VAV box controller · BACnet points list
Trane Symbio 210 VAV BACnet points list
Updated 4 November 2026
The Symbio 210 is Trane's programmable VAV box controller. With the factory VAV program it exposes about 120 objects with short instances (AI 1, AV 14, MV 6...). The BAS sends setpoints, sensor values and occupancy through the '... BAS' and '... Request' objects; the BAS value objects ship Out of Service and must be put In Service before the controller uses them. Which objects exist depends on the application (STC, VFC or FTC) and the heat and fan options.
This page lists 118 BACnet objects for the Trane Symbio 210 VAV — 60 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 210 VAV
- Equipment
- VAV box controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 118 (60 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 210 VAV
Write occupancy to MV 6 Occupancy Request and the space setpoint to AV 27 Space Temperature Setpoint BAS after putting it In Service. Read AV 59 Space Temperature Active, AV 20 Discharge Air Flow and AV 13 Air Flow Setpoint Active. If the BMS supplies space temperature or CO2, put AV 14/AV 22 In Service and rewrite them every 15 minutes.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 6 | Occupancy Request | Occupancy command from the BMS | Write |
| MV 4 | Heat Cool Mode Request | Heat/cool mode command from the BMS | Write |
| AV 27 | Space Temperature Setpoint BAS | Space setpoint; put In Service before writing | Write |
| MV 7 | Occupancy Status | Confirms the occupancy in effect | Read |
| MV 5 | Heat Cool Mode Status | Current heat/cool mode | Read |
| AV 59 | Space Temperature Active | Space temperature used for control | Read |
| AV 13 | Air Flow Setpoint Active | Airflow setpoint in use | Read |
| AV 20 | Discharge Air Flow | Measured box airflow | Read |
| BV 13 | Diagnostic: Flow Sensor Failure | Flow (pressure) sensor fault | Read |
Enable & remote start
No enable point. The '... BAS' value objects ship Out of Service and are ignored until the BMS (or Tracer SC) puts them In Service. Symbio UI (Tools > BAS Control Selection) chooses BAS or Local as the source for each sensor and setpoint.
Heartbeat & communication loss
AV 14 Space Temperature BAS and AV 22 Space CO2 Concentration BAS must be written at least every 15 minutes while In Service; otherwise the controller puts the point in fault.
Sensors & values from the BMS
Space temperature goes to AV 14, CO2 to AV 22 and supply air temperature to AV 29, each after putting the object In Service. AV 59, AV 50 and AV 60 show the values in use. Select BAS as the source in Symbio UI BAS Control Selection.
Network setup
- Three rotary switches set a three-digit address used as both the MS/TP MAC address and the Device ID; valid MAC addresses are 001-127.
- Symbio UI is a web page served over the USB service port at http://198.80.18.1; it sets protocol, IP settings, name, time and system units.
- Changing system units (IP/SI) or protocol settings restarts the controller.
Watch out for
- Writes to BAS objects do nothing while they are Out of Service (the factory default).
- MV 2 Air Flow Override and MV 3 Water Valve Override force the box; release them when done.
- AV 37 Space Temp Setpoint Default and the airflow min/max setpoints are commissioning values, not for cyclic writes.
Trane Symbio 210 VAV BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Space Temperature Local | Temperature sensor in the space | °F or °C | Read | |
| AI | 2 | Space Temperature Setpoint Local | Zone sensor thumbwheel | °F or °C | Read | |
| AI | 3 | Pressure 1 | Pressure across the flow ring (120% flow = 2 in. H2O) | in. H2O or Pa | Read | |
| AI | 4 | Discharge Air Temperature | Discharge air temperature sensor wired to the controller | °F or °C | Read | |
| AI | 5 | Supply Air Temperature Local | Supply air temperature sensor wired to the controller | °F or °C | Read | |
| AI | 6 | Actual Air Valve Position | Air valve position, % open | % | Read | |
| AI | 7 | Actual Reheat Position | Reheat valve position, % open | % | Read | |
| AI | 8 | Space CO2 Concentration Local | Space CO2 concentration in ppm | ppm | Read | |
| AI | 9 | Air Valve 1 Stroke Time | Air valve stroke time, milliseconds | Read | ||
| AI | 10 | Minimum Actuator Time | Air valve minimum actuator time, ms (minimum 500) | Read | ||
| AI | 11 | Water Valve Maximum Stroke Time | Modulating water heat valve stroke time, ms | Read | ||
| AI | 12 | Water Valve Minimum Actuator Time | Water valve minimum actuator time, ms | Read | ||
| AO | 1 | Air Valve Drive Command | Requested air valve position, % open | % | Read | |
| AO | 2 | Supply Fan Speed | Supply fan output; single-speed fans 0% = off, 100% = on | % | Read | |
| AO | 3 | Heating Valve Command | Requested modulating reheat valve position | % | Read | |
| AV | 2 | Air Flow Minimum Setpoint Active | Minimum airflow setpoint in use | in. H2O or Pa | Read | |
| AV | 8 | Air Flow Nominal Status | Nominal airflow set by configurator based on the unit size selected | in. H2O or Pa | Read | |
| AV | 9 | Reheat Enable Point | °F or °C | Write | ||
| AV | 10 | Auto Changeover Point | °F or °C | Write | ||
| AV | 12 | Heat Output Secondary Status | Secondary heat output, % (valve position, PWM capacity or stage) | % | Read | |
| AVmin | 13 | Air Flow Setpoint Active | cfm or L/s | Read | ||
| AV | 14 | Space Temperature BAS | Space temperature from the BAS; Out of Service by default | °F or °C | Write | |
| AV | 15 | Air Flow Override Percent | Write | |||
| AV | 16 | Discharge Air Temperature Setpoint BAS | Discharge air setpoint from the BAS (VFC only) | °F or °C | Write | |
| AV | 18 | Air Flow Gain | Airflow gain from air balancing, default 1.0 | Write | ||
| AV | 19 | Air Flow Measurement Offset | Set when air balancing | % | Write | |
| AVmin | 20 | Discharge Air Flow | Pressure sensor 1 value converted to flow | cfm or L/s | Read | |
| AV | 21 | Outdoor Air Low Limit | VFC freeze protection | °F or °C | Write | |
| AV | 22 | Space CO2 Concentration BAS | Space CO2 from the BAS; Out of Service by default | ppm | Write | |
| AV | 23 | Unoccupied Cooling Setpoint | °F or °C | Write | ||
| AV | 24 | Unoccupied Heating Setpoint | °F or °C | Write | ||
| AV | 25 | Air Flow Setpoint BAS | Communicated airflow setpoint used for flow tracking units | cfm or L/s | Write | |
| AV | 26 | Air Flow Offset | Flow set point of Flow Tracking box relative to supply air VAV box | cfm or L/s | Write | |
| AVmin | 27 | Space Temperature Setpoint BAS | Space setpoint from the BAS; Out of Service by default | °F or °C | Write | |
| AV | 28 | Space Temperature Setpoint Active | Space temperature setpoint being used by algorithm | °F or °C | Read | |
| AV | 29 | Supply Air Temperature BAS | Supply air temperature from the BAS; Out of Service by default | °F or °C | Write | |
| AV | 30 | Occupied Offset | Setpoint offset used during occupied mode | Δ°F or Δ°C | Write | |
| AV | 31 | Air Flow Setpoint Minimum Local Heat | Reheat minimum used when local heat is On | cfm or L/s | Write | |
| AV | 33 | Occupied Bypass Time | Minutes in occupied bypass after a timed override | Write | ||
| AV | 34 | Standby Offset | Setpoint offset used during occupied standby mode | Δ°F or Δ°C | Write | |
| AV | 35 | Ventilation Setpoint Active | cfm or L/s | Read | ||
| AV | 36 | Ventilation Ratio | Required outdoor-air to primary-air ratio, 0-100% | % | Read | |
| AV | 37 | Space Temp Setpoint Default | Default space temperature setpoint stored in the controller and set by service tool | °F or °C | Write | |
| AV | 38 | Ventilation Setpoint Local | cfm or L/s | Write | ||
| AV | 39 | Discharge Air Temp Setpoint Local | Discharge air setpoint from the wired sensor (VFC only) | °F or °C | Write | |
| AV | 40 | Space CO2 Limit | Point where CO2 demand ventilation ends in ppm | ppm | Write | |
| AV | 41 | Space CO2 Low Limit | Point where CO2 demand ventilation begins in ppm | ppm | Write | |
| AV | 42 | Air Flow Setpoint Minimum | cfm or L/s | Write | ||
| AV | 43 | Air Flow Setpoint Minimum Standby | cfm or L/s | Write | ||
| AV | 44 | Air Flow Setpoint Minimum Standby Heat | cfm or L/s | Write | ||
| AV | 45 | Air Flow Setpoint Minimum Heat | cfm or L/s | Write | ||
| AV | 46 | Air Flow Setpoint Maximum Heat | cfm or L/s | Write | ||
| AV | 47 | Air Flow Setpoint Maximum | cfm or L/s | Write | ||
| AV | 48 | Ventilation Setpoint BAS | Ventilation setpoint from the BAS; Out of Service by default | cfm or L/s | Write | |
| AV | 49 | Ventilation Standby Setpoint | cfm or L/s | Write | ||
| AV | 50 | Space CO2 Concentration Active | Space CO2 concentration in ppm, used by algorithm | ppm | Read | |
| AV | 51 | Ventilation Ratio Limit BAS | Ventilation ratio limit from the BAS; Out of Service by default | % | Write | |
| AV | 52 | PD Mode Min Air Valve Position | Minimum air valve position in percent when using pressure dependent control | % | Write | |
| AV | 53 | ECM Fan Correction Factor | ECM fan correction factor (ECM fan only) | Write | ||
| AV | 54 | ECM Fan Maximum Flow | ECM fan maximum flow, factory set | cfm or L/s | Write | |
| AV | 55 | ECM Fan Minimum Flow | ECM fan minimum flow, factory set | cfm or L/s | Write | |
| AV | 56 | ECM Fan Flow Setpoint | ECM fan flow setpoint | cfm or L/s | Write | |
| AV | 57 | Parallel Fan Flow Enable Point | cfm or L/s | Write | ||
| AV | 58 | Parallel Fan Temp Enable Point | Δ°F or Δ°C | Write | ||
| AVmin | 59 | Space Temperature Active | Space temperature being used by algorithm | °F or °C | Read | |
| AV | 60 | Supply Air Temperature Active | °F or °C | Read | ||
| AV | 66 | Cabinet Style | Read | |||
| AV | 67 | Auxiliary Heat Control Request | Auxiliary heat enable - reheat enable | % | Write | |
| AV | 68 | Fan Override BAS | Fan override: 0% off, 1-100% on/ECM speed, 101% = no override | % | Write | |
| AV | 69 | Pressure Sensor Calibration Offset | Zero pressure reading saved during calibration | cfm or L/s | Read | |
| AV | 70 | Fan Air Flow Rating | Fan airflow rating for ECM fan balancing, factory set | cfm or L/s | Write | |
| AV | 74 | Auto Commissioning Air Valve 40 | Percent air valve position at 40% | % | Read | |
| AV | 75 | Auto Commissioning Air Valve 100 | Percent air valve position at 100% | % | Read | |
| AV | 76 | Auto Commissioning Discharge Air Temperature Fan Off | Discharge air temp is recorded during auto commissioning | °F or °C | Read | |
| AV | 77 | Auto Commissioning Discharge Air Temperature Fan On | Auto commissioning discharge air temperature, fan on | °F or °C | Read | |
| AV | 78 | Auto Commissioning Discharge Air Temperature Reheat | Auto commissioning discharge air temperature, reheat on | °F or °C | Read | |
| AV | 79 | Auto Commissioning Discharge Air Temperature Water Valve | Auto commissioning discharge air temperature, water valve open | °F or °C | Read | |
| AV | 80 | Auto Commissioning Discharge Air Temperature Stage 1 Heat | Auto commissioning discharge air temperature, 1 heat stage on | °F or °C | Read | |
| AV | 81 | Auto Commissioning Discharge Air Temperature Stage 2 Heat | Auto commissioning discharge air temperature, 2 heat stages on | °F or °C | Read | |
| AV | 82 | Auto Commissioning Discharge Air Temperature Stage 3 Heat | Auto commissioning discharge air temperature, 3 heat stages on | °F or °C | Read | |
| AV | 83 | Cool Type | Read | |||
| AV | 84 | Preheat Type | Read | |||
| AV | 85 | Reheat Type | Read | |||
| AV | 86 | Supply Fan Type | Read | |||
| AV | 87 | Cooling Setpoint High Limit | High limit for cooling setpoint | °F or °C | Write | |
| AV | 88 | Cooling Setpoint Low Limit | Low limit for cooling setpoint | °F or °C | Write | |
| AV | 89 | Heating Setpoint High Limit | High limit for heating setpoint | °F or °C | Write | |
| AV | 90 | Heating Setpoint Low Limit | Low limit for heating setpoint | °F or °C | Write | |
| BI | 1 | Occupancy Input | Occupancy sensor | Read | ||
| BO | 1 | ECM Fan Output | ECM fan on/off | Read | ||
| BO | 2 | Fan Output | Fan on/off (standard motor) | Read | ||
| BO | 5 | Heat Output 3 | Heat stage 3 | Read | ||
| BO | 6 | Heat Output 2 | Heat stage 2 | Read | ||
| BO | 7 | Heat Output 1 | Heat stage 1 | Read | ||
| BV | 1 | Air Valve Position Control | Pressure independent or position (pressure dependent) control | Write | 0 = Pressure independent, 1 = Position control / pressure dependent | |
| BV | 2 | Default Supply Air Temperature Mode | Default supply air temperature mode | Write | 0 = Cold (cooling, default), 1 = Hot (heating) | |
| BV | 3 | Diagnostic: Air Flow Override Local | Local thumbwheel is in override position of * or ** | Read | 0 = Inactive, 1 = Active | |
| BV | 5 | Reheat Priority | Reheat priority of local and remote heat | Write | ||
| BV | 6 | Pressure Dependent Mode Reheat Enable | Write | |||
| BV | 7 | Diagnostic: Flow Sensor Calibration Failure | Read | 0 = Inactive, 1 = Active | ||
| BV | 8 | Auto Calibrate | Write | |||
| BV | 9 | Diagnostic: Low Primary Air Flow | Low primary airflow diagnostic (electric heat only) | Read | 0 = Inactive, 1 = Active | |
| BV | 10 | Diagnostic: Freeze Protection | Freeze protection diagnostic (only for ventilation flow control units) | Read | 0 = Inactive, 1 = Active | |
| BV | 11 | Auto Commissioning Command | Auto commissioning command | Write | ||
| BV | 12 | Diagnostic: High Air Flow | Flow sensor reads above 120% of nominal flow | Read | 0 = Inactive, 1 = Active | |
| BVmin | 13 | Diagnostic: Flow Sensor Failure | Pressure sensor faulted diagnostic | Read | 0 = Inactive, 1 = Active | |
| MI | 1 | Timed Override Status | Timed override button push detected | Read | ||
| MI | 2 | Air Flow Override Local | Thumbwheel at * or ** | Read | ||
| MV | 1 | Air Flow Minimum Setpoint Source | Write | |||
| MV | 2 | Air Flow Override | Write | |||
| MV | 3 | Water Valve Override | Write | |||
| MVmin | 4 | Heat Cool Mode Request | Heat/cool mode request from the BAS | Write | ||
| MVmin | 5 | Heat Cool Mode Status | Read | |||
| MVmin | 6 | Occupancy Request | Occupancy request from the BAS | Write | ||
| MVmin | 7 | Occupancy Status | Read | |||
| MV | 8 | Auto Commissioning State | Read | |||
| MV | 9 | Emergency Override BAS | Emergency override request | Write | ||
| MV | 12 | Manual Test Sequence | Manual Test Sequence number | Write |
No points match these filters.
Object ID lookup: Trane Symbio 210 VAV point IDs by name
AI1Space Temperature LocalAI2Space Temperature Setpoint LocalAI3Pressure 1AI4Discharge Air TemperatureAI5Supply Air Temperature LocalAI6Actual Air Valve PositionAI7Actual Reheat PositionAI8Space CO2 Concentration LocalAI9Air Valve 1 Stroke TimeAI10Minimum Actuator TimeAI11Water Valve Maximum Stroke TimeAI12Water Valve Minimum Actuator TimeAO1Air Valve Drive CommandAO2Supply Fan SpeedAO3Heating Valve CommandAV2Air Flow Minimum Setpoint ActiveAV8Air Flow Nominal StatusAV9Reheat Enable PointAV10Auto Changeover PointAV12Heat Output Secondary StatusAV13Air Flow Setpoint ActiveAV14Space Temperature BASAV15Air Flow Override PercentAV16Discharge Air Temperature Setpoint BASAV18Air Flow GainAV19Air Flow Measurement OffsetAV20Discharge Air FlowAV21Outdoor Air Low LimitAV22Space CO2 Concentration BASAV23Unoccupied Cooling SetpointAV24Unoccupied Heating SetpointAV25Air Flow Setpoint BASAV26Air Flow OffsetAV27Space Temperature Setpoint BASAV28Space Temperature Setpoint ActiveAV29Supply Air Temperature BASAV30Occupied OffsetAV31Air Flow Setpoint Minimum Local HeatAV33Occupied Bypass TimeAV34Standby OffsetAV35Ventilation Setpoint ActiveAV36Ventilation RatioAV37Space Temp Setpoint DefaultAV38Ventilation Setpoint LocalAV39Discharge Air Temp Setpoint LocalAV40Space CO2 LimitAV41Space CO2 Low LimitAV42Air Flow Setpoint MinimumAV43Air Flow Setpoint Minimum StandbyAV44Air Flow Setpoint Minimum Standby HeatAV45Air Flow Setpoint Minimum HeatAV46Air Flow Setpoint Maximum HeatAV47Air Flow Setpoint MaximumAV48Ventilation Setpoint BASAV49Ventilation Standby SetpointAV50Space CO2 Concentration ActiveAV51Ventilation Ratio Limit BASAV52PD Mode Min Air Valve PositionAV53ECM Fan Correction FactorAV54ECM Fan Maximum FlowAV55ECM Fan Minimum FlowAV56ECM Fan Flow SetpointAV57Parallel Fan Flow Enable PointAV58Parallel Fan Temp Enable PointAV59Space Temperature ActiveAV60Supply Air Temperature ActiveAV66Cabinet StyleAV67Auxiliary Heat Control RequestAV68Fan Override BASAV69Pressure Sensor Calibration OffsetAV70Fan Air Flow RatingAV74Auto Commissioning Air Valve 40AV75Auto Commissioning Air Valve 100AV76Auto Commissioning Discharge Air Temperature Fan OffAV77Auto Commissioning Discharge Air Temperature Fan OnAV78Auto Commissioning Discharge Air Temperature ReheatAV79Auto Commissioning Discharge Air Temperature Water ValveAV80Auto Commissioning Discharge Air Temperature Stage 1 HeatAV81Auto Commissioning Discharge Air Temperature Stage 2 HeatAV82Auto Commissioning Discharge Air Temperature Stage 3 HeatAV83Cool TypeAV84Preheat TypeAV85Reheat TypeAV86Supply Fan TypeAV87Cooling Setpoint High LimitAV88Cooling Setpoint Low LimitAV89Heating Setpoint High LimitAV90Heating Setpoint Low LimitBI1Occupancy InputBO1ECM Fan OutputBO2Fan OutputBO5Heat Output 3BO6Heat Output 2BO7Heat Output 1BV1Air Valve Position ControlBV2Default Supply Air Temperature ModeBV3Diagnostic: Air Flow Override LocalBV5Reheat PriorityBV6Pressure Dependent Mode Reheat EnableBV7Diagnostic: Flow Sensor Calibration FailureBV8Auto CalibrateBV9Diagnostic: Low Primary Air FlowBV10Diagnostic: Freeze ProtectionBV11Auto Commissioning CommandBV12Diagnostic: High Air FlowBV13Diagnostic: Flow Sensor FailureMI1Timed Override StatusMI2Air Flow Override LocalMV1Air Flow Minimum Setpoint SourceMV2Air Flow OverrideMV3Water Valve OverrideMV4Heat Cool Mode RequestMV5Heat Cool Mode StatusMV6Occupancy RequestMV7Occupancy StatusMV8Auto Commissioning StateMV9Emergency Override BASMV12Manual Test Sequence
Integration notes
- The guide has no read/write column. Access is inferred: inputs, hardware outputs and Active/Status/Diagnostic/auto-commissioning results are read-only; the BAS, Request, Override, setpoint and configuration value objects are writable.
- Point availability depends on the application (Space Temperature Control, Ventilation Flow Control, Flow Tracking Control) and the heat type; the guide's Table 9 marks which applications use each point.
- Units follow the controller's system units (IP or SI). AV 2 and AV 8 are printed with pressure units although they hold airflow values; they are kept as printed.
- The PDF at this URL prints document number BAS-SVP043A-EN, June 2021, on its pages.
- Alarm objects: AI 1, AI 2, AI 4 and AI 5 go to fault when the sensor fails, and the Diagnostic BVs (BV 3, 7, 9, 10, 12, 13) carry notification classes 2-4.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 210 VAV and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 210 VAV
How many BACnet points does the Trane Symbio 210 VAV have?
This list has 118 BACnet objects: 12 analog inputs, 3 analog outputs, 73 analog values, 1 binary input, 5 binary outputs, 12 binary values, 2 multi-state inputs, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 210 VAV BACnet points are writable?
60 of the 118 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 210 VAV BACnet documentation?
The source is Integration Guide: Symbio 210 Programmable Controller for Variable-Air-Volume (VAV) Boxes (BAS-SVP043A-EN), revision June 2021, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP043B-EN_11242021.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 210 VAV?
Start with MV 6 Occupancy Request (Occupancy command from the BMS); MV 4 Heat Cool Mode Request (Heat/cool mode command from the BMS); AV 27 Space Temperature Setpoint BAS (Space setpoint; put In Service before writing); MV 7 Occupancy Status (Confirms the occupancy in effect); MV 5 Heat Cool Mode Status (Current heat/cool mode); AV 59 Space Temperature Active (Space temperature used for control); AV 13 Air Flow Setpoint Active (Airflow setpoint in use); AV 20 Discharge Air Flow (Measured box airflow); BV 13 Diagnostic: Flow Sensor Failure (Flow (pressure) sensor fault).
How do I enable BMS control of the Trane Symbio 210 VAV?
No enable point. The '... BAS' value objects ship Out of Service and are ignored until the BMS (or Tracer SC) puts them In Service. Symbio UI (Tools > BAS Control Selection) chooses BAS or Local as the source for each sensor and setpoint.
Does the Trane Symbio 210 VAV need a BACnet heartbeat or have a communication timeout?
AV 14 Space Temperature BAS and AV 22 Space CO2 Concentration BAS must be written at least every 15 minutes while In Service; otherwise the controller puts the point in fault.
Can the BMS supply sensor values to the Trane Symbio 210 VAV?
Space temperature goes to AV 14, CO2 to AV 22 and supply air temperature to AV 29, each after putting the object In Service. AV 59, AV 50 and AV 60 show the values in use. Select BAS as the source in Symbio UI BAS Control Selection.
How do I check these points on the real Symbio 210 VAV?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Integration Guide: Symbio 210 Programmable Controller for Variable-Air-Volume (VAV) Boxes · BAS-SVP043A-EN · rev. June 2021. Object names, instances and units are reproduced as published; descriptions are our own.