Rooftop unit controller · BACnet points list
Trane Symbio 700 Voyager 3 BACnet points list
Updated 6 November 2026
Symbio 700 is the factory controller on Voyager 3 rooftops. It speaks BACnet IP, BACnet MS/TP or BACnet over Zigbee (Air-Fi), and the same guide maps every object to Modbus. Objects use 5-digit instances (AI-10101, AV-11403...). Most writable objects are BAS or Setpoint values that feed Trane's arbitration logic, and the BAS sensor values carry a 900 s heartbeat.
This page lists 568 BACnet objects for the Trane Symbio 700 Voyager 3 — 198 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 700 Voyager 3
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 568 (198 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 700 Voyager 3
Leave MV 11100 Arbitration Method Request at 'Enable External/BAS Control'. Then schedule the unit with MV 10106 Occupancy Request and send setpoints to the setpoint BAS points at a priority above 14. If the BMS supplies sensor values such as space temperature, rewrite the '... BAS' points within their 900 s heartbeat.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10106 | Occupancy Request | Occupancy command (occupied/unoccupied/standby) | Command |
| BV 11113 | Unit Stop Command | BMS stop/auto of the whole unit | Write |
| AV 10159 | Occupied Cooling Setpoint BAS | Occupied cooling setpoint (dual-setpoint units) | Command |
| AV 10160 | Occupied Heating Setpoint BAS | Occupied heating setpoint (dual-setpoint units) | Command |
| AV 10127 | Space Temperature Setpoint BAS | Single-setpoint alternative to the two setpoints above | Command |
| MI 10101 | Heat Cool Mode Status | Current heat/cool operating mode | Read |
| MV 11123 | Occupancy Status | Confirms the occupancy the unit is running in | Read |
| BI 10226 | Supply Fan Status | Supply fan on/off status | Read |
| AV 11178 | Space Temperature Active | Space temperature the unit is actually controlling to | Read |
| BV 11100 | Alarm Indicator Status | Unit alarm output; on when the controller is in alarm | Read |
Enable & remote start
MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the default: the controller weighs BAS, Air-Fi and wired sources. 'Standalone Control' ignores all BAS input and is meant for troubleshooting. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.
Heartbeat & communication loss
The sensor BAS points (AV 10113 Outdoor Air Temperature BAS, AV 10114 Space Temperature BAS, AV 10116-10119, AV 11103 Return Air Humidity BAS, AV 11119 Return Air Temperature BAS) have a 900 s heartbeat in the tables, so the BMS must keep rewriting them. The setpoint and command points have no heartbeat.
Sensors & values from the BMS
Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it; the '... Arbitrator' object shows which source wins and the '... Active' object reports the value in use. Space setpoints go to AV 10127 (single setpoint) or AV 10159/10160 (dual setpoint). BV 10113 Occupancy Input BAS is the communicated occupancy input.
Network setup
- The rotary address (001-127) sets the BACnet MS/TP MAC and the default Device ID; changing it takes effect without a power cycle.
- A software Device ID (1-4194302) can be set in the Symbio Service and Installation mobile app (Bluetooth) or on the onboard display.
- MS/TP default baud is 76,800 bps; MS/TP wiring lands on connector J17. BACnet IP uses the Ethernet port.
- For BACnet IP set the IP address first, then the protocol, Device ID and UDP port; tick BBMD only if this is the only BACnet IP device on the subnet.
- Communicated units can be switched between IP and SI in the mobile app or onboard display.
Watch out for
- Wired setpoints write at priority 15 and Air-Fi at 14, so the BMS must write setpoint BAS points at a priority above 14 or the value is ignored.
- Setpoints changed from the onboard display or mobile app go to the relinquish default, not the priority array.
- Arbitrator objects are for reading only, even though the table marks them writable.
- 'Command' points may be persisted once written, so don't write them cyclically.
- Air-Fi installs are integrated through a Tracer SC+ system controller, not directly.
Trane Symbio 700 Voyager 3 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10101 | Cooling Capacity Status | Actual operating unit cooling capacity, in % | % | Read | |
| AI | 10102 | Heating Capacity Primary Status | Unit (primary) heating capacity, in % [Primary Heating Source Installed] | % | Read | |
| AI | 10104 | Outdoor Air Relative Humidity Local | OA humidity value from sensor connected to the controller | % | Read | |
| AI | 10110 | Return Air Humidity Local | Return air humidity value from sensor connected to the controller | % | Read | |
| AI | 10111 | Outdoor Air Damper Position | OA Damper Actuator feedback signal [Outside Air is Configured at 0-100% or 0-50% Motorized Damper] | % | Read | |
| AI | 10112 | Relief Damper Position | Unit commanded Relief damper position [Relief fan installed] | % | Read | |
| AI | 10116 | Space Humidity Active | Active space relative humidity being used by the controller [Humidity Sensor Configured] | % | Read | |
| AI | 10117 | Outdoor Air Dew Point | Outdoor air dewpoint value being utilized by the unit [Hot Gas Reheat is configured as Installed] | °F | Read | |
| AI | 10118 | Outdoor Air Temperature Active | Active OA temperature currently being used by the controller | °F | Read | |
| AI | 10120 | Outdoor Air Humidity Active | Active outdoor air humidity value used by the controller | % | Read | |
| AI | 10124 | Discharge Air Temperature Local | Discharge air temperature value from a sensor connected to the controller | °F | Read | |
| AI | 10126 | Return Air Temperature Input | Actual return air temperature being used by the controller | °F | Read | |
| AI | 10155 | Duct Static Pressure Local | Duct static pressure value from a sensor connected to the controller | in. w.c. | Read | |
| AI | 10156 | Outdoor Air Temperature Local | OA temp value from a sensor connected to the controller | °F | Read | |
| AI | 10185 | Outdoor Air Flow Active | Outdoor airflow used by the unit [0 to 100% Economizer w/ TRAQ installed] | cfm | Read | |
| AI | 10187 | Space Static Pressure Active | Space static pressure from a unit-mounted sensor [StatiTrac Space Pressure Control configured] | in. w.c. | Read | |
| AI | 10218 | Space Temperature Input | Space temp from a wired sensor | °F | Read | |
| AI | 10226 | Space Dew Point | Calculated Space Dewpoint [Hot Gas Reheat is Configured as Installed] | °F | Read | |
| AI | 11103 | Space CO2 Concentration Input | Space CO2 concentration from a sensor hardwired to the controller [CO2 Sensor Configured] | ppm | Read | |
| AI | 11104 | Space Humidity Input | Space relative humidity from a sensor wired to the controller [Humidity Sensor Configured] | % | Read | |
| AI | 11106 | Supply Fan Speed Command Status | Unit commanded supply fan speed output [Indoor Fan Type Configured as Multi Speed or Variable Speed] | % | Read | |
| AI | 11109 | Modulating Heat Command Status | Unit commanded modulating heat output [Modulating gas heat installed] | % | Read | |
| AI | 11111 | Outdoor Air Damper Command | Unit commanded outside air damper position [Outside Air is Configured at 0-100%] | % | Read | |
| AI | 11112 | Outdoor Airflow Pressure | Hardwired input for outdoor airflow pressure sensor [0 to 100% Economizer w/ TRAQ installed] | in. w.c. | Read | |
| AI | 11132 | On-Board I/O Firmware Major Version | Software Major Version for On-Board I/O Module | Read | ||
| AI | 11133 | On-Board I/O Firmware Minor Version | On-Board I/O Module Software build number | Read | ||
| AI | 11134 | Indoor Options Module Firmware Major Version | Software Major Version for Indoor Options Module [Indoor Options Module Installed and In-Use] | Read | ||
| AI | 11135 | Indoor Options Module Firmware Minor Version | Indoor Options Module Software build number [Indoor Options Module Installed and In-Use] | Read | ||
| AI | 11136 | Fresh Air Options Module Firmware Major Version | Software Major Version for Fresh Air Options Module [Fresh Air Options Module Installed and In-Use] | Read | ||
| AI | 11137 | Fresh Air Options Module Firmware Minor Version | Fresh Air Options Module Software build number [Fresh Air Options Module Installed and In-Use] | Read | ||
| AI | 11140 | Customer Options Module Firmware Major Version | Software Major Version for Customer Connection Options Module [Customer Options Module Installed and In-Use] | Read | ||
| AI | 11141 | Customer Options Module Firmware Minor Version | Customer Options Module Software build number [Customer Options Module Installed and In-Use] | Read | ||
| AI | 11142 | IGN Module 1 Firmware Major Version | Software Major Version for Gas Heat Ignition Module 1 [Primary Heating Source is Configured as Gas] | Read | ||
| AI | 11143 | IGN Module 1 Firmware Minor Version | Software Major Version for Gas Heat Ignition Module 1 [Primary Heating Source is Configured as Gas] | Read | ||
| AI | 11144 | IGN Module 2 Firmware Major Version | Software Major Version for Gas Heat Ignition Module 2 | Read | ||
| AI | 11145 | IGN Module 2 Firmware Minor Version | Software Minor Version for Gas Heat Ignition Module 2 | Read | ||
| AI | 11148 | Remote Minimum Position | Hardwired remote minimum position for OA damper control [Remote Minimum Position is Configured as Installed] | % | Read | |
| AI | 11149 | Return Air Temperature Active | Return Air Temperature being used for control | °F | Read | |
| AI | 11150 | Sensor Battery Status Air-Fi | Status %age of connected AirFi sensor(s) [Air-Fi Sensor Installed and Communicating] | % | Read | |
| AI | 11151 | Space CO2 Concentration Air-Fi | Space CO2 concentration from a wireless sensor connected to the controller [Air-Fi Sensor Installed and Communicating] | ppm | Read | |
| AI | 11152 | Space Humidity Air-Fi | Space relative humidity from a connected wireless sensor [Air-Fi Sensor Installed and Communicating] | % | Read | |
| AI | 11154 | Space Temperature Air-Fi | Space temp from a connected wireless (AirFi) sensor [Air-Fi Sensor Installed and Communicating] | °F | Read | |
| AI | 11155 | Space Temperature Cooling Setpoint Air-Fi | (occupied) cooling setpoint from the connected wireless space sensor [Air-Fi Sensor Installed and Communicating] | °F | Read | |
| AI | 11156 | Space Temperature Heating Setpoint Air-Fi | (occupied) heating setpoint from the connected wireless space sensor [Air-Fi Sensor Installed and Communicating] | °F | Read | |
| AI | 11157 | Space Temperature Setpoint Air-Fi | Space Temperature Setpoint from a connected wireless sensor [Air-Fi Sensor Installed and Communicating] | °F | Read | |
| AI | 11158 | Space Static Pressure Input | Space statice pressure from a wired sensor connected to the controller [StatiTrac Space Pressure Control configured.] | in. w.c. | Read | |
| AI | 11159 | Space Temperature Cooling Setpoint Input | (occupied) cooling setpoint from the connected wired space sensor | °F | Read | |
| AI | 11160 | Space Temperature Heating Setpoint Input | (occupied) heating setpoint from the connected wired space sensor | °F | Read | |
| AI | 11161 | Space Temperature Setpoint Input | Space Temperature Setpoint from a connected wired sensor [Space Controller Configured as Single Setpoint Zone Sensor] | °F | Read | |
| AI | 11164 | Reheat Valve 1 Step Status | Reheat Valve 1 Status in steps from Stepper Motor Module | Read | ||
| AI | 11165 | Reheat Valve 2 Step Status | Reheat Valve 2 (Cooling) Status in steps from Stepper Motor Module | Read | ||
| AI | 11166 | Evaporator Entering Refrigerant Temperature | Evaporator Entering Refrigerant Temperature from a connected wire sensor on the Indoor | °F | Read | |
| AI | 11167 | Stepper Motor Module Firmware Major Version | Software Major Version for Stepper Motor Module [Stepper Motor Module Installed and In-Use] | Read | ||
| AI | 11168 | Stepper Motor Module Firmware Minor Version | Stepper Motor Module Software build number [Stepper Motor Module Installed and In-Use] | Read | ||
| AI | 11171 | Refrigerant LFL Concentration Sensor A | Expressed in % of LFL (Lower Flammability Limit) [Refrigerant Type is R454B] | % | Read | |
| AI | 11172 | Refrigerant LFL Concentration Alarm Threshold Sensor A | Defines the %LFL setpoint [Refrigerant Type is R454B] | % | Read | |
| AV | 10103 | Outdoor Air Temperature Arbitrator | OA temp determined by arbitration | °F | Write | |
| AV | 10104 | Outdoor Air Humidity Arbitrator | Actual outdoor air humidity being used by the controller | % | Write | |
| AV | 10106 | Space Temperature Arbitrator | Space temp determined by arbitration [Space Controller is Configured as Single or Dual Setpoint Zone Sensor] | °F | Write | |
| AV | 10107 | Space Static Pressure Arbitrator | Space static pressure value from a unit mounted sensor [StatiTrac Space Pressure Control configured.] | in. w.c. | Write | |
| AV | 10108 | Space CO2 Concentration Arbitrator | Space CO2 concentration being used by the controller [CO2 Sensor Configured] | ppm | Write | |
| AV | 10109 | Space Humidity Arbitrator | Space relative humidity, determined by the arbitration [Space Humidity Sensor Configured] | % | Write | |
| AV | 10113 | Outdoor Air Temperature BAS | Used to send the outdoor air temperature sensor value | °F | Write | |
| AV | 10114 | Space Temperature BAS | Used to send the space temperature value | °F | Write | |
| AV | 10116 | Outdoor Air Humidity BAS | Used to send the outdoor air humidity sensor value | % | Write | |
| AV | 10117 | Space Static Pressure BAS | BAS space static pressure sensor value [StatiTrac Space Pressure Control configured.] | in. w.c. | Write | |
| AV | 10118 | Space CO2 Concentration BAS | Used to send the space CO2 concentration value [CO2 Sensor Configured] | ppm | Write | |
| AV | 10119 | Space Humidity BAS | Used to send the space relative humidity value [Space Humidity Sensor Configured] | % | Write | |
| AV | 10121 | Discharge Air Cooling Setpoint BAS | Used to request the discharge air temp cooling setpoint value [System Type is Configured as VVDA] | °F | Command | |
| AV | 10122 | Discharge Air Heating Setpoint BAS | Used to request the discharge air temperature heating setpoint value | °F | Command | |
| AV | 10123 | Unoccupied Cooling Setpoint | Used to define the cooling temp setpoint used for control in unoccupied | °F | Write | |
| AV | 10124 | Unoccupied Heating Setpoint | Used to define the heating temp setpoint used for control in unoccupied | °F | Write | |
| AV | 10125 | Outdoor Air Minimum Flow Setpoint BAS | Used to send the requested minimum OA flow setpoint [0 to 100% Economizer w/ TRAQ installed] | cfm | Command | |
| AVmin | 10127 | Space Temperature Setpoint BAS | BAS-supplied space temperature setpoint value [Space Controller Configured as Single Setpoint Zone Sensor] | °F | Command | |
| AV | 10128 | Space Static Pressure Setpoint BAS | Space Static Pressure Setpoint [StatiTrac Space Pressure Control configured.] | in. w.c. | Command | |
| AV | 10130 | Occupied Offset | Difference between the occ cool and heat setpts when a single setpoint | Δ°F | Write | |
| AV | 10134 | Discharge Air Reheat Setpoint BAS | Used to request the discharge air temperature reheat setpoint value | °F | Command | |
| AV | 10138 | Filter Runtime Hours Setpoint | Setpoint value used by the filter run hours calculation | Command | ||
| AV | 10139 | Cooling Capacity Enable | Used to limit the cooling capacity of the unit | % | Command | |
| AV | 10140 | Heat Primary Enable BAS | Used to demand limit the heating capacity; 0% = No Heating Possible | % | Command | |
| AV | 10141 | Morning Warmup Setpoint BAS | Defines the space temp below which MWU is enabled | °F | Command | |
| AV | 10142 | Occupied Standby Offset | Difference between the occ standby cool and heat setpts when a single | Δ°F | Write | |
| AV | 10143 | Duct Static Pressure Setpoint BAS | Used to request the duct static pressure setpoint value [System Type is Configured as VVDA] | in. w.c. | Command | |
| AV | 10144 | Economizer Minimum Position Setpoint BAS | Used to request the ecominizer minimum position setpoint | % | Command | |
| AV | 10149 | Daytime Warmup Setpoint BAS | Defines the space temp below which daytime warmup will be enabled | °F | Command | |
| AV | 10150 | Economizer Outdoor Air Enable Setpoint BAS | Temperature setpoint below which economizing can be used [Outside Air is Configured as 0-100%] | °F | Command | |
| AV | 10154 | Space Cooling Setpoint High Limit BAS | Space Cooling Setpoint High Limit BAS | °F | Write | |
| AV | 10155 | Space Cooling Setpoint Low Limit BAS | Space Cooling Setpoint Low Limit BAS | °F | Write | |
| AV | 10157 | Space Heating Setpoint High Limit BAS | Space Heating Setpoint High Limit BAS | °F | Write | |
| AV | 10158 | Space Heating Setpoint Low Limit BAS | Space Heating Setpoint Low Limit BAS | °F | Write | |
| AVmin | 10159 | Occupied Cooling Setpoint BAS | Used to define the occ cooling setpt when both heat and cool | °F | Command | |
| AVmin | 10160 | Occupied Heating Setpoint BAS | Used to define the occ heating setpt when both heat and cool | °F | Command | |
| AV | 10161 | Occupied Standby Cooling Setpoint BAS | Defines the occ standby cooling setpt when both heat/cool setpoints are provided | °F | Command | |
| AV | 10162 | Occupied Standby Heating Setpoint BAS | Defines the occ standby heating setpt when both heat/cool setpoints are provided | °F | Command | |
| AV | 10167 | Discharge Air Temperature Minimum Cool Limit | Used to define the discharge air temperature minimum cool limit | °F | Command | |
| AV | 10168 | Relief Enable Position Setpoint | OA damper position above which the Relief sequence is enabled [Space Pressure Control is Configured] | % | Command | |
| AV | 10169 | Occupied Bypass Time | Used to configure the occupied bypass time (occupancy override) | Write | ||
| AV | 10170 | Economizer Outdoor Air Enthalpy Enable Setpoint BAS | Used to determine the outdoor air enthalpy below which economizing is enabled | Btu/lb | Command | |
| AV | 10175 | Space CO2 High Limit | Used to define the CO2 high limit, for ventilation purposes | ppm | Command | |
| AV | 10176 | Space CO2 Low Limit | Normally provided by the BMS to define the CO2 low limit | ppm | Command | |
| AV | 10214 | Space Dehumidification Unoccupied Setpoint Active | Active value for Space Dehumidification Setpoint BAS point being used for control | % | Read | |
| AV | 10228 | Space Dew Point Unoccupied Setpoint Active | Unoccupied Space Dew Point Setpoint actively being used for dehumidification control | °F | Read | |
| AV | 10281 | Discharge Air Temperature Setpoint Active | Discharge air temp setpoint actively being used for control [System Type Configured as VVZTand] | °F | Read | |
| AV | 11103 | Return Air Humidity BAS | BAS Source for Return Air Humidity [Economizer Type is Configured as Comparative Enthalpy] | % | Write | |
| AV | 11104 | Run Time - Compressor 3 (Hours) | Compressor 3 Runtime | Read | ||
| AV | 11105 | Starts - Compressor 3 | Compressor 3 Starts | Read | ||
| AV | 11106 | Run Time - Condenser Fan 3 (Hours) | Condenser Fan 3 Runtime | Read | ||
| AV | 11107 | Starts - Condenser Fan 3 | Condenser Fan 3 Starts | Read | ||
| AV | 11108 | Cabinet Style | Cabinet style of the unit | Read | ||
| AV | 11110 | Supply Fan Speed Command | Remote supply fan speed request | % | Command | |
| AV | 11112 | Cooling Capacity Setpoint BAS | Remote cooling capacity request | % | Command | |
| AV | 11113 | Space Dehumidification Setpoint Offset BAS - Active | Active value for the offset applied to the Space Dehumidification Setpoint | % | Read | |
| AV | 11115 | Exhaust Or Return Fan Type | Identifies the product exhaust or return fan type | Read | ||
| AV | 11116 | Filter Runtime Hours | Number of hours air has flowed through the filter | Read | ||
| AV | 11117 | Outdoor Air Enthalpy Active | Outdoor air enthalpy value being utilized by the unit | Btu/lb | Read | |
| AV | 11118 | Return Air Temperature Arbitrator | Arbitrator for Return Air Temperature [Economizer Type is Configured as Comparative Enthalpy or Differential Drybulb] | °F | Write | |
| AV | 11119 | Return Air Temperature BAS | BAS source for Return Air Temperature [Economizer Type is Configured as Comparative Enthalpy or Differential Drybulb] | °F | Write | |
| AV | 11120 | Heating Demand Limit Capacity Enable Setpoint | Heating Demand Limit Capacity Enable Setpoint | % | Command | |
| AV | 11121 | Discharge Air Temperature Maximum Cool Limit | Maximum discharge air temperature allowed during space temperature cooling mode of operation | °F | Command | |
| AV | 11122 | Run Time - Condenser Fan 1 (Hours) | Condenser Fan 1 Runtime | Read | ||
| AV | 11123 | Run Time - Condenser Fan 2 (Hours) | Condenser Fan 2 Runtime [Dual Condenser Fan Systems] | Read | ||
| AV | 11124 | Run Time - Relief Fan (Hours) | Relief Fan Runtime [Space Pressure Control is Configured] | Read | ||
| AV | 11125 | Run Time - Electric Heat Stage 1 (Hours) | Electric Heat Stage 1 Runtime [One or more stages of Staged Electric Heat configured] | Read | ||
| AV | 11126 | Run Time - Electric Heat Stage 2 (Hours) | Electric Heat Stage 2 Runtime [Two or more stages of Staged Electric Heat configured] | Read | ||
| AV | 11127 | Run Time - Supply Fan (Hours) | Supply Fan Runtime | Read | ||
| AV | 11128 | Space Temp Cooling Setpoint Status | Space cooling setpoint, determined by arbitration | °F | Read | |
| AV | 11129 | Space Temp Heating Setpoint Status | Space heating setpoint, determined by arbitration | °F | Read | |
| AV | 11130 | Design Minimum OA Damper Position at Full Fan Capacity | Design Minimum OA Damper Position at Full Fan Capacity [Outside Air is Configured as 0-100%] | % | Command | |
| AV | 11131 | Design Minimum OA Damper Position at Mid Fan Capacity | Design Minimum OA Damper Position at Mid Fan Capacity | % | Command | |
| AV | 11132 | Design Minimum OA Damper Position at Min Fan Capacity | Design Minimum OA Damper Position at Min Fan Capacity | % | Command | |
| AV | 11133 | DCV Minimum OA Damper Position at Full Fan Capacity | DCV Minimum OA Damper Position at Full Fan Capacity | % | Command | |
| AV | 11134 | DCV Minimum OA Damper Position at Mid Fan Capacity | DCV Minimum OA Damper Position at Mid Fan Capacity | % | Command | |
| AV | 11135 | DCV Minimum OA Damper Position at Min Fan Capacity | DCV Minimum OA Damper Position at Min Fan Capacity | % | Command | |
| AV | 11136 | Space Dehumidification Setpoint BAS - Active | Active value for the Space Dehumidification Setpoint for Relative Humidity control | % | Read | |
| AV | 11137 | Discharge Air Heating Setpoint High Limit | Discharge Air Heating Setpoint High Limit (deg F) [VVZT and modulating gas heat installed] | °F | Command | |
| AV | 11138 | Discharge Air Heating Setpoint (Target) | Discharge Air Heating Setpoint (Target) [VVZT and modulating gas heat installed] | °F | Command | |
| AV | 11140 | Discharge Air Cooling Setpoint (Target) | Discharge Air Cooling Setpoint (Target) | °F | Command | |
| AV | 11142 | Space Static Pressure Setpoint Deadband | Space Static Pressure Setpoint Deadband [StatiTrac Space Pressure Control configured.] | in. w.c. | Command | |
| AV | 11143 | Design Min Outdoor Airflow Setpoint | Design Minimum OA CFM Setpoint [0 to 100% Economizer w/ TRAQ and Demand Controlled Ventilation installed] | cfm | Command | |
| AV | 11144 | Standby Min Outdoor Airflow Setpoint | Standby Minimum OA CFM Setpoint [0 to 100% Economizer w/ TRAQ and Demand Controlled Ventilation installed] | cfm | Command | |
| AV | 11145 | DCV Min Outdoor Airflow Setpoint | DCV Minimum OA CFM Setpoint [0 to 100% Economizer w/ TRAQ and Demand Controlled Ventilation installed] | cfm | Command | |
| AV | 11147 | Economizer Dry Bulb Enable Offset | Outdoor air temperature offset below dry bulb economizer enable setpoint [Outside Air is Configured as 0-100%] | Δ°F | Write | |
| AV | 11148 | Duct Static Pressure P-Gain (%/IWC) | Proportional gain for fan speed on duct static pressure control (%/IWC) [System Type Configured as VVDA] | % | Write | |
| AV | 11149 | Duct Static Pressure Deadband BAS | Supply Air Pressure Setpoint Deadband [System Type Configured as VVDA] | in. w.c. | Command | |
| AV | 11150 | Cooling Reset Start Temp | Discharge air cooling reset start temperature [System Type Configured as VVDA] | °F | Write | |
| AV | 11151 | Cooling Reset End Temp | Discharge air cooling reset end temperature [System Type Configured as VVDA] | °F | Write | |
| AV | 11152 | Cooling Reset Amount | Discharge air cooling amount to reset between start and end temperatures [System Type Configured as VVDA] | Δ°F | Write | |
| AV | 11153 | Service Test Timeout (Minutes) | Timer (minutes) to indicate when the unit should cease service test | Write | ||
| AV | 11154 | Economizer Cooling Reference Enthalpy Offset | Economizer Cooling Reference Enthalpy Offset [Economizer Type is Configured as Comparative Enthalpy or Reference Enthalpy] | Btu/lb | Write | |
| AV | 11155 | Starts - Condenser Fan 1 | Condenser Fan 1 Starts | Read | ||
| AV | 11156 | Starts - Condenser Fan 2 | Condenser Fan 2 Starts [Dual Condenser Fan Systems] | Read | ||
| AV | 11157 | Starts - Relief Fan | Relief Fan Starts [Space Pressure Control is Configured] | Read | ||
| AV | 11158 | Starts - Electric Heat Stage 1 | Electric Heat Stage 1 Starts [One or more stages of Staged Electric Heat configured] | Read | ||
| AV | 11159 | Starts - Electric Heat Stage 2 | Electric heat stage 2 starts [Two or more stages of Staged Electric Heat configured] | Read | ||
| AV | 11160 | Starts - Supply Fan | Counter for supply fan starts | Read | ||
| AV | 11161 | Supply Fan Type | Unit supply fan type | Read | ||
| AV | 11163 | Supply Fan Speed Status | Estimated supply fan speed being utilized | % | Read | |
| AV | 11164 | Heating Capacity Setpoint BAS | Setpoint to command the unit to a given heating capacity output [Primary Heating Source Configured] | % | Command | |
| AV | 11167 | Demand Shed Offset Setpoint | Demand Shed Offset Setpoint [Demand Management Configured as Demand Shed] | Δ°F | Command | |
| AV | 11168 | Cooling Demand Limit Capacity Enable Setpoint | Cooling Demand Limit Capacity Enable Setpoint [Demand Management Configured as Demand Limit] | % | Command | |
| AV | 11169 | Run Time - Compressor 1 (Hours) | Compressor 1 Runtime | Read | ||
| AV | 11170 | Run Time - Compressor 2 (Hours) | Compressor 2 Runtime [Multi-Compressor Systems] | Read | ||
| AV | 11173 | Supply Fan Minimum Speed Setpoint | Minimum supply fan speed command [Indoor Fan Type Configured as Multi Speed or Variable Speed] | % | Command | |
| AV | 11174 | Supply Fan Maximum Speed Setpoint | Maximum supply fan speed command [Indoor Fan Type Configured as Multi Speed or Variable Speed] | % | Command | |
| AVmin | 11178 | Space Temperature Active | Active space temperature being used by the controller | °F | Read | |
| AV | 11180 | Space Temperature Heating Setpoint Input Active | Active heating space temperature input setpoint as determined by arbitrating the heating | °F | Read | |
| AV | 11181 | Space Temperature Setpoint Active | Active space temperature setpoint being used by the controller | °F | Read | |
| AV | 11183 | Starts - Compressor 1 | Compressor 1 Starts | Read | ||
| AV | 11184 | Starts - Compressor 2 | Compressor 2 Starts [Multi-Compressor Systems] | Read | ||
| AV | 11185 | Cooling Capacity Enable - Active | Active value for Cooling Capacity Enable point being used for control | % | Read | |
| AV | 11186 | Daytime Warmup Setpoint BAS - Active | Active value for Daytime Warmup Setpoint BAS point being used for control | °F | Read | |
| AV | 11187 | Supply Fan Speed Command - Active | Active value for Supply Fan Speed Command point being used for control | % | Read | |
| AV | 11189 | Cooling Capacity Setpoint BAS - Active | Active value for Cooling Capacity Setpoint BAS point being used for control | % | Read | |
| AV | 11190 | Discharge Air Cooling Setpoint BAS - Active | Active value for Discharge Air Cooling Setpoint BAS point being used for | °F | Read | |
| AV | 11191 | Discharge Air Heating Setpoint BAS - Active | Active value for Discharge Air Heating Setpoint BAS point being used for | °F | Read | |
| AV | 11192 | Discharge Air Reheat Setpoint BAS - Active | Active value for Discharge Air Reheat Setpoint BAS point being used for | °F | Read | |
| AV | 11193 | Discharge Air Temperature Minimum Cool Limit - Active | Active value for Discharge Air Temperature Minimum Cool Limit point being used | °F | Read | |
| AV | 11195 | Economizer Minimum Position Setpoint BAS - Active | Active value for Economizer Minimum Position Setpoint BAS point being used for | % | Read | |
| AV | 11196 | Economizer Outdoor Air Enthalpy Enable Setpoint BAS - Active | Active value for Economizer Outdoor Air Enthalpy Enable Setpoint BA point being | Btu/lb | Read | |
| AV | 11197 | Economizer Outdoor Air Enable Setpoint BAS - Active | Active value for Economizing Outdoor Air Enable Setpoint point being used for | °F | Read | |
| AV | 11198 | Relief Enable Position Setpoint - Active | Active value for Relief Enable Position Setpoint point being used for control | % | Read | |
| AV | 11199 | Heating Demand Limit Capacity Enable Setpoint - Active | Active value for Heating Demand Limit Capacity Enable Setpoint point being used | % | Read | |
| AV | 11200 | Discharge Air Temperature Maximum Cool Limit - Active | Active value for Discharge Air Temperature Maximum Cool Limit point being used | °F | Read | |
| AV | 11202 | Cool Type | Type of cooling in the unit | Read | ||
| AV | 11203 | DCV Min Outdoor Airflow Setpoint - Active | Active value for DCV Minimum OA CFM Setpoint point being used for | cfm | Read | |
| AV | 11204 | DCV Minimum OA Damper Position at Full Fan Capacity - Active | Active value for DCV Minimum OA Damper Position at Full Fan Capacity | % | Read | |
| AV | 11205 | DCV Minimum OA Damper Position at Mid Fan Capacity - Active | Active value for DCV Minimum OA Damper Position at Mid Fan Capacity | % | Read | |
| AV | 11206 | DCV Minimum OA Damper Position at Min Fan Capacity - Active | Active value for DCV Minimum OA Damper Position at Min Fan Capacity | % | Read | |
| AV | 11209 | Demand Shed Offset Setpoint - Active | Active value for Demand Shed Offset Setpoint point being used for control | Δ°F | Read | |
| AV | 11210 | Design Min Outdoor Airflow Setpoint - Active | Active value for Design Minimum OA CFM Setpoint point being used for | cfm | Read | |
| AV | 11211 | Design Minimum OA Damper Position at Full Fan Capacity - Active | Active value for Design Minimum OA Damper Position at Full Fan Capacity | % | Read | |
| AV | 11212 | Design Minimum OA Damper Position at Mid Fan Capacity - Active | Active value for Design Minimum OA Damper Position at Mid Fan Capacity | % | Read | |
| AV | 11213 | Design Minimum OA Damper Position at Min Fan Capacity - Active | Active value for Design Minimum OA Damper Position at Min Fan Capacity | % | Read | |
| AV | 11214 | Economizer Dry Bulb Disable Return Air Offset | Differential dry bulb economizer disable offset [Outside Air is Configured as 0-100%] | Δ°F | Write | |
| AV | 11217 | Filter Runtime Hours Setpoint - Active | Filter runtime hours setpoint in use | Read | ||
| AV | 11218 | Heat Primary Enable BAS - Active | Heat primary enable value in use [Primary Heating Source] | % | Read | |
| AV | 11219 | Heating Capacity Setpoint BAS - Active | Active value for Heating Capacity Setpoint BAS point being used for control [Primary Heating Source Configured] | % | Read | |
| AV | 11220 | Morning Warmup Setpoint BAS - Active | Active value for Morning Warmup Setpoint BAS point being used for control | °F | Read | |
| AV | 11222 | Outdoor Air Minimum Flow Setpoint BAS - Active | Active value for Outdoor Air Minimum Flow Setpoint BAS point being used | cfm | Read | |
| AV | 11226 | Space CO2 High Limit - Active | Active value for Space CO2 High Limit point being used for control | ppm | Read | |
| AV | 11227 | Space CO2 Low Limit - Active | Active value for Space CO2 Low Limit point being used for control | ppm | Read | |
| AV | 11229 | Space Static Pressure Setpoint Deadband - Active | Active value for Space Static Pressure Setpoint Deadband point being used for | in. w.c. | Read | |
| AV | 11231 | Standby Min Outdoor Airflow Setpoint - Active | Active value for Standby Minimum OA CFM Setpoint point being used for | cfm | Read | |
| AV | 11236 | Discharge Air Cooling Setpoint (Target) - Active | Active value for Discharge Air Cooling Setpoint (Target) point being used for | °F | Read | |
| AV | 11237 | Discharge Air Heating Setpoint High Limit - Active | Active value for Discharge Air Heating Setpoint High Limit point being used | °F | Read | |
| AV | 11238 | Duct Static Pressure Reset Time (seconds) | Reset time for fan speed on duct static pressure control (seconds) [System Type Configured as VVDA] | Write | ||
| AV | 11240 | Duct Static Pressure Deadband Active | Active value for Supply Air Pressure Setpoint Deadband point being used for | in. w.c. | Read | |
| AV | 11241 | Heating Reset Start Temp | Discharge air heating reset start temperature [Heating is Installed and System Type is Configured as VVDA] | °F | Write | |
| AV | 11242 | Heating Reset End Temp | Discharge air heating reset end temperature [Heating is Installed and System Type is Configured as VVDA] | °F | Write | |
| AV | 11243 | Supply Fan Maximum Speed Setpoint - Active | Active value for Supply Fan Maximum Speed Setpoint point being used for | % | Read | |
| AV | 11244 | Supply Fan Maximum Output Frequency Status | Active value for Supply Fan Maximum Output Frequency point being used for | Read | ||
| AV | 11245 | Supply Fan Minimum Speed Setpoint - Active | Active value for Supply Fan Minimum Speed Setpoint point being used for | % | Read | |
| AV | 11246 | Supply Fan Minimum Output Frequency Status | Active value for Supply Fan Minimum Output Frequency point being used for | Read | ||
| AV | 11247 | Cooling Demand Limit Capacity Enable Setpoint - Active | Active value for Cooling Demand Limit Capacity Enable Setpoint point being used | % | Read | |
| AV | 11248 | Economizer Minimum Position Setpoint Active | Economizer min position setpoint value resulting from arbitration | % | Read | |
| AV | 11249 | Heating Capacity Secondary Status | Unit secondary heating capacity being utilized [Secondary Heating Source Configured] | % | Read | |
| AV | 11250 | Occupied Standby Cooling Setpoint BAS - Active | Active value for Occupied Standby Cooling Setpoint BAS | °F | Read | |
| AV | 11251 | Occupied Standby Heating Setpoint BAS - Active | Active value for Occupied Standby Heating Setpoint BAS | °F | Read | |
| AV | 11252 | Preheat Type | Identifies the product preheat type | Read | ||
| AV | 11253 | Reheat Type | Identifies the product reheat type | Read | ||
| AV | 11254 | Space CO2 Concentration Active | Active space CO2 concentration being used by the controller [CO2 Sensor Configured] | ppm | Read | |
| AV | 11256 | Compressor Cooling P-Gain (%/F) | Compressor cooling PI gain; row repeated per control type | % | Write | |
| AV | 11257 | Compressor Cooling Reset Time (seconds) | Compressor cooling PI reset time; row repeated per control type | Write | ||
| AV | 11258 | Economizer Cooling P-Gain - 1 (%/F) | Proportional gain for 1st loop Econ PI controller (%/F), for CVZT/VVZT systems | % | Write | |
| AV | 11259 | Economizer Cooling Reset Time - 1 (Seconds) | Reset time for 1st loop Econ PI controller (seconds), for CVZT/VVZT systems | Write | ||
| AV | 11266 | Auxiliary Heating P-Gain (%/F) | Auxiliary heat PI gain; meaning varies by heat type | % | Write | |
| AV | 11267 | Auxiliary Heating Reset Time (seconds) | Auxiliary heat PI reset time; meaning varies by heat type | Write | ||
| AV | 11268 | Compressor Cooling P-Gain - 1 (%/F) | Proportional gain for 1st loop Cooling PI controller (%/F) | % | Write | |
| AV | 11269 | Compressor Cooling Reset Time - 1 (seconds) | Reset time for 1st loop Cooling PI controller (second) | Write | ||
| AV | 11270 | Compressor Cooling P-Gain - 2 (%/F) | Proportional gain for 2nd loop compressor cooling PI controller (%/F) | % | Write | |
| AV | 11271 | Compressor Cooling Reset Time - 2 (seconds) | Reset time for 2nd loop compressor cooling PI controller (second) | Write | ||
| AV | 11272 | Economizer Discharge Air Setpoint | Discharge Air Setpoint selection to be used for Economizer control on Conventional | °F | Command | |
| AV | 11273 | Economizer Discharge Air Setpoint - Active | Active Discharge Air Setpoint used for Economizer control on Conventional Thermostat controlled | °F | Read | |
| AV | 11276 | Space Temperature Setpoint Input Active | Active space temperature input setpoint as determined by arbitrating the space temperature | °F | Read | |
| AV | 11277 | Space Temperature Cooling Setpoint Input Active | Active cooling space temperature input setpoint as determined by arbitrating the cooling | °F | Read | |
| AV | 11278 | Supply Fan Power | Supply Fan Drive Output Power [Indoor Fan Type Configured as Multi Speed or Variable Speed] | kW | Read | |
| AV | 11279 | Supply Fan Current | Supply Fan Drive Output Current [Indoor Fan Type Configured as Multi Speed or Variable Speed] | A | Read | |
| AV | 11280 | Duct Static Pressure Setpoint Active | Duct static pressure control setpoint value resulting from arbitration [System Type Configured as VVDA] | in. w.c. | Read | |
| AV | 11281 | Dehumidification Control Status | Status of the unit dehumidification capacity [Hot Gas Reheat is Configured as Installed] | % | Read | |
| AV | 11286 | Motorized Damper Position Setpoint | Motorized Damper Position Setpoint [Outside Air is Configured as 0-50% Motorized Damper] | % | Command | |
| AV | 11287 | Motorized Damper Position Setpoint - Active | Active value for Motorized Damper Position Setpoint [Outside Air is Configured as 0-50% Motorized Damper] | % | Read | |
| AV | 11288 | Standby Minimum OA Damper Position at Full Fan Capacity | Standby Minimum OA Damper Position at Full Fan Capacity | % | Command | |
| AV | 11289 | Standby Minimum OA Damper Position at Full Fan Capacity - Active | Active value for Standby Minimum OA Damper Position at Full Fan Capacity | % | Read | |
| AV | 11290 | Standby Minimum OA Damper Position at Mid Fan Capacity | Standby Minimum OA Damper Position at Mid Fan Capacity | % | Command | |
| AV | 11291 | Standby Minimum OA Damper Position at Mid Fan Capacity - Active | Active value for Standby Minimum OA Damper Position at Mid Fan Capacity | % | Read | |
| AV | 11292 | Standby Minimum OA Damper Position at Min Fan Capacity | Standby Minimum OA Damper Position at Min Fan Capacity | % | Command | |
| AV | 11293 | Standby Minimum OA Damper Position at Min Fan Capacity - Active | Active value for Standby Minimum OA Damper Position at Min Fan Capacity | % | Read | |
| AV | 11299 | Return Air Humidity Active | Active Return Air Humidity sensor used for control [Economizer Type is Configured as Comparative Enthalpy] | % | Read | |
| AV | 11300 | Return Air Humidity Arbitrator | Arbitrator for Return Air Humidity [Economizer Type is Configured as Comparative Enthalpy] | % | Write | |
| AV | 11301 | Return Air Enthalpy Active | Return air enthalpy value being utilized by the unit [Economizer Type is Configured as Comparative Enthalpy] | Btu/lb | Read | |
| AV | 11302 | Relief Enable Position Setpoint Status | Outdoor air damper position to enable Relief sequence [Space Pressure Control is Configured] | % | Read | |
| AV | 11307 | Discharge Air Heating Setpoint (Target) - Active | Active value for Discharge Air Heating Setpoint (Target) point being used for | °F | Read | |
| AV | 11308 | Duct Static Pressure Setpoint High Limit Setpoint BAS | Duct Static Pressure Setpoint High Limit is used to limit fan speed | in. w.c. | Command | |
| AV | 11309 | Duct Static Pressure Setpoint High Limit Setpoint BAS - Active | Active Duct Static Pressure Setpoint High Limit is used to limit fan | in. w.c. | Read | |
| AV | 11314 | Comfort Purge Interval (minutes) | User adjustable setpoint used to set the amount of time the compressor | Write | ||
| AV | 11315 | Reheat Purge Interval (minutes) | User adjustable setpoint used to set the amount of time the compressors | Write | ||
| AV | 11316 | Reheat P-Gain 1 | Proportional gain for 1st loop Reheat PI controller (%/F) | % | Write | |
| AV | 11317 | Reheat Reset Time - 1 | Reset time for 1st loop Reheat PI controller (second) | Write | ||
| AV | 11318 | Reheat P-Gain 2 | Proportional gain for 2nd loop Reheat PI controller (%/F) | % | Write | |
| AV | 11319 | Reheat Reset Time - 2 | Reset time for discharge air Reheat PI controller (second) | Write | ||
| AV | 11320 | Space Dew Point Setpoint BAS | User adjustable setpoint used to set the maximum Space Dew Point Setpoint | °F | Command | |
| AV | 11321 | Dew Point Setpoint Offset BAS | User adjustable setpoint used to set the maximum Space Dew Point Setpoint | °F | Command | |
| AV | 11323 | Outdoor Air Dew Point Setpoint BAS | User adjustable setpoint used to set the Outdoor Air Dew Point Setpoint | °F | Command | |
| AV | 11325 | Space Static Pressure Setpoint Active | Active space static pressure being used by the controller [StatiTrac Space Pressure Control configured.] | in. w.c. | Read | |
| AV | 11326 | Space Dehumidification Setpoint Offset BAS | Setting for unit to use for applying a % offset to the | % | Command | |
| AV | 11327 | Space Dehumidification Setpoint BAS | Setting for unit to use to control dehumidification [Hot Gas Reheat is Configured as Installed] | % | Command | |
| AV | 11329 | Space Dehumidification Unoccupied Setpoint BAS | Used to define the (occupied) space dehumidification setpoint | % | Command | |
| AV | 11330 | Space Dew Point Unoccupied Setpoint BAS | User adjustable setpoint used to set the maximum Space Dew Point Unoccupied | °F | Command | |
| AV | 11331 | Compressor Dehumid P-Gain 2 | Proportional Gain for 2nd loop Compressor Dehumid PI controller (%/deg F) | °F | Write | |
| AV | 11332 | Compressor Dehumid P-Gain 1 | Proportional gain for 1st loop Compressor Dehumid PI controller (%/F) | °F | Write | |
| AV | 11333 | Compressor Dehumid Reset Time - 2 (seconds) | Reset time for 2nd loop compressor Dehumid PI controller (second) | Write | ||
| AV | 11334 | Compressor Dehumid Reset Time - 1 (seconds) | Reset time for 1st loop Dehumid PI controller (second) [Hot Gas Reheat is configured as Installed] | Write | ||
| AV | 11335 | Pre Cool Setpoint BAS | Defines the space temp above which Pre Cool is enabled | °F | Command | |
| AV | 11336 | Pre Cool Setpoint BAS - Active | Active value for Pre Cool Setpoint BAS point being used for control | °F | Read | |
| AV | 11337 | Refrigerant Target Setpoint Active | Refrigerant target setpoint actively being used for dehumidification control [Hot Gas Reheat is Configured as installed] | °F | Read | |
| AV | 11338 | Space Dew Point Setpoint Active | Occupied Space Dew Point Setpoint actively being used for dehumidification control | °F | Read | |
| AV | 11340 | Dew Point Setpoint Offset BAS - Active | Dew Point Setpoint Offset actively being used for dehumidification control | °F | Read | |
| AV | 11341 | Outdoor Air Dew Point Setpoint BAS - Active | Outdoor Air Dew Point Setpoint Offset actively being used for dehumidification control | °F | Read | |
| AV | 11342 | Unoccupied Dehumidification Timer | User adjustable time the space relative humidity is controlled <65% in unoccupied | Write | ||
| AV | 11343 | Heating Reset Amount | Discharge air heating amount to reset between start and end temperatures | Δ°F | Write | |
| AV | 11344 | VAV Box Stroke Timer | User adjustable VAV Box Stroke time that should be allowed for full | Write | ||
| AV | 11346 | Economizer Cooling P-Gain (%/F) | Proportional gain for VVDA systems Econ PI controller (%/F) | % | Write | |
| AV | 11347 | Economizer Cooling Reset Time (Seconds) | Reset time for VVDA systems Econ PI controller (in seconds) | Write | ||
| AV | 11348 | Economizer Cooling P-Gain - 2 (%/F) | Proportional gain for 2nd loop Econ PI controller (%/F), for CVZT/VVZT systems | % | Write | |
| AV | 11349 | Economizer Cooling Reset Time - 2 (Seconds) | Reset time for 2nd loop Econ PI controller (seconds), for CVZT/VVZT systems | Write | ||
| AV | 11350 | Auxiliary Heating P-Gain - 1 (%/F) | Space control proportional gain for 1st loop Heating PI controller (%/F) | % | Write | |
| AV | 11351 | Auxiliary Heating Reset Time - 1 (seconds) | Space control reset Time for 1st loop Auxiliary Heating PI Controller (in | Write | ||
| AV | 11352 | Auxiliary Heating P-Gain - 2 (%/F) | Space control proportional gain for 2nd loop Heating PI controller (%/F) | % | Write | |
| AV | 11353 | Auxiliary Heating Reset Time - 2 (seconds) | Space control reset Time for 2nd loop Auxiliary Heating PI Controller (in | Write | ||
| AV | 11354 | Discharge Air Heating Setpoint Low Limit | Discharge Air Heating Setpoint Low Limit (deg F) | °F | Command | |
| AV | 11355 | Discharge Air Heating Setpoint Low Limit - Active | Active value for Discharge Air Heating Setpoint Low Limit point being used | °F | Read | |
| AV | 11356 | Discharge Air Cooling Setpoint Status | Actual discharge air cooling setpoint value being used for control [System Type is Configured as VVDA] | °F | Read | |
| AV | 11357 | Discharge Air Heating Setpoint Status | Actual discharge air heating setpoint value being used for control | °F | Read | |
| AV | 11358 | Discharge Air Reheating Setpoint High Limit - Active | Active value for Discharge Air Reheating Setpoint High Limit point being used | °F | Read | |
| AV | 11359 | Discharge Air Reheating Setpoint Low Limit - Active | Active value for Discharge Air Reheating Setpoint Low Limit point being used | °F | Read | |
| AV | 11360 | Discharge Air Reheating Setpoint High Limit | Discharge Air Reheating Setpoint High Limit (deg F) | °F | Command | |
| AV | 11361 | Discharge Air Reheating Setpoint Low Limit | Discharge Air Reheating Setpoint Low Limit (deg F) | °F | Command | |
| AV | 11362 | Run Time - Gas Heat Manifold 1 Burner 1 (Hours) | Gas heat runtime | Read | ||
| AV | 11363 | Starts - Gas Heat Manifold 1 Burner 1 | Gas heat starts | Read | ||
| AV | 11364 | Run Time - Gas Heat Manifold 1 Burner 2 (Hours) | Gas heat runtime [Gas Heat is installed with a second gas valve on manifold 1.] | Read | ||
| AV | 11365 | Starts - Gas Heat Manifold 1 Burner 2 | Gas heat starts [Gas Heat is installed with a second gas valve on manifold 1.] | Read | ||
| AV | 11366 | Run Time - Gas Heat Manifold 2 Burner 1 (Hours) | Gas heat runtime | Read | ||
| AV | 11367 | Starts - Gas Heat Manifold 2 Burner 1 | Gas heat starts | Read | ||
| AV | 11368 | Auxiliary Heating P-Gain Modulating Gas Staging (%/F) | Proportional gain for 2nd loop-Staging control for Modulating Gas Heating [Modulating gas heat is configured] | % | Write | |
| AV | 11369 | Auxiliary Heating Reset Time Modulating Gas Staging (seconds) | Reset Time for 2nd loop-Staging control for Modulating Gas Heating [Modulating gas heat is configured] | Write | ||
| AV | 11370 | Outdoor Airflow Calibration Gain | Outdoor airflow Traq measurement Calibration Gain [Outside Air Configured as 0% to 100% w/ TRAQ] | Write | ||
| AV | 11371 | Outdoor Airflow Calibration Offset | Outdoor airflow Traq measurement calibration Offset [Outside Air Configured as 0% to 100% w/ TRAQ] | Write | ||
| AV | 11372 | Outdoor Airflow P-Gain (%/CFM) | Proportional gain for outdoor airflow Traq Minimum Position Control | % | Write | |
| AV | 11373 | Outdoor Airflow Reset Time (Seconds) | Reset time for Outdoor airflow Traq Minimum Position Control | Write | ||
| AV | 11374 | Local Atmospheric Pressure | Local atmospheric pressure [Outside Air Configured as 0% to 100% w/ TRAQ] | psi | Write | |
| AV | 11379 | Space Pressure Control P-Gain (%/IWC) | Proportional gain for building static space pressure control [StatiTrac Space Pressure Control configured.] | % | Write | |
| AV | 11380 | Space Pressure Control Reset Time (Seconds) | Reset time for building static space pressure control [StatiTrac Space Pressure Control configured.] | Write | ||
| AV | 11381 | Space Pressure Control Feed Forward Gain | Feed Forward gain for building static space pressure control [StatiTrac Space Pressure Control configured.] | % | Write | |
| AV | 11382 | Relief Air Damper Minimum Position Setpoint | Relief Air Damper Minimum Position Setpoint [StatiTrac Space Pressure Control configured.] | % | Write | |
| AV | 11383 | Condenser Fan Capacity | Status of the total unit condenser fan capacity | % | Read | |
| AV | 11388 | Control State | Control State Status | Read | ||
| BI | 10105 | FDD: Unit Economizing When It Should Not | Diagnostic: Unit Economizing When It Should Not [Outside Air is Configured as 0-100% Economizer] | Read | false = Inactive, true = Active | |
| BI | 10106 | FDD: Unit Not Economizing When It Should | Diagnostic: Unit Not Economizing When It Should [Outside Air is Configured as 0-100% Economizer] | Read | false = Inactive, true = Active | |
| BI | 10107 | FDD: Excessive Outdoor Air | Diagnostic: Excessive Air [Outside Air is Configured as 0-100% Economizer] | Read | false = Inactive, true = Active | |
| BI | 10108 | FDD: Outdoor Air Damper Not Modulating | Diagnostic: Damper NOT Modulating [Outside Air is Configured as 0-100% Economizer] | Read | false = Inactive, true = Active | |
| BI | 10121 | Relief Fan Output Status | Status of the Relief fan output on the controller [Space Pressure Control is Configured] | Read | false = Off, true = On | |
| BI | 10143 | VAV Box Command | Whether the associated VAV boxes should be AUTO or forced open | Read | false = Off, true = On | |
| BI | 10170 | Condensate Overflow Input | Status of the condensate overflow input [Condensate Overflow Switch is Configured as Installed] | Read | false = Open, true = Closed | |
| BI | 10172 | Occupancy Input | Status of the wired occupancy input | Read | false = Occupied, true = Unoccupied | |
| BI | 10210 | Equipment Shutdown Input Status | Status of the equipment shutdown function of the unit | Read | false = Equipment Run, true = Equipment Shutdown | |
| BI | 10211 | External Auto Stop Input Status | Status of the externally-wired auto/stop input [External Auto/Stop Configured as Installed] | Read | false = Stop, true = Auto | |
| BI | 10219 | Economizer Airside Status | Status of airside economizing [Outside Air is Configured as 0-100%] | Read | false = Inactive, true = Active | |
| BImin | 10226 | Supply Fan Status | Status of the supply fan output of the controller | Read | false = Off, true = On | |
| BI | 11100 | Compressor 1 Command Status | Compressor 1 Run Command Status [Efficiency is not Configured as High] | Read | false = Off, true = On | |
| BI | 11101 | Circuit 1 LPC Status | Circuit 1 LPC Input Status | Read | false = Open, true = Closed | |
| BI | 11102 | Compressor 1 Proving Status | Status of input for monitoring Compressor 1 proof of operation circuit | Read | false = Not Proved, true = Proved | |
| BI | 11103 | Compressor 2 Command Status | Compressor 2 Run Command Status [Multi-Compressor Systems] | Read | false = Off, true = On | |
| BI | 11105 | Compressor 2 Proving Status | Status of input for monitoring Compressor 2 proof of operation circuit [Multi-Compressor Systems] | Read | false = Not Proved, true = Proved | |
| BI | 11106 | Compressor 3 Command Status | Compressor 3 Run Command Status | Read | false = Off, true = On | |
| BI | 11108 | Compressor 3 Proving Status | Status of input for monitoring Compressor 3 proof of operation circuit | Read | false = Not Proved, true = Proved | |
| BI | 11113 | Demand Limit Input | Configurable, hardwired input to command Demand Limit [Demand Management Configured as Demand Limit] | Read | false = Not Limited, true = Limited | |
| BI | 11114 | Demand Shed Input | Configurable, hardwired input to command Demand Shed [Demand Management Configured as Demand Shed] | Read | false = Off, true = On | |
| BI | 11115 | Phase Monitor Status | Status of local Phase Monitor Input | Read | false = Tripped, true = Okay | |
| BI | 11116 | Condenser Fan 1 Command Status | Condenser Fan 1 Run Command Status | Read | false = Off, true = On | |
| BI | 11117 | Condenser Fan 2 Command Status | Condenser Fan 2 Run Command Status [Dual Condenser Fan Systems] | Read | false = Off, true = On | |
| BI | 11120 | Thermostat G Input | Thermostat Fan Request [Space Controller Configured as Conventional TStat] | Read | false = Open, true = Closed | |
| BI | 11121 | Thermostat W1/O Input | Thermostat Heat Stage 1 Request or Thermostat Heat/Cool Mode Request for HP | Read | false = Open, true = Closed | |
| BI | 11122 | Thermostat W2 Input | Thermostat Heat Stage 2 Request (or Emergency Heat) [Space Controller Configured as Conventional TStat] | Read | false = Open, true = Closed | |
| BI | 11123 | Thermostat X2 Input | Thermostat Emergency Heat Request [Space Controller Configured as Conventional TStat] | Read | false = Open, true = Closed | |
| BI | 11124 | Thermostat Y1 Input | Thermostat Compressor Stage 1 Request [Space Controller Configured as Conventional TStat] | Read | false = Open, true = Closed | |
| BI | 11125 | Thermostat Y2 Input | Thermostat Compressor Stage 2 Request [Space Controller Configured as Conventional TStat] | Read | false = Open, true = Closed | |
| BI | 11127 | FroStat Input | Status of Hardwired Frostat Input [FroStat Configured as Installed] | Read | false = Open, true = Closed | |
| BI | 11128 | Electric Heat Stage 1 Status | Status of Electric Heat Stage 1 command [One or more stages of Staged Electric Heat configured] | Read | false = Off, true = On | |
| BI | 11129 | Electric Heat Stage 2 Status | Status of Electric Heat Stage 2 command [Two or more stages of Staged Electric Heat configured] | Read | false = Off, true = On | |
| BI | 11130 | Clogged Filter Input | Status of Hardwired Clogged Filter Input [Clogged Filter Configured as Installed] | Read | false = Clean, true = Dirty Filter | |
| BI | 11131 | Condenser Fan 3 Command Status | Condenser Fan 3 Run Command Status | Read | false = Off, true = On | |
| BI | 11133 | Ventilation Override Exhaust Status | Hardwired input VOM Exhaust [Ventilation Override Configured as Installed] | Read | false = Open, true = Closed | |
| BI | 11134 | Ventilation Override Pressurize Status | Hardwired input VOM Pressurize [Ventilation Override Configured as Installed] | Read | false = Open, true = Closed | |
| BI | 11135 | Ventilation Override Purge Status | Hardwired input VOM Purge [Ventilation Override Configured as Installed] | Read | false = Open, true = Closed | |
| BI | 11143 | Reheat Humidistat Input | Hardwired input to support dehumidification requests on hot gas reheat units [Humidistat is Configured as Installed] | Read | false = Open, true = Closed | |
| BI | 11144 | Diagnostic: VFD Fault Supply Fan - 1 | Diagnostic: VFD Fault Supply Fan - 1 | Read | false = Inactive, true = Active | |
| BI | 11145 | Diagnostic: VFD Supply Fan Ground Fault - 1 | Diagnostic: VFD Supply Fan Ground Fault - 1 | Read | false = Inactive, true = Active | |
| BI | 11147 | Diagnostic: VFD Supply Fan Motor Current Overload - 1 | Diagnostic: VFD Supply Fan Motor Current Overload - 1 | Read | false = Inactive, true = Active | |
| BI | 11148 | Diagnostic: VFD Supply Fan Short Circuit - 1 | Diagnostic: VFD Supply Fan Short Circuit - 1 | Read | false = Inactive, true = Active | |
| BI | 11149 | Fan Mode - Air-Fi | Supply Fan Mode as set from a wireless sensor connected to the | Read | false = Cycling, true = Continuous | |
| BI | 11150 | Occupancy Input - Air-Fi | Local Occupancy Input as detected by a wireless sensor connected to the | Read | false = Occupied, true = Unoccupied | |
| BI | 11151 | Fan Mode Input | Supply Fan Mode as set from a wired sensor connected to the | Read | false = Cycling, true = Continuous | |
| BI | 11154 | Gas Heat Stage 1 Status | Status of gas heat Stage 1 | Read | false = Off, true = On | |
| BI | 11155 | Gas Heat Stage 2 Status | Status of gas heat Stage 2 | Read | false = Off, true = On | |
| BI | 11187 | Reheat Pumpout Solenoid Status | Reheat Pumpout Solenoid IMC Command Status [Hot Gas Reheat is Configured as Installed] | Read | false = Off, true = On | |
| BI | 11188 | Reheat Valve 2 Fault Status | Reheat Valve 2 (Cooling) Fault Status [Hot Gas Reheat is Configured as Installed] | Read | false = Inactive, true = Active | |
| BI | 11189 | Reheat Valve 1 Fault Status | Reheat Valve 1 Fault Status [Hot Gas Reheat is Configured as Installed] | Read | false = Inactive, true = Active | |
| BI | 11190 | Reheat Valve 1 Calibration Status | Reheat Valve 1 Calibration Status from Stepper Motor Module [Hot Gas Reheat is Configured as Installed] | Read | false = Inactive, true = Active | |
| BI | 11191 | Reheat Valve 2 Calibration Status | Reheat Valve 2 (Cooling) Calibration Status from Stepper Motor Module | Read | false = Inactive, true = Active | |
| BI | 11192 | VAV Changeover Input | VAV Changeover Request [System Type is Configured as VVDA] | Read | false = Open, true = Closed | |
| BI | 11194 | Diagnostic: VFD Supply Fan Broken Belt - 1 | Diagnostic: VFD Supply Fan Broken Belt - 1 | Read | false = Inactive, true = Active | |
| BI | 11195 | Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 1 | Modulating gas heat ignition controller [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11196 | Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 2 | Modulating gas heat ignition controller [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11197 | Diagnostic: Modulating Gas Invalid ID Plug Manifold 1 | Gas heat ignition controller detected an invalid or failed ID Plug [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11198 | Diagnostic: Modulating Gas Heat Configuration Invalid | Unit controller configuration does not match gas heat ignition controller ID Plug | Read | false = Inactive, true = Active | |
| BI | 11199 | Diagnostic: Gas Heat Weak Flame Manif 1 Burner 1 | Weak flame or aged flame rod detected on burner 1 [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11200 | Diagnostic: Gas Heat Weak Flame Manif 1 Burner 2 | Weak flame or aged flame rod detected on burner 2 [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11201 | Diagnostic: Gas Heat Insufficient Combustion Air | Gas heat is being derated/reduced due to insufficient combustion air [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11202 | Diagnostic: Modulating Gas Primary Limit Open Manifold 1 | Gas heat failure, primary limit detected open [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11203 | Diagnostic: Modulating Gas Heat Open Fuse Manifold 1 | Gas heat failure, fuse detected open [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11204 | Diagnostic: Gas Heat Failed Ignition Manifold 1 | Gas heat is locked out for one hour due to failed ignition | Read | false = Inactive, true = Active | |
| BI | 11205 | Diagnostic: Modulating Gas Valve Failure Manifold 1 | Modulating gas valve did not reach park or full On position [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11206 | Diagnostic: Modulating Gas Control Board Failure Manifold 1 | Ignition control board failure during startup self test [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11207 | Diagnostic: Gas Heat Unexpected Flame Manifold 1 | Staged gas heat ignition controller [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11208 | Diagnostic: Staged Gas Heat Invalid ID Plug Manifold 1 | Gas heat ignition controller detected an invalid or failed ID Plug [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11209 | Diagnostic: Staged Gas Heat Configuration Invalid Manifold 1 | Unit controller configuration does not match gas heat ignition controller ID Plug | Read | false = Inactive, true = Active | |
| BI | 11210 | Diagnostic: Staged Gas Heat Primary Limit Open Manifold 1 | Gas heat failure, primary limit detected open [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11211 | Diagnostic: Staged Gas Heat Open Fuse Manifold 1 | Gas heat failure, fuse detected open [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11212 | Diagnostic: Heat Failed Ignition Manifold 1 | Gas heat is locked out for one hour due to failed ignition | Read | false = Disabled, true = Enabled | |
| BI | 11213 | Diagnostic: Staged Gas Heat Valve Failure Manifold 1 | Gas valve state is low when it should be high [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11214 | Diagnostic: Gas Heat Inducer High Pressure Manifold 1 | Gas heat inducer air pressure switch high is open when it is | Read | false = Inactive, true = Active | |
| BI | 11215 | Diagnostic: Gas Heat Valve Short Manifold 1 | Gas heat valve shorted to 24V, ignition control failure or faulty wiring | Read | false = Inactive, true = Active | |
| BI | 11216 | Diagnostic: Gas Heat Flame Loss Manifold 1 | Gas heat locked out due to flame loss occurring three times [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11217 | Diagnostic: Staged Gas Heat Control Board Failure Manifold 1 | Ignition control board failure during startup self test [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11218 | Diagnostic: Gas Heat Start Failure Manifold 1 | Ignition controller checks at startup failed or flame circuitry idle state is | Read | false = Inactive, true = Active | |
| BI | 11219 | Diagnostic: Gas Heat Unexpected Flame Manifold 2 | Staged gas heat ignition controller | Read | false = Inactive, true = Active | |
| BI | 11220 | Diagnostic: Staged Gas Heat Invalid ID Plug Manifold 2 | Gas heat ignition controller detected an invalid or failed ID Plug | Read | false = Inactive, true = Active | |
| BI | 11221 | Diagnostic: Staged Gas Heat Configuration Invalid Manifold 2 | Unit controller configuration does not match gas heat ignition controller ID Plug | Read | false = Inactive, true = Active | |
| BI | 11222 | Diagnostic: Staged Gas Heat Primary Limit Open Manifold 2 | Gas heat failure, primary limit detected open | Read | false = Inactive, true = Active | |
| BI | 11223 | Diagnostic: Staged Gas Heat Open Fuse Manifold 2 | Gas heat failure, fuse detected open | Read | false = Inactive, true = Active | |
| BI | 11224 | Diagnostic: Heat Failed Ignition Manifold 2 | Gas heat is locked out for one hour due to failed ignition | Read | false = Inactive, true = Active | |
| BI | 11225 | Diagnostic: Staged Gas Heat Valve Failure Manifold 2 | Gas valve state is low when it should be high | Read | false = Inactive, true = Active | |
| BI | 11226 | Diagnostic: Gas Heat Inducer High Pressure Manifold 2 | Gas heat inducer air pressure switch high is open when it is | Read | false = Inactive, true = Active | |
| BI | 11227 | Diagnostic: Gas Heat Valve Short Manifold 2 | Gas heat valve shorted to 24V, ignition control failure or faulty wiring | Read | false = Inactive, true = Active | |
| BI | 11228 | Diagnostic: Gas Heat Flame Loss Manifold 2 | Gas heat locked out due to flame loss occurring three times | Read | false = Inactive, true = Active | |
| BI | 11229 | Diagnostic: Staged Gas Heat Control Board Failure Manifold 2 | Ignition control board failure during startup self test | Read | false = Inactive, true = Active | |
| BI | 11230 | Diagnostic: Gas Heat Start Failure Manifold 2 | Ignition controller checks at startup failed or flame circuitry idle state is | Read | false = Inactive, true = Active | |
| BI | 11231 | Diagnostic: Gas Heat Lockout Manifold 1 | Gas heat ignition controller locked out (modulating or staged gas) | Read | false = Inactive, true = Active | |
| BI | 11232 | Diagnostic: Gas Heat Lockout Manifold 2 | Staged gas heat ignition controller is operation locked out on manifold 2 | Read | false = Inactive, true = Active | |
| BI | 11233 | Diagnostic: Gas Heat Flame Rod Aged Manifold 1 | Weak flame or aged flame rod detected on manifold 1 [Staged Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11234 | Diagnostic: Gas Heat Flame Rod Aged Manifold 2 | Weak flame or aged flame rod detected on manifold 1 [800 MBH Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11235 | Diagnostic: Gas Heat Failed Ignition Manifold 1 Burner 2 | Modulating gas heat ignition controller burner 2 operation failed ignition [Modulating gas heat configured] | Read | false = Inactive, true = Active | |
| BI | 11236 | Reheat LPC Status | Reheat LPC Status [Modulating Hot Gas Reheat on Voyager 3] | Read | false = Open, true = Closed | |
| BI | 11241 | Diagnostic: Gas Heat Air Pressure Sensor Reading Low | Modulating gas heat ignition controller, air pressure sensor is reading low [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11242 | Diagnostic: Gas Heat Air Pressure Sensor Reading High | Modulating gas heat ignition controller, air pressure sensor is reading high [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11243 | Diagnostic: Gas Heat Loss of Inducer Motor Control | Modulating gas heat ignition controller, loss of inducer motor control [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11244 | Diagnostic: Gas Heat Air Sensor Null Pressure Check | Modulating gas heat ignition controller [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11245 | Diagnostic: Gas Heat Limited Low Fire | Modulating gas heat ignition controller [Modulating Gas Heat is Configured] | Read | false = Inactive, true = Active | |
| BI | 11247 | Diagnostic: Refrigerant Concentration Sensor A | Diagnostic point that is be active when Refrigerant Leak Sensor is in [Refrigerant Type is R454B] | Read | false = Inactive, true = Active | |
| BI | 11248 | Refrigerant Leak Detection System Input | Active state will be maintained for the duration of the alarm state [Refrigerant Type is R454B] | Read | false = Inactive, true = Active | |
| BI | 11249 | Diagnostic: Refrigerant Leak Sensor Failure Sensor A | Diagnostic point that shall be active when the refrigerant sensor reports a [Refrigerant Type is R454B] | Read | false = Inactive, true = Active | |
| BV | 10103 | Heat Lockout Command | Normally used by the BMS to command the unit to prevent heating [Primary Heating Source Installed] | Command | false = Normal, true = Locked out | |
| BV | 10104 | Supply Fan Configuration Command | Used to command the supply fan configuration as either cycling or continuous | Write | false = Cycling, true = Continuous | |
| BV | 10106 | Dehumidification Enable Command | Normally used by the BMS to disable unit dehumidification [Hot Gas Reheat is Configured as Installed] | Command | false = Disabled, true = Auto | |
| BV | 10109 | Filter Timer Reset | Commands the unit to reset the accumulated filter run hours | Write | false = Accumulating, true = Reset | |
| BV | 10110 | Reset Diagnostic | Used to initiate a request to reset any controller diagnostics | Write | false = Normal, true = Reset | |
| BV | 10111 | Daytime Warmup Enable Command | Used to enable daytime warmup [System Type is Configured as VVDA and Primary Heat is Configured.] | Command | false = Disabled, true = Enabled | |
| BV | 10112 | Morning Warmup Enable Command | Normally used by the BMS to enable morning warmup | Command | false = Disabled, true = Enabled | |
| BV | 10113 | Occupancy Input BAS | Normally used by the BMS to provide the requested occupancy state to | Write | false = Occupied, true = Unoccupied | |
| BV | 10115 | Cooling Lockout BAS | Used to prevent all mechanical cooling | Command | false = Normal, true = Locked out | |
| BV | 10119 | Supply Air Tempering Enable | Used to enable the supply (discharge) air tempering feature of the unit | Command | false = Disabled, true = Enabled | |
| BVmin | 11100 | Alarm Indicator Status | State of the controller alarm output | Read | false = Off, true = On | |
| BV | 11111 | Compressor Lockout Status | One or more compressors are locked out with no diagnostic | Read | false = Normal, true = Locked out | |
| BVmin | 11113 | Unit Stop Command | Point used to force the unit into an immediate stop condition | Write | false = Auto, true = Stop | |
| BV | 11114 | Supply Fan Speed Command Enable | Enables the unit to use Supply Fan Speed Command to override the | Command | false = Disabled, true = Enabled | |
| BV | 11115 | Cooling Capacity Setpoint Enable BAS | Commands the unit to use Cooling Capacity Setpoint BAS value to override | Command | false = Disabled, true = Enabled | |
| BV | 11116 | Heating Capacity Setpoint Enable BAS | Commands the unit to use Heating Capacity Setpoint BAS value to override [Primary Heating Source Installed] | Command | false = Disabled, true = Enabled | |
| BV | 11119 | Supply Fan Compensation | Commands the unit to utilize "Economizer Minimum Position Setpoint BAS" instead of | Command | false = Disabled, true = Enabled | |
| BV | 11121 | Compressor 1 Run Time Reset | Compressor 1 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11122 | Compressor 1 Starts Reset | Compressor 1 Starts Reset | Write | false = Accumulating, true = Reset | |
| BV | 11123 | Compressor 2 Run Time Reset | Compressor 2 Runtime Reset [Multi-Compressor Systems] | Write | false = Accumulating, true = Reset | |
| BV | 11124 | Compressor 2 Starts Reset | Compressor 2 Starts Reset [Multi-Compressor Systems] | Write | false = Accumulating, true = Reset | |
| BV | 11125 | Compressor 3 Run Time Reset | Compressor 3 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11126 | Compressor 3 Starts Reset | Compressor 3 Starts Reset | Write | false = Accumulating, true = Reset | |
| BV | 11127 | Condenser Fan 1 Run Time Reset | Condenser fan 1 runtime reset | Write | false = Accumulating, true = Reset | |
| BV | 11128 | Condenser Fan 1 Starts Reset | Condenser fan 1 starts reset | Write | false = Accumulating, true = Reset | |
| BV | 11129 | Condenser Fan 2 Run Time Reset | Condenser Fan 2 Runtime Reset [Dual Condenser Fan Systems] | Write | false = Accumulating, true = Reset | |
| BV | 11130 | Condenser Fan 2 Starts Reset | Condenser Fan 2 Starts Reset [Dual Condenser Fan Systems] | Write | false = Accumulating, true = Reset | |
| BV | 11131 | Condenser Fan 3 Run Time Reset | Condenser Fan 3 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11132 | Condenser Fan 3 Starts Reset | Condenser Fan 3 Starts Reset | Write | false = Accumulating, true = Reset | |
| BV | 11133 | Relief Fan Run Time Reset | Relief Fan Runtime Reset [Space Pressure Control is Configured] | Write | false = Accumulating, true = Reset | |
| BV | 11134 | Relief Fan Starts Reset | Relief Fan Starts Reset [Space Pressure Control is Configured] | Write | false = Accumulating, true = Reset | |
| BV | 11135 | Electric Heat Stage 1 Run Time Reset | Electric Heat Stage 1 Runtime Reset [One or more stages of Staged Electric Heat configured] | Write | false = Accumulating, true = Reset | |
| BV | 11136 | Electric Heat Stage 1 Starts Reset | Electric Heat Stage 1 Starts Reset [One or more stages of Staged Electric Heat configured] | Write | false = Accumulating, true = Reset | |
| BV | 11137 | Electric Heat Stage 2 Run Time Reset | Electric Heat Stage 2 Runtime Reset [Two or more stages of Staged Electric Heat configured] | Write | false = Accumulating, true = Reset | |
| BV | 11138 | Electric Heat Stage 2 Starts Reset | Electric Heat Stage 2 Starts Reset [Two or more stages of Staged Electric Heat configured] | Write | false = Accumulating, true = Reset | |
| BV | 11139 | Supply Fan Run Time Reset | Supply Fan Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11140 | Supply Fan Starts Reset | Supply Fan Starts Reset | Write | false = Accumulating, true = Reset | |
| BV | 11141 | Diagnostic: Supply Fan Failure | Diagnostic: Fan Failure [Indoor Fan Type Configured as Multi Speed or Variable Speed] | Read | false = Inactive, true = Active | |
| BV | 11143 | Diagnostic: Duct Static Pressure Limit Trip | Diagnostic: Duct Static Pressure Limit Trip [System Type is Configured as VVDA] | Read | false = Inactive, true = Active | |
| BV | 11144 | Diagnostic: Filter Change Required | Diagnostic: Dirty Filter [Clogged Filter Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11145 | Diagnostic: Condensate Overflow Lockout | Condensate Drain Pan Overflow Lockout [Condensate Overflow Switch is Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11146 | Diagnostic: FroStat Trip | Diagnostic: FroStat Trip [FroStat Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11155 | Diagnostic: Comp 1 Proving Trip | Diagnostic: Comp 1 Proving Trip | Read | false = Inactive, true = Active | |
| BV | 11156 | Diagnostic: Comp 2 Proving Trip | Diagnostic: Comp 2 Proving Trip [Multi-Compressor Systems] | Read | false = Inactive, true = Active | |
| BV | 11157 | Diagnostic: Comp 3 Proving Trip | Diagnostic: Comp 3 Proving Trip | Read | false = Inactive, true = Active | |
| BV | 11158 | Diagnostic: Circuit 1 LPC Trip | Diagnostic: Circuit 1 LPC Trip | Read | false = Inactive, true = Active | |
| BV | 11161 | Diagnostic: Compressor 1 Contactor Failure | Diagnostic: Compressor 1 Contactor Fail Lockout | Read | false = Inactive, true = Active | |
| BV | 11162 | Diagnostic: Circuit 1 LPC Lockout | Diagnostic: Circuit 1 LPC Lockout | Read | false = Inactive, true = Active | |
| BV | 11166 | VVZT DAT Control Mode | Determines Auto or Manual mode for discharge air temperature control for VVZT | Command | false = Auto, true = Manual | |
| BV | 11172 | Diagnostic: Compressor 1 Proving Lockout | Diagnostic: Compressor 1 Proving Lockout | Read | false = Inactive, true = Active | |
| BV | 11173 | Occupancy Input Active | Occupancy Input being actively used for status determination | Read | false = Occupied, true = Unoccupied | |
| BV | 11174 | Diagnostic: Compressor 2 Contactor Failure | Diagnostic: Compressor 2 Contactor Fail Lockout [Multi-Compressor Systems] | Read | false = Inactive, true = Active | |
| BV | 11175 | Diagnostic: Circuit 2 LPC Lockout | Diagnostic: Circuit 2 LPC Lockout [Multi-Compressor Systems] | Read | false = Inactive, true = Active | |
| BV | 11176 | Diagnostic: Compressor 2 Proving Lockout | Diagnostic: Compressor 2 Proving Lockout [Multi-Compressor Systems] | Read | false = Inactive, true = Active | |
| BV | 11190 | Diagnostic: Maintenance Required | Diagnostic: Maintenance Required | Read | false = Inactive, true = Active | |
| BV | 11192 | Diagnostic: Unit Communications Failure | Diagnostic: Unit Communications Failure | Read | false = Inactive, true = Active | |
| BV | 11199 | Supply Fan Configuration Status | Supply fan configuration | Read | false = Cycling, true = Continuous | |
| BV | 11200 | Timed Override Timer Is Active | Whether or not the timed override timer is active | Read | false = Inactive, true = Active | |
| BV | 11201 | Supply Fan Speed Command Enable - Active | Active value for Supply Fan Speed Command Enable point being used for | Read | false = Disabled, true = Enabled | |
| BV | 11202 | Cooling Capacity Setpoint Enable BAS - Active | Active value for Cooling Capacity Setpoint Enable BAS point being used for | Read | false = Disabled, true = Enabled | |
| BV | 11203 | Cooling Lockout BAS - Active | Active value for Cooling Lockout BAS point being used for control | Read | false = Normal, true = Locked out | |
| BV | 11204 | Heating Capacity Setpoint Enable BAS - Active | Active value for Heating Capacity Setpoint Enable point being used for control [Primary Heating Source Installed] | Read | false = Disabled, true = Enabled | |
| BV | 11205 | Daytime Warmup Enable Command - Active | Active value for Daytime Warmup Enable Command point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11208 | Supply Fan Compensation - Active | Active value for Supply Fan Compensation point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11209 | Dehumidification Enable Command - Active | Active value for Dehumidification Enable Command point being used for control | Read | false = Disabled, true = Auto | |
| BV | 11211 | VVZT DAT Control Mode - Active | Active value for VVZT DAT Control Mode point being used for control | Read | false = Auto, true = Manual | |
| BV | 11216 | Heat Lockout Command - Active | Active value for Heat Lockout Command point being used for control [Primary Heating Source Installed] | Read | false = Normal, true = Locked out | |
| BV | 11217 | Morning Warmup Enable Command - Active | Active value for Morning Warmup Enable Command point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11221 | Supply Air Tempering Status | Status of the Supply Air Tempering function [Supply Air Tempering Configured as Enabled] | Read | false = Disabled, true = Enabled | |
| BV | 11222 | Supply Air Tempering Enable - Active | Active value for Supply Air Tempering Enable point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11224 | Occupancy Input Arbitrator | Status of the arbitrated occupancy inputs | Write | false = Occupied, true = Unoccupied | |
| BV | 11226 | Demand Limit Request BAS | Used to demand limit the unit remotely [Demand Management Configured as Demand Limit] | Write | false = Not Limited, true = Limited | |
| BV | 11227 | Demand Limit Request - Active | Active Demand Limit Request value used by the equipment [Demand Management Configured as Demand Limit] | Read | false = Not Limited, true = Limited | |
| BV | 11228 | Diagnostic: Compressor 3 Contactor Failure | Diagnostic: Compressor 3 Contactor Fail Lockout | Read | false = Inactive, true = Active | |
| BV | 11229 | Diagnostic: Compressor 3 Proving Lockout | Diagnostic: Compressor 3 Proving Lockout | Read | false = Inactive, true = Active | |
| BV | 11231 | Daytime Warmup Active | Whether daytime warmup is currently active | Read | false = Inactive, true = Active | |
| BV | 11232 | Morning Warmup Active | Whether morning warmup is active | Read | false = Inactive, true = Active | |
| BV | 11235 | Occupied Standby Supply Fan Configuration Command | Supply fan mode in Occupied Standby [zone sensor configured] | Command | false = Cycling, true = Continuous | |
| BV | 11236 | Occupied Standby Supply Fan Configuration Command - Active | Occupied Standby Fan Mode setting | Read | false = Cycling, true = Continuous | |
| BV | 11248 | Diagnostic: High Condensate Level Detected | Diagnostic: High Condensate Level Detected [Condensate Overflow Switch is Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11249 | Diagnostic: Morning Warmup Mode Exceeded 120 Minutes | Diagnostic: Morning Warmup Mode Exceeded 120 Minutes | Read | false = Inactive, true = Active | |
| BV | 11250 | Diagnostic: Pre Cool Mode Exceeded 120 Minutes | Diagnostic: Precool Mode Exceeded 120 Minutes | Read | false = Inactive, true = Active | |
| BV | 11251 | Diagnostic: Night Purge Mode Exceeded 120 Minutes | Diagnostic: Night Purge Mode Exceeded 120 Minutes | Read | false = Inactive, true = Active | |
| BV | 11252 | Diagnostic: Circuit 3 LPC Lockout | Diagnostic: Circuit 3 LPC Lockout | Read | false = Inactive, true = Active | |
| BV | 11255 | Dehumidification Status | Active state showing whether dehumidification is active or inactive [Hot Gas Reheat is Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11256 | Pre Cool Enable Command | Normally used by the BMS to enable pre Cool | Command | false = Disabled, true = Enabled | |
| BV | 11257 | Pre Cool Enable Command - Active | Active value for Pre Cool Enable Command point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11258 | Pre Cool Active | Whether Pre Cool is active | Read | false = Inactive, true = Active | |
| BV | 11259 | Occupied Dehumidification Enable BAS | Setting for unit to use "Enable" or "Disable" for Occupied Dehumidification Control | Command | false = Disabled, true = Enabled | |
| BV | 11260 | Occupied Dehumidification Enable BAS - Active | Active value for Dehumidification Enable BAS point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11261 | Unoccupied Dehumidification Enable BAS | Setting for unit to use "Enable" or "Disable" for Occupied Dehumidification Control | Command | false = Disabled, true = Enabled | |
| BV | 11262 | Unoccupied Dehumidification Enable BAS - Active | Active value for Dehumidification Enable BAS point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11263 | Diagnostic: Duct Static Pressure Limit Lockout | Diagnostic: Duct Static Pressure Limit Lockout [System Type is configured as VVDA] | Read | false = Inactive, true = Active | |
| BV | 11265 | Diagnostic: Duct Static Pressure Local Lockout | Diagnostic: Duct Static Pressure Local Lockout [System Type is configured as VVDA] | Read | false = Inactive, true = Active | |
| BV | 11266 | Gas Heat Manifold 1 Burner 1 Run Time Reset | Gas heat runtime reset | Write | false = Accumulating, true = Reset | |
| BV | 11267 | Gas Heat Manifold 1 Burner 1 Starts Reset | Gas heat starts counter reset | Write | false = Accumulating, true = Reset | |
| BV | 11268 | Gas Heat Manifold 1 Burner 2 Run Time Reset | Gas heat runtime reset [Gas Heat is installed with a second gas valve on manifold 1.] | Write | false = Accumulating, true = Reset | |
| BV | 11269 | Gas Heat Manifold 1 Burner 2 Starts Reset | Gas heat starts reset counter | Write | false = Accumulating, true = Reset | |
| BV | 11270 | Gas Heat Manifold 2 Burner 1 Run Time Reset | Gas heat runtime reset | Write | false = Accumulating, true = Reset | |
| BV | 11271 | Gas Heat Manifold 2 Burner 1 Starts Reset | Gas heat starts counter reset | Write | false = Accumulating, true = Reset | |
| BV | 11276 | Diagnostic: Supply Fan Bypass Enable | Diagnostic: Supply Fan VFD Bypass Enable [Unit has Supply Fan VFD Bypass feature installed.] | Read | false = Inactive, true = Active | |
| BV | 11277 | Diagnostic: Reheat Valve 1 Fault | Diagnostic: Reheat Valve 1 Fault [Hot Gas Reheat is Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11278 | Diagnostic: Reheat Valve 2 Fault | Diagnostic: Reheat Valve 2 Fault [Hot Gas Reheat is Configured as Installed] | Read | false = Inactive, true = Active | |
| BV | 11279 | Diagnostic: Outdoor Airflow Pressure Calibration Limit | Diagnostic: Outdoor Airflow Pressure Calibration Limit (Traq) [Economizer with Fresh Air Measurement and Control (Traq) Installed.] | Read | false = Inactive, true = Active | |
| BV | 11280 | Diagnostic: Space Pressure Calibration Limit | Diagnostic: Space Pressure Calibration Limit (Statitrac) [Space Pressure Control (Statitrac) is configured.] | Read | false = Inactive, true = Active | |
| BV | 11281 | Diagnostic: Reheat LPC Trip | Diagnostic: Reheat LPC Trip [Modulating Hot Gas Reheat on Voyager 3] | Read | false = Inactive, true = Active | |
| BV | 11282 | Diagnostic: Reheat LPC Lockout | Diagnostic: Reheat LPC Lockout [Modulating Hot Gas Reheat on Voyager 3] | Read | false = Inactive, true = Active | |
| BV | 11283 | Refrigerant Mitigation Active | Active when the Symbio 700 controller is in a mitigation state for [Refrigerant Type is R454B] | Read | false = Inactive, true = Active | |
| MImin | 10101 | Heat Cool Mode Status | Current heat cool mode of the controller | Read | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MI | 10144 | Economizer System Status | Operating state of the airside economizer system | Read | 1 = Disabled, 2 = Enabled, 3 = Not Present | |
| MI | 11100 | System Mode Switch Air-Fi | Status of the wireless system mode switch connected to the controller | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | |
| MI | 11101 | Timed Override Air-Fi | Status of the Timed Override wireless input | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MI | 11102 | System Mode Switch Input | Status of the wired system mode switch connected to the controller | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | |
| MI | 11103 | Timed Override Input | Status of the Timed Override wired input | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MV | 10101 | Cooling Reset Type Status | Type of cooling reset used by the controller [System Type is Configured as VVDA] | Read | 1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air | |
| MV | 10102 | Emergency Override BAS | Used to command the unit into an emergency mode of operation | Command | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 10103 | Economizer Airside Enable BAS | Normally provided by the BAS to enable airside economizing | Command | 1 = Disabled, 2 = Enabled, 3 = Auto | |
| MV | 10104 | Heat Cool Mode Request | Used to command the unit into a heat/cool mode | Command | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MVmin | 10106 | Occupancy Request | Normally used by the BMS to command the unit into an occupancy | Command | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 10110 | Timed Override Request | Used to request a temporary timed override during unoccupied | Write | 1 = Idle, 2 = On, 3 = Cancel | |
| MV | 11100 | Arbitration Method Request | Setting for unit to use "Enable External/BAS Control" or "Standalone Control" data | Write | 1 = Enable External/BAS Control, 2 = Standalone Control | |
| MV | 11101 | Customer Options Module Communication Status | Communication Status of the Customer Options Module [Customer Options Module Installed and In-Use] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11102 | Economizer Type | General description of the type of economizer system | Read | 1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/ Sensor, 9 = Waterside Economizer and TRAQ Damper/Sensor, 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor | |
| MV | 11103 | Fresh Air Options Module Communication Status | Communication Status of the Fresh Air Options Module [Fresh Air Options Module Installed and In-Use] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11105 | Indoor Options Module Communication Status | Communication Status of the Indoor Options Module [Indoor Options Module Installed and In-Use] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11106 | On-Board I/O Communication Status | Communication Status of the On-Board Inputs and Outputs | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11110 | Service Test State Request | Requests a service test step | Write | 1 = Inactive; the remaining test steps depend on unit configuration | |
| MV | 11111 | Cooling Reset Type | Selectable discharge air cooling reset type based on outdoor, space [System Type is Configured as VVDA] | Write | 1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air | |
| MV | 11112 | System Mode Switch Local | Status of the system mode switch connected to the controller as arbitrated | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | |
| MV | 11113 | Timed Override Status | Status of the timed override request | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MV | 11114 | Trane Unit Type | Equipment type according to the manufacturer's classification | Read | 1 = 1 Heat/1 Cool, 2 = Heat Pump, 3 = Blower Coil, 4 = Unit Ventilator, 5 = Fan Coil, 6 = Rooftop, 7 = Air Handler, 8 = Vertical Self Contained, 9 = Unitary, 10 = VAV Box | |
| MV | 11115 | Unit Stop Source | Source of the stop command that turned off the equipment | Read | 1 = None, 2 = Emergency Stop, 3 = Drain Pan Overflow, 4 = Local HI, 5 = Remote HI, 6 = External Auto Stop, 7 = Phase Monitor, 8 = Emergency Override, 9 = Supply Fan Fault, 10 = Equipment Shutdown Input, 11 = Smoke Detector, 12 = Equipment Limit, 13 = Sensor Failure | |
| MV | 11116 | Emergency Override BAS - Active | Active value for Emergency Override BAS point being used for control | Read | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 11118 | Economizer Decision Method | Used to indicate the method of enabling airside economizing [Outside Air is configured as 0-100%] | Read | 1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy, 5 = Differential Dry Bulb | |
| MV | 11119 | Refrigerant Type | Type of refrigerant used in the equipment | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E), 17 = R-454B | |
| MV | 11120 | Economizer Airside Enable BAS - Active | Active value for Economizer Airside Enable BAS point being used for control | Read | 1 = Disabled, 2 = Enabled, 3 = Auto | |
| MV | 11121 | Heat Cool Mode Request - Active | Active value for Heat Cool Mode Request point being used for control | Read | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MVmin | 11123 | Occupancy Status | Active occupancy mode of the controller | Read | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 11124 | Supply Fan VFD Communication Status | Modbus supply fan VFD comm status [multi/variable speed fan] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11125 | Occupancy Request Active | Active Occupancy mode being requested of the unit | Read | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 11128 | Gas Heat Ignition Module 1 Communication Status | Communication Status of the Modbus Gas Heat Ignition Module 1 | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11129 | Gas Heat Ignition Module 2 Communication Status | Communication Status of the Modbus Gas Heat Ignition Module 2 [800 MBH Gas Heat is Configured] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11130 | Emergency Override Status | Active Emergency Override mode in control of the equipment | Read | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 11133 | Stepper Motor Communication Status | Communication Status of the Stepper Motor Inputs and Outputs [Stepper Motor Module Installed and In-Use] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11136 | Heating Reset Type | Selectable discharge air heating reset type of outdoor, space | Write | 1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air | |
| MV | 11137 | Heating Reset Type Status | Discharge air heating reset type status [System Type is Configured as VVDA] | Read | 1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air | |
| MV | 11139 | Refrigerant Leak Sensor Communication Status Sensor A | Communication status of the Modbus communicating refrigerant detection system [Refrigerant Type is R-454B] | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured |
No points match these filters.
Object ID lookup: Trane Symbio 700 Voyager 3 point IDs by name
AI10101Cooling Capacity StatusAI10102Heating Capacity Primary StatusAI10104Outdoor Air Relative Humidity LocalAI10110Return Air Humidity LocalAI10111Outdoor Air Damper PositionAI10112Relief Damper PositionAI10116Space Humidity ActiveAI10117Outdoor Air Dew PointAI10118Outdoor Air Temperature ActiveAI10120Outdoor Air Humidity ActiveAI10124Discharge Air Temperature LocalAI10126Return Air Temperature InputAI10155Duct Static Pressure LocalAI10156Outdoor Air Temperature LocalAI10185Outdoor Air Flow ActiveAI10187Space Static Pressure ActiveAI10218Space Temperature InputAI10226Space Dew PointAI11103Space CO2 Concentration InputAI11104Space Humidity InputAI11106Supply Fan Speed Command StatusAI11109Modulating Heat Command StatusAI11111Outdoor Air Damper CommandAI11112Outdoor Airflow PressureAI11132On-Board I/O Firmware Major VersionAI11133On-Board I/O Firmware Minor VersionAI11134Indoor Options Module Firmware Major VersionAI11135Indoor Options Module Firmware Minor VersionAI11136Fresh Air Options Module Firmware Major VersionAI11137Fresh Air Options Module Firmware Minor VersionAI11140Customer Options Module Firmware Major VersionAI11141Customer Options Module Firmware Minor VersionAI11142IGN Module 1 Firmware Major VersionAI11143IGN Module 1 Firmware Minor VersionAI11144IGN Module 2 Firmware Major VersionAI11145IGN Module 2 Firmware Minor VersionAI11148Remote Minimum PositionAI11149Return Air Temperature ActiveAI11150Sensor Battery Status Air-FiAI11151Space CO2 Concentration Air-FiAI11152Space Humidity Air-FiAI11154Space Temperature Air-FiAI11155Space Temperature Cooling Setpoint Air-FiAI11156Space Temperature Heating Setpoint Air-FiAI11157Space Temperature Setpoint Air-FiAI11158Space Static Pressure InputAI11159Space Temperature Cooling Setpoint InputAI11160Space Temperature Heating Setpoint InputAI11161Space Temperature Setpoint InputAI11164Reheat Valve 1 Step StatusAI11165Reheat Valve 2 Step StatusAI11166Evaporator Entering Refrigerant TemperatureAI11167Stepper Motor Module Firmware Major VersionAI11168Stepper Motor Module Firmware Minor VersionAI11171Refrigerant LFL Concentration Sensor AAI11172Refrigerant LFL Concentration Alarm Threshold Sensor AAV10103Outdoor Air Temperature ArbitratorAV10104Outdoor Air Humidity ArbitratorAV10106Space Temperature ArbitratorAV10107Space Static Pressure ArbitratorAV10108Space CO2 Concentration ArbitratorAV10109Space Humidity ArbitratorAV10113Outdoor Air Temperature BASAV10114Space Temperature BASAV10116Outdoor Air Humidity BASAV10117Space Static Pressure BASAV10118Space CO2 Concentration BASAV10119Space Humidity BASAV10121Discharge Air Cooling Setpoint BASAV10122Discharge Air Heating Setpoint BASAV10123Unoccupied Cooling SetpointAV10124Unoccupied Heating SetpointAV10125Outdoor Air Minimum Flow Setpoint BASAV10127Space Temperature Setpoint BASAV10128Space Static Pressure Setpoint BASAV10130Occupied OffsetAV10134Discharge Air Reheat Setpoint BASAV10138Filter Runtime Hours SetpointAV10139Cooling Capacity EnableAV10140Heat Primary Enable BASAV10141Morning Warmup Setpoint BASAV10142Occupied Standby OffsetAV10143Duct Static Pressure Setpoint BASAV10144Economizer Minimum Position Setpoint BASAV10149Daytime Warmup Setpoint BASAV10150Economizer Outdoor Air Enable Setpoint BASAV10154Space Cooling Setpoint High Limit BASAV10155Space Cooling Setpoint Low Limit BASAV10157Space Heating Setpoint High Limit BASAV10158Space Heating Setpoint Low Limit BASAV10159Occupied Cooling Setpoint BASAV10160Occupied Heating Setpoint BASAV10161Occupied Standby Cooling Setpoint BASAV10162Occupied Standby Heating Setpoint BASAV10167Discharge Air Temperature Minimum Cool LimitAV10168Relief Enable Position SetpointAV10169Occupied Bypass TimeAV10170Economizer Outdoor Air Enthalpy Enable Setpoint BASAV10175Space CO2 High LimitAV10176Space CO2 Low LimitAV10214Space Dehumidification Unoccupied Setpoint ActiveAV10228Space Dew Point Unoccupied Setpoint ActiveAV10281Discharge Air Temperature Setpoint ActiveAV11103Return Air Humidity BASAV11104Run Time - Compressor 3 (Hours)AV11105Starts - Compressor 3AV11106Run Time - Condenser Fan 3 (Hours)AV11107Starts - Condenser Fan 3AV11108Cabinet StyleAV11110Supply Fan Speed CommandAV11112Cooling Capacity Setpoint BASAV11113Space Dehumidification Setpoint Offset BAS - ActiveAV11115Exhaust Or Return Fan TypeAV11116Filter Runtime HoursAV11117Outdoor Air Enthalpy ActiveAV11118Return Air Temperature ArbitratorAV11119Return Air Temperature BASAV11120Heating Demand Limit Capacity Enable SetpointAV11121Discharge Air Temperature Maximum Cool LimitAV11122Run Time - Condenser Fan 1 (Hours)AV11123Run Time - Condenser Fan 2 (Hours)AV11124Run Time - Relief Fan (Hours)AV11125Run Time - Electric Heat Stage 1 (Hours)AV11126Run Time - Electric Heat Stage 2 (Hours)AV11127Run Time - Supply Fan (Hours)AV11128Space Temp Cooling Setpoint StatusAV11129Space Temp Heating Setpoint StatusAV11130Design Minimum OA Damper Position at Full Fan CapacityAV11131Design Minimum OA Damper Position at Mid Fan CapacityAV11132Design Minimum OA Damper Position at Min Fan CapacityAV11133DCV Minimum OA Damper Position at Full Fan CapacityAV11134DCV Minimum OA Damper Position at Mid Fan CapacityAV11135DCV Minimum OA Damper Position at Min Fan CapacityAV11136Space Dehumidification Setpoint BAS - ActiveAV11137Discharge Air Heating Setpoint High LimitAV11138Discharge Air Heating Setpoint (Target)AV11140Discharge Air Cooling Setpoint (Target)AV11142Space Static Pressure Setpoint DeadbandAV11143Design Min Outdoor Airflow SetpointAV11144Standby Min Outdoor Airflow SetpointAV11145DCV Min Outdoor Airflow SetpointAV11147Economizer Dry Bulb Enable OffsetAV11148Duct Static Pressure P-Gain (%/IWC)AV11149Duct Static Pressure Deadband BASAV11150Cooling Reset Start TempAV11151Cooling Reset End TempAV11152Cooling Reset AmountAV11153Service Test Timeout (Minutes)AV11154Economizer Cooling Reference Enthalpy OffsetAV11155Starts - Condenser Fan 1AV11156Starts - Condenser Fan 2AV11157Starts - Relief FanAV11158Starts - Electric Heat Stage 1AV11159Starts - Electric Heat Stage 2AV11160Starts - Supply FanAV11161Supply Fan TypeAV11163Supply Fan Speed StatusAV11164Heating Capacity Setpoint BASAV11167Demand Shed Offset SetpointAV11168Cooling Demand Limit Capacity Enable SetpointAV11169Run Time - Compressor 1 (Hours)AV11170Run Time - Compressor 2 (Hours)AV11173Supply Fan Minimum Speed SetpointAV11174Supply Fan Maximum Speed SetpointAV11178Space Temperature ActiveAV11180Space Temperature Heating Setpoint Input ActiveAV11181Space Temperature Setpoint ActiveAV11183Starts - Compressor 1AV11184Starts - Compressor 2AV11185Cooling Capacity Enable - ActiveAV11186Daytime Warmup Setpoint BAS - ActiveAV11187Supply Fan Speed Command - ActiveAV11189Cooling Capacity Setpoint BAS - ActiveAV11190Discharge Air Cooling Setpoint BAS - ActiveAV11191Discharge Air Heating Setpoint BAS - ActiveAV11192Discharge Air Reheat Setpoint BAS - ActiveAV11193Discharge Air Temperature Minimum Cool Limit - ActiveAV11195Economizer Minimum Position Setpoint BAS - ActiveAV11196Economizer Outdoor Air Enthalpy Enable Setpoint BAS - ActiveAV11197Economizer Outdoor Air Enable Setpoint BAS - ActiveAV11198Relief Enable Position Setpoint - ActiveAV11199Heating Demand Limit Capacity Enable Setpoint - ActiveAV11200Discharge Air Temperature Maximum Cool Limit - ActiveAV11202Cool TypeAV11203DCV Min Outdoor Airflow Setpoint - ActiveAV11204DCV Minimum OA Damper Position at Full Fan Capacity - ActiveAV11205DCV Minimum OA Damper Position at Mid Fan Capacity - ActiveAV11206DCV Minimum OA Damper Position at Min Fan Capacity - ActiveAV11209Demand Shed Offset Setpoint - ActiveAV11210Design Min Outdoor Airflow Setpoint - ActiveAV11211Design Minimum OA Damper Position at Full Fan Capacity - ActiveAV11212Design Minimum OA Damper Position at Mid Fan Capacity - ActiveAV11213Design Minimum OA Damper Position at Min Fan Capacity - ActiveAV11214Economizer Dry Bulb Disable Return Air OffsetAV11217Filter Runtime Hours Setpoint - ActiveAV11218Heat Primary Enable BAS - ActiveAV11219Heating Capacity Setpoint BAS - ActiveAV11220Morning Warmup Setpoint BAS - ActiveAV11222Outdoor Air Minimum Flow Setpoint BAS - ActiveAV11226Space CO2 High Limit - ActiveAV11227Space CO2 Low Limit - ActiveAV11229Space Static Pressure Setpoint Deadband - ActiveAV11231Standby Min Outdoor Airflow Setpoint - ActiveAV11236Discharge Air Cooling Setpoint (Target) - ActiveAV11237Discharge Air Heating Setpoint High Limit - ActiveAV11238Duct Static Pressure Reset Time (seconds)AV11240Duct Static Pressure Deadband ActiveAV11241Heating Reset Start TempAV11242Heating Reset End TempAV11243Supply Fan Maximum Speed Setpoint - ActiveAV11244Supply Fan Maximum Output Frequency StatusAV11245Supply Fan Minimum Speed Setpoint - ActiveAV11246Supply Fan Minimum Output Frequency StatusAV11247Cooling Demand Limit Capacity Enable Setpoint - ActiveAV11248Economizer Minimum Position Setpoint ActiveAV11249Heating Capacity Secondary StatusAV11250Occupied Standby Cooling Setpoint BAS - ActiveAV11251Occupied Standby Heating Setpoint BAS - ActiveAV11252Preheat TypeAV11253Reheat TypeAV11254Space CO2 Concentration ActiveAV11256Compressor Cooling P-Gain (%/F)AV11257Compressor Cooling Reset Time (seconds)AV11258Economizer Cooling P-Gain - 1 (%/F)AV11259Economizer Cooling Reset Time - 1 (Seconds)AV11266Auxiliary Heating P-Gain (%/F)AV11267Auxiliary Heating Reset Time (seconds)AV11268Compressor Cooling P-Gain - 1 (%/F)AV11269Compressor Cooling Reset Time - 1 (seconds)AV11270Compressor Cooling P-Gain - 2 (%/F)AV11271Compressor Cooling Reset Time - 2 (seconds)AV11272Economizer Discharge Air SetpointAV11273Economizer Discharge Air Setpoint - ActiveAV11276Space Temperature Setpoint Input ActiveAV11277Space Temperature Cooling Setpoint Input ActiveAV11278Supply Fan PowerAV11279Supply Fan CurrentAV11280Duct Static Pressure Setpoint ActiveAV11281Dehumidification Control StatusAV11286Motorized Damper Position SetpointAV11287Motorized Damper Position Setpoint - ActiveAV11288Standby Minimum OA Damper Position at Full Fan CapacityAV11289Standby Minimum OA Damper Position at Full Fan Capacity - ActiveAV11290Standby Minimum OA Damper Position at Mid Fan CapacityAV11291Standby Minimum OA Damper Position at Mid Fan Capacity - ActiveAV11292Standby Minimum OA Damper Position at Min Fan CapacityAV11293Standby Minimum OA Damper Position at Min Fan Capacity - ActiveAV11299Return Air Humidity ActiveAV11300Return Air Humidity ArbitratorAV11301Return Air Enthalpy ActiveAV11302Relief Enable Position Setpoint StatusAV11307Discharge Air Heating Setpoint (Target) - ActiveAV11308Duct Static Pressure Setpoint High Limit Setpoint BASAV11309Duct Static Pressure Setpoint High Limit Setpoint BAS - ActiveAV11314Comfort Purge Interval (minutes)AV11315Reheat Purge Interval (minutes)AV11316Reheat P-Gain 1AV11317Reheat Reset Time - 1AV11318Reheat P-Gain 2AV11319Reheat Reset Time - 2AV11320Space Dew Point Setpoint BASAV11321Dew Point Setpoint Offset BASAV11323Outdoor Air Dew Point Setpoint BASAV11325Space Static Pressure Setpoint ActiveAV11326Space Dehumidification Setpoint Offset BASAV11327Space Dehumidification Setpoint BASAV11329Space Dehumidification Unoccupied Setpoint BASAV11330Space Dew Point Unoccupied Setpoint BASAV11331Compressor Dehumid P-Gain 2AV11332Compressor Dehumid P-Gain 1AV11333Compressor Dehumid Reset Time - 2 (seconds)AV11334Compressor Dehumid Reset Time - 1 (seconds)AV11335Pre Cool Setpoint BASAV11336Pre Cool Setpoint BAS - ActiveAV11337Refrigerant Target Setpoint ActiveAV11338Space Dew Point Setpoint ActiveAV11340Dew Point Setpoint Offset BAS - ActiveAV11341Outdoor Air Dew Point Setpoint BAS - ActiveAV11342Unoccupied Dehumidification TimerAV11343Heating Reset AmountAV11344VAV Box Stroke TimerAV11346Economizer Cooling P-Gain (%/F)AV11347Economizer Cooling Reset Time (Seconds)AV11348Economizer Cooling P-Gain - 2 (%/F)AV11349Economizer Cooling Reset Time - 2 (Seconds)AV11350Auxiliary Heating P-Gain - 1 (%/F)AV11351Auxiliary Heating Reset Time - 1 (seconds)AV11352Auxiliary Heating P-Gain - 2 (%/F)AV11353Auxiliary Heating Reset Time - 2 (seconds)AV11354Discharge Air Heating Setpoint Low LimitAV11355Discharge Air Heating Setpoint Low Limit - ActiveAV11356Discharge Air Cooling Setpoint StatusAV11357Discharge Air Heating Setpoint StatusAV11358Discharge Air Reheating Setpoint High Limit - ActiveAV11359Discharge Air Reheating Setpoint Low Limit - ActiveAV11360Discharge Air Reheating Setpoint High LimitAV11361Discharge Air Reheating Setpoint Low LimitAV11362Run Time - Gas Heat Manifold 1 Burner 1 (Hours)AV11363Starts - Gas Heat Manifold 1 Burner 1AV11364Run Time - Gas Heat Manifold 1 Burner 2 (Hours)AV11365Starts - Gas Heat Manifold 1 Burner 2AV11366Run Time - Gas Heat Manifold 2 Burner 1 (Hours)AV11367Starts - Gas Heat Manifold 2 Burner 1AV11368Auxiliary Heating P-Gain Modulating Gas Staging (%/F)AV11369Auxiliary Heating Reset Time Modulating Gas Staging (seconds)AV11370Outdoor Airflow Calibration GainAV11371Outdoor Airflow Calibration OffsetAV11372Outdoor Airflow P-Gain (%/CFM)AV11373Outdoor Airflow Reset Time (Seconds)AV11374Local Atmospheric PressureAV11379Space Pressure Control P-Gain (%/IWC)AV11380Space Pressure Control Reset Time (Seconds)AV11381Space Pressure Control Feed Forward GainAV11382Relief Air Damper Minimum Position SetpointAV11383Condenser Fan CapacityAV11388Control StateBI10105FDD: Unit Economizing When It Should NotBI10106FDD: Unit Not Economizing When It ShouldBI10107FDD: Excessive Outdoor AirBI10108FDD: Outdoor Air Damper Not ModulatingBI10121Relief Fan Output StatusBI10143VAV Box CommandBI10170Condensate Overflow InputBI10172Occupancy InputBI10210Equipment Shutdown Input StatusBI10211External Auto Stop Input StatusBI10219Economizer Airside StatusBI10226Supply Fan StatusBI11100Compressor 1 Command StatusBI11101Circuit 1 LPC StatusBI11102Compressor 1 Proving StatusBI11103Compressor 2 Command StatusBI11105Compressor 2 Proving StatusBI11106Compressor 3 Command StatusBI11108Compressor 3 Proving StatusBI11113Demand Limit InputBI11114Demand Shed InputBI11115Phase Monitor StatusBI11116Condenser Fan 1 Command StatusBI11117Condenser Fan 2 Command StatusBI11120Thermostat G InputBI11121Thermostat W1/O InputBI11122Thermostat W2 InputBI11123Thermostat X2 InputBI11124Thermostat Y1 InputBI11125Thermostat Y2 InputBI11127FroStat InputBI11128Electric Heat Stage 1 StatusBI11129Electric Heat Stage 2 StatusBI11130Clogged Filter InputBI11131Condenser Fan 3 Command StatusBI11133Ventilation Override Exhaust StatusBI11134Ventilation Override Pressurize StatusBI11135Ventilation Override Purge StatusBI11143Reheat Humidistat InputBI11144Diagnostic: VFD Fault Supply Fan - 1BI11145Diagnostic: VFD Supply Fan Ground Fault - 1BI11147Diagnostic: VFD Supply Fan Motor Current Overload - 1BI11148Diagnostic: VFD Supply Fan Short Circuit - 1BI11149Fan Mode - Air-FiBI11150Occupancy Input - Air-FiBI11151Fan Mode InputBI11154Gas Heat Stage 1 StatusBI11155Gas Heat Stage 2 StatusBI11187Reheat Pumpout Solenoid StatusBI11188Reheat Valve 2 Fault StatusBI11189Reheat Valve 1 Fault StatusBI11190Reheat Valve 1 Calibration StatusBI11191Reheat Valve 2 Calibration StatusBI11192VAV Changeover InputBI11194Diagnostic: VFD Supply Fan Broken Belt - 1BI11195Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 1BI11196Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 2BI11197Diagnostic: Modulating Gas Invalid ID Plug Manifold 1BI11198Diagnostic: Modulating Gas Heat Configuration InvalidBI11199Diagnostic: Gas Heat Weak Flame Manif 1 Burner 1BI11200Diagnostic: Gas Heat Weak Flame Manif 1 Burner 2BI11201Diagnostic: Gas Heat Insufficient Combustion AirBI11202Diagnostic: Modulating Gas Primary Limit Open Manifold 1BI11203Diagnostic: Modulating Gas Heat Open Fuse Manifold 1BI11204Diagnostic: Gas Heat Failed Ignition Manifold 1BI11205Diagnostic: Modulating Gas Valve Failure Manifold 1BI11206Diagnostic: Modulating Gas Control Board Failure Manifold 1BI11207Diagnostic: Gas Heat Unexpected Flame Manifold 1BI11208Diagnostic: Staged Gas Heat Invalid ID Plug Manifold 1BI11209Diagnostic: Staged Gas Heat Configuration Invalid Manifold 1BI11210Diagnostic: Staged Gas Heat Primary Limit Open Manifold 1BI11211Diagnostic: Staged Gas Heat Open Fuse Manifold 1BI11212Diagnostic: Heat Failed Ignition Manifold 1BI11213Diagnostic: Staged Gas Heat Valve Failure Manifold 1BI11214Diagnostic: Gas Heat Inducer High Pressure Manifold 1BI11215Diagnostic: Gas Heat Valve Short Manifold 1BI11216Diagnostic: Gas Heat Flame Loss Manifold 1BI11217Diagnostic: Staged Gas Heat Control Board Failure Manifold 1BI11218Diagnostic: Gas Heat Start Failure Manifold 1BI11219Diagnostic: Gas Heat Unexpected Flame Manifold 2BI11220Diagnostic: Staged Gas Heat Invalid ID Plug Manifold 2BI11221Diagnostic: Staged Gas Heat Configuration Invalid Manifold 2BI11222Diagnostic: Staged Gas Heat Primary Limit Open Manifold 2BI11223Diagnostic: Staged Gas Heat Open Fuse Manifold 2BI11224Diagnostic: Heat Failed Ignition Manifold 2BI11225Diagnostic: Staged Gas Heat Valve Failure Manifold 2BI11226Diagnostic: Gas Heat Inducer High Pressure Manifold 2BI11227Diagnostic: Gas Heat Valve Short Manifold 2BI11228Diagnostic: Gas Heat Flame Loss Manifold 2BI11229Diagnostic: Staged Gas Heat Control Board Failure Manifold 2BI11230Diagnostic: Gas Heat Start Failure Manifold 2BI11231Diagnostic: Gas Heat Lockout Manifold 1BI11232Diagnostic: Gas Heat Lockout Manifold 2BI11233Diagnostic: Gas Heat Flame Rod Aged Manifold 1BI11234Diagnostic: Gas Heat Flame Rod Aged Manifold 2BI11235Diagnostic: Gas Heat Failed Ignition Manifold 1 Burner 2BI11236Reheat LPC StatusBI11241Diagnostic: Gas Heat Air Pressure Sensor Reading LowBI11242Diagnostic: Gas Heat Air Pressure Sensor Reading HighBI11243Diagnostic: Gas Heat Loss of Inducer Motor ControlBI11244Diagnostic: Gas Heat Air Sensor Null Pressure CheckBI11245Diagnostic: Gas Heat Limited Low FireBI11247Diagnostic: Refrigerant Concentration Sensor ABI11248Refrigerant Leak Detection System InputBI11249Diagnostic: Refrigerant Leak Sensor Failure Sensor ABV10103Heat Lockout CommandBV10104Supply Fan Configuration CommandBV10106Dehumidification Enable CommandBV10109Filter Timer ResetBV10110Reset DiagnosticBV10111Daytime Warmup Enable CommandBV10112Morning Warmup Enable CommandBV10113Occupancy Input BASBV10115Cooling Lockout BASBV10119Supply Air Tempering EnableBV11100Alarm Indicator StatusBV11111Compressor Lockout StatusBV11113Unit Stop CommandBV11114Supply Fan Speed Command EnableBV11115Cooling Capacity Setpoint Enable BASBV11116Heating Capacity Setpoint Enable BASBV11119Supply Fan CompensationBV11121Compressor 1 Run Time ResetBV11122Compressor 1 Starts ResetBV11123Compressor 2 Run Time ResetBV11124Compressor 2 Starts ResetBV11125Compressor 3 Run Time ResetBV11126Compressor 3 Starts ResetBV11127Condenser Fan 1 Run Time ResetBV11128Condenser Fan 1 Starts ResetBV11129Condenser Fan 2 Run Time ResetBV11130Condenser Fan 2 Starts ResetBV11131Condenser Fan 3 Run Time ResetBV11132Condenser Fan 3 Starts ResetBV11133Relief Fan Run Time ResetBV11134Relief Fan Starts ResetBV11135Electric Heat Stage 1 Run Time ResetBV11136Electric Heat Stage 1 Starts ResetBV11137Electric Heat Stage 2 Run Time ResetBV11138Electric Heat Stage 2 Starts ResetBV11139Supply Fan Run Time ResetBV11140Supply Fan Starts ResetBV11141Diagnostic: Supply Fan FailureBV11143Diagnostic: Duct Static Pressure Limit TripBV11144Diagnostic: Filter Change RequiredBV11145Diagnostic: Condensate Overflow LockoutBV11146Diagnostic: FroStat TripBV11155Diagnostic: Comp 1 Proving TripBV11156Diagnostic: Comp 2 Proving TripBV11157Diagnostic: Comp 3 Proving TripBV11158Diagnostic: Circuit 1 LPC TripBV11161Diagnostic: Compressor 1 Contactor FailureBV11162Diagnostic: Circuit 1 LPC LockoutBV11166VVZT DAT Control ModeBV11172Diagnostic: Compressor 1 Proving LockoutBV11173Occupancy Input ActiveBV11174Diagnostic: Compressor 2 Contactor FailureBV11175Diagnostic: Circuit 2 LPC LockoutBV11176Diagnostic: Compressor 2 Proving LockoutBV11190Diagnostic: Maintenance RequiredBV11192Diagnostic: Unit Communications FailureBV11199Supply Fan Configuration StatusBV11200Timed Override Timer Is ActiveBV11201Supply Fan Speed Command Enable - ActiveBV11202Cooling Capacity Setpoint Enable BAS - ActiveBV11203Cooling Lockout BAS - ActiveBV11204Heating Capacity Setpoint Enable BAS - ActiveBV11205Daytime Warmup Enable Command - ActiveBV11208Supply Fan Compensation - ActiveBV11209Dehumidification Enable Command - ActiveBV11211VVZT DAT Control Mode - ActiveBV11216Heat Lockout Command - ActiveBV11217Morning Warmup Enable Command - ActiveBV11221Supply Air Tempering StatusBV11222Supply Air Tempering Enable - ActiveBV11224Occupancy Input ArbitratorBV11226Demand Limit Request BASBV11227Demand Limit Request - ActiveBV11228Diagnostic: Compressor 3 Contactor FailureBV11229Diagnostic: Compressor 3 Proving LockoutBV11231Daytime Warmup ActiveBV11232Morning Warmup ActiveBV11235Occupied Standby Supply Fan Configuration CommandBV11236Occupied Standby Supply Fan Configuration Command - ActiveBV11248Diagnostic: High Condensate Level DetectedBV11249Diagnostic: Morning Warmup Mode Exceeded 120 MinutesBV11250Diagnostic: Pre Cool Mode Exceeded 120 MinutesBV11251Diagnostic: Night Purge Mode Exceeded 120 MinutesBV11252Diagnostic: Circuit 3 LPC LockoutBV11255Dehumidification StatusBV11256Pre Cool Enable CommandBV11257Pre Cool Enable Command - ActiveBV11258Pre Cool ActiveBV11259Occupied Dehumidification Enable BASBV11260Occupied Dehumidification Enable BAS - ActiveBV11261Unoccupied Dehumidification Enable BASBV11262Unoccupied Dehumidification Enable BAS - ActiveBV11263Diagnostic: Duct Static Pressure Limit LockoutBV11265Diagnostic: Duct Static Pressure Local LockoutBV11266Gas Heat Manifold 1 Burner 1 Run Time ResetBV11267Gas Heat Manifold 1 Burner 1 Starts ResetBV11268Gas Heat Manifold 1 Burner 2 Run Time ResetBV11269Gas Heat Manifold 1 Burner 2 Starts ResetBV11270Gas Heat Manifold 2 Burner 1 Run Time ResetBV11271Gas Heat Manifold 2 Burner 1 Starts ResetBV11276Diagnostic: Supply Fan Bypass EnableBV11277Diagnostic: Reheat Valve 1 FaultBV11278Diagnostic: Reheat Valve 2 FaultBV11279Diagnostic: Outdoor Airflow Pressure Calibration LimitBV11280Diagnostic: Space Pressure Calibration LimitBV11281Diagnostic: Reheat LPC TripBV11282Diagnostic: Reheat LPC LockoutBV11283Refrigerant Mitigation ActiveMI10101Heat Cool Mode StatusMI10144Economizer System StatusMI11100System Mode Switch Air-FiMI11101Timed Override Air-FiMI11102System Mode Switch InputMI11103Timed Override InputMV10101Cooling Reset Type StatusMV10102Emergency Override BASMV10103Economizer Airside Enable BASMV10104Heat Cool Mode RequestMV10106Occupancy RequestMV10110Timed Override RequestMV11100Arbitration Method RequestMV11101Customer Options Module Communication StatusMV11102Economizer TypeMV11103Fresh Air Options Module Communication StatusMV11105Indoor Options Module Communication StatusMV11106On-Board I/O Communication StatusMV11110Service Test State RequestMV11111Cooling Reset TypeMV11112System Mode Switch LocalMV11113Timed Override StatusMV11114Trane Unit TypeMV11115Unit Stop SourceMV11116Emergency Override BAS - ActiveMV11118Economizer Decision MethodMV11119Refrigerant TypeMV11120Economizer Airside Enable BAS - ActiveMV11121Heat Cool Mode Request - ActiveMV11123Occupancy StatusMV11124Supply Fan VFD Communication StatusMV11125Occupancy Request ActiveMV11128Gas Heat Ignition Module 1 Communication StatusMV11129Gas Heat Ignition Module 2 Communication StatusMV11130Emergency Override StatusMV11133Stepper Motor Communication StatusMV11136Heating Reset TypeMV11137Heating Reset Type StatusMV11139Refrigerant Leak Sensor Communication Status Sensor A
Integration notes
- Only the points that match the unit's factory configuration show up; the guide lists every possible point.
- Name suffixes carry meaning: Status/Local/Active/Input are read-only, BAS/Command/Request/Setpoint value objects are the ones a BAS writes, and Arbitrator objects show which source is winning.
- Access 'C' marks writable objects whose arbitration pattern is setpoint with a priority array, plus AV 10127, AV 10159 and AV 10160, which the appendix calls commandable; other writable objects are 'W'.
- Several objects are printed more than once with different descriptions or state lists for different unit configurations (PI gain/reset AVs, AI 11142-11143, BI 11231, BV 11100, MV 11110 Service Test State Request, MV 11128). Each is listed once here.
- Eight objects whose rows ran together in the table (AI 10185, AI 10187, AV 11159, AV 11160, AV 11217, AV 11218, BV 11127, BV 11128) were checked against the page text.
- The same guide gives Modbus RTU/TCP registers for every object; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 700 Voyager 3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 700 Voyager 3
How many BACnet points does the Trane Symbio 700 Voyager 3 have?
This list has 568 BACnet objects: 56 analog inputs, 260 analog values, 105 binary inputs, 108 binary values, 6 multi-state inputs, 33 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 700 Voyager 3 BACnet points are writable?
198 of the 568 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Trane Symbio 700 Voyager 3 BACnet documentation?
The source is Integration Guide: BACnet and Modbus Integration to Voyager 3 Packaged Rooftop Air-Conditioners with Symbio 700 Controls (BAS-SVP066B-EN), revision April 2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP066B-EN_04132024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 700 Voyager 3?
Start with MV 10106 Occupancy Request (Occupancy command (occupied/unoccupied/standby)); BV 11113 Unit Stop Command (BMS stop/auto of the whole unit); AV 10159 Occupied Cooling Setpoint BAS (Occupied cooling setpoint (dual-setpoint units)); AV 10160 Occupied Heating Setpoint BAS (Occupied heating setpoint (dual-setpoint units)); AV 10127 Space Temperature Setpoint BAS (Single-setpoint alternative to the two setpoints above); MI 10101 Heat Cool Mode Status (Current heat/cool operating mode); MV 11123 Occupancy Status (Confirms the occupancy the unit is running in); BI 10226 Supply Fan Status (Supply fan on/off status); AV 11178 Space Temperature Active (Space temperature the unit is actually controlling to); BV 11100 Alarm Indicator Status (Unit alarm output; on when the controller is in alarm).
How do I enable BMS control of the Trane Symbio 700 Voyager 3?
MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the default: the controller weighs BAS, Air-Fi and wired sources. 'Standalone Control' ignores all BAS input and is meant for troubleshooting. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.
Does the Trane Symbio 700 Voyager 3 need a BACnet heartbeat or have a communication timeout?
The sensor BAS points (AV 10113 Outdoor Air Temperature BAS, AV 10114 Space Temperature BAS, AV 10116-10119, AV 11103 Return Air Humidity BAS, AV 11119 Return Air Temperature BAS) have a 900 s heartbeat in the tables, so the BMS must keep rewriting them. The setpoint and command points have no heartbeat.
Can the BMS supply sensor values to the Trane Symbio 700 Voyager 3?
Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it; the '... Arbitrator' object shows which source wins and the '... Active' object reports the value in use. Space setpoints go to AV 10127 (single setpoint) or AV 10159/10160 (dual setpoint). BV 10113 Occupancy Input BAS is the communicated occupancy input.
How do I check these points on the real Symbio 700 Voyager 3?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Integration Guide: BACnet and Modbus Integration to Voyager 3 Packaged Rooftop Air-Conditioners with Symbio 700 Controls · BAS-SVP066B-EN · rev. April 2024. Object names, instances and units are reproduced as published; descriptions are our own.