valve Load - 1BRead
BI669Comm Loss: Slide Valve Unload - 2ARead
BI670Comm Loss: Slide Valve Load - 2ARead
BI671Comm Loss: Slide Valve Unload - 2BRead
BI672Comm Loss: Slide Valve Load - 2BRead
BI673Comm Loss: Step Load - 1ARead
BI674Comm Loss: Step Load - 1BRead
BI675Comm Loss: Step Load - 2ARead
BI676Comm Loss: Step Load - 2BRead
BI677Comm Loss: External Auto/StopRead
BI678Comm Loss: Emergency StopRead
BI679Comm Loss: External Ckt Lockout - Ckt1Read
BI680Comm Loss: External Ckt Lockout - Ckt2Read
BI681Comm Loss: External Ice Building CommandRead
BI682Comm Loss: Outdoor Air TemperatureRead
BI683Comm Loss: Evap Leaving Water TempRead
BI684Comm Loss: Evap Entering Water TempRead
BI685Comm Loss: Oil Temperature – 1A’Read
BI686Comm Loss: Oil Temperature – 1B’Read
BI687Comm Loss: Oil Temperature – 2A’Read
BI688Comm Loss: Oil Temperature – 2B’Read
BI689Comm Loss: Ext Chilled Water SetpointRead
BI690Comm Loss: Ext Current Limit SetpointRead
BI691Comm Loss: High Pressure Cutout Sw - 1ARead
BI692Comm Loss: High Pressure Cutout Sw - 1BRead
BI693Comm Loss: High Pressure Cutout Sw - 2ARead
BI694Comm Loss: High Pressure Cutout Sw - 2BRead
BI695Comm Loss: Evaporator Water Flow SwitchRead
BI696Comm Loss: Condenser Rfgt Pressure - Ckt1Read
BI697Comm Loss: Condenser Rfgt Pressure - Ckt2Read
BI698Comm Loss: Intermediate Oil Pressure - 1ARead
BI699Comm Loss: Intermediate Oil Pressure - 1BRead
BI700Comm Loss: Intermediate Oil Pressure - 2ARead
BI701Comm Loss: Intermediate Oil Pressure - 2BRead
BI702Comm Loss: Evaporator Water Pump RelayRead
BI703Comm Loss: Ice Building Status RelayRead
BI704Comm Loss: Suction Rfgt Pressure - 1ARead
BI705Comm Loss: Suction Rfgt Pressure - 1BRead
BI706Comm Loss: Suction Rfgt Pressure - 2ARead
BI707Comm Loss: Suction Rfgt Pressure - 2BRead
BI708Comm Loss: Fan Control Ckt1, Stage 1Read
BI709Comm Loss: Fan Control Ckt1, Stage 2Read
BI710Comm Loss: Fan Control Ckt1, Stage 3Read
BI711Comm Loss: Fan Control Ckt1, Stage 4Read
BI712Comm Loss: Fan Control Ckt2, Stage 1Read
BI713Comm Loss: Fan Control Ckt2, Stage 2Read
BI714Comm Loss: Fan Control Ckt2, Stage 3Read
BI715Comm Loss: Fan Control Ckt2, Stage 4Read
BI716Comm Loss: Evap Rfgt Liquid Level - Ckt1Read
BI717Comm Loss: Evap Rfgt Liquid Level - Ckt2Read
BI718Comm Loss: Fan Inverter Power- Ckt1Read
BI719Comm Loss: Fan Inverter Speed Cmd - Ckt1Read
BI720Comm Loss: Fan Inv Fault, Ckt1, Dr 1Read
BI721Comm Loss: Fan Inv Fault, Ckt1, Dr 2Read
BI722Comm Loss: Oil Return Solenoid Valve - 1ARead
BI723Comm Loss: Oil Return Solenoid Valve - 2ARead
BI724Comm Loss: Oil Return Solenoid Valve - 1BRead
BI725Comm Loss: Oil Return Solenoid Valve - 2BRead
BI726Comm Loss: Starter 1ARead
BI727Comm Loss: Starter 1BRead
BI728Comm Loss: Starter 2ARead
BI729Comm Loss: Starter 2BRead
BI730Comm Loss: Electronic Expansion Valve 1Read
BI731Comm Loss: Electronic Expansion Valve 2Read
BI734Comm Loss: Fan Inverter Power - Ckt2Read
BI735Comm Loss: Fan Inverter Speed Cmd - Ckt2Read
BI736Comm Loss: Fan Inv Fault, Ckt 2, Dr 1Read
BI737Comm Loss: Fan Inv Fault, Ckt 2, Dr 2Read
BI738Starter 1A Loss of Comm with MPRead
BI739Starter 1B Loss of Comm with MPRead
BI740Starter 2A Loss of Comm with MPRead
BI741Starter 2B Loss of Comm with MPRead
BI742Comm Loss: Local BAS InterfaceRead
BI743Comm Loss: Programmable Relay Board 1Read
BI744Starter Panel Thermostat Comm Loss 2ARead
BI745Starter Panel Thermostat Comm Loss 1BRead
BI746Starter Panel Thermostat Comm Loss 2BRead
BI747Comm Loss: Evap Rfgt Drain Valve - Ckt1Read
BI748Comm Loss: Evap Rfgt Drain Valve - Ckt2Read
BI749Comm Loss: AFD 1ARead
BI750Comm Loss: AFD 2ARead
BV2BAS Diagnostic ResetWrite0 = false (no reset), 1 = true (can reset)
MI1Chiller Running StatusRead1 = Chiller off, 2 = Chiller in start mode, 3 = Chiller in run mode, 4 = Chiller in pre-shutdown mode
MI2Operating ModeRead1 = Cool, 3 = Ice
MI4Refrigerant TypeRead5 = R134a, 15 = R514A
MI5Model InformationRead1 = RTA
MI6Cooling TypeRead2 = Air cooled
MI7Manufacturing LocationRead1 = Field Applied, 3 = Pueblo, 4 = Charmes, 14 = Curitiba, 15 = Taicang, 17 = Epinal, 18 = Golbey
MVmin1BAS Chiller Auto Stop CommandWrite1 = Stop, 2 = Auto
MVmin2BAS Chiller Mode CommandWrite1 = Cool, 3 = Ice

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 RTAC (UC800) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 RTAC (UC800)

How many BACnet points does the Trane Symbio 800 RTAC (UC800) have?

This list has 335 BACnet objects: 72 analog inputs, 2 analog values, 252 binary inputs, 1 binary value, 6 multi-state inputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 RTAC (UC800) BACnet points are writable?

5 of the 335 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 RTAC (UC800) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - RTAC (UC800) (BAS-PTS032A-EN), revision 12/6/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS032A-EN_12062024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 RTAC (UC800)?

Start with MV 1 BAS Chiller Auto Stop Command (BMS auto/stop command (1 = Stop, 2 = Auto)); MV 2 BAS Chiller Mode Command (Cool/ice mode command); AV 1 BAS Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 2 BAS Current Limit Setpoint (Current limit from the BMS, % RLA); BI 4 Chiller Running Indicator (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 45 Evaporator Leaving Water Temp (Leaving chilled water temperature); AI 5 Actual Running Capacity (Actual running capacity in percent); BI 23 Alarm Present (Any active alarm on the chiller).

How do I enable BMS control of the Trane Symbio 800 RTAC (UC800)?

MV 1 BAS Chiller Auto Stop Command (1 = Stop, 2 = Auto; relinquish default Auto) is the BMS auto/stop. BI 1 Run Enabled shows stop/auto. The document doesn't say how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Does the Trane Symbio 800 RTAC (UC800) need a BACnet heartbeat or have a communication timeout?

No timeout or heartbeat is described. BI 742 'Comm Loss: Local BAS Interface' is a diagnostic flag; the document doesn't say what the chiller does when it is set.

How do I check these points on the real Symbio 800 RTAC (UC800)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - RTAC (UC800) · BAS-PTS032A-EN · rev. 12/6/2024. Object names, instances and units are reproduced as published; descriptions are our own.