Rooftop unit communication interface (IntelliPak) · BACnet points list

Trane BCI2-I (IntelliPak) BACnet points list

Updated 4 November 2026

Short answer

The BCI2-I is a non-programmable BACnet MS/TP card for IntelliPak rooftops and Commercial Self-Contained units. It scans the unit at first power-up and creates only the objects that match the installed options, so the full table is a superset. The BAS writes AO/BO/MO output objects (commands, setpoints, BAS sensor values) and reads AI/BI/MI status and diagnostics. This is the older IntelliPak interface, not the Symbio 800 IntelliPak controller.

This page lists 331 BACnet objects for the Trane BCI2-I (IntelliPak) — 54 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
BCI2-I (IntelliPak)
Equipment
Rooftop unit communication interface (IntelliPak)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
331 (54 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series
Source document
Integration Guide: BACnet Communication Interface (BCI2-I) for IntelliPak and Commercial Self-Contained · BAS-SVP054B-EN · rev. September 2023
Download CSV 331 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane BCI2-I (IntelliPak)

Integration in brief

Set Unit Control to BAS/NETWORK at the unit's Human Interface, then set BO 1 System Control Command to Active (BAS Control). Put each output object the BMS will drive in service (Out_Of_Service = FALSE). Schedule with MO 7 Occupancy Request, set the mode with MO 8 and the space setpoint with AO 2 (or the discharge air setpoints on VAV units). Keep rewriting BAS sensor values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1System Control CommandActive = BAS control; Inactive = standalone, monitor onlyCommand
MO 7Occupancy RequestOccupancy command (1 = Occupied, 2 = Unoccupied)Command
MO 8Heat Cool Mode Request BASHeat/cool mode command (1 = Auto)Command
AO 2Space Temperature Setpoint BASSpace setpoint; occupied/standby offsets apply to itCommand
AO 6Discharge Air Cooling Setpoint BASSupply air cooling setpoint on VAV unitsCommand
BI 1System Control StatusConfirms the unit is under BAS controlRead
MI 20Occupancy StatusConfirms the occupancy the unit is running inRead
MI 41Supply Fan StatusSupply fan on/off (2 = On)Read
AI 15Space Temperature ActiveSpace temperature the unit is controlling toRead
BI 165Alarm Relay Output StatusUnit alarm relay; Active = energizedRead

Enable & remote start

At the unit Human Interface, BAS Communication Module must read Installed and Setup > Unit Control must be BAS/NETWORK. Then BO 1 System Control Command must be Active (BAS Control); while Inactive the unit runs on local sensors and setpoints and ignores BAS values. Output objects ship with Out_Of_Service = TRUE, so the unit uses its local value until the BMS sets Out_Of_Service to FALSE on each output it will write.

Heartbeat & communication loss

BAS-supplied sensor objects with a 900 s refresh rate (AO 10-15, AO 17, AO 18, AO 25) must be rewritten within that time. If not, the BCI2-I puts the object in fault and the unit reverts to its own sensor. At power-up these objects stay in fault until the first write. Setpoints and commands have no refresh limit (AO 22 is printed with a 5 s refresh rate).

Sensors & values from the BMS

Write BMS sensor values to the '... BAS' AOs (AO 11 Space Temperature BAS, AO 12 Discharge Air Temperature BAS, AO 13 Duct Static Pressure BAS, AO 14 Outdoor Air Temperature BAS, AO 15 Outdoor Air Humidity BAS, AO 17 Outdoor Air Flow BAS, AO 18 Space CO2 Concentration BAS, AO 25 Space Humidity BAS, AO 10 Space Static Pressure BAS) with the object in service, and keep refreshing them. The matching '... Active' AIs show the value in use.

Network setup

Watch out for

Trane BCI2-I (IntelliPak) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

331 of 331 shown
Type
Access
Show
Trane BCI2-I (IntelliPak) BACnet Points List
DescriptionStates
AO1Economizer Minimum Position Setpoint BASBAS economizer position minimum setpoint value [With Economizer installed]%Command
AOmin2Space Temperature Setpoint BASBase value to calculate setpoints in occupied and standby modes°FCommand
AO4Morning Warmup Setpoint BASBAS temperature setpoint used in morning warm-up mode [With any heat installed]°FCommand
AO5Daytime Warmup Terminate Temperature Setpoint BASBAS daytime warm-up terminate temperature setpoint [With any heat installed]°FCommand
AOmin6Discharge Air Cooling Setpoint BASBAS discharge air temperature cooling setpoint value [Variable Air Volume]°FCommand
AO7Discharge Air Heating Setpoint BASBAS discharge air temperature heating setpoint value [Variable Air Volume]°FCommand
AO8Duct Static Pressure Setpoint BASBAS duct static air pressure setpoint value [Variable Air Volume]in. w.c.Command
AO9Space Static Pressure Setpoint BASBAS space static air pressure setpoint value [With StatiTrac]in. w.c.Command
AO10Space Static Pressure BASBAS space static air pressure sensor value [With StatiTrac]in. w.c.Command
AO11Space Temperature BASBAS space air temperature sensor value°FCommand
AO12Discharge Air Temperature BASBAS discharge air temperature sensor value°FCommand
AO13Duct Static Pressure BASBAS duct static air pressure sensor value [Variable Air Volume]in. w.c.Command
AO14Outdoor Air Temperature BASBAS outdoor air temperature sensor value°FCommand
AO15Outdoor Air Humidity BASBAS outdoor air humidity sensor value%Command
AO16Outdoor Air Minimum Flow Setpoint BASBAS minimum outdoor airflow setpoint [Fresh Air Management installed]cfmCommand
AO17Outdoor Air Flow BASBAS outdoor airflow sensor value [Fresh Air Management installed]cfmCommand
AO18Space CO2 Concentration BASBAS space CO2 sensor valueppmCommand
AO19Cool Capacity Enable Setpoint BASBAS cooling demand limit capacity setpoint value [With all cooling types]%Command
AO20Heat Capacity Enable Setpoint BASBAS heating demand limit capacity setpoint value [With any heat installed]%Command
AO21Space Dehumidification Setpoint BASBAS space dehumidification setpoint value [Dehumidification Configuration]%Command
AO22Discharge Air Dewpoint Setpoint BASBAS discharge air dewpoint setpoint value°FCommand
AO23Discharge Air Reheat Setpoint BASBAS discharge air reheat setpoint value [Dehumidification Configuration]°FCommand
AO25Space Humidity BASBAS space humidity sensor value [Dehumidification or Humidification Configuration]%Command
AO26Space Humidification Setpoint BASBAS space humidification setpoint value [Roof Top Unit with Humidification Configured]%Command
AO29Occupied OffsetOffset used to calculate setpoints in occupied mode°FCommand
AO30Standby OffsetOffset value used to calculate setpoints in standby mode°FCommand
AO31Unoccupied Cooling SetpointCooling temperature setpoint used for control in unoccupied mode°FCommand
AO32Unoccupied Heating SetpointHeating temperature setpoint used for control in unoccupied mode°FCommand
AO33Chemical Purge Water Treatment DurationSet BAS time duration (minutes) for Chemical Purge Water Treatment event (CSCminCommand
AO39Supply Fan Speed Command Setpoint BASBAS Supply Fan Speed Setpoint [Variable Air Volume]%Command
AO40Exhaust Fan Speed Setpoint BASBAS Exhaust Fan Speed Setpoint [Variable Air Volume]%Command
AO43Daytime Warm-up Initiate Temperature Setpoint BASBAS initiate temperature setpoint used in morning warm-up mode [With any heat installed]°FCommand
AO1001Digital Scroll Compressor SignalSupplied voltage to the Digital Scroll Compressor [Digital Scroll Compressor present]VCommand
AI1Cooling Capacity StatusUnit cooling capacity being utilized%Read
AI2Heat Primary Capacity StatusUnit primary heating capacity being utilized%Read
AI3Heat Secondary Capacity StatusUnit secondary heating capacity being utilized [Roof Top Unit]%Read
AI5Reheat Capacity StatusUnit reheat heating capacity being utilized [Dehumidification]%Read
AI6Filter Runtime HoursNumber of hours air has flowed through the filterhRead
AI7Supply Fan Speed CommandUnit commanded supply fan speed%Read
AI8Exhaust Fan Speed CommandUnit commanded exhaust fan speed [With 100% exhaust capabilities]%Read
AI9Exhaust Damper Position StatusUnit exhaust damper position [With 100% exhaust capabilities or Return Fan]%Read
AI10Return Fan Speed CommandUnit commanded return fan speed%Read
AI11Outdoor Air Damper Position StatusUnit outdoor air damper position [With Economizer installed]%Read
AI12Waterside Economizer Valve Position StatusUnit waterside economizer valve position [Commercial Self Contained with Waterside Economizer]%Read
AI13Frost Avoidance Temperature SetpointFrost coil avoidance temperature setpoint°FRead
AI14Condenser Capacity StatusUnit condenser capacity being utilized%Read
AImin15Space Temperature ActiveSpace temperature currently used for unit control°FRead
AI16Space Humidity ActiveSpace humidity value from a unit-mounted control [With Dehumidification or with Economizing and Comparative Enthalpy Module]%RHRead
AI17Space EnthalpySpace enthalpy value from a unit-mounted control [With Dehumidification or with Economizing and Comparative Enthalpy Module]Btu/lbRead
AI18Outdoor Air Temperature ActiveOutdoor air temperature currently used for unit control°FRead
AI19Outdoor Air Temperature LocalOutdoor air temperature value from a unit-mounted sensor°FRead
AI20Outdoor Air Humidity ActiveOutdoor air humidity value used for unit control [With Economizing and Comparative Enthalpy Module]%RHRead
AI21Outdoor Air Humidity LocalOutdoor air humidity value from a unit-mounted sensor [With Economizing and Comparative Enthalpy Module]%RHRead
AI22Outdoor Air DewpointOutdoor air dewpoint value being utilized by the unit°FRead
AI23Outdoor Air EnthalpyOutdoor air enthalpy value being utilized by the unit [With Economizing and Comparative Enthalpy Module]Btu/lbRead
AI24Discharge Air Temperature ActiveDischarge air temperature currently used for unit control°FRead
AI25Mixed Air TemperatureMixed air temperature value from a unit-mounted sensor°FRead
AI26Return Air TemperatureReturn air temperature value from a unit-mounted sensor [With Economizing and Comparative Enthalpy Module]°FRead
AI28Duct Static Pressure ActiveDuct static air pressure value currently being used for unit control [Variable Air Volume]in. w.c.Read
AI29Duct Static Pressure LocalDuct static air pressure value measured by a unit-mounted sensor [Variable Air Volume]in. w.c.Read
AI30Return Fan Air PressureReturn fan air pressure value measured by a unit-mounted sensor [Return fan with StatiTrac]in. w.c.Read
AI31Space Static Air Pressure ActiveSpace static air pressure value being used for unit control [With StatiTrac installed]in. w.c.Read
AI32Space CO2 Concentration ActiveSpace CO2 concentration being used for unit control [With DCV option]ppmRead
AI33Discharge Air DewpointDischarge air temperature dewpoint being used by the unit [Dehumidification]°FRead
AI34Outdoor Air Flow ActiveOutdoor airflow utilized by the unit [With Ventilation Control Module]cfmRead
AI35Condenser Water Entering TemperatureTemperature of the water entering the condenser°FRead
AI36Evaporator Entering Temperature Circuit 1Entering evaporator temperature for circuit 1 [DX Roof Top Unit]°FRead
AI37Evaporator Entering Temperature Circuit 2Entering evaporator temperature for circuit 2 [DX Roof Top Unit]°FRead
AI38Evaporator Leaving Temperature Circuit 1Leaving evaporator temperature for circuit 1 [Commercial Self Contained or DX Roof Top Unit]°FRead
AI39Evaporator Leaving Temperature Circuit 2Leaving evaporator temperature for circuit 2 [Commercial Self Contained or DX Roof Top Unit]°FRead
AI40Evaporator Leaving Temperature Circuit 3Leaving evaporator temperature for circuit 3°FRead
AI41Evaporator Leaving Temperature Circuit 4Leaving evaporator temperature for circuit 4°FRead
AI42Condensing Saturated Temperature Circuit 1Saturated condenser temperature for circuit 1 [DX]°FRead
AI43Condensing Saturated Temperature Circuit 2Saturated condenser temperature for circuit 2 [For 2 or more refrigerant circuits]°FRead
AI44Condensing Saturated Temperature Circuit 3Saturated condenser temperature for circuit 3 [For 3 or more refrigerant circuits]°FRead
AI45Condensing Saturated Temperature Circuit 4Saturated condenser temperature for circuit 4 [For 4 refrigerant circuits]°FRead
AI46Condenser Water Leaving Temperature ActiveCondenser water leaving temperature value used for unit control°FRead
AI47Condenser Water Temperature LocalCondenser water leaving temperature from a unit mounted sensor°FRead
AI48Duct Static Pressure Setpoint ActiveDuct static pressure setpoint value being used for unit control [Variable Air Volume]in. w.c.Read
AI50Space Temperature Setpoint ActiveSpace temperature setpoint value being used for unit control°FRead
AI52Discharge Air Temperature Setpoint ActiveDischarge air temperature setpoint value being used for unit control [Variable Air Volume]°FRead
AI54Morning Warmup Temperature Setpoint ActiveAir temperature setpoint used during morning warm-up mode [With any heat installed]°FRead
AI55Daytime Warmup Air Temperature Terminate Setpoint ActiveAir temperature setpoint used to end daytime warm-up mode [Variable Air Volume with any heat installed]°FRead
AI56Economizer Minimum Position Setpoint ActiveMinimum position value the economizer damper will utilize [With Economizer installed]%Read
AI57Outdoor Air Minimum Flow Setpoint ActiveMinimum outdoor airflow setpoint being utilized by the unitcfmRead
AI58Dehumidification High Limit SetpointHumidity setpoint value that starts dehumidification control [Roof Top Unit with Dehumidification]%Read
AI60Discharge Air Dewpoint Temperature SetpointHumidity setpoint value used during dehumidification control [With Dehumidification]°FRead
AI61Discharge Air Reheat Setpoint ActiveActive supply air reheat temperature setpoint [Roof Top Unit with Dehumidification]°FRead
AI62Space Humidification Setpoint ActiveSetpoint used during space humidification control [Roof Top Unit]%Read
AI64Energy Recovery Exhaust Air Bypass Damper PositionEnergy recovery exhaust air bypass damper position [Roof Top Unit with Energy Recovery]%Read
AI65Energy Recovery Leaving Exhaust TemperatureEnergy recovery leaving exhaust air temperature [Roof Top Unit with Energy Recovery]°FRead
AI66Energy Recovery Outdoor Air Bypass Damper PositionEnergy recovery outdoor air bypass damper position [Roof Top Unit with Energy Recovery]%Read
AI67Daytime Warmup Initiate Temperature Setpoint LocalLocal daytime warm-up initiate temperature setpoint [Variable Air Volume with any heat installed]°FRead
AI68Daytime Warmup Terminate Temperature Setpoint LocalTemperature setpoint that will exit daytime warm-up mode [Variable Air Volume with any heat installed]°FRead
AI69Economizing Temperature Enable SetpointTemperature setpoint below which economizing can be used [With Economizer installed]°FRead
AI70Economizing Enthalpy Enable SetpointEnthalpy setpoint below which economizing can be used [With Economizer installed]Btu/lbRead
AI71Exhaust Enable Position Setpoint StatusExhaust air damper minimum position to enable exhaust sequence [With Economizer installed]%Read
AI74Space Temperature Cooling Setpoint InputCooling temperature setpoint from space sensor module°FRead
AI75Space Temperature Heating Setpoint InputHeating temperature setpoint from space sensor module°FRead
AI76Humidification Capacity StatusUnit humidification capacity being utilized [With Humidification]%Read
AI78Space Temperature Setpoint LocalLocal space temperature setpoint°FRead
AI79Dehumidification Capacity StatusUnit dehumidification capacity being utilized [Roof Top Unit with Dehumidification]%Read
AI80Cabinet StyleCabinet style of the unitRead8 = Modular, 24 = Signature, 4 = Air Handler
AI81Cool TypeCooling type installed in the unitRead1 = None, 2 = Modulating Cold Water, 6 = Modulating DX, 33 = 2-Stage Air-Cooled DX 1 Circuit 2 Compressor Relays, 34 = 2-Stage Air-Cooled DX 2 Circuit 2 Compressor Relays, 35 = 3-Stage Air-Cooled DX 2 Circuit 1 Compressor Relays, 36 = 3-Stage Air-Cooled DX 2 Circuit 2 Compr Relays, 37 = 2-Stage Water-Cooled DX 1 Circuit 2 Compressor Relays, 38 = 2-Stage Water-Cooled DX 2 Circuit 2 Compressor Relays, 39 = 3-Stage Water-Cooled DX 1 Circuit 2 Compressor Relays, 40 = 3-Stage Water-Cooled DX 2 Circuit 2 Compressor Relays, 41 = 3-Stage Air-Cooled DX 2 Circuit 3 Compressor Relays, 42 = 4-Stage Air-Cooled DX 2 Circuit 3 Compressor Relays, 43 = 3-Stage Water-Cooled DX 2 Circuit 3 Compressor Relays, 44 = 4-Stage Water-Cooled DX 2 Circuit 3 Compressor Relays, 45 = 3-Stage Water-Cooled DX 3 Circuit 3 Compressor Relays, 46 = 4-Stage Water-Cooled DX 3 Circuit 3 Compressor Relays, 47 = 4-Stage Air-Cooled DX 2 Circuit 4 Compressor Relays, 48 = 4-Stage Water-Cooled DX 2 Circuit 4 Compressor Relays, 49 = 4-Stage Water-Cooled DX 4 Circuit 4 Compressor Relays
AI82Preheat TypeHeating type installed in the unitRead129 = None, 130 = Modulating Hot Water, 134 = Modulating Electric, 135 = 1-Stage Electric, 136 = 2-Stage Electric, 137 = 3-Stage Electric, 138 = 4-Stage Electric, 158 = 5-Stage Electric, 160 = 7-Stage Electric, 141 = 2-Stage Gas, 162 = 4-Stage Gas, 142 = Modulating Gas, 163 = External Heat
AI83Reheat TypeReheat type installed in the unitRead1 = None, 17 = Hot Gas
AI84Space CO2 High Limit SetpointHigh limit space CO2 setpoint for ventilationppmRead
AI85Space CO2 Low LimitLow limit space CO2 setpoint for ventilation [With DCV option]ppmRead
AI86Economizer Minimum Position Setpoint LocalLocal economizer minimum position setpoint [With Economizer installed]%Read
AI87Space Temperature LocalSpace air temperature measured by a unit-mounted sensor°FRead
AI88Unit Energy DemandCurrent heat/cool energy demand of the unit%Read
AI89Supply Fan TypeSupply fan type installed in the unitRead1 = None, 2 = 1-Speed, 6 = Variable Speed
AI90Exhaust or Return Fan TypeExhaust or return fan type installed in the unitRead1 = None, 2 = 1-Speed Exhaust Fan, 7 = 1-Speed Exhaust Fan with Modulating Exhaust Damper, 22 = 1-Speed Return Fan with Modulating Exhaust Damper, 26 = Variable Speed Fan with Modulating Exhaust Damper
AI110Daytime Warmup Air Temperature Initiate Setpoint ActiveActive daytime warmup initiate setpoint [Variable Air Volume with any Heat Installed]°FRead
AI1001Resistance Compressor Minimum CapacityCreated when Digital Scroll Compressor is present [Digital Scroll Compressor present]ohmRead
AV1Filter Runtime Hours SetpointSetpoint value used by the filter run hours calculationhCommand
AV1001Digital Scroll Compressor Cooling P GainCreated when Digital Scroll Compressor is presentCommand
AV1002Digital Scroll Compressor Cooling Capacity StatusCreated when Digital Scroll Compressor is present%Command
MO1Economizer Airside Enable BASCommands the state of the airside economizer system [With Economizer installed]Command1 = Disabled, 2 = Enabled, 3 = Auto
MO2Emergency Override CommandCommands the unit into an emergency mode of operationCommand1 = Normal, 2 = Pressurize, 3 = De-pressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MO3Economizer Waterside Enable BASCommands the state of the waterside economizer system [Commercial Self Contained with Water Side Economizer]Command1 = Disabled, 2 = Enabled, 3 = Auto
MO6Language Selection CommandCommands the unit to provide diagnostics in foreign languagesCommand1 = English, 2 = French, 3 = German, 4 = Spanish, 5 = Portuguese, 6 = Dutch, 7 = Italian
MOmin7Occupancy RequestCommands the unit into an occupancy modeCommand1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby
MOmin8Heat Cool Mode Request BASCommands the unit to a specific application modeCommand1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre-cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice Making, 13 = Max Heat, 14 = Economy Mode, 15 = Dehumidifying, 16 = Calibrate
MO10Condenser Water Flow BASCommands the unit to utilize a remote water flow indicationCommand1 = Flow, 2 = No Flow, 3 = Auto
MI2Trane Unit TypeGeneral description of the equipment-type classificationRead1 = 1 Heat/1 Cool, 2 = Heat Pump, 3 = Blower Coil, 4 = Unit Ventilator, 5 = Fan Coil, 6 = Rooftop, 7 = Air Handler, 8 = Vertical Self Contained, 9 = Unitary, 10 = VAV Box, 11 = Fan Coil
MI9Economizer TypeGeneral description of the equipment economizer systemRead1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/Sensor, 9 = Waterside Economizer and TRAQ Damper/Sensor, 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor
MI10Condenser TypeGeneral description of the equipment condenser systemRead1 = None, 2 = Air Cooled, 3 = Water Cooled, 4 = Evaporative
MI13Ventilation Override StatusWhether the unit is in a ventilation override mode of operation [Configured with Ventilation Override Module]Read1 = Inactive, 2 = Mode A Active, 3 = Mode B Active, 4 = Mode C Active, 5 = Mode D Active, 6 = Mode E Active
MI15Economizer Decision MethodUnit method to determine when the economizer system is enabled [Configured with Economizer]Read1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy
MI17Cooling Reset Type StatusType of cooling reset [Variable Air Volume]Read1 = None, 2 = Outdoor Air, 3 = Zone
MI18Heating Reset Type StatusType of heating reset [Variable Air Volume]Read1 = None, 2 = Outdoor Air, 3 = Zone
MI19Application Mode StatusCurrent application mode of the equipmentRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre-cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economy Mode, 15 = Dehumidifying, 16 = Calibrate
MImin20Occupancy StatusCurrent occupancy mode of the unitRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby
MI21Unit Stop SourceSource of the stop command that turned off the equipmentRead1 = None, 2 = Emergency Stop, 3 = External Auto/Stop, 4 = Local HI, 5 = Remote HI
MI22Cooling Setpoint SourceSource of the space cooling setpointRead1 = RTM Zone Sensor, 2 = Night Setback Panel, 3 = Human Interface, 4 = GBAS 0-5V, 5 = BAS/Network, 6 = GBAS 0-10V
MI23Heating Setpoint SourceSource of the space heating setpointRead1 = RTM Zone Sensor, 2 = Night Setback Panel, 3 = Human Interface, 4 = GBAS 0-5V, 5 = BAS/Network, 6 = GBAS 0-10V
MI24Timed Override StatusTimed override request or cancel from zone sensorRead1 = Idle, 2 = On, 3 = Cancel
MI25Cool Output 1Commanded state of cooling output 1 [DX]Read1 = Off, 2 = On, 3 = Not Present
MI26Cool Output 2Commanded state of cooling output 2 [With 2 or more refrigerant circuits]Read1 = Off, 2 = On, 3 = Not Present
MI27Cool Output 3Commanded state of cooling output 3 [With 3 or more refrigerant circuits]Read1 = Off, 2 = On, 3 = Not Present
MI28Cool Output 4Commanded state of cooling output 4Read1 = Off, 2 = On, 3 = Not Present
MI29Heat Output 1Commanded state of heating output 1 [Configured with any heat]Read1 = Off, 2 = On, 3 = Not Present
MI30Heat Output 2Commanded state of heating output 2 [Configured with 2 or more stages of heat]Read1 = Off, 2 = On, 3 = Not Present
MI31Heat Output 3Commanded state of heating output 3Read1 = Off, 2 = On, 3 = Not Present
MI32Heat Output 4Commanded state of heating output 4Read1 = Off, 2 = On, 3 = Not Present
MI33Heat Output 5Commanded state of heating output 5Read1 = Off, 2 = On, 3 = Not Present
MI34Prefilter StatusPre-filter media state [Roof Top Unit Configured with Energy Recovery]Read1 = Clean, 2 = Dirty, 3 = Not Present
MI35Primary Filter StatusPrimary filter media stateRead1 = Clean, 2 = Dirty, 3 = Not Present
MI36Final Filter StatusFinal filter media state [Configured with Final Filter]Read1 = Clean, 2 = Dirty, 3 = Not Present
MI37Supply Fan Proving StatusCurrent state of the supply fanRead1 = Off, 2 = On, 3 = Not Present
MI38Exhaust Fan StatusCommanded state of the exhaust fan [Configured with 100% or 50/100% Powered Exhaust]Read1 = Off, 2 = On, 3 = Not Present
MI39Exhaust Fan Proving StatusWhether the unit exhaust fan is off or on [Configured with 100% or 50/100% Powered Exhaust]Read1 = Off, 2 = On, 3 = Not Present
MI40Return Fan Proving StatusCurrent state of the return fan [Configured with return fan]Read1 = Off, 2 = On, 3 = Not Present
MImin41Supply Fan StatusState of the supply fanRead1 = Off, 2 = On, 3 = Not Present
MI42Return Fan StatusState of the return fanRead1 = Off, 2 = On, 3 = Not Present
MI43Outdoor Damper StatusOperating state of the outdoor damper [With Economizer installed]Read1 = At or Below Minimum Position, 2 = Above Minimum Position, 3 = Not Present
MI44Economizer System StatusOperating state of the waterside economizer system [With Economizer installed]Read1 = Disabled, 2 = Enabled, 3 = Not Present
MI46Cool Output 5Commanded state of cooling output 5 [With 5 or more cooling outputs]Read1 = Off, 2 = On, 3 = Not Present
BOmin1System Control CommandCommands the unit to standalone-or BAS-controlled operationCommandInactive = Standalone Control, Active = BAS Control
BO5Heat Lockout CommandCommands the unit to prevent heating operationCommandInactive = Allow Heating, Active = Heating Locked Out
BO6Cool Lockout CommandCommands the unit to prevent cooling operationCommandInactive = Allow Cooling, Active = Cooling Locked Out
BO7Remote Minimum Position Enabled CommandCommands the unit to the minimum position operationCommandInactive = Disabled, Active = Enabled
BO8Supply Fan Configuration CommandCommands the unit supply fan to cycling or continuous operationCommandInactive = Auto, Active = On
BO12Primary Heat Reheat Enable CommandEnable the heating or reheating system during dehumidification modeCommandInactive = Disabled, Active = Enabled
BO13Filter Timer ResetCommands the unit to reset the accumulated filter run hoursCommandInactive = Accumulating, Active = Reset
BO14Reset DiagnosticCommands the unit to reset and clear diagnosticsCommandInactive = Normal, Active = Reset
BO15Dehumidification Enable CommandCommands the operating state of the dehumidification system [Roof Top Unit with Dehumidification]CommandInactive = Disabled, Active = Enabled Out of Service = Auto
BO16Humidification CommandCommands the operating state of the humidification system [Configured with Humidification]CommandInactive = Disabled, Active = Enabled Out of Service = Auto
BO17Chemical Purge Water Treatment RequestCommands the unit into a Chemical Purge Water Treatment event through BASCommandInactive = Not Requested, Active = Requested
BImin1System Control StatusControl system currently in command of the unitReadInactive = Standalone control, Active = BAS control
BI2Compressor Lockout StatusOne or more compressors are locked out with no diagnosticReadInactive = Normal, Active = Locked Out
BI3Unit On Off StatusCurrent state of the unitReadInactive = Off, Active = On
BI9VAV Box CommandWhether VAV boxes should be in control or wide open [Variable Air Volume]ReadInactive = Auto, Active = Open
BI10Demand Limit StatusWhether the unit is in an energy-demand limit modeReadInactive = Inactive, Active = Active
BI11Service Test Mode StatusWhether the unit is in service test modeReadInactive = Inactive, Active = Active
BI15Supply Fan Configuration StatusSupply fan configuration [Constant Volume]ReadInactive = Cycling, Active = Continuous
BI22Economizer Airside Enable StatusStatus of the airside economizer system [With Economizer installed]ReadInactive = Disabled, Active = Enabled
BI23Waterside Economizer Enable StatusStatus of the waterside economizer system [Configured with Water Side Economizer]ReadInactive = Disabled, Active = Enabled
BI24Condenser Water Pump StatusStatus of the condenser water system pump [Water Cooled Commercial Self Contained or Roof Top Unit]ReadInactive = Inactive, Active = Active
BI25Condenser Water Flow StatusFlow status of water in the condenser systemReadInactive = No Flow, Active = Flow
BI26Energy Recovery Frost Avoidance StatusStatus of the energy recovery system frost protection function [With Energy Recovery]ReadInactive = Inactive, Active = Active
BI27Energy Recovery StatusStatus of the energy recover system [With Energy Recovery]ReadInactive = Inactive, Active = Active
BI28Energy Recovery Preheat StatusStatus of the energy recovery preheat function [With Energy Recovery]ReadInactive = Inactive, Active = Active
BI161Evaporator Frost Protection Circuit 1 StatusStatus of evaporator frost protection function for circuit 1 [DX]ReadInactive = Inactive, Active = Active
BI162Evaporator Frost Protection Circuit 2 StatusStatus of evaporator frost protection function for circuit 2 [For 2 or more refrigerant circuits]ReadInactive = Inactive, Active = Active
BI163Evaporator Frost Protection Circuit 3 StatusStatus of evaporator frost protection function for circuit 3 [For 3 or more refrigerant circuits]ReadInactive = Inactive, Active = Active
BI164Evaporator Frost Protection Circuit 4 StatusStatus of evaporator frost protection function for circuit 4 [For 4 or more refrigerant circuits]ReadInactive = Inactive, Active = Active
BImin165Alarm Relay Output StatusState of the alarm relay on the unitReadInactive = De-energized, Active = Energized
BI166Diagnostic Stop StatusWhether the unit diagnostic has caused the unit to shutdownReadInactive = Inactive, Active = Active
BI243Condenser Water Drain StatusStatus of the condenser water drain [Roof Top Unit]ReadInactive = Closed, Active = Open
BI244Chemical Purge Water Treatment StatusActive status of the Chemical Purge Water Treatment event (CSC units only)ReadInactive = Inactive, Active = Active
BI245Rapid Restart StatusActive status of the Rapid Restart event [Roof Top Unit]ReadInactive = Inactive, Active = Active
BI246Supply Air Tempering StatusCurrent status of the Supply Air Tempering event [Roof Top Unit and Commercial Self Contained]ReadInactive = Inactive, Active = Active
BI311Supply Air Low Limit ActiveActive status of the Supply Air Low Limit eventReadInactive = Inactive, Active = Active
BI1001Digital Scroll Compressor StatusCreated when Digital Scroll Compressor is present [Digital Scroll Compressor present]Read
BI29Diagnostic: RTM Zone Temp Sensor FailureUnit diagnosticReadInactive, Active
BI30Diagnostic: Supply Air Temp Sensor FailUnit diagnosticReadInactive, Active
BI31Diagnostic: RTM Aux Temp Sensor FailureUnit diagnostic; ID used on RTor CSC unitsReadInactive, Active
BI32Diagnostic: OA Temperature Sensor FailUnit diagnosticReadInactive, Active
BI33Diagnostic: Mode Input FailureUnit diagnosticReadInactive, Active
BI34Diagnostic: Occ Zone Cool Setpoint FailUnit diagnosticReadInactive, Active
BI35Diagnostic: Occ Zone Heat Setpoint FailUnit diagnosticReadInactive, Active
BI36Diagnostic: Supply Air Press Sensor FailUnit diagnosticReadInactive, Active
BI37Diagnostic: OA Humidity Sensor FailureUnit diagnosticReadInactive, Active
BI38Diagnostic: Emergency Stop (man)Unit diagnosticReadInactive, Active
BI39Diagnostic: Supply Fan Failure (man)Unit diagnosticReadInactive, Active
BI40Diagnostic: Exhaust/Return Fan Failure (man)Unit diagnosticReadInactive, Active
BI41Diagnostic: Lvg Evap Temp Sensor Fail - Ckt1Unit diagnosticReadInactive, Active
BI42Diagnostic: Lvg Evap Temp Sensor Fail - Ckt2Unit diagnosticReadInactive, Active
BI43Diagnostic: Low Pressure Ctl Open - Ckt1 (man)Unit diagnosticReadInactive, Active
BI44Diagnostic: Low Pressure Ctl Open - Ckt2 (man)Unit diagnosticReadInactive, Active
BI45Diagnostic: Cond Temp Sensor Fail - Ckt1Unit diagnosticReadInactive, Active
BI46Diagnostic: Cond Temp Sensor Fail - Ckt2Unit diagnosticReadInactive, Active
BI47Diagnostic: Compressor Trip - Ckt1 (man)Unit diagnosticReadInactive, Active
BI48Diagnostic: Compressor Trip - Ckt2 (man)Unit diagnosticReadInactive, Active
BI49Diagnostic: HEAT Aux Temp Sensor FailUnit diagnosticReadInactive, Active
BI50Diagnostic: Low Air Temp Limit Trip (man)Unit diagnosticReadInactive, Active
BI51Diagnostic: Heat FailureUnit diagnosticReadInactive, Active
BI52Diagnostic: Unocc Zone Cool Stpnt FailUnit diagnosticReadInactive, Active
BI53Diagnostic: Unocc Zone Heat Stpnt FailUnit diagnosticReadInactive, Active
BI54Diagnostic: SA Duct Press Setpoint FailUnit diagnosticReadInactive, Active
BI55Diagnostic: Space Pressure Setpoint FailUnit diagnosticReadInactive, Active
BI56Diagnostic: Space Pressure Sensor FailUnit diagnosticReadInactive, Active
BI57Diagnostic: Return Air Temp Sensor FailUnit diagnosticReadInactive, Active
BI58Diagnostic: Return Air RH Sensor FailureUnit diagnostic; ID used on RTor CSC unitsReadInactive, Active
BI59Diagnostic: SA High Press LimitUnit diagnosticReadInactive, Active
BI60Diagnostic: Man - SA High Press LimitUnit diagnosticReadInactive, Active
BI61Diagnostic: SCM Communications FailureUnit diagnosticReadInactive, Active
BI62Diagnostic: MCM Communications FailureUnit diagnosticReadInactive, Active
BI63Diagnostic: HEAT Communications FailureUnit diagnosticReadInactive, Active
BI64Diagnostic: ECEM Communications FailureUnit diagnosticReadInactive, Active
BI65Diagnostic: GBAS 0-5 VDC Comm FailureUnit diagnosticReadInactive, Active
BI66Diagnostic: BACnet Module Comm FailUnit diagnosticReadInactive, Active
BI67Diagnostic: BAS/Network Comm FailUnit diagnosticReadInactive, Active
BI68Diagnostic: NSB Panel Communication FailUnit diagnosticReadInactive, Active
BI69Diagnostic: RTM EEPROM FailureUnit diagnosticReadInactive, Active
BI70Diagnostic: Unit HI Communications FailUnit diagnosticReadInactive, Active
BI71Diagnostic: VOM Communications FailureUnit diagnosticReadInactive, Active
BI72Diagnostic: Compressor Contact Fail-Ckt1 (man)Unit diagnosticReadInactive, Active
BI73Diagnostic: Compressor Contact Fail-Ckt2 (man)Unit diagnosticReadInactive, Active
BI74Diagnostic: SA Temp Cool Setpoint FailUnit diagnosticReadInactive, Active
BI75Diagnostic: SA Temp Heat Setpoint FailUnit diagnosticReadInactive, Active
BI76Diagnostic: Dirty FilterUnit diagnosticReadInactive, Active
BI77Diagnostic: NSB Zone Temp Sensor FailUnit diagnosticReadInactive, Active
BI78Diagnostic: VOM Mode A ActiveUnit diagnosticReadInactive, Active
BI79Diagnostic: VOM Mode B ActiveUnit diagnosticReadInactive, Active
BI80Diagnostic: VOM Mode C ActiveUnit diagnosticReadInactive, Active
BI81Diagnostic: VOM Mode D ActiveUnit diagnosticReadInactive, Active
BI82Diagnostic: VOM Mode E ActiveUnit diagnosticReadInactive, Active
BI83Diagnostic: CO2 Sensor FailureUnit diagnosticReadInactive, Active
BI84Diagnostic: VCM Aux Temp Sensor FailureUnit diagnosticReadInactive, Active
BI85Diagnostic: Blocked Air Return (man)Unit diagnosticReadInactive, Active
BI86Diagnostic: Velocity Press Sensor FailUnit diagnostic; other meaning on some unit types (see notes)ReadInactive, Active
BI87Diagnostic: VCM Communications FailureUnit diagnosticReadInactive, Active
BI88Diagnostic: Low Space Pressure WarningUnit diagnostic; other meaning on some unit types (see notes)ReadInactive, Active
BI89Diagnostic: Low Space Pressure Trip - AutoUnit diagnostic; other meaning on some unit types (see notes)ReadInactive, Active
BI90Diagnostic: Low Space Pressure Trip - ManualUnit diagnostic; other meaning on some unit types (see notes)ReadInactive, Active
BI91Diagnostic: Exh Fan VFD Bypass EnabledUnit diagnosticReadInactive, Active
BI92Diagnostic: Cond Temp Sensor Fail - Ckt3Unit diagnosticReadInactive, Active
BI93Diagnostic: Cond Temp Sensor Fail - Ckt4Unit diagnosticReadInactive, Active
BI94Diagnostic: Ent Cond Wtr Tmp Sensor FailUnit diagnosticReadInactive, Active
BI95Diagnostic: WSM MA Temp Sensor FailureUnit diagnosticReadInactive, Active
BI96Diagnostic: Enter Water Temp Sensor FailUnit diagnosticReadInactive, Active
BI97Diagnostic: Water Flow FailureUnit diagnosticReadInactive, Active
BI98Diagnostic: Supply Fan VFD Bypass EnableUnit diagnosticReadInactive, Active
BI99Diagnostic: High CO2 LevelUnit diagnosticReadInactive, Active
BI100Diagnostic: Low Pressure Ctl Open - Ckt4Unit diagnosticReadInactive, Active
BI101Diagnostic: Low Pressure Ctl Open - Ckt3Unit diagnosticReadInactive, Active
BI102Diagnostic: Compressor Contact Fail-Ckt4Unit diagnosticReadInactive, Active
BI103Diagnostic: Compressor Contact Fail-Ckt3Unit diagnosticReadInactive, Active
BI104Diagnostic: Evap Temp Sensor Fail - Ckt4Unit diagnosticReadInactive, Active
BI105Diagnostic: Evap Temp Sensor Fail - Ckt3Unit diagnosticReadInactive, Active
BI106Diagnostic: RTM Zone Humidity Sensor FailUnit diagnosticReadInactive, Active
BI107Diagnostic: Ent Evap Temp Sensor Fail-Ckt 1Unit diagnosticReadInactive, Active
BI108Diagnostic: Ent Evap Temp Sensor Fail-Ckt 2Unit diagnosticReadInactive, Active
BI111Diagnostic: Recovery Dirty PrefilterUnit diagnosticReadInactive, Active
BI112Diagnostic: Recovery Lvg Exh Sensor FailUnit diagnosticReadInactive, Active
BI113Diagnostic: Energy Recovery Wheel Fail (man)Unit diagnosticReadInactive, Active
BI114Diagnostic: Cond Sump Max Level FailUnit diagnosticReadInactive, Active
BI115Diagnostic: Cond Sump Min Level or DrainUnit diagnosticReadInactive, Active
BI116Diagnostic: Cond Sump Pump Fail (man)Unit diagnosticReadInactive, Active
BI117Diagnostic: Cond Sump Pump FailUnit diagnosticReadInactive, Active
BI118Diagnostic: Cond Water Temp Sensor FailUnit diagnosticReadInactive, Active
BI119Diagnostic: Cond Sump Heater Fail (man)Unit diagnosticReadInactive, Active
BI120Diagnostic: GBAS 0-10 VDC Comm FailureUnit diagnosticReadInactive, Active
BI121Diagnostic: Reheat Head Press HighUnit diagnostic; ID used on RT unitsReadInactive, Active
BI122Diagnostic: Improper Airflow for Dehumid (man)Unit diagnosticReadInactive, Active
BI123Diagnostic: SA Reheat Setpoint FailureUnit diagnosticReadInactive, Active
BI124Diagnostic: Unocc Dehumid Setpoint FailUnit diagnosticReadInactive, Active
BI125Diagnostic: Occ Dehumid Setpoint FailureUnit diagnosticReadInactive, Active
BI126Diagnostic: Unocc Humid Setpoint FailUnit diagnosticReadInactive, Active
BI127Diagnostic: Occ Humid Setpoint FailureUnit diagnosticReadInactive, Active
BI128Diagnostic: MDM Communications FailureUnit diagnosticReadInactive, Active
BI129Diagnostic: Dirty Final FilterUnit diagnosticReadInactive, Active
BI130Diagnostic: Vel Press Sensor (Front) FailUnit diagnosticReadInactive, Active
BI131Diagnostic: High Superheat - Ckt 1Unit diagnosticReadInactive, Active
BI132Diagnostic: Low Refrigerant Charge - Ckt 1Unit diagnosticReadInactive, Active
BI133Diagnostic: High Superheat - Ckt 2Unit diagnosticReadInactive, Active
BI134Diagnostic: Low Refrigerant Charge - Ckt 2Unit diagnosticReadInactive, Active
BI139Diagnostic: MPM Communications FailureUnit diagnosticReadInactive, Active
BI140Diagnostic: TPM Communications FailureUnit diagnosticReadInactive, Active
BI141Diagnostic: Return Plenum Press SensorUnit diagnosticReadInactive, Active
BI142Diagnostic: Return Press High Limit (Man)Unit diagnosticReadInactive, Active
BI143Diagnostic: Return Press High Limit (Auto)Unit diagnosticReadInactive, Active
BI146Diagnostic: Invalid Unit ConfigurationUnit diagnosticReadInactive, Active
BI147Diagnostic: Maintenance RequiredUnit diagnosticReadInactive, Active
BI148Diagnostic: Unit Communications FailureUnit diagnosticReadInactive, Active
BI149Diagnostic: Unit Stopped at Local HIUnit diagnosticReadInactive, Active
BI150Diagnostic: Unit Stopped at Remote HIUnit diagnosticReadInactive, Active
BI151Diagnostic: RTM External StopUnit diagnosticReadInactive, Active
BI153Diagnostic: Ckt2 High Compressor Pressure Differential (Man)Unit diagnosticReadInactive, Active
BI154Diagnostic: VSM Communications FailureUnit diagnosticReadInactive, Active
BI155Diagnostic: Ckt1 High Compressor Pressure Differential (Man)Unit diagnosticReadInactive, Active
BI233Diagnostic: Sump Min Level Cycling (man)Unit diagnosticReadInactive, Active
BI235Diagnostic: Cond Press Sensor Fail – Ckt2Unit diagnosticReadInactive, Active
BI236Diagnostic: Cond Press Sensor Fail – Ckt1Unit diagnosticReadInactive, Active
BI237Diagnostic: Ent Evap Temp Sensor Fail-Ckt 3Unit diagnosticReadInactive, Active
BI238Diagnostic: Ent Evap Temp Sensor Fail-Ckt 4Unit diagnosticReadInactive, Active
BI239Diagnostic: Morning Warmup Setpoint FailUnit diagnosticReadInactive, Active
BI240Diagnostic: Min Position Setpoint FailUnit diagnosticReadInactive, Active
BI241Diagnostic: Econ Drybulb Setpoint FailUnit diagnosticReadInactive, Active
BI242Diagnostic: Min OA Flow Setpoint FailUnit diagnosticReadInactive, Active
BI247Diagnostic: Single Zone VAV Hardware Configuration FailureUnit diagnosticReadInactive, Active
BI248Diagnostic: Rapid Restart Hardware Configuration FailureUnit diagnosticReadInactive, Active
BI305Diagnostic: Unit Economizing When It Should NotUnit diagnostic [With Economizer installed]ReadInactive, Active
BI306Diagnostic: Unit Not Economizing When It ShouldUnit diagnostic [With Economizer installed]ReadInactive, Active
BI307Diagnostic: Excessive Outdoor AirUnit diagnosticReadInactive, Active
BI308Diagnostic: Outdoor Air Damper Not ModulatingUnit diagnosticReadInactive, Active
BI312Morning Warmup EnabledWhether Morning Warmup is EnabledRead
BI313Daytime Warmup EnabledWhether Daytime Warmup is EnabledRead
Object ID lookup: Trane BCI2-I point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BCI2-I (IntelliPak) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane BCI2-I (IntelliPak)

How many BACnet points does the Trane BCI2-I (IntelliPak) have?

This list has 331 BACnet objects: 82 analog inputs, 33 analog outputs, 3 analog values, 161 binary inputs, 11 binary outputs, 34 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane BCI2-I (IntelliPak) BACnet points are writable?

54 of the 331 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane BCI2-I (IntelliPak) BACnet documentation?

The source is Integration Guide: BACnet Communication Interface (BCI2-I) for IntelliPak and Commercial Self-Contained (BAS-SVP054B-EN), revision September 2023, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP054B-EN_09222023.pdf.

What are the minimum BACnet points to integrate the Trane BCI2-I (IntelliPak)?

Start with BO 1 System Control Command (Active = BAS control; Inactive = standalone, monitor only); MO 7 Occupancy Request (Occupancy command (1 = Occupied, 2 = Unoccupied)); MO 8 Heat Cool Mode Request BAS (Heat/cool mode command (1 = Auto)); AO 2 Space Temperature Setpoint BAS (Space setpoint; occupied/standby offsets apply to it); AO 6 Discharge Air Cooling Setpoint BAS (Supply air cooling setpoint on VAV units); BI 1 System Control Status (Confirms the unit is under BAS control); MI 20 Occupancy Status (Confirms the occupancy the unit is running in); MI 41 Supply Fan Status (Supply fan on/off (2 = On)); AI 15 Space Temperature Active (Space temperature the unit is controlling to); BI 165 Alarm Relay Output Status (Unit alarm relay; Active = energized).

How do I enable BMS control of the Trane BCI2-I (IntelliPak)?

At the unit Human Interface, BAS Communication Module must read Installed and Setup > Unit Control must be BAS/NETWORK. Then BO 1 System Control Command must be Active (BAS Control); while Inactive the unit runs on local sensors and setpoints and ignores BAS values. Output objects ship with Out_Of_Service = TRUE, so the unit uses its local value until the BMS sets Out_Of_Service to FALSE on each output it will write.

Does the Trane BCI2-I (IntelliPak) need a BACnet heartbeat or have a communication timeout?

BAS-supplied sensor objects with a 900 s refresh rate (AO 10-15, AO 17, AO 18, AO 25) must be rewritten within that time. If not, the BCI2-I puts the object in fault and the unit reverts to its own sensor. At power-up these objects stay in fault until the first write. Setpoints and commands have no refresh limit (AO 22 is printed with a 5 s refresh rate).

Can the BMS supply sensor values to the Trane BCI2-I (IntelliPak)?

Write BMS sensor values to the '... BAS' AOs (AO 11 Space Temperature BAS, AO 12 Discharge Air Temperature BAS, AO 13 Duct Static Pressure BAS, AO 14 Outdoor Air Temperature BAS, AO 15 Outdoor Air Humidity BAS, AO 17 Outdoor Air Flow BAS, AO 18 Space CO2 Concentration BAS, AO 25 Space Humidity BAS, AO 10 Space Static Pressure BAS) with the object in service, and keep refreshing them. The matching '... Active' AIs show the value in use.

How do I check these points on the real BCI2-I (IntelliPak)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide: BACnet Communication Interface (BCI2-I) for IntelliPak and Commercial Self-Contained · BAS-SVP054B-EN · rev. September 2023. Object names, instances and units are reproduced as published; descriptions are our own.