Air-cooled scroll chiller controller · BACnet points list

Trane Symbio 800 CGAM BACnet points list

Updated 28 October 2026

Short answer

CGAM chillers with Symbio 800 publish about 300 BACnet objects. Status is AI/BI/MI, and AV/BV/MV objects take BAS setpoints and commands. Multistate inputs report things like refrigerant type and chiller model code.

This page lists 301 BACnet objects for the Trane Symbio 800 CGAM — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 CGAM
Equipment
Air-cooled scroll chiller controller
Equipment type
Chillers
BACnet objects
301 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
CGAM, CGAM air-cooled chiller, BAS-PTS019
Source document
Symbio 800 Integration Points List BACnet - CGAM · BAS-PTS019A-EN · rev. 11/15/2024
Download CSV 301 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 CGAM

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10106Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10114Chiller Running StateChiller on/off statusRead
BI 10106Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10101Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10126Actual Running CapacityActual running capacity in percentRead
BI 10123Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10106 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10104 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10105 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10106 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

Network setup

Watch out for

Trane Symbio 800 CGAM BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

301 of 301 shown
Type
Access
Show
Trane Symbio 800 CGAM BACnet Points List
DescriptionStates
AI10100Active Cool/Heat Setpoint TemperatureTemperatureRead
AImin10101Evaporator Leaving Water TemperatureTemperatureRead
AI10102Evaporator Entering Water TemperatureTemperatureRead
AI10103Active Chilled Water SetpointTemperatureRead
AI10104Chilled Water Setpoint StatusTemperatureRead
AI10105Hot Water Setpoint ActiveTemperatureRead
AI10106Hot Water Setpoint StatusTemperatureRead
AI10107Active Demand Limit SetpointPercentageRead
AI10108Active Demand Limit SetpointPercentageRead
AI10109Demand Limit Setpoint StatusPercentageRead
AI10110Unit Power ConsumptionPower, ElectricalRead
AI10111Outdoor Air TemperatureTemperatureRead
AI10112Evaporator Refrigerant Pressure Circuit 1Pressure, FluidicRead
AI10113Condenser Refrigerant Pressure Circuit 1Pressure, FluidicRead
AI10114Differential Refrigerant Pressure Circuit 1Pressure, FluidicRead
AI10115Evaporator Saturated Refrigerant Temperature Circuit 1TemperatureRead
AI10116Condenser Saturated Refrigerant Temperature Circuit 1TemperatureRead
AI10117Evaporator Refrigerant Pressure Circuit 2Pressure, FluidicRead
AI10118Condenser Refrigerant Pressure Circuit 2Pressure, FluidicRead
AI10119Differential Refrigerant Pressure Circuit 2Pressure, FluidicRead
AI10120Evaporator Saturated Refrigerant Temperature Circuit 2TemperatureRead
AI10121Condenser Saturated Refrigerant Temperature Circuit 2TemperatureRead
AI10122Evaporator Refrigerant Absolute Pressure Circuit 1Pressure, FluidicRead
AI10123Condenser Refrigerant Absolute Pressure Circuit 1Pressure, FluidicRead
AI10124Evaporator Refrigerant Absolute Pressure Circuit 2Pressure, FluidicRead
AI10125Condenser Refrigerant Absolute Pressure Circuit 2Pressure, FluidicRead
AImin10126Actual Running CapacityPercentageRead
AI10127Air Flow Percentage Circuit 1PercentageRead
AI10128Air Flow Percentage Circuit 2PercentageRead
AI10129Starts - Compressor 1ARead
AI10130Run Time - Compressor 1ARead
AI10131Starts - Compressor 1BRead
AI10132Run Time - Compressor 1BRead
AI10133Starts - Compressor 1CRead
AI10134Run Time - Compressor 1CRead
AI10135Starts - Compressor 2ARead
AI10136Run Time - Compressor 2ARead
AI10137Starts - Compressor 2BRead
AI10138Run Time - Compressor 2BRead
AI10139Starts - Compressor 2CRead
AI10140Run Time - Compressor 2CRead
AI10141Heat Recovery Leaving Water Temperature Setpoint ActiveTemperatureRead
AI10142Heat Recovery Entering Water TemperatureTemperatureRead
AI10143Heat Recovery Leaving Water TemperatureTemperatureRead
AI10144Chiller Design CapacityPower, CoolingRead
AI10145Number of CircuitsRead
AI10146Number of Compressors Circuit 1Read
AI10147Number of Compressors Circuit 2Read
AI10148Refrigerant Discharge Temperature Estimate Circuit 1TemperatureRead
AI10149Refrigerant Discharge Temperature Estimate Circuit 2TemperatureRead
AI10150Refrigerant Discharge Temperature Circuit 1TemperatureRead
AI10151Refrigerant Discharge Temperature Circuit 2TemperatureRead
AI10152Unit Source ID (Last Diagnostic Code)Read
AI10154Energy Consumption LifetimeEnergy, ElectricalRead
AI10155Energy ConsumptionEnergy, ElectricalRead
AI10156Average CurrentCurrentRead
AI10157Average Voltage L-LVoltageRead
AI10158Current L1CurrentRead
AI10159Current L2CurrentRead
AI10160Current L3CurrentRead
AI10161Voltage L1-L2VoltageRead
AI10162Voltage L2-L3VoltageRead
AI10163Voltage L1-L3VoltageRead
AI10164Unit Power DemandPower, ElectricalRead
AI10165Line FrequencyRead
AI10166Power FactorRead
AI10168Supplemental Heat StatusPercentageRead
AI10169Evaporator Approach Temperature Circuit 1Temperature, DeltaRead
AI10170Condenser Approach Temperature Circuit 1Temperature, DeltaRead
AI10171Evaporator Approach Temperature Circuit 2Temperature, DeltaRead
AI10172Condenser Approach Temperature Circuit 2Temperature, DeltaRead
AI10173Compressor Suction Superheat Ckt1Temperature, DeltaRead
AI10174Compressor Suction Superheat Ckt2Temperature, DeltaRead
AVmin10100Chilled Water SetpointTemperatureWrite
AVmin10101Demand Limit SetpointPercentageWrite
AV10102Hot Water SetpointTemperatureWrite
AV10103Heat Recovery Leaving Water Temperature Setpoint BASTemperatureWrite
BI10100Limit Mode Relay StatusRead0 = Auto, 1 = On
BI10101Emergency StopRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10102Manual Override ExistsRead0 = Off, 1 = On
BI10103Front Panel Auto Stop StatusRead0 = Stop, 1 = Auto
BI10104External Auto Stop Input StatusRead0 = Stop, 1 = Auto
BI10105Run EnabledRead0 = Run Not Enabled, 1 = Run Enabled
BImin10106Local Setpoint ControlRead0 = Remote Control, 1 = Local Control
BI10107Maximum CapacityRead0 = Off, 1 = On
BI10108Compressor 1A StatusRead0 = Off, 1 = Running
BI10109Compressor 1B StatusRead0 = Off, 1 = Running
BI10110Compressor 1C StatusRead0 = Off, 1 = Running
BI10111Compressor 2A StatusRead0 = Off, 1 = Running
BI10112Compressor 2B StatusRead0 = Off, 1 = Running
BI10113Compressor 2C StatusRead0 = Off, 1 = Running
BImin10114Chiller Running StateRead0 = Off, 1 = On
BI10115Heat Recovery Control Active StatusRead0 = Inactive, 1 = Active
BI10116Heat Recovery Request ActiveRead0 = Off, 1 = On
BI10117Evaporator Water Pump RequestRead0 = Off, 1 = On
BI10118Evaporator Water Flow StatusRead0 = No Flow, 1 = Flow
BI10119Diagnostic Present: InformationRead0 = Normal, 1 = In Alarm
BI10120Diagnostic Present: AdvisoryRead0 = Normal, 1 = In Alarm
BI10121Diagnostic Present: CriticalRead0 = Normal, 1 = In Alarm
BI10122Diagnostic Present: Service RequiredRead0 = Normal, 1 = In Alarm
BImin10123Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10124Diagnostic Shutdown PresentRead0 = Normal, 1 = In Alarm
BI10125Diagnostic: Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10126Diagnostic: Local Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10127Noise Reduction Request ActiveRead0 = Off, 1 = On
BI10128In DefrostRead0 = Not In Defrost, 1 = Defrost
BI10129Circuit 1 Lockout Front PanelRead0 = Normal, 1 = Locked Out
BI10130Circuit 2 Lockout Front PanelRead0 = Normal, 1 = Locked Out
BI10131Circuit 1 Lockout ExternalRead0 = Normal, 1 = Locked Out
BI10132Circuit 2 Lockout ExternalRead0 = Normal, 1 = Locked Out
BI10133Circuit 1 Lockout ActiveRead0 = Normal, 1 = Locked Out
BI10134Circuit 2 Lockout ActiveRead0 = Normal, 1 = Locked Out
BI10135Circuit 1 AvailableRead0 = Unavailable, 1 = Available
BI10136Circuit 2 AvailableRead0 = Unavailable, 1 = Available
BI10137Circuit 1 Running StatusRead0 = Off, 1 = On
BI10138Circuit 2 Running StatusRead0 = Off, 1 = On
BI11000Comm Loss: Percent Capacity OutputRead0 = Normal, 1 = In Alarm
BI11001Comm Loss: Supplemental Heater Relay 1Read0 = Normal, 1 = In Alarm
BI11002Comm Loss: Supplemental Heater Relay 2Read0 = Normal, 1 = In Alarm
BI11003Comm Loss: Supplemental Heater Relay 3Read0 = Normal, 1 = In Alarm
BI11004Comm Loss: Supplemental Heater Relay 4Read0 = Normal, 1 = In Alarm
BI11005Comm Loss: Energy MeterRead0 = Normal, 1 = In Alarm
BI11006Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11007Comm Loss: Phase Protection Fault InputRead0 = Normal, 1 = In Alarm
BI11008Diagnostic: Energy Meter Write Value FailureRead0 = Normal, 1 = In Alarm
BI11009Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11010Diagnostic: Phase Protection FaultRead0 = Normal, 1 = In Alarm
BI11011Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11012Diagnostic: Software Error 1002: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11013Diagnostic: Software Error 1003: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11014Diagnostic: Pumpdown Terminated By Time - Ckt1Read0 = Normal, 1 = In Alarm
BI11015Diagnostic: Pumpdown Terminated By Time - Ckt2Read0 = Normal, 1 = In Alarm
BI11016Comm Loss: Discharge Pressure Transducer - Ckt1Read0 = Normal
BI11017Comm Loss: Discharge Pressure Transducer - Ckt2Read0 = Normal, 1 = In Alarm
BI11018Comm Loss: Discharge Temperature Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11019Comm Loss: Discharge Temperature Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11020Comm Loss: External Ckt1 LockoutRead0 = Normal, 1 = In Alarm
BI11021Comm Loss: External Ckt2 LockoutRead0 = Normal, 1 = In Alarm
BI11022Comm Loss: Reversing Valve - Ckt1Read0 = Normal, 1 = In Alarm
BI11023Comm Loss: Reversing Valve - Ckt2Read0 = Normal, 1 = In Alarm
BI11024Comm Loss: Suction Pressure Transducer - Ckt1Read0 = Normal, 1 = In Alarm
BI11025Comm Loss: Suction Pressure Transducer - Ckt2Read0 = Normal, 1 = In Alarm
BI11026Comm Loss: Suction Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11027Comm Loss: Suction Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11028Diagnostic: Discharge Pressure Transducer - Ckt1Read0 = Normal, 1 = In Alarm
BI11029Diagnostic: Discharge Pressure Transducer - Ckt2Read0 = Normal, 1 = In Alarm
BI11030Diagnostic: Discharge Temperature Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11031Diagnostic: Discharge Temperature Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11032Diagnostic: Suction Pressure Transducer - Ckt1Read0 = Normal, 1 = In Alarm
BI11033Diagnostic: Suction Pressure Transducer - Ckt2Read0 = Normal, 1 = In Alarm
BI11034Diagnostic: Suction Temperature Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11035Diagnostic: Suction Temperature Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11036Comm Loss: Subcooler Shutoff Valve Relay - Ckt1Read0 = Normal, 1 = In Alarm
BI11037Comm Loss: Subcooler Shutoff Valve Relay - Ckt2Read0 = Normal, 1 = In Alarm
BI11038Comm Loss: Receiver Fill Valve Relay - Ckt1Read0 = Normal, 1 = In Alarm
BI11039Comm Loss: Receiver Fill Valve Relay - Ckt2Read0 = Normal, 1 = In Alarm
BI11040Diagnostic: High Compressor Pressure Differential - Ckt1Read0 = Normal, 1 = In Alarm
BI11041Diagnostic: High Compressor Pressure Differential - Ckt2Read0 = Normal, 1 = In Alarm
BI11042Diagnostic: High Discharge Refrigerant Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11043Diagnostic: High Discharge Refrigerant Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11044Diagnostic: High Discharge Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11045Diagnostic: High Discharge Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11046Diagnostic: High Discharge Temperature Lockout - Ckt1Read0 = Normal, 1 = In Alarm
BI11047Diagnostic: High Discharge Temperature Lockout - Ckt2Read0 = Normal, 1 = In Alarm
BI11048Diagnostic: Loss of Charge - Ckt1Read0 = Normal, 1 = In Alarm
BI11049Diagnostic: Loss of Charge - Ckt2Read0 = Normal, 1 = In Alarm
BI11050Diagnostic: Low Discharge Saturated Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11051Diagnostic: Low Discharge Saturated Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11052Diagnostic: Low Refrigerant Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11053Diagnostic: Low Refrigerant Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11054Diagnostic: Low Suction Refrigerant Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11055Diagnostic: Low Suction Refrigerant Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11056Diagnostic: Low Suction Superheat - Ckt1Read0 = Normal, 1 = In Alarm
BI11057Diagnostic: Low Suction Superheat - Ckt2Read0 = Normal, 1 = In Alarm
BI11058Diagnostic: Suction Temperature Too High - Ckt1Read0 = Normal, 1 = In Alarm
BI11059Diagnostic: Suction Temperature Too High - Ckt2Read0 = Normal, 1 = In Alarm
BI11060Diagnostic: Very Low Suction Pressure - Circuit 1Read0 = Normal, 1 = In Alarm
BI11061Diagnostic: Very Low Suction Pressure - Circuit 2Read0 = Normal, 1 = In Alarm
BI11062Diagnostic: Low Differential Refrigerant Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11063Diagnostic: Low Differential Refrigerant Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11064Comm Loss: Compressor 1A Fault InputRead0 = Normal, 1 = In Alarm
BI11065Comm Loss: Compressor 1B Fault InputRead0 = Normal, 1 = In Alarm
BI11066Comm Loss: Compressor 1C Fault InputRead0 = Normal, 1 = In Alarm
BI11067Diagnostic: Compressor 1A FaultRead0 = Normal, 1 = In Alarm
BI11068Diagnostic: Compressor 1B FaultRead0 = Normal, 1 = In Alarm
BI11069Diagnostic: Compressor 1C FaultRead0 = Normal, 1 = In Alarm
BI11070Diagnostic: Compressor 1A Fault LockoutRead0 = Normal, 1 = In Alarm
BI11071Diagnostic: Compressor 1B Fault LockoutRead0 = Normal, 1 = In Alarm
BI11072Diagnostic: Compressor 1C Fault LockoutRead0 = Normal, 1 = In Alarm
BI11073Diagnostic: Starts/Hours Modified 1ARead0 = Normal, 1 = In Alarm
BI11074Diagnostic: Starts/Hours Modified 1BRead0 = Normal, 1 = In Alarm
BI11075Diagnostic: Starts/Hours Modified 1CRead0 = Normal, 1 = In Alarm
BI11076Comm Loss: Compressor 2A Fault InputRead0 = Normal, 1 = In Alarm
BI11077Comm Loss: Compressor 2B Fault InputRead0 = Normal, 1 = In Alarm
BI11078Comm Loss: Compressor 2C Fault InputRead0 = Normal, 1 = In Alarm
BI11079Diagnostic: Compressor 2A FaultRead0 = Normal, 1 = In Alarm
BI11080Diagnostic: Compressor 2B FaultRead0 = Normal, 1 = In Alarm
BI11081Diagnostic: Compressor 2C FaultRead0 = Normal, 1 = In Alarm
BI11082Diagnostic: Compressor 2A Fault LockoutRead0 = Normal, 1 = In Alarm
BI11083Diagnostic: Compressor 2B Fault LockoutRead0 = Normal, 1 = In Alarm
BI11084Diagnostic: Compressor 2C Fault LockoutRead0 = Normal, 1 = In Alarm
BI11085Diagnostic: Starts/Hours Modified 2ARead0 = Normal, 1 = In Alarm
BI11086Diagnostic: Starts/Hours Modified 2BRead0 = Normal, 1 = In Alarm
BI11087Diagnostic: Starts/Hours Modified 2CRead0 = Normal, 1 = In Alarm
BI11088Comm Loss: High Pressure Cutout Switch - Ckt1Read0 = Normal, 1 = In Alarm
BI11089Comm Loss: High Pressure Cutout Switch - Ckt2Read0 = Normal, 1 = In Alarm
BI11090Diagnostic: High Pressure Cutout - Ckt1Read0 = Normal, 1 = In Alarm
BI11091Diagnostic: High Pressure Cutout - Ckt2Read0 = Normal, 1 = In Alarm
BI11092Comm Loss: Evaporator Antifreeze HeaterRead0 = Normal, 1 = In Alarm
BI11093Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11094Diagnostic: Evaporator Water Flow Lost LockoutRead0 = Normal, 1 = In Alarm
BI11095Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11096Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11097Diagnostic: High Suction Rfgt PressureRead0 = Normal, 1 = In Alarm
BI11098Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11099Diagnostic: Inverted Water Temp (Heating)Read0 = Normal, 1 = In Alarm
BI11100Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11101Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11102Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11103Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11104Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11105Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11106Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11107Comm Loss: Cooling EXV - Ckt1Read0 = Normal, 1 = In Alarm
BI11108Comm Loss: Cooling EXV - Ckt2Read0 = Normal, 1 = In Alarm
BI11109Comm Loss: Electronic Expansion Valve - Ckt1Read0 = Normal, 1 = In Alarm
BI11110Comm Loss: Electronic Expansion Valve - Ckt2Read0 = Normal, 1 = In Alarm
BI11111Comm Loss: Heating EXV - Ckt1Read0 = Normal, 1 = In Alarm
BI11112Comm Loss: Heating EXV - Ckt2Read0 = Normal, 1 = In Alarm
BI11113Comm Loss: Auxiliary Setpoint CommandRead0 = Normal, 1 = In Alarm
BI11114Comm Loss: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11115Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11116Comm Loss: Ext Noise Reduction RequestRead0 = Normal, 1 = In Alarm
BI11117Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11118Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11119Comm Loss: External Hot Water CommandRead0 = Normal, 1 = In Alarm
BI11120Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11122Diagnostic: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11123Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11124Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11125Comm Loss: Condenser Fan Enable - Ckt1Read0 = Normal, 1 = In Alarm
BI11126Comm Loss: Condenser Fan Enable - Ckt2Read0 = Normal, 1 = In Alarm
BI11127Comm Loss: Condenser Fan Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11128Comm Loss: Condenser Fan Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11129Comm Loss: Fan Inverter Speed Command - Ckt1Read0 = Normal, 1 = In Alarm
BI11130Comm Loss: Fan Inverter Speed Command - Ckt2Read0 = Normal, 1 = In Alarm
BI11131Diagnostic: Condenser Fan Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11132Diagnostic: Condenser Fan Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11133Comm Loss: Comm Loss: Fan Inverter Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11134Comm Loss: Comm Loss: Fan Inverter Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11135Diagnostic: Fan Inverter Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11136Diagnostic: Fan Inverter Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11137Comm Loss: Noise Reduction Request RelayRead0 = Normal, 1 = In Alarm
BI11140Comm Loss: Heat Recovery Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11141Comm Loss: Heat Recovery Leaving Water TemperatureRead0 = Normal, 1 = In Alarm
BI11144Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11145Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11147Diagnostic: No Partial Heat Recovery - Ckt1Read0 = Normal, 1 = In Alarm
BI11148Diagnostic: No Partial Heat Recovery - Ckt2Read0 = Normal, 1 = In Alarm
BI11149Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11156Comm Loss: Run Command Compressor 1ARead0 = Normal, 1 = In Alarm
BI11157Comm Loss: Run Command Compressor 1BRead0 = Normal, 1 = In Alarm
BI11158Comm Loss: Run Command Compressor 1CRead0 = Normal, 1 = In Alarm
BI11159Comm Loss: Run Command Compressor 2ARead0 = Normal, 1 = In Alarm
BI11160Comm Loss: Run Command Compressor 2BRead0 = Normal, 1 = In Alarm
BI11161Comm Loss: Run Command Compressor 2CRead0 = Normal, 1 = In Alarm
BI11162Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11163Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11164Comm Loss: Evap Pump Inv1 Fault InputRead0 = Normal, 1 = In Alarm
BI11165Comm Loss: Evap Pump Inv1 Freq FeedbackRead0 = Normal, 1 = In Alarm
BI11166Comm Loss: Evap Pump Inv1 Run CommandRead0 = Normal, 1 = In Alarm
BI11167Comm Loss: Evaporator Pump 1 Fault InputRead0 = Normal, 1 = In Alarm
BI11168Comm Loss: Evaporator Pump 2 Fault InputRead0 = Normal, 1 = In Alarm
BI11169Comm Loss: Evaporator Water Pump 1 RelayRead0 = Normal, 1 = In Alarm
BI11170Comm Loss: Evaporator Water Pump 2 RelayRead0 = Normal, 1 = In Alarm
BI11171Diagnostic: Evaporator Pump 1 Starts/Hours ModifiedRead0 = Normal, 1 = In Alarm
BI11172Diagnostic: Evaporator Pump 2 Starts/Hours ModifiedRead0 = Normal, 1 = In Alarm
BI11173Diagnostic: Evaporator Pump 1 FaultRead0 = Normal, 1 = In Alarm
BI11174Diagnostic: Evaporator Pump 2 FaultRead0 = Normal, 1 = In Alarm
BI11175Diagnostic: Evaporator Water Flow Lost - Pump1Read0 = Normal, 1 = In Alarm
BI11176Diagnostic: Evaporator Water Flow Lost - Pump2Read0 = Normal, 1 = In Alarm
BI11177Diagnostic: Evaporator Water Flow Overdue - Pump1Read0 = Normal, 1 = In Alarm
BI11178Diagnostic: Evaporator Water Flow Overdue - Pump2Read0 = Normal, 1 = In Alarm
BI11179Diagnostic: Evaporator Water Flow Too LowRead0 = Normal, 1 = In Alarm
BI11180Diagnostic: Power Factor Correction FaultRead0 = Normal, 1 = In Alarm
BI11181Comm Loss: Power Factor Correction Fault InputRead0 = Normal, 1 = In Alarm
BV10100Reset DiagnosticWrite0 = Normal, 1 = Reset
BV10101Noise Reduction Request BASWrite0 = Normal, 1 = Reduce Noise
BV10102Heat Recovery RequestWrite0 = Off, 1 = On
BV10103Energy Consumption ResetWrite0 = Accumulating, 1 = Reset
BV10104Circuit 1 Lockout BASWrite0 = Normal, 1 = Locked Out
BV10105Circuit 2 Lockout BASWrite0 = Normal, 1 = Locked Out
BVmin10106Chiller Auto Stop Command BASWrite0 = Stop, 1 = Auto
MI10100Running ModeRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10102Chiller Setpoint SourceRead1 = BAS, 2 = External, 3 = Front Panel
MI10103Refrigerant TypeRead1 = R-11, 2 = R-12, 3= R-22, 4= R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(e), 15 = R-514A, 16 = R-1234ze(e), 17 = R-454B, 18 = R-515B
MI10104Cooling TypeRead1 = Water Cooled, 2 = Air Cooled
MI10105Manufacturing LocationRead1 = Field Applied, 2= La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey, 19 = Bari
MI10106Model Information GEN2Read1 = CVHF, 2 = CVGF, 3= CVHS, 4= RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTWE, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = AXCA, 35 = CMAF, 36 = ACRB Large, 37 = ACRB Small, 38 = CVHE, 39 = CVHG, 40 = CVHL, 41 = RTWF XSE, 42 = CGWF, 43 = CDHG, 44 = ACCA, 45 = RTWD, 46 = RTUD, 47 = CXWF, 48 = CCUF, 49 = RTHG, 50 = CGAM, 51 = CXAM
MVmin10100Chiller Mode Command BASWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CGAM and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 CGAM

How many BACnet points does the Trane Symbio 800 CGAM have?

This list has 301 BACnet objects: 73 analog inputs, 4 analog values, 209 binary inputs, 7 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 CGAM BACnet points are writable?

12 of the 301 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 CGAM BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - CGAM (BAS-PTS019A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS019A-EN_11152024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 CGAM?

Start with BV 10106 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10114 Chiller Running State (Chiller on/off status); BI 10106 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10101 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10126 Actual Running Capacity (Actual running capacity in percent); BI 10123 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 CGAM?

BV 10106 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10104 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10105 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10106 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

How do I check these points on the real Symbio 800 CGAM?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - CGAM · BAS-PTS019A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.