Easy BACnet
  1. Home
  2. BACnet points lists
  3. Trane
  4. Symbio 800 Ascend ACR Series C

Air-cooled chiller controller · BACnet points list

Trane Symbio 800 Ascend ACR Series C BACnet points list

Updated 28 October 2026

Short answer

Ascend ACR Series C chillers with Symbio 800 publish about 770 BACnet objects; roughly 550 are diagnostic binary inputs. AIs cover water temperatures and pressures, refrigerant circuits, compressor drives, free cooling and power metering. The BAS writes chilled water setpoint, demand limit, pump speed or flow setpoints, mode, lockouts and auto/stop.

This page lists 772 BACnet objects for the Trane Symbio 800 Ascend ACR Series C — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 Ascend ACR Series C
Equipment
Air-cooled chiller controller
Equipment type
Chillers
BACnet objects
772 (15 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021
Source document
Symbio 800 Integration Points List BACnet - Ascend Model ACR Series C · BAS-PTS021A-EN · rev. 11/15/2024
Download CSV 772 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 Ascend ACR Series C

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10108Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10103Chiller Running StateChiller on/off statusRead
BI 10101Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10104Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10180Actual Running CapacityActual running capacity in percentRead
BI 10116Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10108 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10124 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10106 Chiller Setpoint Source shows BAS, External or Front Panel.

Network setup

Watch out for

Trane Symbio 800 Ascend ACR Series C BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

772 of 772 shown
Type
Access
Show
Trane Symbio 800 Ascend ACR Series C BACnet Points List
DescriptionStates
AI10100Active Chilled Water SetpointValue of the active Chilled Water Setpoint actively beingTemperatureRead
AI10101Active Demand Limit SetpointWith Ice Building not InstalledPercentageRead
AI10103Evaporator Entering Water TemperatureCurrent temperature of the water entering the evaporatorTemperatureRead
AImin10104Evaporator Leaving Water TemperatureCurrent temperature of the water leaving the evaporatorTemperatureRead
AI10106Unit Power ConsumptionMeasurement of the power being consumed by the ChillerPower, ElectricalRead
AI10107Outdoor Air TemperatureCurrent temperature of the outdoor airTemperatureRead
AI10110Evaporator Refrigerant Pressure Circuit 1Current pressure of the refrigerant in the evaporator on circuit 1Pressure, FluidicRead
AI10111Condenser Refrigerant Pressure Circuit 1Current pressure of the refrigerant in the condenser on circuit 1Pressure, FluidicRead
AI10112Differential Refrigerant Pressure Circuit 1Pressure difference between the suction and discharge lines on circuit 1Pressure, FluidicRead
AI10113Evaporator Saturated Refrigerant Temperature Circuit 1Saturated refrigerant temperature of the evaporator on circuit 1TemperatureRead
AI10114Condenser Saturated Refrigerant Temperature Circuit 1Saturated refrigerant temperature of the condenser on circuit 1TemperatureRead
AI10115Evaporator Refrigerant Pressure Circuit 2Current pressure of the refrigerant in the evaporator on circuit 2Pressure, FluidicRead
AI10116Condenser Refrigerant Pressure Circuit 2Current pressure of the refrigerant in the condenser on circuit 2Pressure, FluidicRead
AI10117Differential Refrigerant Pressure Circuit 2Pressure difference between the suction and discharge lines on circuit 2Pressure, FluidicRead
AI10118Evaporator Saturated Refrigerant Temperature Circuit 2Saturated refrigerant temperature of the evaporator on circuit 2TemperatureRead
AI10119Condenser Saturated Refrigerant Temperature Circuit 2Saturated refrigerant temperature of the condenser on circuit 2TemperatureRead
AI10120Refrigerant Discharge Temperature - Compressor 1ACurrent temperature of the refrigerant being discharged from Compressor 1ATemperatureRead
AI10121High Side Oil Pressure - Compressor 1APressure of the oil on the high pressure side of Compressor 1APressure, FluidicRead
AI10122Refrigerant Discharge Temperature - Compressor 2ACurrent temperature of the refrigerant being discharged from Compressor 2ATemperatureRead
AI10123High Side Oil Pressure - Compressor 2APressure of the oil on the high pressure side of Compressor 2APressure, FluidicRead
AI10124Air Flow Percentage Circuit 1Approximate air flow percentage of Circuit 1PercentageRead
AI10125Air Flow Percentage Circuit 2Approximate air flow percentage of Circuit 2PercentageRead
AI10126Drive Motor Average Voltage Circuit 1Average voltage line to line at AFD for Compressor 1AVoltageRead
AI10127Drive Motor Current U Circuit 1CurrentRead
AI10128Drive Motor Current V Circuit 1CurrentRead
AI10129Drive Motor Current W Circuit 1CurrentRead
AI10130Drive Motor Current U RLA Circuit 1PercentageRead
AI10131Drive Motor Current V RLA Circuit 1PercentageRead
AI10132Drive Motor Current W RLA Circuit 1PercentageRead
AI10133Drive Motor Average Current RLA Circuit 1Average current at AFD for Compressor 1A in terms of % RLAPercentageRead
AI10134Drive DC Bus Voltage Circuit 1Voltage of the DC Bus from the AFD for Compressor 1AVoltageRead
AI10135Drive Output Power Circuit 1Power output from the AFD for Compressor 1APower, ElectricalRead
AI10136AFD Transistor Temperature Circuit 1Temperature of the transistor for the AFD for Compressor 1ATemperatureRead
AI10137Motor Winding Temperature 1 Circuit 1First temperaure sensor of the windings on motor 1ATemperatureRead
AI10138Motor Winding Temperature 2 Circuit 1Second temperaure sensor of the windings on motor 1ATemperatureRead
AI10139Drive Motor Average Voltage Circuit 2Average voltage line to line at AFD for Compressor 2AVoltageRead
AI10140Drive Motor Current U Circuit 2CurrentRead
AI10141Drive Motor Current V Circuit 2CurrentRead
AI10142Drive Motor Current W Circuit 2CurrentRead
AI10143Drive Motor Current U RLA Circuit 2PercentageRead
AI10144Drive Motor Current V RLA Circuit 2PercentageRead
AI10145Drive Motor Current W RLA Circuit 2PercentageRead
AI10146Drive Motor Average Current RLA Circuit 2Average current at AFD for Compressor 2A in terms of % RLAPercentageRead
AI10147Drive DC Bus Voltage Circuit 2Voltage of the DC Bus from the AFD for Compressor 2AVoltageRead
AI10148Drive Output Power Circuit 2Power output from the AFD for Compressor 2APower, ElectricalRead
AI10149AFD Transistor Temperature Circuit 2Temperature of the transidtor for the AFD for Compressor 2ATemperatureRead
AI10150Motor Winding Temperature 1 Circuit 2First temperaure sensor of the windings on motor 2ATemperatureRead
AI10151Motor Winding Temperature 2 Circuit 2Second temperaure sensor of the windings on motor 2ATemperatureRead
AI10152Sub Cooled Liquid Temperature Circuit 1Sub cooled liquid temperature of circuit 1TemperatureRead
AI10153Sub Cooled Liquid Temperature Circuit 2Sub cooled liquid temperature of circuit 2TemperatureRead
AI10154Evaporator Differential Water PressureDifferential water pressure of the evaporator; with Variable Primary FlowTemperatureRead
AI10155System Chilled Water Differential PressureDifferential water pressure of the chilled water systemPressure, FluidicRead
AI10158Phase AB Voltage - Compressor 1BMeasurement of voltage in Phase AB for Compressor 1BVoltageRead
AI10159Line 1 Current - Compressor 1BMeasurement of Line 1 current for Compressor 1B in terms of AmpsCurrentRead
AI10160Line 2 Current - Compressor 1BMeasurement of Line 2 current for Compressor 1B in terms of AmpsCurrentRead
AI10161Line 3 Current - Compressor 1BMeasurement of Line 3 current for Compressor 1B in terms of AmpsCurrentRead
AI10162Line 1 Current RLA - Compressor 1BPercentageRead
AI10163Line 2 Current RLA - Compressor 1BPercentageRead
AI10164Line 3 Current RLA - Compressor 1BPercentageRead
AI10165Phase AB Voltage - Compressor 2BMeasurement of voltage in Phase AB for Compressor 2BVoltageRead
AI10166Line 1 Current - Compressor 2BMeasurement of Line 1 current for Compressor 2B in terms of AmpsCurrentRead
AI10167Line 2 Current - Compressor 2BMeasurement of Line 2 current for Compressor 2B in terms of AmpsCurrentRead
AI10168Line 3 Current - Compressor 2BMeasurement of Line 3 current for Compressor 2B in terms of AmpsCurrentRead
AI10169Line 1 Current RLA - Compressor 2BPercentageRead
AI10170Line 2 Current RLA - Compressor 2BPercentageRead
AI10171Line 3 Current RLA - Compressor 2BPercentageRead
AI10173Refrigerant Discharge Temperature - Compressor 1BCurrent temperature of the refrigerant being discharged from Compressor 1BTemperatureRead
AI10174High Side Oil Pressure - Compressor 1BPressure of the oil on the high pressure side of Compressor 1BPressure, FluidicRead
AI10175Refrigerant Discharge Temperature - Compressor 2BCurrent temperature of the refrigerant being discharged from Compressor 2BTemperatureRead
AI10176High Side Oil Pressure - Compressor 2BPressure of the oil on the high pressure side of Compressor 2BPressure, FluidicRead
AI10177Number of CircuitsNumber of refrigeration circuits in the chillerRead
AI10178Number of Compressors Circuit 1Number of compressors on circuit 1 of the chillerRead
AI10179Number of Compressors Circuit 2Number of compressors on circuit 2 of the chillerRead
AImin10180Actual Running CapacityMeasurement of the power being consumed by the ChillerPercentageRead
AI10181Free Cooling Capacity Status% capacity of the free cooling being usedPercentageRead
AI10182Free Cooling Entering Water Temperature ActiveEntering water temperature of the free cooling circuitTemperatureRead
AI10185Evaporator Differential Water Pressure Setpoint StatusSetpoint status of the evaporator differential water pressurePressure, FluidicRead
AI10186Energy Consumption LifetimeTotal energy consumption of the chiller (for the lifetime of the chiller)Energy, ElectricalRead
AI10187Energy ConsumptionTotal energy consumption of the chiller (since last accumulation reset)Energy, ElectricalRead
AI10188Starts - Compressor 1ANumber of starts of Compressor 1ARead
AI10189Run Time - Compressor 1ARun time of Compressor 1A in secondsRead
AI10190Starts - Compressor 2ANumber of starts of Compressor 2ARead
AI10191Run Time - Compressor 2ARun time of Compressor 2A in secondsRead
AI10192Starts - Compressor 1BNumber of starts of Compressor 1BRead
AI10193Run Time - Compressor 1BRun time of Compressor 1B in secondsRead
AI10194Starts - Compressor 2BNumber of starts of Compressor 2BRead
AI10195Run Time - Compressor 2BRun time of Compressor 2B in secondsRead
AI10196Chiller Design CapacityDesign capacity of chilllerPower, CoolingRead
AI10198Chilled Water Setpoint StatusChilled water setpoint temperatureTemperatureRead
AI10199Demand Limit Setpoint Status% capacity of the demand limit being usedPercentageRead
AI10200Unit Source IDLast diagnostic of the chillerRead
AI10201Drive Input Voltage Calculated 1AInput voltage at the AFD for Compressor 1AVoltageRead
AI10202Drive Input Voltage Calculated 2AInput voltage at the AFD for Compressor 2AVoltageRead
AI10203Active Cool/Heat Setpoint TemperatureValue of the active Chilled Water Setpoint actively beingTemperatureRead
AI10204Phase BC Voltage - Compressor 1BMeasurement of voltage in Phase BC for Compressor 1BVoltageRead
AI10205Phase CA Voltage - Compressor 1BMeasurement of voltage in Phase CA for Compressor 1BVoltageRead
AI10206Phase BC Voltage - Compressor 2BMeasurement of voltage in Phase BC for Compressor 2BVoltageRead
AI10207Phase CA Voltage - Compressor 2BMeasurement of voltage in Phase CA for Compressor 2BVoltageRead
AI10208Average Line Current Circuit 1Average current, reported in Circuit 1CurrentRead
AI10209Average Line Current Circuit 2Average current, reported in Circuit 2CurrentRead
AI10210Average Line Voltage Circuit 1Average voltage, line-to-line reported in Circuit 1VoltageRead
AI10211Average Line Voltage Circuit 2Average voltage, line-to-line reported in Circuit 2VoltageRead
AI10212Line Current L1 Circuit 1Current for line/leg 1 of Circuit 1CurrentRead
AI10213Line Current L2 Circuit 1Current for line/leg 2 of Circuit 1CurrentRead
AI10214Line Current L3 Circuit 1Current for line/leg 3 of Circuit 1CurrentRead
AI10215Line Current L1 Circuit 2Current for line/leg 1 of Circuit 2CurrentRead
AI10216Line Current L2 Circuit 2Current for line/leg 2 of Circuit 2CurrentRead
AI10217Line Current L3 Circuit 2Current for line/leg 3 of Circuit 2CurrentRead
AI10218Voltage L1-L2 Circuit 1Voltage between line/leg L1 and L2 of Circuit 1VoltageRead
AI10219Voltage L2-L3 Circuit 1Voltage between line/leg L2 and L3 of Circuit 1VoltageRead
AI10220Voltage L1-L3 Circuit 1Voltage between line/leg L1 and L3 of Circuit 1VoltageRead
AI10221Voltage L1-L2 Circuit 2Voltage between line/leg L1 and L2 of Circuit 2VoltageRead
AI10222Voltage L2-L1 Circuit 2Voltage between line/leg L2 and L3 of Circuit 2VoltageRead
AI10223Voltage L1-L3 Circuit 2Voltage between line/leg L1 and L3 of Circuit 2VoltageRead
AI10224Total Real PowerTotal real power reportedPower, ElectricalRead
AI10225Line Frequency Circuit 1Estimated input frequency for Circuit 1Read
AI10226Line Frequency Circuit 2Estimated input frequency for Circuit 2Read
AI10227Power Factor Circuit 1Reported power factor for Circuit 1Read
AI10228Power Factor Circuit 2Reported power factor for Circuit 2Read
AI10229Power Demand Circuit 1Reported power demand for Circuit 1Power, ElectricalRead
AI10230Power Demand Circuit 2Reported power demand for Circuit 2Power, ElectricalRead
AI10231Evaporator Approach Temperature Circuit 1Evaporator approach temperature for circuit 1Temperature, DeltaRead
AI10232Evaporator Approach Temperature Circuit 2Evaporator approach temperature for circuit 2Temperature, DeltaRead
AI10233Discharge Superheat Compressor 1ADischarge superheat for compressor 1ATemperature, DeltaRead
AI10234Discharge Superheat Compressor 1BDischarge superheat for compressor 1BTemperature, DeltaRead
AI10235Discharge Superheat Compressor 2ADischarge superheat for compressor 2ATemperature, DeltaRead
AI10236Discharge Superheat Compressor 2BDischarge superheat for compressor 2BTemperature, DeltaRead
AI10237Evaporator Water Flow RateApproximate evaporator water flow rateFlow, FluidicRead
AI10238Evaporator Differential Water PressureWith Evap Water Flow Measurement Differential Pressure or Dual Pressure SensorsPressure, FluidicRead
AI10239Entering Evaporator Water PressureEvaporator entering water pressurePressure, FluidicRead
AI10240Leaving Evaporator Water PressureEvaporator leaving water pressurePressure, FluidicRead
AI10241Power FactorUnit power factorRead
AI10242Current L1Current for line/leg 1CurrentRead
AI10243Current L2Current for line/leg 2CurrentRead
AI10244Current L3Current for line/leg 3CurrentRead
AI10245Average CurrentAverage current reportedCurrentRead
AI10246Voltage L1-L2Voltage between line/leg L1 and L2VoltageRead
AI10247Voltage L2-L3Voltage between line/leg L2 and L3VoltageRead
AI10248Voltage L1-L3Voltage between line/leg L1 and L3VoltageRead
AI10249Average Voltage L-LAverage voltage, line-to-lineVoltageRead
AI10250Line FrequencyChiller line frequencyRead
AI10251AFD Coolant Supply Temperature Compressor 1AAFD cooling supply temperature for circuit 1TemperatureRead
AI10253AFD Coolant Supply Temperature Compressor 2AAFD cooling supply temperature for circuit 2TemperatureRead
AI10254Evaporator Water Pump Speed CommandPercentageRead
AI10255Evaporator Water Pump Speed FeedbackPercentageRead
AI10256Evaporator Water Pump Speed Setpoint ActiveT the active evaporator water pump speed setpointPercentageRead
AI10257Evaporator Water Pump Flow Rate Setpoint ActiveT the active evaporator water pump flow rate setpointFlow, FluidicRead
AI10258Free Cooling Dedicated Fans AirflowFree cooling dedicated fan air flowPercentageRead
AI10259Drive Heat Sink Temperature Compressor 1AHeatsink temperature for the circuit 1A AFDTemperatureRead
AI10260Drive Heat Sink Temperature Compressor 2AHeatsink temperature for the circuit 2A AFDTemperatureRead
AI10261Compressor 1A Speed StatusPercent speed status for compressor 1APercentageRead
AI10262Compressor 2A Speed StatusPercent speed status for compressor 2APercentageRead
AI10263Calculated Chiller CapacityPower, CoolingRead
AI10264Free Cooling Target OffsetTemperature, DeltaRead
AI10265Free Cooling Valve Position StatusFree cooling valve percent open positionPercentageRead
AI10266Active Demand Limit SetpointWith Ice BuildingPercentageRead
AI10267Evaporator Refrigerant Absolute Pressure Circuit 1Current absolute pressure of the refrigerant in the evaporator on circuit 1Pressure, FluidicRead
AI10268Condenser Refrigerant Absolute Pressure Circuit 1Current absolute pressure of the refrigerant in the condenser on circuit 1Pressure, FluidicRead
AI10269Evaporator Refrigerant Absolute Pressure Circuit 2Current absolute pressure of the refrigerant in the evaporator on circuit 2Pressure, FluidicRead
AI10270Condenser Refrigerant Absolute Pressure Circuit 2Current absolute pressure of the refrigerant in the condenser on circuit 2Pressure, FluidicRead
AI10271High Side Oil Absolute Pressure - Compressor 1APressure, FluidicRead
AI10272High Side Oil Absolute Pressure - Compressor 2APressure, FluidicRead
AI10273High Side Oil Absolute Pressure - Compressor 1BPressure, FluidicRead
AI10274High Side Oil Absolute Pressure - Compressor 2BPressure, FluidicRead
AI10275Entering Evaporator Water Absolute PressureAbsolute pressure of the entering evaporator waterPressure, FluidicRead
AI10276Leaving Evaporator Water Absolute PressureAbsolute pressure of the leaving evaporator waterPressure, FluidicRead
AVmin10100Chilled Water SetpointWritten by the BAS; goes through arbitration before useTemperatureWrite
AVmin10101Demand Limit SetpointWritten by the BAS; goes through arbitration before usePercentageWrite
AV10102Evaporator Water Pump Flow Rate Setpt BASBAS Evap Water Flow Rate SetptFlow, FluidicWrite
AV10103Evaporator Water Pump Speed Setpt BASBAS Evap Water Pump Speed SetptPercentageWrite
BI10100Run EnableThat chiller is available to run or is currently runningRead0 = Run Not Enabled, 1 = Run Enabled
BImin10101Local Setpoint ControlWhich setpoint is used for control purposes, Remote (BAS) or LocalRead0 = Remote Control, 1 = Local Control
BI10102Limit Mode Relay StatusStatus of the chiller limit relayRead0 = Off, 1 = On
BImin10103Chiller Running StateThe chiller is onRead0 = Off, 1 = On
BI10104Maximum CapacityStatus of the maximum capacity relayRead0 = Off, 1 = On
BI10106Manual Override ExistsD a manual override is presentRead0 = Off, 1 = On
BI10107Compressor 1A StatusRunning state of Compressor 1ARead0 = Off, 1 = Running
BI10108Compressor 2A StatusRunning state of Compressor 2ARead0 = Off, 1 = Running
BI10109Emergency StopStatus of the emergency stop function of the chillerRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10110Evaporator Water Pump RequestRequest from the chiller to turn on the Evaporator Water PumpRead0 = Off, 1 = On
BI10111Evaporator Water Flow StatusFlow of water through evaporatorRead0 = No Flow, 1 = Flow
BI10112Compressor 1B StatusRunning state of Compressor 1BRead0 = Off, 1 = Running
BI10113Compressor 2B StatusRunning state of Compressor 2BRead0 = Off, 1 = Running
BI10114Free Cooling ActiveD the free cooling mode is activeRead0 = Inactive, 1 = Active
BImin10116Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10117Diagnostic Shutdown PresentChiller is shut down due to diagnosticsRead0 = Normal, 1 = In Alarm
BI10118Diagnostic: Manual Reset RequiredWhen a diagnostic exists that requires manual resetRead0 = Normal, 1 = In Alarm
BI10119Diagnostic: Local Manual Reset RequiredWhen a diagnostic exists that requires manual reset [Local only]Read0 = Normal, 1 = In Alarm
BI10120Diagnostic Present: InformationDiagnostic present with Information CategoryRead0 = Normal, 1 = In Alarm
BI10121Diagnostic Present: AdvisoryDiagnostic present with Warning CategoryRead0 = Normal, 1 = In Alarm
BI10122Diagnostic Present: CriticalDiagnostic present with Critical CategoryRead0 = Normal, 1 = In Alarm
BI10123Diagnostic Present: Service RequiredDiagnostic present with Service Required CategoryRead0 = Normal, 1 = In Alarm
BI10124External Auto Stop Input StatusStatus of the externally-wired auto/stop inputRead0 = Stop, 1 = Auto
BI10125Front Panel Auto StopAuto/stop status of the Front PanelRead0 = Stop, 1 = Auto
BI10126Noise Reduction Request ActiveWherther Noise Reduction activeRead0 = Off, 1 = On
BI10127Circuit 1 Lockout Front PanelLockout state of Circuit 1 Comprosser from Front PanelRead0 = Normal, 1 = Locked Out
BI10128Circuit 2 Lockout Front PanelLockout state of Circuit 2 Comprosser from Front PanelRead0 = Normal, 1 = Locked Out
BI10129Circuit 1 Lockout ExternalLockout state of Circuit 1 Comprosser from ExternalRead0 = Normal, 1 = Locked Out
BI10130Circuit 2 Lockout ExternalLockout state of Circuit 2 Comprosser from ExternalRead0 = Normal, 1 = Locked Out
BI10131Circuit 1 Lockout ActiveLockout state of Circuit 1Read0 = Normal, 1 = Locked Out
BI10132Circuit 2 Lockout ActiveLockout state of Circuit 2Read0 = Normal, 1 = Locked Out
BI10133Circuit 1 AvailableCircuit 1 is available to startRead0 = Unavailable, 1 = Available
BI10134Circuit 2 AvailableCircuit 2 is available to startRead0 = Unavailable, 1 = Available
BI10135Oil Sensor Circuit 1Status of the circuit 1 oil sensorRead0 = Dry, 1 = Wet
BI10136Oil Sensor Circuit 2Status of the circuit 2 oil sensorRead0 = Dry, 1 = Wet
BI10137Evaporator Water Pump 1 Inverter Running StatusRunning status of the evaporator water pump 1 inverterRead0 = Off, 1 = On
BI10138Evaporator Water Pump 1 Fault StatusFault status of the evaporator water pump 1 inverterRead0 = Fault, 1 = No Fault
BI10139Compressor 1B Lockout ActiveLockout state of Compressor 1BRead0 = Normal, 1 = Locked Out
BI10140Compressor 2B Lockout ActiveLockout state of Compressor 2BRead0 = Normal, 1 = Locked Out
BI10141Free Cooling Front Panel Command StatusStatus of the front panel free cooling commandRead0 = Off, 1 = Auto
BI11000Diagnostic: AFD 1A Bus Over VoltageRead0 = Normal, 1 = In Alarm
BI11001Diagnostic: AFD 1A Bus Under VoltageRead0 = Normal, 1 = In Alarm
BI11002Diagnostic: AFD 1A Comm Loss: Main ProcessorRead0 = Normal, 1 = In Alarm
BI11003Diagnostic: AFD 1A Customized Protection FaultRead0 = Normal, 1 = In Alarm
BI11004Diagnostic: AFD 1A Gate Kill ActiveRead0 = Normal, 1 = In Alarm
BI11005Diagnostic: AFD 1A General Failure (PF755)Read0 = Normal, 1 = In Alarm
BI11006Diagnostic: AFD 1A General Failure (TR200)Read0 = Normal, 1 = In Alarm
BI11007Diagnostic: AFD 1A Ground FaultRead0 = Normal, 1 = In Alarm
BI11008Diagnostic: AFD 1A Input Phase LossRead0 = Normal, 1 = In Alarm
BI11009Diagnostic: AFD 1A Input Transf or Filter Over TempRead0 = Normal, 1 = In Alarm
BI11010Diagnostic: AFD 1A Loss Of Motor ControlRead0 = Normal, 1 = In Alarm
BI11011Diagnostic: AFD 1A Low Rotor Flux FeedbackRead0 = Normal, 1 = In Alarm
BI11012Diagnostic: AFD 1A Motor Current OverloadRead0 = Normal, 1 = In Alarm
BI11013Diagnostic: AFD 1A Motor FaultRead0 = Normal, 1 = In Alarm
BI11014Diagnostic: AFD 1A Motor ShortedRead0 = Normal, 1 = In Alarm
BI11015Diagnostic: AFD 1A Over TemperatureRead0 = Normal, 1 = In Alarm
BI11016Diagnostic: AFD 1A Precharge FaultRead0 = Normal, 1 = In Alarm
BI11017Diagnostic: AFD 2A Bus Over VoltageRead0 = Normal, 1 = In Alarm
BI11018Diagnostic: AFD 2A Bus Under VoltageRead0 = Normal, 1 = In Alarm
BI11019Diagnostic: AFD 2A Comm Loss: Main ProcessorRead0 = Normal, 1 = In Alarm
BI11020Diagnostic: AFD 2A Customized Protection FaultRead0 = Normal, 1 = In Alarm
BI11021Diagnostic: AFD 2A Gate Kill ActiveRead0 = Normal, 1 = In Alarm
BI11022Diagnostic: AFD 2A General Failure (PF755)Read0 = Normal, 1 = In Alarm
BI11023Diagnostic: AFD 2A General Failure (TR200)Read0 = Normal, 1 = In Alarm
BI11024Diagnostic: AFD 2A Ground FaultRead0 = Normal, 1 = In Alarm
BI11025Diagnostic: AFD 2A Input Phase LossRead0 = Normal, 1 = In Alarm
BI11026Diagnostic: AFD 2A Input Transf or Filter Over TempRead0 = Normal, 1 = In Alarm
BI11027Diagnostic: AFD 2A Loss Of Motor ControlRead0 = Normal, 1 = In Alarm
BI11028Diagnostic: AFD 2A Low Rotor Flux FeedbackRead0 = Normal, 1 = In Alarm
BI11029Diagnostic: AFD 2A Motor Current OverloadRead0 = Normal, 1 = In Alarm
BI11030Diagnostic: AFD 2A Motor FaultRead0 = Normal, 1 = In Alarm
BI11031Diagnostic: AFD 2A Motor ShortedRead0 = Normal, 1 = In Alarm
BI11032Diagnostic: AFD 2A Over TemperatureRead0 = Normal, 1 = In Alarm
BI11033Diagnostic: AFD 2A Precharge FaultRead0 = Normal, 1 = In Alarm
BI11034Diagnostic: AFD Bus Over Voltage - 1ARead0 = Normal, 1 = In Alarm
BI11035Diagnostic: AFD Bus Over Voltage - 2ARead0 = Normal, 1 = In Alarm
BI11036Diagnostic: AFD Bus Under Voltage - 1ARead0 = Normal, 1 = In Alarm
BI11037Diagnostic: AFD Bus Under Voltage - 2ARead0 = Normal, 1 = In Alarm
BI11038Diagnostic: AFD Comm Loss – 1ARead0 = Normal, 1 = In Alarm
BI11039Diagnostic: AFD Comm Loss – 2ARead0 = Normal, 1 = In Alarm
BI11040Diagnostic: AFD Comm Loss: Main Processor - 1ARead0 = Normal, 1 = In Alarm
BI11041Diagnostic: AFD Comm Loss: Main Processor - 2ARead0 = Normal, 1 = In Alarm
BI11042Diagnostic: AFD Failure to Arm or Start - 1ARead0 = Normal, 1 = In Alarm
BI11043Diagnostic: AFD Failure to Arm or Start - 2ARead0 = Normal, 1 = In Alarm
BI11044Diagnostic: AFD Fault Mains - 1ARead0 = Normal, 1 = In Alarm
BI11045Diagnostic: AFD Fault Mains - 2ARead0 = Normal, 1 = In Alarm
BI11046Diagnostic: AFD General Fault - 1ARead0 = Normal, 1 = In Alarm
BI11047Diagnostic: AFD General Fault - 2ARead0 = Normal, 1 = In Alarm
BI11048Diagnostic: AFD Ground Fault - 1ARead0 = Normal, 1 = In Alarm
BI11049Diagnostic: AFD Ground Fault - 2ARead0 = Normal, 1 = In Alarm
BI11050Diagnostic: AFD Harmonic Filter Over Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11051Diagnostic: AFD Harmonic Filter Over Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11052Diagnostic: AFD High Pressure Cutout - 1ARead0 = Normal, 1 = In Alarm
BI11053Diagnostic: AFD High Pressure Cutout - 2ARead0 = Normal, 1 = In Alarm
BI11054Diagnostic: AFD High Torque - 1ARead0 = Normal, 1 = In Alarm
BI11055Diagnostic: AFD High Torque - 2ARead0 = Normal, 1 = In Alarm
BI11056Diagnostic: AFD Initialized - 1ARead0 = Normal, 1 = In Alarm
BI11057Diagnostic: AFD Initialized - 2ARead0 = Normal, 1 = In Alarm
BI11058Diagnostic: AFD Internal Fault - 1ARead0 = Normal, 1 = In Alarm
BI11059Diagnostic: AFD Internal Fault - 2ARead0 = Normal, 1 = In Alarm
BI11060Diagnostic: AFD Interrupt Failure - 1ARead0 = Normal, 1 = In Alarm
BI11061Diagnostic: AFD Interrupt Failure - 1BRead0 = Normal, 1 = In Alarm
BI11062Diagnostic: AFD Interrupt Failure - 2ARead0 = Normal, 1 = In Alarm
BI11063Diagnostic: AFD Interrupt Failure - 2BRead0 = Normal, 1 = In Alarm
BI11064Diagnostic: AFD Inverter Heatsink Over Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11065Diagnostic: AFD Inverter Heatsink Over Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11066Diagnostic: AFD Locked Rotor - 1ARead0 = Normal, 1 = In Alarm
BI11067Diagnostic: AFD Locked Rotor - 2ARead0 = Normal, 1 = In Alarm
BI11068Diagnostic: AFD Mains Phase Loss - 1ARead0 = Normal, 1 = In Alarm
BI11069Diagnostic: AFD Mains Phase Loss - 2ARead0 = Normal, 1 = In Alarm
BI11070Diagnostic: AFD Missing Motor - 1ARead0 = Normal, 1 = In Alarm
BI11071Diagnostic: AFD Missing Motor - 2ARead0 = Normal, 1 = In Alarm
BI11073Diagnostic: AFD Motor Current Overload - 1A (TR200)Read0 = Normal, 1 = In Alarm
BI11074Diagnostic: AFD Motor Current Overload - 1BRead0 = Normal, 1 = In Alarm
BI11076Diagnostic: AFD Motor Current Overload - 2A (TR200)Read0 = Normal, 1 = In Alarm
BI11077Diagnostic: AFD Motor Current Overload - 2BRead0 = Normal, 1 = In Alarm
BI11078Diagnostic: AFD Motor Fault - 1ARead0 = Normal, 1 = In Alarm
BI11079Diagnostic: AFD Motor Fault - 2ARead0 = Normal, 1 = In Alarm
BI11080Diagnostic: AFD New Spare Parts - 1ARead0 = Normal, 1 = In Alarm
BI11081Diagnostic: AFD New Spare Parts - 2ARead0 = Normal, 1 = In Alarm
BI11082Diagnostic: AFD Option Configuration Change - 1ARead0 = Normal, 1 = In Alarm
BI11083Diagnostic: AFD Option Configuration Change - 2ARead0 = Normal, 1 = In Alarm
BI11084Diagnostic: AFD Output Phase U Loss - 1ARead0 = Normal, 1 = In Alarm
BI11085Diagnostic: AFD Output Phase U Loss - 2ARead0 = Normal, 1 = In Alarm
BI11086Diagnostic: AFD Output Phase V Loss - 1ARead0 = Normal, 1 = In Alarm
BI11087Diagnostic: AFD Output Phase V Loss - 2ARead0 = Normal, 1 = In Alarm
BI11088Diagnostic: AFD Output Phase W Loss - 1ARead0 = Normal, 1 = In Alarm
BI11089Diagnostic: AFD Output Phase W Loss - 2ARead0 = Normal, 1 = In Alarm
BI11090Diagnostic: AFD Over Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11091Diagnostic: AFD Over Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11092Diagnostic: AFD Short Circuit - 1ARead0 = Normal, 1 = In Alarm
BI11093Diagnostic: AFD Short Circuit - 2ARead0 = Normal, 1 = In Alarm
BI11094Diagnostic: AFD Unexpected Shutdown - 1ARead0 = Normal, 1 = In Alarm
BI11095Diagnostic: AFD Unexpected Shutdown - 2ARead0 = Normal, 1 = In Alarm
BI11096Diagnostic: Check ClockRead0 = Normal, 1 = In Alarm
BI11097Diagnostic: Chiller Service RecommendedRead0 = Normal, 1 = In Alarm
BI11098Comm Loss: %RLA Indication Output(Vdc)Read0 = Normal, 1 = In Alarm
BI11099Comm Loss: AFD Fault Input 1ARead0 = Normal, 1 = In Alarm
BI11100Comm Loss: AFD Fault Input 1BRead0 = Normal, 1 = In Alarm
BI11101Comm Loss: AFD Fault Input 2ARead0 = Normal, 1 = In Alarm
BI11102Comm Loss: AFD Fault Input 2BRead0 = Normal, 1 = In Alarm
BI11103Comm Loss: Auxiliary Setpoint CommandRead0 = Normal, 1 = In Alarm
BI11104Comm Loss: Cond Fan Enbl Shared Ckt 1&2Read0 = Normal, 1 = In Alarm
BI11105Comm Loss: Cond Rfgt Tank Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11106Comm Loss: Cond Rfgt Tank Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11107Comm Loss: Condenser Fan Enable Circuit 1Read0 = Normal, 1 = In Alarm
BI11108Comm Loss: Condenser Fan Enable Circuit 2Read0 = Normal, 1 = In Alarm
BI11109Comm Loss: Condenser Rfgt Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11110Comm Loss: Condenser Rfgt Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11111Comm Loss: Cprsr Disch Rfgt Temp - 1ARead0 = Normal, 1 = In Alarm
BI11112Comm Loss: Cprsr Disch Rfgt Temp - 1BRead0 = Normal, 1 = In Alarm
BI11113Comm Loss: Cprsr Disch Rfgt Temp - 2ARead0 = Normal, 1 = In Alarm
BI11114Comm Loss: Cprsr Disch Rfgt Temp - 2BRead0 = Normal, 1 = In Alarm
BI11115Comm Loss: Drive Cooling Bypass Valve 1ARead0 = Normal, 1 = In Alarm
BI11116Comm Loss: Drive Cooling Bypass Valve 2ARead0 = Normal, 1 = In Alarm
BI11117Comm Loss: Drive Cooling Supply Temp 1ARead0 = Normal, 1 = In Alarm
BI11118Comm Loss: Drive Cooling Supply Temp 2ARead0 = Normal, 1 = In Alarm
BI11119Comm Loss: Economizer Disch Press - 1ARead0 = Normal, 1 = In Alarm
BI11120Comm Loss: Economizer Disch Press - 1BRead0 = Normal, 1 = In Alarm
BI11121Comm Loss: Economizer Disch Press - 2ARead0 = Normal, 1 = In Alarm
BI11122Comm Loss: Economizer Disch Press - 2BRead0 = Normal, 1 = In Alarm
BI11123Comm Loss: Economizer Disch Temp - 1ARead0 = Normal, 1 = In Alarm
BI11124Comm Loss: Economizer Disch Temp - 1BRead0 = Normal, 1 = In Alarm
BI11125Comm Loss: Economizer Disch Temp - 2ARead0 = Normal, 1 = In Alarm
BI11126Comm Loss: Economizer Disch Temp - 2BRead0 = Normal, 1 = In Alarm
BI11127Comm Loss: Economizer Valve - 1ARead0 = Normal, 1 = In Alarm
BI11128Comm Loss: Economizer Valve - 1BRead0 = Normal, 1 = In Alarm
BI11129Comm Loss: Economizer Valve - 2ARead0 = Normal, 1 = In Alarm
BI11130Comm Loss: Economizer Valve - 2BRead0 = Normal, 1 = In Alarm
BI11131Comm Loss: Electronic Expansion Valve 1 Compressor 1ARead0 = Normal, 1 = In Alarm
BI11132Comm Loss: Electronic Expansion Valve 1 Compressor 2ARead0 = Normal, 1 = In Alarm
BI11133Comm Loss: Electronic Expansion Valve 2 Compressor 1BRead0 = Normal, 1 = In Alarm
BI11134Comm Loss: Electronic Expansion Valve 2 Compressor 2BRead0 = Normal, 1 = In Alarm
BI11135Comm Loss: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11136Comm Loss: Energy Meter 1Read0 = Normal, 1 = In Alarm
BI11137Comm Loss: Energy Meter 2Read0 = Normal, 1 = In Alarm
BI11138Comm Loss: Evap Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11139Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11140Comm Loss: Evap Iso Valve Close Switch Compressor 1ARead0 = Normal, 1 = In Alarm
BI11141Comm Loss: Evap Iso Valve Close Switch Compressor 2ARead0 = Normal, 1 = In Alarm
BI11142Comm Loss: Evap Iso Valve Open Switch Compressor 1ARead0 = Normal, 1 = In Alarm
BI11143Comm Loss: Evap Iso Valve Open Switch Compressor 2ARead0 = Normal, 1 = In Alarm
BI11144Comm Loss: Evap Isolation Valve Relay Compressor 1ARead0 = Normal, 1 = In Alarm
BI11145Comm Loss: Evap Isolation Valve Relay Compressor 2ARead0 = Normal, 1 = In Alarm
BI11146Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11147Comm Loss: Evap Pump Inv1 Fault InputRead0 = Normal, 1 = In Alarm
BI11148Comm Loss: Evap Pump Inv1 Run CommandRead0 = Normal, 1 = In Alarm
BI11149Comm Loss: Evap Rfgt Pool Temp Circuit 1Read0 = Normal, 1 = In Alarm
BI11150Comm Loss: Evap Rfgt Pool Temp Circuit 2Read0 = Normal, 1 = In Alarm
BI11151Comm Loss: Evap Water Pump Inv Freq InputRead0 = Normal, 1 = In Alarm
BI11152Comm Loss: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11153Comm Loss: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11154Comm Loss: Evaporator Oil Return Purge Valve - 1ARead0 = Normal, 1 = In Alarm
BI11155Comm Loss: Evaporator Oil Return Purge Valve - 2ARead0 = Normal, 1 = In Alarm
BI11156Comm Loss: Evaporator Pump 1 Fault InputRead0 = Normal, 1 = In Alarm
BI11157Comm Loss: Evaporator Pump 2 Fault InputRead0 = Normal, 1 = In Alarm
BI11158Comm Loss: Evaporator Pump Fault InputRead0 = Normal, 1 = In Alarm
BI11159Comm Loss: Evaporator Pump Inverter Running StatusRead0 = Normal, 1 = In Alarm
BI11160Comm Loss: Evaporator Pump Speed CommandRead0 = Normal, 1 = In Alarm
BI11161Comm Loss: Evaporator Pump Speed FeedbackRead0 = Normal, 1 = In Alarm
BI11162Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11163Comm Loss: Evaporator Water Pump 1 RelayRead0 = Normal, 1 = In Alarm
BI11164Comm Loss: Evaporator Water Pump 2 RelayRead0 = Normal, 1 = In Alarm
BI11165Comm Loss: Evaporator Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11166Comm Loss: Ext Chilled Water SetpointRead0 = Normal, 1 = In Alarm
BI11167Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11168Comm Loss: Ext Noise Reduction RequestRead0 = Normal, 1 = In Alarm
BI11169Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11170Comm Loss: External Ckt Lockout Circuit 1Read0 = Normal, 1 = In Alarm
BI11171Comm Loss: External Ckt Lockout Circuit 2Read0 = Normal, 1 = In Alarm
BI11172Comm Loss: External Heat Recovery CommandRead0 = Normal, 1 = In Alarm
BI11173Comm Loss: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11174Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11175Comm Loss: Fan Board 1 Relay 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11176Comm Loss: Fan Board 1 Relay 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11177Comm Loss: Fan Board 1 Relay 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11178Comm Loss: Fan Board 1 Relay 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11179Comm Loss: Fan Board 1 Relay 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11180Comm Loss: Fan Board 1 Relay 3 Circuit 2Read0 = Normal, 1 = In Alarm
BI11181Comm Loss: Fan Board 1 Relay 4 Circuit 1Read0 = Normal, 1 = In Alarm
BI11182Comm Loss: Fan Board 1 Relay 4 Circuit 2Read0 = Normal, 1 = In Alarm
BI11183Comm Loss: Fan Board 2 Relay 1 Circuit 1Read0 = Normal, 1 = In Alarm
BI11184Comm Loss: Fan Board 2 Relay 1 Circuit 2Read0 = Normal, 1 = In Alarm
BI11185Comm Loss: Fan Board 2 Relay 2 Circuit 1Read0 = Normal, 1 = In Alarm
BI11186Comm Loss: Fan Board 2 Relay 2 Circuit 2Read0 = Normal, 1 = In Alarm
BI11187Comm Loss: Fan Board 2 Relay 3 Circuit 1Read0 = Normal, 1 = In Alarm
BI11188Comm Loss: Fan Board 2 Relay 3 Circuit 2Read0 = Normal, 1 = In Alarm
BI11189Comm Loss: Fan Board 2 Relay 4 Circuit 1Read0 = Normal, 1 = In Alarm
BI11190Comm Loss: Fan Board 2 Relay 4 Circuit 2Read0 = Normal, 1 = In Alarm
BI11191Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1 & 2Read0 = Normal, 1 = In Alarm
BI11192Comm Loss: Fan Inverter Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11193Comm Loss: Fan Inverter Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11194Comm Loss: Fan Inverter Speed Command Circuit 1Read0 = Normal, 1 = In Alarm
BI11195Comm Loss: Fan Inverter Speed Command Circuit 2Read0 = Normal, 1 = In Alarm
BI11196Comm Loss: FC Entering Glycol TempRead0 = Normal, 1 = In Alarm
BI11197Comm Loss: FC Entering Water TempRead0 = Normal, 1 = In Alarm
BI11198Comm Loss: FC Leaving Glycol TempRead0 = Normal, 1 = In Alarm
BI11199Comm Loss: Free Cooling Bypass ValveRead0 = Normal, 1 = In Alarm
BI11200Comm Loss: Free Cooling Dedicated Fan EnableRead0 = Normal, 1 = In Alarm
BI11201Comm Loss: Free Cooling Dedicated Fan Inverter FaultRead0 = Normal, 1 = In Alarm
BI11202Comm Loss: Free Cooling Dedicated Fan Inverter Speed CommandRead0 = Normal, 1 = In Alarm
BI11203Comm Loss: Free Cooling Glycol Flow SwitchRead0 = Normal, 1 = In Alarm
BI11204Comm Loss: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11205Comm Loss: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11206Comm Loss: Free Cooling PumpRead0 = Normal, 1 = In Alarm
BI11207Comm Loss: Free Cooling ValveRead0 = Normal, 1 = In Alarm
BI11208Comm Loss: Heat Recovery Mode Valve Command - Ckt1Read0 = Normal, 1 = In Alarm
BI11209Comm Loss: Heat Recovery Mode Valve Command - Ckt2Read0 = Normal, 1 = In Alarm
BI11210Comm Loss: Heat Recovery Water Flow CmdRead0 = Normal, 1 = In Alarm
BI11211Comm Loss: Heat Recovery Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11212Comm Loss: Heat Recovery Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11213Comm Loss: High Pressure Cutout Sw - 1ARead0 = Normal, 1 = In Alarm
BI11214Comm Loss: High Pressure Cutout Sw - 1BRead0 = Normal, 1 = In Alarm
BI11215Comm Loss: High Pressure Cutout Sw - 2ARead0 = Normal, 1 = In Alarm
BI11216Comm Loss: High Pressure Cutout Sw - 2BRead0 = Normal, 1 = In Alarm
BI11217Comm Loss: Hot Gas Oil Return Valve - 1ARead0 = Normal, 1 = In Alarm
BI11218Comm Loss: Hot Gas Oil Return Valve - 2ARead0 = Normal, 1 = In Alarm
BI11219Comm Loss: HR Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11220Comm Loss: HR Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11221Comm Loss: Liquid Line Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11222Comm Loss: Liquid Line Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11223Comm Loss: Liquid Line Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11224Comm Loss: Liquid Line Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11225Comm Loss: Motor Winding Tstat Cprsr1ARead0 = Normal, 1 = In Alarm
BI11226Comm Loss: Motor Winding Tstat Cprsr2ARead0 = Normal, 1 = In Alarm
BI11227Comm Loss: Off-cycle Freeze Prot RelayRead0 = Normal, 1 = In Alarm
BI11228Comm Loss: Oil Loss Level Sensor Input Circuit 1Read0 = Normal, 1 = In Alarm
BI11229Comm Loss: Oil Loss Level Sensor Input Circuit 2Read0 = Normal, 1 = In Alarm
BI11230Comm Loss: Oil Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11231Comm Loss: Oil Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11232Comm Loss: Oil Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11233Comm Loss: Oil Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11234Comm Loss: Oil Return Solenoid Valve - 1BRead0 = Normal, 1 = In Alarm
BI11235Comm Loss: Oil Return Solenoid Valve - 2BRead0 = Normal, 1 = In Alarm
BI11236Comm Loss: Oil Return Valve - 1ARead0 = Normal, 1 = In Alarm
BI11237Comm Loss: Oil Return Valve - 2ARead0 = Normal, 1 = In Alarm
BI11238Comm Loss: Oil Supply TemperatureRead0 = Normal, 1 = In Alarm
BI11239Comm Loss: Oil Supply TemperatureRead0 = Normal, 1 = In Alarm
BI11240Comm Loss: Oil Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11241Comm Loss: Oil Temperature - 1BRead0 = Normal, 1 = In Alarm
BI11242Comm Loss: Oil Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11243Comm Loss: Oil Temperature - 2BRead0 = Normal, 1 = In Alarm
BI11244Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11245Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11246Comm Loss: Programmable Relay Board 2Read0 = Normal, 1 = In Alarm
BI11247Comm Loss: Slide Valve Load - 1ARead0 = Normal, 1 = In Alarm
BI11248Comm Loss: Slide Valve Load - 1BRead0 = Normal, 1 = In Alarm
BI11249Comm Loss: Slide Valve Load - 2ARead0 = Normal, 1 = In Alarm
BI11250Comm Loss: Slide Valve Load - 2BRead0 = Normal, 1 = In Alarm
BI11251Comm Loss: Slide Valve Unload - 1ARead0 = Normal, 1 = In Alarm
BI11252Comm Loss: Slide Valve Unload - 1BRead0 = Normal, 1 = In Alarm
BI11253Comm Loss: Slide Valve Unload - 2ARead0 = Normal, 1 = In Alarm
BI11254Comm Loss: Slide Valve Unload - 2BRead0 = Normal, 1 = In Alarm
BI11255Comm Loss: Starter 1ARead0 = Normal, 1 = In Alarm
BI11256Comm Loss: Starter 1BRead0 = Normal, 1 = In Alarm
BI11257Comm Loss: Starter 2ARead0 = Normal, 1 = In Alarm
BI11258Comm Loss: Starter 2BRead0 = Normal, 1 = In Alarm
BI11259Comm Loss: Step Load - 1ARead0 = Normal, 1 = In Alarm
BI11260Comm Loss: Step Load - 1BRead0 = Normal, 1 = In Alarm
BI11261Comm Loss: Step Load - 2ARead0 = Normal, 1 = In Alarm
BI11262Comm Loss: Step Load - 2BRead0 = Normal, 1 = In Alarm
BI11263Comm Loss: Suction Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11264Comm Loss: Suction Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11265Comm Loss: Suction Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11266Comm Loss: Suction Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11267Comm Loss: Var Vi Valve – Cprsr1ARead0 = Normal, 1 = In Alarm
BI11268Comm Loss: Var Vi Valve – Cprsr2ARead0 = Normal, 1 = In Alarm
BI11269Comm Loss: Winding Temp 1, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11270Comm Loss: Winding Temp 1, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11271Comm Loss: Winding Temp 2, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11272Comm Loss: Winding Temp 2, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11273Diagnostic: Condenser Rfgt Pressure Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11274Diagnostic: Condenser Rfgt Pressure Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11275Diagnostic: Cprsr Did Not Accel: Shutdown - 1ARead0 = Normal, 1 = In Alarm
BI11276Diagnostic: Cprsr Did Not Accel: Shutdown - 1BRead0 = Normal, 1 = In Alarm
BI11277Diagnostic: Cprsr Did Not Accel: Shutdown - 2ARead0 = Normal, 1 = In Alarm
BI11278Diagnostic: Cprsr Did Not Accel: Shutdown - 2BRead0 = Normal, 1 = In Alarm
BI11279Diagnostic: Cprsr Did Not Accel: Transition - 1ARead0 = Normal, 1 = In Alarm
BI11280Diagnostic: Cprsr Did Not Accel: Transition - 1BRead0 = Normal, 1 = In Alarm
BI11281Diagnostic: Cprsr Did Not Accel: Transition - 2ARead0 = Normal, 1 = In Alarm
BI11282Diagnostic: Cprsr Did Not Accel: Transition - 2BRead0 = Normal, 1 = In Alarm
BI11283Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11284Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11285Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11286Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11287Diagnostic: Drive Cooling Supply Temp Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11288Diagnostic: Drive Cooling Supply Temp Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11289Diagnostic: Economizer Disch Press Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11290Diagnostic: Economizer Disch Press Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11291Diagnostic: Economizer Disch Press Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11292Diagnostic: Economizer Disch Press Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11293Diagnostic: Economizer Disch Temp Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11294Diagnostic: Economizer Disch Temp Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11295Diagnostic: Economizer Disch Temp Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11296Diagnostic: Economizer Disch Temp Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11297Diagnostic: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11298Diagnostic: Evap Iso Valve Illegal Switch State Compressor 1ARead0 = Normal, 1 = In Alarm
BI11299Diagnostic: Evap Iso Valve Illegal Switch State Compressor 2ARead0 = Normal, 1 = In Alarm
BI11300Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 1ARead0 = Normal, 1 = In Alarm
BI11301Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 2ARead0 = Normal, 1 = In Alarm
BI11302Diagnostic: Evap Isolation Valve Failed To Close Compressor 1ARead0 = Normal, 1 = In Alarm
BI11303Diagnostic: Evap Isolation Valve Failed To Close Compressor 2ARead0 = Normal, 1 = In Alarm
BI11304Diagnostic: Evap Isolation Valve Failed To Open Compressor 1ARead0 = Normal, 1 = In Alarm
BI11305Diagnostic: Evap Isolation Valve Failed To Open Compressor 2ARead0 = Normal, 1 = In Alarm
BI11306Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 1ARead0 = Normal, 1 = In Alarm
BI11307Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 2ARead0 = Normal, 1 = In Alarm
BI11308Diagnostic: Evap Pump 1 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11309Diagnostic: Evap Pump 2 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11310Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11311Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11312Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1Read0 = Normal, 1 = In Alarm
BI11313Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2Read0 = Normal, 1 = In Alarm
BI11314Diagnostic: Evap Water Pump 1 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11315Diagnostic: Evap Water Pump 2 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11316Diagnostic: Evaporator Approach Error Circuit 1Read0 = Normal, 1 = In Alarm
BI11317Diagnostic: Evaporator Approach Error Circuit 2Read0 = Normal, 1 = In Alarm
BI11318Diagnostic: Evaporator Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11319Diagnostic: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11320Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11321Diagnostic: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11322Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11323Diagnostic: Evaporator Pump 1 FaultRead0 = Normal, 1 = In Alarm
BI11324Diagnostic: Evaporator Pump 2 FaultRead0 = Normal, 1 = In Alarm
BI11325Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11326Diagnostic: Evaporator Water Flow Lost - Pump1Read0 = Normal, 1 = In Alarm
BI11327Diagnostic: Evaporator Water Flow Lost - Pump2Read0 = Normal, 1 = In Alarm
BI11328Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11329Diagnostic: Evaporator Water Flow Overdue - Pump1Read0 = Normal, 1 = In Alarm
BI11330Diagnostic: Evaporator Water Flow Overdue - Pump2Read0 = Normal, 1 = In Alarm
BI11331Diagnostic: Evaporator Water Pump FaultRead0 = Normal, 1 = In Alarm
BI11332Diagnostic: Evaporator Water Pump Speed FeedbackRead0 = Normal, 1 = In Alarm
BI11333Diagnostic: Excessive Condenser Pressure Circuit 1Read0 = Normal, 1 = In Alarm
BI11334Diagnostic: Excessive Condenser Pressure Circuit 2Read0 = Normal, 1 = In Alarm
BI11335Diagnostic: External Chilled Water SetpointRead0 = Normal, 1 = In Alarm
BI11336Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11337Diagnostic: External Heat Recovery SetpointRead0 = Normal, 1 = In Alarm
BI11338Diagnostic: Fan Inverter Fault Circuit 1Read0 = Normal, 1 = In Alarm
BI11339Diagnostic: Fan Inverter Fault Circuit 2Read0 = Normal, 1 = In Alarm
BI11340Diagnostic: Free Cooling Dedicated Fan Inverter FaultRead0 = Normal, 1 = In Alarm
BI11341Diagnostic: Free Cooling Entering Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11342Diagnostic: Free Cooling Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11343Diagnostic: Free Cooling Glycol Flow LostRead0 = Normal, 1 = In Alarm
BI11344Diagnostic: Free Cooling Glycol Flow OverdueRead0 = Normal, 1 = In Alarm
BI11345Diagnostic: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11346Diagnostic: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11347Diagnostic: Free Cooling Glycol Temperature Equalization OverdueRead0 = Normal, 1 = In Alarm
BI11348Diagnostic: Free Cooling Leaving Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11349Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11350Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11351Diagnostic: Heat Recovery Water Flow LostRead0 = Normal, 1 = In Alarm
BI11352Diagnostic: Heat Recovery Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11353Diagnostic: High Cprsr Rfgt Discharge Temp - 1ARead0 = Normal, 1 = In Alarm
BI11354Diagnostic: High Cprsr Rfgt Discharge Temp - 1BRead0 = Normal, 1 = In Alarm
BI11355Diagnostic: High Cprsr Rfgt Discharge Temp - 2ARead0 = Normal, 1 = In Alarm
BI11356Diagnostic: High Cprsr Rfgt Discharge Temp - 2BRead0 = Normal, 1 = In Alarm
BI11357Diagnostic: High Differential Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11358Diagnostic: High Differential Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11359Diagnostic: High Differential Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11360Diagnostic: High Differential Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11361Diagnostic: High Evaporator Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11362Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11363Diagnostic: High Motor Winding Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11364Diagnostic: High Motor Winding Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11365Diagnostic: High Oil Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11366Diagnostic: High Oil Temperature - 1BRead0 = Normal, 1 = In Alarm
BI11367Diagnostic: High Oil Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11368Diagnostic: High Oil Temperature - 2BRead0 = Normal, 1 = In Alarm
BI11369Diagnostic: High Pressure Cutout - 1ARead0 = Normal, 1 = In Alarm
BI11370Diagnostic: High Pressure Cutout - 1BRead0 = Normal, 1 = In Alarm
BI11371Diagnostic: High Pressure Cutout - 2ARead0 = Normal, 1 = In Alarm
BI11372Diagnostic: High Pressure Cutout - 2BRead0 = Normal, 1 = In Alarm
BI11373Diagnostic: High Refrigerant Pressure Ratio - 1ARead0 = Normal, 1 = In Alarm
BI11374Diagnostic: High Refrigerant Pressure Ratio - 1BRead0 = Normal, 1 = In Alarm
BI11375Diagnostic: High Refrigerant Pressure Ratio - 2ARead0 = Normal, 1 = In Alarm
BI11376Diagnostic: High Refrigerant Pressure Ratio - 2BRead0 = Normal, 1 = In Alarm
BI11377Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11378Diagnostic: Liquid Line Pressure Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11379Diagnostic: Liquid Line Pressure Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11380Diagnostic: Liquid Line Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11381Diagnostic: Liquid Line Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11382Diagnostic: Loss of Oil for Compressor (Running) Compressor 1ARead0 = Normal, 1 = In Alarm
BI11383Diagnostic: Loss of Oil for Compressor (Running) Compressor 2ARead0 = Normal, 1 = In Alarm
BI11384Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 1ARead0 = Normal, 1 = In Alarm
BI11385Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 2ARead0 = Normal, 1 = In Alarm
BI11386Diagnostic: Low Differential Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11387Diagnostic: Low Differential Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11388Diagnostic: Low Differential Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11389Diagnostic: Low Differential Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11390Diagnostic: Low Discharge Superheat - 1ARead0 = Normal, 1 = In Alarm
BI11391Diagnostic: Low Discharge Superheat - 1BRead0 = Normal, 1 = In Alarm
BI11392Diagnostic: Low Discharge Superheat - 2ARead0 = Normal, 1 = In Alarm
BI11393Diagnostic: Low Discharge Superheat - 2BRead0 = Normal, 1 = In Alarm
BI11394Diagnostic: Low Drive Cooling Supply Temperature - 1ARead0 = Normal, 1 = In Alarm
BI11395Diagnostic: Low Drive Cooling Supply Temperature - 2ARead0 = Normal, 1 = In Alarm
BI11396Diagnostic: Low Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11397Diagnostic: Low Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11398Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffRead0 = Normal, 1 = In Alarm
BI11399Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffRead0 = Normal, 1 = In Alarm
BI11400Diagnostic: Low Evaporator Water FlowRead0 = Normal, 1 = In Alarm
BI11401Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11402Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11403Diagnostic: Low Glycol Pressure Free CoolingRead0 = Normal, 1 = In Alarm
BI11404Diagnostic: Low Glycol Temp Free CoolingRead0 = Normal, 1 = In Alarm
BI11405Diagnostic: Low Oil Flow - 1ARead0 = Normal, 1 = In Alarm
BI11406Diagnostic: Low Oil Flow - 1BRead0 = Normal, 1 = In Alarm
BI11407Diagnostic: Low Oil Flow - 2ARead0 = Normal, 1 = In Alarm
BI11408Diagnostic: Low Oil Flow - 2BRead0 = Normal, 1 = In Alarm
BI11409Diagnostic: Low Refrigerant Temperature Circuit 1Read0 = Normal, 1 = In Alarm
BI11410Diagnostic: Low Refrigerant Temperature Circuit 2Read0 = Normal, 1 = In Alarm
BI11411Diagnostic: Low Suction Refrigerant Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11412Diagnostic: Low Suction Refrigerant Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11413Diagnostic: Low Suction Refrigerant Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11414Diagnostic: Low Suction Refrigerant Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11415Diagnostic: Mfr Maintenance Recommended - 1ARead0 = Normal, 1 = In Alarm
BI11416Diagnostic: Mfr Maintenance Recommended - 1BRead0 = Normal, 1 = In Alarm
BI11417Diagnostic: Mfr Maintenance Recommended - 2ARead0 = Normal, 1 = In Alarm
BI11418Diagnostic: Mfr Maintenance Recommended - 2BRead0 = Normal, 1 = In Alarm
BI11419Diagnostic: Momentary Power Loss Compressor 1ARead0 = Normal, 1 = In Alarm
BI11420Diagnostic: Momentary Power Loss Compressor 2ARead0 = Normal, 1 = In Alarm
BI11421Diagnostic: Motor Current Overload - 1ARead0 = Normal, 1 = In Alarm
BI11422Diagnostic: Motor Current Overload - 1BRead0 = Normal, 1 = In Alarm
BI11423Diagnostic: Motor Current Overload - 2ARead0 = Normal, 1 = In Alarm
BI11424Diagnostic: Motor Current Overload - 2BRead0 = Normal, 1 = In Alarm
BI11425Diagnostic: Motor Winding Temp Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11426Diagnostic: Motor Winding Temp Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11427Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11428Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11429Diagnostic: No Differential Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11430Diagnostic: No Differential Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11431Diagnostic: No Differential Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11432Diagnostic: No Differential Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11433Diagnostic: Oil Filter Change Recommended - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11434Diagnostic: Oil Filter Change Recommended - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11435Diagnostic: Oil Flow Protection Fault - 1ARead0 = Normal, 1 = In Alarm
BI11436Diagnostic: Oil Flow Protection Fault - 1BRead0 = Normal, 1 = In Alarm
BI11437Diagnostic: Oil Flow Protection Fault - 2ARead0 = Normal, 1 = In Alarm
BI11438Diagnostic: Oil Flow Protection Fault - 2BRead0 = Normal, 1 = In Alarm
BI11439Diagnostic: Oil Pressure Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11440Diagnostic: Oil Pressure Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11441Diagnostic: Oil Pressure Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11442Diagnostic: Oil Pressure Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11443Diagnostic: Oil Supply Temp Sensor Circuit 1Read0 = Normal, 1 = In Alarm
BI11444Diagnostic: Oil Supply Temp Sensor Circuit 2Read0 = Normal, 1 = In Alarm
BI11445Diagnostic: Oil Temperature Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11446Diagnostic: Oil Temperature Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11447Diagnostic: Oil Temperature Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11448Diagnostic: Oil Temperature Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11449Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11450Diagnostic: Over VoltageRead0 = Normal, 1 = In Alarm
BI11451Diagnostic: Phase Loss - 1ARead0 = Normal, 1 = In Alarm
BI11452Diagnostic: Phase Loss - 1BRead0 = Normal, 1 = In Alarm
BI11453Diagnostic: Phase Loss - 2ARead0 = Normal, 1 = In Alarm
BI11454Diagnostic: Phase Loss - 2BRead0 = Normal, 1 = In Alarm
BI11455Diagnostic: Phase Reversal - 1ARead0 = Normal, 1 = In Alarm
BI11456Diagnostic: Phase Reversal - 1BRead0 = Normal, 1 = In Alarm
BI11457Diagnostic: Phase Reversal - 2ARead0 = Normal, 1 = In Alarm
BI11458Diagnostic: Phase Reversal - 2BRead0 = Normal, 1 = In Alarm
BI11459Diagnostic: Power Loss - 1ARead0 = Normal, 1 = In Alarm
BI11460Diagnostic: Power Loss - 1BRead0 = Normal, 1 = In Alarm
BI11461Diagnostic: Power Loss - 2ARead0 = Normal, 1 = In Alarm
BI11462Diagnostic: Power Loss - 2BRead0 = Normal, 1 = In Alarm
BI11463Diagnostic: Pumpdown Terminated By Time Circuit 1Read0 = Normal, 1 = In Alarm
BI11464Diagnostic: Pumpdown Terminated By Time Circuit 2Read0 = Normal, 1 = In Alarm
BI11465Diagnostic: Restart Inhibit Invoked - 1ARead0 = Normal, 1 = In Alarm
BI11466Diagnostic: Restart Inhibit Invoked - 1BRead0 = Normal, 1 = In Alarm
BI11467Diagnostic: Restart Inhibit Invoked - 2ARead0 = Normal, 1 = In Alarm
BI11468Diagnostic: Restart Inhibit Invoked - 2BRead0 = Normal, 1 = In Alarm
BI11469Diagnostic: Severe Current Imbalance - 1ARead0 = Normal, 1 = In Alarm
BI11470Diagnostic: Severe Current Imbalance - 1BRead0 = Normal, 1 = In Alarm
BI11471Diagnostic: Severe Current Imbalance - 2ARead0 = Normal, 1 = In Alarm
BI11472Diagnostic: Severe Current Imbalance - 2BRead0 = Normal, 1 = In Alarm
BI11473Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11474Diagnostic: Software Error 1002: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11475Diagnostic: Software Error 1003: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11476Diagnostic: Starter Comm Loss: Main Processor - 1ARead0 = Normal, 1 = In Alarm
BI11477Diagnostic: Starter Comm Loss: Main Processor - 1BRead0 = Normal, 1 = In Alarm
BI11478Diagnostic: Starter Comm Loss: Main Processor - 2ARead0 = Normal, 1 = In Alarm
BI11479Diagnostic: Starter Comm Loss: Main Processor - 2BRead0 = Normal, 1 = In Alarm
BI11480Diagnostic: Starter Contactor Interrupt Failure - 1ARead0 = Normal, 1 = In Alarm
BI11481Diagnostic: Starter Contactor Interrupt Failure - 1BRead0 = Normal, 1 = In Alarm
BI11482Diagnostic: Starter Contactor Interrupt Failure - 2ARead0 = Normal, 1 = In Alarm
BI11483Diagnostic: Starter Contactor Interrupt Failure - 2BRead0 = Normal, 1 = In Alarm
BI11484Diagnostic: Starter Did Not Fully AccelerateRead0 = Normal, 1 = In Alarm
BI11485Diagnostic: Starter Did Not Transition - 1ARead0 = Normal, 1 = In Alarm
BI11486Diagnostic: Starter Did Not Transition - 1BRead0 = Normal, 1 = In Alarm
BI11487Diagnostic: Starter Did Not Transition - 2ARead0 = Normal, 1 = In Alarm
BI11488Diagnostic: Starter Did Not Fully Accelerate Compressor 2ARead0 = Normal, 1 = In Alarm
BI11489Diagnostic: Starter Did Not Transition - 2BRead0 = Normal, 1 = In Alarm
BI11490Diagnostic: Starter Dry Run Test - 1ARead0 = Normal, 1 = In Alarm
BI11491Diagnostic: Starter Dry Run Test - 1BRead0 = Normal, 1 = In Alarm
BI11492Diagnostic: Starter Dry Run Test - 2ARead0 = Normal, 1 = In Alarm
BI11493Diagnostic: Starter Dry Run Test - 2BRead0 = Normal, 1 = In Alarm
BI11494Diagnostic: Starter Failed to Arm/Start - 1ARead0 = Normal, 1 = In Alarm
BI11495Diagnostic: Starter Failed to Arm/Start - 1BRead0 = Normal, 1 = In Alarm
BI11496Diagnostic: Starter Failed to Arm/Start - 2ARead0 = Normal, 1 = In Alarm
BI11497Diagnostic: Starter Failed to Arm/Start - 2BRead0 = Normal, 1 = In Alarm
BI11498Diagnostic: Starter Fault Type I - 1ARead0 = Normal, 1 = In Alarm
BI11499Diagnostic: Starter Fault Type I - 1BRead0 = Normal, 1 = In Alarm
BI11500Diagnostic: Starter Fault Type I - 2ARead0 = Normal, 1 = In Alarm
BI11501Diagnostic: Starter Fault Type I - 2BRead0 = Normal, 1 = In Alarm
BI11502Diagnostic: Starter Fault Type II - 1ARead0 = Normal, 1 = In Alarm
BI11503Diagnostic: Starter Fault Type II - 1BRead0 = Normal, 1 = In Alarm
BI11504Diagnostic: Starter Fault Type II - 2ARead0 = Normal, 1 = In Alarm
BI11505Diagnostic: Starter Fault Type II - 2BRead0 = Normal, 1 = In Alarm
BI11506Diagnostic: Starter Fault Type III - 1ARead0 = Normal, 1 = In Alarm
BI11507Diagnostic: Starter Fault Type III - 1BRead0 = Normal, 1 = In Alarm
BI11508Diagnostic: Starter Fault Type III - 2ARead0 = Normal, 1 = In Alarm
BI11509Diagnostic: Starter Fault Type III - 2BRead0 = Normal, 1 = In Alarm
BI11510Diagnostic: Starter Module Memory Error Type 1 - 1ARead0 = Normal, 1 = In Alarm
BI11511Diagnostic: Starter Module Memory Error Type 1 - 1BRead0 = Normal, 1 = In Alarm
BI11512Diagnostic: Starter Module Memory Error Type 1 - 2ARead0 = Normal, 1 = In Alarm
BI11513Diagnostic: Starter Module Memory Error Type 1 - 2BRead0 = Normal, 1 = In Alarm
BI11514Diagnostic: Starter Module Memory Error Type 2 - 1ARead0 = Normal, 1 = In Alarm
BI11515Diagnostic: Starter Module Memory Error Type 2 - 1BRead0 = Normal, 1 = In Alarm
BI11516Diagnostic: Starter Module Memory Error Type 2 - 2ARead0 = Normal, 1 = In Alarm
BI11517Diagnostic: Starter Module Memory Error Type 2 - 2BRead0 = Normal, 1 = In Alarm
BI11518Diagnostic: Starts/Hours Modified 1ARead0 = Normal, 1 = In Alarm
BI11519Diagnostic: Starts/Hours Modified 1BRead0 = Normal, 1 = In Alarm
BI11520Diagnostic: Starts/Hours Modified 2ARead0 = Normal, 1 = In Alarm
BI11521Diagnostic: Starts/Hours Modified 2BRead0 = Normal, 1 = In Alarm
BI11522Diagnostic: Suction Refrigerant Pressure Sensor - 1ARead0 = Normal, 1 = In Alarm
BI11523Diagnostic: Suction Refrigerant Pressure Sensor - 1BRead0 = Normal, 1 = In Alarm
BI11524Diagnostic: Suction Refrigerant Pressure Sensor - 2ARead0 = Normal, 1 = In Alarm
BI11525Diagnostic: Suction Refrigerant Pressure Sensor - 2BRead0 = Normal, 1 = In Alarm
BI11526Diagnostic: Transition Complete Input Opened - 1ARead0 = Normal, 1 = In Alarm
BI11527Diagnostic: Transition Complete Input Opened - 1BRead0 = Normal, 1 = In Alarm
BI11528Diagnostic: Transition Complete Input Opened - 2ARead0 = Normal, 1 = In Alarm
BI11529Diagnostic: Transition Complete Input Opened - 2BRead0 = Normal, 1 = In Alarm
BI11530Diagnostic: Transition Complete Input Shorted - 1ARead0 = Normal, 1 = In Alarm
BI11531Diagnostic: Transition Complete Input Shorted - 1BRead0 = Normal, 1 = In Alarm
BI11532Diagnostic: Transition Complete Input Shorted - 2ARead0 = Normal, 1 = In Alarm
BI11533Diagnostic: Transition Complete Input Shorted - 2BRead0 = Normal, 1 = In Alarm
BI11534Diagnostic: Under VoltageRead0 = Normal, 1 = In Alarm
BI11535Diagnostic: Unexpected Starter Shutdown - 1ARead0 = Normal, 1 = In Alarm
BI11536Diagnostic: Unexpected Starter Shutdown - 1BRead0 = Normal, 1 = In Alarm
BI11537Diagnostic: Unexpected Starter Shutdown - 2ARead0 = Normal, 1 = In Alarm
BI11538Diagnostic: Unexpected Starter Shutdown - 2BRead0 = Normal, 1 = In Alarm
BI11539Diagnostic: Very Low Evap Rfgt Pressure - 1ARead0 = Normal, 1 = In Alarm
BI11540Diagnostic: Very Low Evap Rfgt Pressure - 1BRead0 = Normal, 1 = In Alarm
BI11541Diagnostic: Very Low Evap Rfgt Pressure - 2ARead0 = Normal, 1 = In Alarm
BI11542Diagnostic: Very Low Evap Rfgt Pressure - 2BRead0 = Normal, 1 = In Alarm
BI11543Diagnostic: Write Command Failure Energy Meter 1Read0 = Normal, 1 = In Alarm
BI11544Diagnostic: Write Command Failure Energy Meter 2Read0 = Normal, 1 = In Alarm
BI11545Comm Loss: Ice Building Status RelayRead0 = Normal, 1 = In Alarm
BV10100Reset DiagnosticBAS Diagnostic ResetWrite0 = Normal, 1 = Reset
BV10101Noise Reduction Request BASBAS Noise Reduction CommandWrite0 = Normal, 1 = Reduce Noise
BV10102Circuit 1 Lockout BASWrite0 = Normal, 1 = Locked Out
BV10103Circuit 2 Lockout BASWrite0 = Normal, 1 = Locked Out
BV10107Energy Consumption ResetWrite0 = Accumulating, 1 = Reset
BVmin10108Chiller Auto Stop Command BASWrite0 = Stop, 1 = Auto
BV10109Free Cooling Auto Stop Command BASWrite0 = Stop, 1 = Auto
BV10110Free Cooling Compressor LockoutWrite0 = Normal, 1 = Locked Out
BV10111Compressor 1B Lockout BASWrite0 = Normal, 1 = Locked Out
BV10112Compressor 2B Lockout BASWrite0 = Normal, 1 = Locked Out
MI10100Running ModeRunning state of the chillerRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeOperating mode of the chillerRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Refrigerant TypeChiller refrigerant typeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E)
MI10103Cooling TypeCooling Type of chillerRead1 = Water Cooled, 2 = Air Cooled
MI10104Manufacture LocationLocation that the chiller was manufacturedRead1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey
MI10105Model Information [GEN2]Model information of chillerRead1 = CVHF, 2 = CVGF, 3 = CVHS, 4 = RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTWE, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = ACXA, 35 = CMAF, 36 = ACRB Large, 37 = ACRB Small, 38 = CVHE, 39 = CVHG, 40 = CVHL, 41 = RTWF XSE, 42 = CGWF, 43 = CDHG, 44 = ACCA, 45 = RTWD, 46 = RTUD, 47 = CXWF, 48 = CCUF, 49 = RTHG, 50 = CGAM, 51 = CXAM, 52 = CGAX, 53 = CXAX, 54 = EIC, 55 = EIH, 56 = RTXG, 57 = RTMG, 58 = ACRC, 59 = HSWB
MI10106Chiller Setpoint SourceSelected setpoint source for control purposeRead1 = BAS, 2 = External, 3 = Front Panel
MVmin10100Chiller Mode Command BASCommand the chiller ModeWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Ascend ACR Series C and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 Ascend ACR Series C

How many BACnet points does the Trane Symbio 800 Ascend ACR Series C have?

This list has 772 BACnet objects: 166 analog inputs, 4 analog values, 584 binary inputs, 10 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 Ascend ACR Series C BACnet points are writable?

15 of the 772 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 Ascend ACR Series C BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - Ascend Model ACR Series C (BAS-PTS021A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS021A-EN_11152024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 Ascend ACR Series C?

Start with BV 10108 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10104 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10180 Actual Running Capacity (Actual running capacity in percent); BI 10116 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 Ascend ACR Series C?

BV 10108 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10124 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10106 Chiller Setpoint Source shows BAS, External or Front Panel.

How do I check these points on the real Symbio 800 Ascend ACR Series C?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - Ascend Model ACR Series C · BAS-PTS021A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.