Split system controller · BACnet points list

Trane Symbio 800 IntelliCore Split System (RAUK) BACnet points list

Updated 28 October 2026

Short answer

The Symbio 800 on IntelliCore RAUK split systems exposes about 135 objects with 5-digit instances (AI-10101...). Many points depend on unit size (second circuit from 40 T, third compressor on some sizes), on the system control type (no system control, supply-air VAV or EVP) and on the power-monitoring option. The BAS writes auto/stop, discharge cooling setpoint, demand limit, lockouts and the discharge and outdoor air temperatures.

This page lists 136 BACnet objects for the Trane Symbio 800 IntelliCore Split System (RAUK) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 IntelliCore Split System (RAUK)
Equipment
Split system controller
Equipment type
VRF & split air conditioners
BACnet objects
136 (16 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
62000844-1-00-0003
Also known as
IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036
Source document
Symbio 800 Integration Points List BACnet/Modbus - IntelliCore Split System (RAUK) · BAS-PTS036A-EN · rev. 12/04/2024
Download CSV 136 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 IntelliCore Split System (RAUK)

Integration in brief

Use BV 10140 Auto Stop Command BAS to run or stop the unit. On supply-air VAV or EVP units write AV 10121 Discharge Cooling Setpoint BAS; to limit capacity set AV 10163 Demand Limit Setpoint and turn on BV 10116 Demand Limit Request BAS. MI 10119 Arbitration Method must read Full Source for BAS values to be used. Sensor BAS points carry a 900 s heartbeat.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10140Auto Stop Command BASBMS auto/stop command (0 = Stop, 1 = Auto)Write
AV 10121Discharge Cooling Setpoint BASDischarge air cooling setpoint (VAV/EVP control)Write
AV 10163Demand Limit SetpointDemand limit from the BMS, %Write
BV 10116Demand Limit Request BASMust be Limited for the demand limit to applyWrite
MI 10119Arbitration MethodMust read Full Source for BAS values to be usedRead
MI 10140Unit StatusOff, waiting or cooling runningRead
AI 10101Cooling Capacity StatusActual cooling capacity, %Read
AI 10124Discharge TemperatureDischarge temperature in useRead
BI 10176Diagnostic PresentSummary alarmRead

Enable & remote start

BV 10140 Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10211 Equipment Stop Status reports the hardwired auto/stop input and BI 13000 Front Panel Auto Stop Status the local setting; BI 10210 shows an emergency stop that needs a manual reset. The integration guide describes the arbitration method: with Full the BMS value is used ahead of local or default values, with Local BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active.

Heartbeat & communication loss

The points list gives a 900 s heartbeat for AV 10111 Discharge Temperature BAS and AV 10113 Outdoor Air Temperature BAS; the other AVs list 0. The documents don't describe what happens when it expires.

Sensors & values from the BMS

Write AV 10113 Outdoor Air Temperature BAS or AV 10111 Discharge Temperature BAS and keep refreshing them within the heartbeat. AV 10103 and AV 10101 (Arbitrator) show every source in their priority array, and AI 10118 Outdoor Air Temperature Active and AI 10124 Discharge Temperature show the value in use. The guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor.

Network setup

Watch out for

Trane Symbio 800 IntelliCore Split System (RAUK) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

136 of 136 shown
Type
Access
Show
Trane Symbio 800 IntelliCore Split System (RAUK) BACnet Points List
DescriptionStates
AImin10101Cooling Capacity StatusActual operating unit cooling capacity%Read
AI10111Outdoor Air Damper PositionRequested position of the Outdoor Air Damper%Read
AI10118Outdoor Air Temperature ActiveActive outdoor air temperature currently being used by the controller°FRead
AI10121Discharge Cooling Setpoint ActiveDischarge temperature cooling setpoint value resulting from arbitration°FRead
AImin10124Discharge TemperatureActual discharge temperature being used by the controller°FRead
AI10154Economizer Minimum Position Setpoint ActiveEconomizer minimum position setpoint value resulting from arbitration%Read
AI10156Outdoor Air Temperature LocalOutdoor air temperature value from a sensor connected to the controller°FRead
AI10161Condenser CapacityStatus of the unit condenser capacity%Read
AI10181Discharge Temperature LocalDischarge temperature value from a sensor connected to the controller°FRead
AI10206Number of CircuitsNumber of refrigeration circuits in the unitRead
AI10207Number of Compressors Circuit 1Number of compressors on DX circuit 1 of the unitRead
AI10208Number of Compressors Circuit 2Number of compressors on DX circuit 2 of the unitRead
AI10224Average CurrentAmpsRead
AI10227Run Time - Compressor 1ARun time of Compressor 1AsecondsRead
AI10228Starts - Compressor 1ANumber of starts for Compressor 1ARead
AI10229Run Time - Compressor 1BRun time of Compressor 1BsecondsRead
AI10230Starts - Compressor 1BNumber of starts for Compressor 1BRead
AI10231Run Time - Compressor 1CRun time of Compressor 1CsecondsRead
AI10232Starts - Compressor 1CNumber of starts for Compressor 1CRead
AI10233Run Time - Compressor 2ARun time of Compressor 2AsecondsRead
AI10234Starts - Compressor 2ANumber of starts for Compressor 2ARead
AI10235Run Time - Compressor 2BRun time of Compressor 2BsecondsRead
AI10236Starts - Compressor 2BNumber of starts for Compressor 2BRead
AI10237Run Time - Compressor 2CRun time of Compressor 2CsecondsRead
AI10238Starts - Compressor 2CNumber of starts for Compressor 2CRead
AI10239Current L1Current for line/leg 1AmpsRead
AI10240Current L2Current for line/leg 2AmpsRead
AI10241Current L3Current for line/leg 3AmpsRead
AI10242Current NeutralCurrent for neutralAmpsRead
AI10243Discharge Cooling Setpoint StatusActual discharge temperature cooling setpoint value°FRead
AI10246Discharge Gauge Pressure Circuit 1Refrigerant discharge gauge pressure for DX circuit 1PSIRead
AI10247Discharge Gauge Pressure Circuit 2Refrigerant discharge gauge pressure for DX circuit 2PSIRead
AI10249Energy Consumption LifetimeTotal energy consumption of the unit (for the lifetime)kWhRead
AI10255Line FrequencyLine frequency when the optional power monitoring option is includedRead
AI10258Power FactorReported power factor from the optional power monitoring option, when applicableRead
AI10262Suction Gauge Pressure Circuit 1Gauge suction pressure for DX circuit 1, in PSIGPSIRead
AI10263Suction Gauge Pressure Circuit 2Gauge suction pressure for DX circuit 2, in PSIGPSIRead
AI10268Total Apparent EnergyTotal apparent energy as reported by the optional power monitoring featurekWhRead
AI10269Energy ConsumptionTotal energy consumption of the unit (since last accumulation reset)kWhRead
AI10270Total Reactive EnergyTotal reactive energy as reported by the optional power monitoring featurekWhRead
AI10271Total Real PowerTotal real power as reported by the optional power monitoring featurekWhRead
AI10272Total Apparent PowerTotal apparent power as reported by the optional power monitoring featurekWhRead
AI10273Total Reactive PowerTotal reactive power as reported by the optional power monitoring featurekWhRead
AI10275Voltage L1-L2Voltage between line/leg L1 and L2VoltsRead
AI10276Voltage L1-L3Voltage between line/leg L1 and L3VoltsRead
AI10277Voltage L1-NVoltage between line/leg L1 and NeutralVoltsRead
AI10278Voltage L2-L3Voltage between line/leg L2 and L3VoltsRead
AI10279Voltage L2-NVoltage between line/leg L2 and NeutralVoltsRead
AI10280Voltage L3-NVoltage between line/leg L3 and NeutralVoltsRead
AI10282Air Flow Percentage Circuit 1Requested condenser percentage for circuit 1%Read
AI10283Air Flow Percentage Circuit 2Requested condenser percentage for circuit 2%Read
AI10284Discharge Saturated Refrigerant Temperature Circuit 1Discharge saturation temperature for DX circuit 1°FRead
AI10285Discharge Saturated Refrigerant Temperature Circuit 2Discharge saturation temperature for DX circuit 2°FRead
AI10286Suction Saturated Refrigerant Temperature Circuit 1Suction saturated refrigerant temperature for DX circuit 1°FRead
AI10287Suction Saturated Refrigerant Temperature Circuit 2Suction saturated refrigerant temperature for DX circuit 2°FRead
AI10288Suction Temperature Ckt1Suction temperature for DX circuit 1°FRead
AI10290Suction Temperature Ckt2Suction temperature for DX circuit 2°FRead
AI10324Run Time - Compressor 1A (Hours)Run time of Compressor 1A, in hoursHoursRead
AI10325Run Time - Compressor 1B (Hours)Run time of Compressor 1B, in hoursHoursRead
AI10326Run Time - Compressor 1C (Hours)Run time of Compressor 1C, in hoursHoursRead
AI10327Run Time - Compressor 2A (Hours)Run time of Compressor 2A, in hoursHoursRead
AI10328Run Time - Compressor 2B (Hours)Run time of Compressor 2B, in hoursHoursRead
AI10329Run Time - Compressor 2C (Hours)Run time of Compressor 2C, in hoursHoursRead
AI10330Discharge Pressure Circuit 1Refrigerant discharge absolute pressure for DX circuit 1, in PSIAPSIRead
AI10331Discharge Pressure Circuit 2Refrigerant discharge absolute pressure for DX circuit 2, in PSIAPSIRead
AI10332Suction Pressure Circuit 1Absolute suction pressure for DX circuit 1, in PSIAPSIRead
AI10333Suction Pressure Circuit 2Absolute suction pressure for DX circuit 2, in PSIAPSIRead
AI10400Local Atmospheric PressureStatus of the Local Atmospheric Pressure SettingPSIRead
AI10401Unit Design CapacityDesign capacity for the UnitkWhRead
AI10402Ctrl Box Ventilation Fan Run TimeRun time of Control Box FanHoursRead
AV10101Discharge Temperature ArbitratorActual discharge temperature being used by the controller°FWrite
AV10103Outdoor Air Temperature ArbitratorActual outdoor air temperature being used by the controller°FWrite
AV10111Discharge Temperature BASDischarge temperature sensor value°FWrite
AV10113Outdoor Air Temperature BASOutdoor air temperature sensor value°FWrite
AVmin10121Discharge Cooling Setpoint BASDischarge air temperature cooling setpoint value°FWrite
AV10139Cooling Capacity EnableDeman limit the cooling capacity%Write
AV10144Economizer Minimum Position Setpoint BASEconomizer minimum position setpoint%Write
AV10150Economizer Outdoor Air Enable Setpoint BAS°FWrite
AVmin10163Demand Limit SetpointDemand limit the unit%Write
BI10001microSDA micro SD card is presentRead0 = MicroSD card is not present, 1 = MicroSD card is present
BI10002USB Port 1A USB device is present in port 1Read0 = USB device is not present, 1 = USB device is present
BI10003USB Port 2A USB device is present in port 2Read0 = USB device is not present, 1 = USB device is present
BI10004USB Port 3A USB device is present in port 3Read0 = USB device is not present, 1 = USB device is present
BI10005USB Port 4A USB device is present in port 4Read0 = USB device is not present, 1 = USB device is present
BI10105FDD: Unit Economizing When It Should NotFDD: Indicates when the unit is economizing but should not beRead0 = Inactive, 1 = Active
BI10106FDD: Unit Not Economizing When it Should BeFDD: Indicates when the unit is not economizing but should beRead0 = Inactive, 1 = Active
BI10111Compressor 1A StatusOperating status of compressor 1ARead0 = Off, 1 = Running
BI10112Compressor 1B StatusOperating status of compressor 1BRead0 = Off, 1 = Running
BI10113Compressor 1C StatusOperating status of compressor 1CRead0 = Off, 1 = Running
BI10114Compressor 2A StatusOperating status of compressor 2ARead0 = Off, 1 = Running
BI10115Compressor 2B StatusOperating status of compressor 2BRead0 = Off, 1 = Running
BI10116Compressor 2C StatusOperating status of compressor 2CRead0 = Off, 1 = Running
BI10132FDD: Outdoor Air Temperature Sensor FailureFDD: Indicates when the outdoor air temperature sensor has failedRead0 = Inactive, 1 = Active
BI10155Rapid Restart StatusActive status of the Rapid Restart eventRead0 = Inactive, 1 = Active
BI10164Coil Frost Protection Status Circuit 1Active when actively in coil frost protection for circuit 1Read0 = Inactive, 1 = Active
BI10165Coil Frost Protection Status Circuit 2Active when actively in coil frost protection for circuit 2Read0 = Inactive, 1 = Active
BImin10176Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10202Condenser Fan Circuit 1 Relay 1 StatusStatus of condenser fan circuit 1, relay 1Read0 = Off, 1 = On
BI10203Condenser Fan Circuit 1 Relay 2 StatusStatus of condenser fan circuit 1, relay 2Read0 = Off, 1 = On
BI10204Condenser Fan Circuit 1 Relay 3 StatusStatus of condenser fan circuit 1, relay 3Read0 = Off, 1 = On
BI10205Condenser Fan Circuit 1 Relay 4 StatusStatus of condenser fan circuit 1, relay 4Read0 = Off, 1 = On
BI10206Condenser Fan Circuit 2 Relay 1 StatusStatus of condenser fan circuit 2, relay 1Read0 = Off, 1 = On
BI10207Condenser Fan Circuit 2 Relay 2 StatusStatus of condenser fan circuit 2, relay 2Read0 = Off, 1 = On
BI10208Condenser Fan Circuit 2 Relay 3 StatusStatus of condenser fan circuit 2, relay 3Read0 = Off, 1 = On
BI10209Condenser Fan Circuit 2 Relay 4 StatusStatus of condenser fan circuit 2, relay 4Read0 = Off, 1 = On
BI10210Emergency StopStatus of the emergency stop function of the unitRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10211Equipment Stop StatusStatus of the externally- wired auto/stop inputRead0 = Stop, 1 = Auto
BI10218Diagnostic: Manual Reset RequiredA diagnostic exists that requires manual resetRead0 = Normal, 1 = In Alarm
BI10219Economizer Airside StatusStatus of airside economizingRead0 = Inactive, 1 = Active
BI10605Diagnostic: Loss of Charge Lockout Ckt1A loss of charge lockout diagnostic exists for DX circuit 1Read0 = No, 1 = Yes
BI10606Diagnostic: Loss of Charge Lockout Ckt2A loss of charge lockout diagnostic exists for DX circuit 2Read1 = No, 1 = Yes
BI10619Diagnostic Shutdown PresentUnit is shut down due to diagnosticsRead0 = Normal, 1 = In Alarm
BI10620Diagnostic: Local Manual Reset RequiredDiagnostic Reset required [Local only]Read0 = Normal, 1 = In Alarm
BI13000Front Panel Auto Stop StatusStatus of the the Local Auto Stop settingRead0 = Stop, 1 = Auto
BI13002Manual Override ExistsIndicator of a Manual Override being activeRead0 = Off, 1 = On
BI13003Frostat Input Status Circuit 1Status of the Frostat input, circuit 1Read0 = Open, 1 = Closed
BI13004Frostat Input Status Circuit 2Status of the Frostat input, circuit 2Read0 = Open, 1 = Closed
BI13005Freezestat Input StatusStatus of the Freezestat InputRead0 = Open, 1 = Closed
BI13006Refrigerant Leak DetectionActive status of a refrigerant leak eventRead0 = Open, 1 = Closed
BV10110Reset DiagnosticRequest to reset any remote controller diangosticWrite0 = Normal, 1 = Reset
BV10115Cooling Lockout BASCommand to (temporarily) prevent all mechanical coolingWrite0 = Normal, 1 = Locked Out
BVmin10116Demand Limit Request BASDemand limit the unitWrite0 = Not Limited, 1 = Limited
BV10117Energy Consumption ResetReset the energy consumption accumulated totalWrite0 = Accumulating, 1 = Reset
BV10120Rapid Restart EnableEnables/Disables rapid restart operationWrite0 = Disable, 1 = Enable
BVmin10140Auto Stop Command BASBAS Auto Stop CommandWrite0 = Stop, 1 = Auto
MI10105Cooling Reset Type StatusType of cooling reset used by the controllerRead1 = None, 2 = Outdor Air
MI10108Economizer TypeGeneral description of the type of economizer systemRead1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/Sensor, 9 = Waterside Economizer and TRAQ
MI10109Condenser TypeGeneral description of the equipment condenser systemRead1 = None, 2 = Air Cooled Condenser, 3 = Water Cooled Condenser, 4 = Evaporative Condenser
MI10117Refrigerant TypeType of refrigerant used in the equipmentRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134A, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E), 17 = R-454B
MImin10119Arbitration MethodRead1 = Full Source, 2 = Local Source, 3 = Default Source
MI10121Electrical Service TypeElectrical service type used for the unitRead1 = A+N, 2 = A+B, 3 = A+B+N, 4 = A+B+C, 5 = A+B+C+N
MI10132Economizer Decision MethodMethod of enabling airside economizingRead1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy
MImin10140Unit StatusRead1 = Off, 2 = Waiting, 3 = Running
MI10144Economizer System StatusStatus of enabling economizingRead1 = Disabled, 2 = Enabled, 3 = Not Present
MI10145Model Information [GEN2]Model InformationRead64 = RAUK
MV10103Economizer Airside Enable BASEnable airside economizingWrite1 = Disabled, 2 = Enabled, 3 = Auto

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 IntelliCore Split System (RAUK) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 IntelliCore Split System (RAUK)

How many BACnet points does the Trane Symbio 800 IntelliCore Split System (RAUK) have?

This list has 136 BACnet objects: 70 analog inputs, 9 analog values, 40 binary inputs, 6 binary values, 10 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 IntelliCore Split System (RAUK) BACnet points are writable?

16 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane Symbio 800 IntelliCore Split System (RAUK) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet/Modbus - IntelliCore Split System (RAUK) (BAS-PTS036A-EN), revision 12/04/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS036A-EN_12042024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 IntelliCore Split System (RAUK)?

Start with BV 10140 Auto Stop Command BAS (BMS auto/stop command (0 = Stop, 1 = Auto)); AV 10121 Discharge Cooling Setpoint BAS (Discharge air cooling setpoint (VAV/EVP control)); AV 10163 Demand Limit Setpoint (Demand limit from the BMS, %); BV 10116 Demand Limit Request BAS (Must be Limited for the demand limit to apply); MI 10119 Arbitration Method (Must read Full Source for BAS values to be used); MI 10140 Unit Status (Off, waiting or cooling running); AI 10101 Cooling Capacity Status (Actual cooling capacity, %); AI 10124 Discharge Temperature (Discharge temperature in use); BI 10176 Diagnostic Present (Summary alarm).

How do I enable BMS control of the Trane Symbio 800 IntelliCore Split System (RAUK)?

BV 10140 Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10211 Equipment Stop Status reports the hardwired auto/stop input and BI 13000 Front Panel Auto Stop Status the local setting; BI 10210 shows an emergency stop that needs a manual reset. The integration guide describes the arbitration method: with Full the BMS value is used ahead of local or default values, with Local BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active.

Does the Trane Symbio 800 IntelliCore Split System (RAUK) need a BACnet heartbeat or have a communication timeout?

The points list gives a 900 s heartbeat for AV 10111 Discharge Temperature BAS and AV 10113 Outdoor Air Temperature BAS; the other AVs list 0. The documents don't describe what happens when it expires.

Can the BMS supply sensor values to the Trane Symbio 800 IntelliCore Split System (RAUK)?

Write AV 10113 Outdoor Air Temperature BAS or AV 10111 Discharge Temperature BAS and keep refreshing them within the heartbeat. AV 10103 and AV 10101 (Arbitrator) show every source in their priority array, and AI 10118 Outdoor Air Temperature Active and AI 10124 Discharge Temperature show the value in use. The guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor.

How do I check these points on the real Symbio 800 IntelliCore Split System (RAUK)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet/Modbus - IntelliCore Split System (RAUK) · BAS-PTS036A-EN · rev. 12/04/2024. Object names, instances and units are reproduced as published; descriptions are our own.