Rooftop unit controller · BACnet points list

Trane Symbio 700 Voyager 3 BACnet points list

Updated 6 November 2026

Short answer

Symbio 700 is the factory controller on Voyager 3 rooftops. It speaks BACnet IP, BACnet MS/TP or BACnet over Zigbee (Air-Fi), and the same guide maps every object to Modbus. Objects use 5-digit instances (AI-10101, AV-11403...). Most writable objects are BAS or Setpoint values that feed Trane's arbitration logic, and the BAS sensor values carry a 900 s heartbeat.

This page lists 568 BACnet objects for the Trane Symbio 700 Voyager 3 — 198 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 700 Voyager 3
Equipment
Rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
568 (198 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066
Source document
Integration Guide: BACnet and Modbus Integration to Voyager 3 Packaged Rooftop Air-Conditioners with Symbio 700 Controls · BAS-SVP066B-EN · rev. April 2024
Download CSV 568 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane Symbio 700 Voyager 3

Integration in brief

Leave MV 11100 Arbitration Method Request at 'Enable External/BAS Control'. Then schedule the unit with MV 10106 Occupancy Request and send setpoints to the setpoint BAS points at a priority above 14. If the BMS supplies sensor values such as space temperature, rewrite the '... BAS' points within their 900 s heartbeat.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10106Occupancy RequestOccupancy command (occupied/unoccupied/standby)Command
BV 11113Unit Stop CommandBMS stop/auto of the whole unitWrite
AV 10159Occupied Cooling Setpoint BASOccupied cooling setpoint (dual-setpoint units)Command
AV 10160Occupied Heating Setpoint BASOccupied heating setpoint (dual-setpoint units)Command
AV 10127Space Temperature Setpoint BASSingle-setpoint alternative to the two setpoints aboveCommand
MI 10101Heat Cool Mode StatusCurrent heat/cool operating modeRead
MV 11123Occupancy StatusConfirms the occupancy the unit is running inRead
BI 10226Supply Fan StatusSupply fan on/off statusRead
AV 11178Space Temperature ActiveSpace temperature the unit is actually controlling toRead
BV 11100Alarm Indicator StatusUnit alarm output; on when the controller is in alarmRead

Enable & remote start

MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the default: the controller weighs BAS, Air-Fi and wired sources. 'Standalone Control' ignores all BAS input and is meant for troubleshooting. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.

Heartbeat & communication loss

The sensor BAS points (AV 10113 Outdoor Air Temperature BAS, AV 10114 Space Temperature BAS, AV 10116-10119, AV 11103 Return Air Humidity BAS, AV 11119 Return Air Temperature BAS) have a 900 s heartbeat in the tables, so the BMS must keep rewriting them. The setpoint and command points have no heartbeat.

Sensors & values from the BMS

Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it; the '... Arbitrator' object shows which source wins and the '... Active' object reports the value in use. Space setpoints go to AV 10127 (single setpoint) or AV 10159/10160 (dual setpoint). BV 10113 Occupancy Input BAS is the communicated occupancy input.

Network setup

Watch out for

Trane Symbio 700 Voyager 3 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

568 of 568 shown
Type
Access
Show
Trane Symbio 700 Voyager 3 BACnet Points List
DescriptionStates
AI10101Cooling Capacity StatusActual operating unit cooling capacity, in %%Read
AI10102Heating Capacity Primary StatusUnit (primary) heating capacity, in % [Primary Heating Source Installed]%Read
AI10104Outdoor Air Relative Humidity LocalOA humidity value from sensor connected to the controller%Read
AI10110Return Air Humidity LocalReturn air humidity value from sensor connected to the controller%Read
AI10111Outdoor Air Damper PositionOA Damper Actuator feedback signal [Outside Air is Configured at 0-100% or 0-50% Motorized Damper]%Read
AI10112Relief Damper PositionUnit commanded Relief damper position [Relief fan installed]%Read
AI10116Space Humidity ActiveActive space relative humidity being used by the controller [Humidity Sensor Configured]%Read
AI10117Outdoor Air Dew PointOutdoor air dewpoint value being utilized by the unit [Hot Gas Reheat is configured as Installed]°FRead
AI10118Outdoor Air Temperature ActiveActive OA temperature currently being used by the controller°FRead
AI10120Outdoor Air Humidity ActiveActive outdoor air humidity value used by the controller%Read
AI10124Discharge Air Temperature LocalDischarge air temperature value from a sensor connected to the controller°FRead
AI10126Return Air Temperature InputActual return air temperature being used by the controller°FRead
AI10155Duct Static Pressure LocalDuct static pressure value from a sensor connected to the controllerin. w.c.Read
AI10156Outdoor Air Temperature LocalOA temp value from a sensor connected to the controller°FRead
AI10185Outdoor Air Flow ActiveOutdoor airflow used by the unit [0 to 100% Economizer w/ TRAQ installed]cfmRead
AI10187Space Static Pressure ActiveSpace static pressure from a unit-mounted sensor [StatiTrac Space Pressure Control configured]in. w.c.Read
AI10218Space Temperature InputSpace temp from a wired sensor°FRead
AI10226Space Dew PointCalculated Space Dewpoint [Hot Gas Reheat is Configured as Installed]°FRead
AI11103Space CO2 Concentration InputSpace CO2 concentration from a sensor hardwired to the controller [CO2 Sensor Configured]ppmRead
AI11104Space Humidity InputSpace relative humidity from a sensor wired to the controller [Humidity Sensor Configured]%Read
AI11106Supply Fan Speed Command StatusUnit commanded supply fan speed output [Indoor Fan Type Configured as Multi Speed or Variable Speed]%Read
AI11109Modulating Heat Command StatusUnit commanded modulating heat output [Modulating gas heat installed]%Read
AI11111Outdoor Air Damper CommandUnit commanded outside air damper position [Outside Air is Configured at 0-100%]%Read
AI11112Outdoor Airflow PressureHardwired input for outdoor airflow pressure sensor [0 to 100% Economizer w/ TRAQ installed]in. w.c.Read
AI11132On-Board I/O Firmware Major VersionSoftware Major Version for On-Board I/O ModuleRead
AI11133On-Board I/O Firmware Minor VersionOn-Board I/O Module Software build numberRead
AI11134Indoor Options Module Firmware Major VersionSoftware Major Version for Indoor Options Module [Indoor Options Module Installed and In-Use]Read
AI11135Indoor Options Module Firmware Minor VersionIndoor Options Module Software build number [Indoor Options Module Installed and In-Use]Read
AI11136Fresh Air Options Module Firmware Major VersionSoftware Major Version for Fresh Air Options Module [Fresh Air Options Module Installed and In-Use]Read
AI11137Fresh Air Options Module Firmware Minor VersionFresh Air Options Module Software build number [Fresh Air Options Module Installed and In-Use]Read
AI11140Customer Options Module Firmware Major VersionSoftware Major Version for Customer Connection Options Module [Customer Options Module Installed and In-Use]Read
AI11141Customer Options Module Firmware Minor VersionCustomer Options Module Software build number [Customer Options Module Installed and In-Use]Read
AI11142IGN Module 1 Firmware Major VersionSoftware Major Version for Gas Heat Ignition Module 1 [Primary Heating Source is Configured as Gas]Read
AI11143IGN Module 1 Firmware Minor VersionSoftware Major Version for Gas Heat Ignition Module 1 [Primary Heating Source is Configured as Gas]Read
AI11144IGN Module 2 Firmware Major VersionSoftware Major Version for Gas Heat Ignition Module 2Read
AI11145IGN Module 2 Firmware Minor VersionSoftware Minor Version for Gas Heat Ignition Module 2Read
AI11148Remote Minimum PositionHardwired remote minimum position for OA damper control [Remote Minimum Position is Configured as Installed]%Read
AI11149Return Air Temperature ActiveReturn Air Temperature being used for control°FRead
AI11150Sensor Battery Status Air-FiStatus %age of connected AirFi sensor(s) [Air-Fi Sensor Installed and Communicating]%Read
AI11151Space CO2 Concentration Air-FiSpace CO2 concentration from a wireless sensor connected to the controller [Air-Fi Sensor Installed and Communicating]ppmRead
AI11152Space Humidity Air-FiSpace relative humidity from a connected wireless sensor [Air-Fi Sensor Installed and Communicating]%Read
AI11154Space Temperature Air-FiSpace temp from a connected wireless (AirFi) sensor [Air-Fi Sensor Installed and Communicating]°FRead
AI11155Space Temperature Cooling Setpoint Air-Fi(occupied) cooling setpoint from the connected wireless space sensor [Air-Fi Sensor Installed and Communicating]°FRead
AI11156Space Temperature Heating Setpoint Air-Fi(occupied) heating setpoint from the connected wireless space sensor [Air-Fi Sensor Installed and Communicating]°FRead
AI11157Space Temperature Setpoint Air-FiSpace Temperature Setpoint from a connected wireless sensor [Air-Fi Sensor Installed and Communicating]°FRead
AI11158Space Static Pressure InputSpace statice pressure from a wired sensor connected to the controller [StatiTrac Space Pressure Control configured.]in. w.c.Read
AI11159Space Temperature Cooling Setpoint Input(occupied) cooling setpoint from the connected wired space sensor°FRead
AI11160Space Temperature Heating Setpoint Input(occupied) heating setpoint from the connected wired space sensor°FRead
AI11161Space Temperature Setpoint InputSpace Temperature Setpoint from a connected wired sensor [Space Controller Configured as Single Setpoint Zone Sensor]°FRead
AI11164Reheat Valve 1 Step StatusReheat Valve 1 Status in steps from Stepper Motor ModuleRead
AI11165Reheat Valve 2 Step StatusReheat Valve 2 (Cooling) Status in steps from Stepper Motor ModuleRead
AI11166Evaporator Entering Refrigerant TemperatureEvaporator Entering Refrigerant Temperature from a connected wire sensor on the Indoor°FRead
AI11167Stepper Motor Module Firmware Major VersionSoftware Major Version for Stepper Motor Module [Stepper Motor Module Installed and In-Use]Read
AI11168Stepper Motor Module Firmware Minor VersionStepper Motor Module Software build number [Stepper Motor Module Installed and In-Use]Read
AI11171Refrigerant LFL Concentration Sensor AExpressed in % of LFL (Lower Flammability Limit) [Refrigerant Type is R454B]%Read
AI11172Refrigerant LFL Concentration Alarm Threshold Sensor ADefines the %LFL setpoint [Refrigerant Type is R454B]%Read
AV10103Outdoor Air Temperature ArbitratorOA temp determined by arbitration°FWrite
AV10104Outdoor Air Humidity ArbitratorActual outdoor air humidity being used by the controller%Write
AV10106Space Temperature ArbitratorSpace temp determined by arbitration [Space Controller is Configured as Single or Dual Setpoint Zone Sensor]°FWrite
AV10107Space Static Pressure ArbitratorSpace static pressure value from a unit mounted sensor [StatiTrac Space Pressure Control configured.]in. w.c.Write
AV10108Space CO2 Concentration ArbitratorSpace CO2 concentration being used by the controller [CO2 Sensor Configured]ppmWrite
AV10109Space Humidity ArbitratorSpace relative humidity, determined by the arbitration [Space Humidity Sensor Configured]%Write
AV10113Outdoor Air Temperature BASUsed to send the outdoor air temperature sensor value°FWrite
AV10114Space Temperature BASUsed to send the space temperature value°FWrite
AV10116Outdoor Air Humidity BASUsed to send the outdoor air humidity sensor value%Write
AV10117Space Static Pressure BASBAS space static pressure sensor value [StatiTrac Space Pressure Control configured.]in. w.c.Write
AV10118Space CO2 Concentration BASUsed to send the space CO2 concentration value [CO2 Sensor Configured]ppmWrite
AV10119Space Humidity BASUsed to send the space relative humidity value [Space Humidity Sensor Configured]%Write
AV10121Discharge Air Cooling Setpoint BASUsed to request the discharge air temp cooling setpoint value [System Type is Configured as VVDA]°FCommand
AV10122Discharge Air Heating Setpoint BASUsed to request the discharge air temperature heating setpoint value°FCommand
AV10123Unoccupied Cooling SetpointUsed to define the cooling temp setpoint used for control in unoccupied°FWrite
AV10124Unoccupied Heating SetpointUsed to define the heating temp setpoint used for control in unoccupied°FWrite
AV10125Outdoor Air Minimum Flow Setpoint BASUsed to send the requested minimum OA flow setpoint [0 to 100% Economizer w/ TRAQ installed]cfmCommand
AVmin10127Space Temperature Setpoint BASBAS-supplied space temperature setpoint value [Space Controller Configured as Single Setpoint Zone Sensor]°FCommand
AV10128Space Static Pressure Setpoint BASSpace Static Pressure Setpoint [StatiTrac Space Pressure Control configured.]in. w.c.Command
AV10130Occupied OffsetDifference between the occ cool and heat setpts when a single setpointΔ°FWrite
AV10134Discharge Air Reheat Setpoint BASUsed to request the discharge air temperature reheat setpoint value°FCommand
AV10138Filter Runtime Hours SetpointSetpoint value used by the filter run hours calculationCommand
AV10139Cooling Capacity EnableUsed to limit the cooling capacity of the unit%Command
AV10140Heat Primary Enable BASUsed to demand limit the heating capacity; 0% = No Heating Possible%Command
AV10141Morning Warmup Setpoint BASDefines the space temp below which MWU is enabled°FCommand
AV10142Occupied Standby OffsetDifference between the occ standby cool and heat setpts when a singleΔ°FWrite
AV10143Duct Static Pressure Setpoint BASUsed to request the duct static pressure setpoint value [System Type is Configured as VVDA]in. w.c.Command
AV10144Economizer Minimum Position Setpoint BASUsed to request the ecominizer minimum position setpoint%Command
AV10149Daytime Warmup Setpoint BASDefines the space temp below which daytime warmup will be enabled°FCommand
AV10150Economizer Outdoor Air Enable Setpoint BASTemperature setpoint below which economizing can be used [Outside Air is Configured as 0-100%]°FCommand
AV10154Space Cooling Setpoint High Limit BASSpace Cooling Setpoint High Limit BAS°FWrite
AV10155Space Cooling Setpoint Low Limit BASSpace Cooling Setpoint Low Limit BAS°FWrite
AV10157Space Heating Setpoint High Limit BASSpace Heating Setpoint High Limit BAS°FWrite
AV10158Space Heating Setpoint Low Limit BASSpace Heating Setpoint Low Limit BAS°FWrite
AVmin10159Occupied Cooling Setpoint BASUsed to define the occ cooling setpt when both heat and cool°FCommand
AVmin10160Occupied Heating Setpoint BASUsed to define the occ heating setpt when both heat and cool°FCommand
AV10161Occupied Standby Cooling Setpoint BASDefines the occ standby cooling setpt when both heat/cool setpoints are provided°FCommand
AV10162Occupied Standby Heating Setpoint BASDefines the occ standby heating setpt when both heat/cool setpoints are provided°FCommand
AV10167Discharge Air Temperature Minimum Cool LimitUsed to define the discharge air temperature minimum cool limit°FCommand
AV10168Relief Enable Position SetpointOA damper position above which the Relief sequence is enabled [Space Pressure Control is Configured]%Command
AV10169Occupied Bypass TimeUsed to configure the occupied bypass time (occupancy override)Write
AV10170Economizer Outdoor Air Enthalpy Enable Setpoint BASUsed to determine the outdoor air enthalpy below which economizing is enabledBtu/lbCommand
AV10175Space CO2 High LimitUsed to define the CO2 high limit, for ventilation purposesppmCommand
AV10176Space CO2 Low LimitNormally provided by the BMS to define the CO2 low limitppmCommand
AV10214Space Dehumidification Unoccupied Setpoint ActiveActive value for Space Dehumidification Setpoint BAS point being used for control%Read
AV10228Space Dew Point Unoccupied Setpoint ActiveUnoccupied Space Dew Point Setpoint actively being used for dehumidification control°FRead
AV10281Discharge Air Temperature Setpoint ActiveDischarge air temp setpoint actively being used for control [System Type Configured as VVZTand]°FRead
AV11103Return Air Humidity BASBAS Source for Return Air Humidity [Economizer Type is Configured as Comparative Enthalpy]%Write
AV11104Run Time - Compressor 3 (Hours)Compressor 3 RuntimeRead
AV11105Starts - Compressor 3Compressor 3 StartsRead
AV11106Run Time - Condenser Fan 3 (Hours)Condenser Fan 3 RuntimeRead
AV11107Starts - Condenser Fan 3Condenser Fan 3 StartsRead
AV11108Cabinet StyleCabinet style of the unitRead
AV11110Supply Fan Speed CommandRemote supply fan speed request%Command
AV11112Cooling Capacity Setpoint BASRemote cooling capacity request%Command
AV11113Space Dehumidification Setpoint Offset BAS - ActiveActive value for the offset applied to the Space Dehumidification Setpoint%Read
AV11115Exhaust Or Return Fan TypeIdentifies the product exhaust or return fan typeRead
AV11116Filter Runtime HoursNumber of hours air has flowed through the filterRead
AV11117Outdoor Air Enthalpy ActiveOutdoor air enthalpy value being utilized by the unitBtu/lbRead
AV11118Return Air Temperature ArbitratorArbitrator for Return Air Temperature [Economizer Type is Configured as Comparative Enthalpy or Differential Drybulb]°FWrite
AV11119Return Air Temperature BASBAS source for Return Air Temperature [Economizer Type is Configured as Comparative Enthalpy or Differential Drybulb]°FWrite
AV11120Heating Demand Limit Capacity Enable SetpointHeating Demand Limit Capacity Enable Setpoint%Command
AV11121Discharge Air Temperature Maximum Cool LimitMaximum discharge air temperature allowed during space temperature cooling mode of operation°FCommand
AV11122Run Time - Condenser Fan 1 (Hours)Condenser Fan 1 RuntimeRead
AV11123Run Time - Condenser Fan 2 (Hours)Condenser Fan 2 Runtime [Dual Condenser Fan Systems]Read
AV11124Run Time - Relief Fan (Hours)Relief Fan Runtime [Space Pressure Control is Configured]Read
AV11125Run Time - Electric Heat Stage 1 (Hours)Electric Heat Stage 1 Runtime [One or more stages of Staged Electric Heat configured]Read
AV11126Run Time - Electric Heat Stage 2 (Hours)Electric Heat Stage 2 Runtime [Two or more stages of Staged Electric Heat configured]Read
AV11127Run Time - Supply Fan (Hours)Supply Fan RuntimeRead
AV11128Space Temp Cooling Setpoint StatusSpace cooling setpoint, determined by arbitration°FRead
AV11129Space Temp Heating Setpoint StatusSpace heating setpoint, determined by arbitration°FRead
AV11130Design Minimum OA Damper Position at Full Fan CapacityDesign Minimum OA Damper Position at Full Fan Capacity [Outside Air is Configured as 0-100%]%Command
AV11131Design Minimum OA Damper Position at Mid Fan CapacityDesign Minimum OA Damper Position at Mid Fan Capacity%Command
AV11132Design Minimum OA Damper Position at Min Fan CapacityDesign Minimum OA Damper Position at Min Fan Capacity%Command
AV11133DCV Minimum OA Damper Position at Full Fan CapacityDCV Minimum OA Damper Position at Full Fan Capacity%Command
AV11134DCV Minimum OA Damper Position at Mid Fan CapacityDCV Minimum OA Damper Position at Mid Fan Capacity%Command
AV11135DCV Minimum OA Damper Position at Min Fan CapacityDCV Minimum OA Damper Position at Min Fan Capacity%Command
AV11136Space Dehumidification Setpoint BAS - ActiveActive value for the Space Dehumidification Setpoint for Relative Humidity control%Read
AV11137Discharge Air Heating Setpoint High LimitDischarge Air Heating Setpoint High Limit (deg F) [VVZT and modulating gas heat installed]°FCommand
AV11138Discharge Air Heating Setpoint (Target)Discharge Air Heating Setpoint (Target) [VVZT and modulating gas heat installed]°FCommand
AV11140Discharge Air Cooling Setpoint (Target)Discharge Air Cooling Setpoint (Target)°FCommand
AV11142Space Static Pressure Setpoint DeadbandSpace Static Pressure Setpoint Deadband [StatiTrac Space Pressure Control configured.]in. w.c.Command
AV11143Design Min Outdoor Airflow SetpointDesign Minimum OA CFM Setpoint [0 to 100% Economizer w/ TRAQ and Demand Controlled Ventilation installed]cfmCommand
AV11144Standby Min Outdoor Airflow SetpointStandby Minimum OA CFM Setpoint [0 to 100% Economizer w/ TRAQ and Demand Controlled Ventilation installed]cfmCommand
AV11145DCV Min Outdoor Airflow SetpointDCV Minimum OA CFM Setpoint [0 to 100% Economizer w/ TRAQ and Demand Controlled Ventilation installed]cfmCommand
AV11147Economizer Dry Bulb Enable OffsetOutdoor air temperature offset below dry bulb economizer enable setpoint [Outside Air is Configured as 0-100%]Δ°FWrite
AV11148Duct Static Pressure P-Gain (%/IWC)Proportional gain for fan speed on duct static pressure control (%/IWC) [System Type Configured as VVDA]%Write
AV11149Duct Static Pressure Deadband BASSupply Air Pressure Setpoint Deadband [System Type Configured as VVDA]in. w.c.Command
AV11150Cooling Reset Start TempDischarge air cooling reset start temperature [System Type Configured as VVDA]°FWrite
AV11151Cooling Reset End TempDischarge air cooling reset end temperature [System Type Configured as VVDA]°FWrite
AV11152Cooling Reset AmountDischarge air cooling amount to reset between start and end temperatures [System Type Configured as VVDA]Δ°FWrite
AV11153Service Test Timeout (Minutes)Timer (minutes) to indicate when the unit should cease service testWrite
AV11154Economizer Cooling Reference Enthalpy OffsetEconomizer Cooling Reference Enthalpy Offset [Economizer Type is Configured as Comparative Enthalpy or Reference Enthalpy]Btu/lbWrite
AV11155Starts - Condenser Fan 1Condenser Fan 1 StartsRead
AV11156Starts - Condenser Fan 2Condenser Fan 2 Starts [Dual Condenser Fan Systems]Read
AV11157Starts - Relief FanRelief Fan Starts [Space Pressure Control is Configured]Read
AV11158Starts - Electric Heat Stage 1Electric Heat Stage 1 Starts [One or more stages of Staged Electric Heat configured]Read
AV11159Starts - Electric Heat Stage 2Electric heat stage 2 starts [Two or more stages of Staged Electric Heat configured]Read
AV11160Starts - Supply FanCounter for supply fan startsRead
AV11161Supply Fan TypeUnit supply fan typeRead
AV11163Supply Fan Speed StatusEstimated supply fan speed being utilized%Read
AV11164Heating Capacity Setpoint BASSetpoint to command the unit to a given heating capacity output [Primary Heating Source Configured]%Command
AV11167Demand Shed Offset SetpointDemand Shed Offset Setpoint [Demand Management Configured as Demand Shed]Δ°FCommand
AV11168Cooling Demand Limit Capacity Enable SetpointCooling Demand Limit Capacity Enable Setpoint [Demand Management Configured as Demand Limit]%Command
AV11169Run Time - Compressor 1 (Hours)Compressor 1 RuntimeRead
AV11170Run Time - Compressor 2 (Hours)Compressor 2 Runtime [Multi-Compressor Systems]Read
AV11173Supply Fan Minimum Speed SetpointMinimum supply fan speed command [Indoor Fan Type Configured as Multi Speed or Variable Speed]%Command
AV11174Supply Fan Maximum Speed SetpointMaximum supply fan speed command [Indoor Fan Type Configured as Multi Speed or Variable Speed]%Command
AVmin11178Space Temperature ActiveActive space temperature being used by the controller°FRead
AV11180Space Temperature Heating Setpoint Input ActiveActive heating space temperature input setpoint as determined by arbitrating the heating°FRead
AV11181Space Temperature Setpoint ActiveActive space temperature setpoint being used by the controller°FRead
AV11183Starts - Compressor 1Compressor 1 StartsRead
AV11184Starts - Compressor 2Compressor 2 Starts [Multi-Compressor Systems]Read
AV11185Cooling Capacity Enable - ActiveActive value for Cooling Capacity Enable point being used for control%Read
AV11186Daytime Warmup Setpoint BAS - ActiveActive value for Daytime Warmup Setpoint BAS point being used for control°FRead
AV11187Supply Fan Speed Command - ActiveActive value for Supply Fan Speed Command point being used for control%Read
AV11189Cooling Capacity Setpoint BAS - ActiveActive value for Cooling Capacity Setpoint BAS point being used for control%Read
AV11190Discharge Air Cooling Setpoint BAS - ActiveActive value for Discharge Air Cooling Setpoint BAS point being used for°FRead
AV11191Discharge Air Heating Setpoint BAS - ActiveActive value for Discharge Air Heating Setpoint BAS point being used for°FRead
AV11192Discharge Air Reheat Setpoint BAS - ActiveActive value for Discharge Air Reheat Setpoint BAS point being used for°FRead
AV11193Discharge Air Temperature Minimum Cool Limit - ActiveActive value for Discharge Air Temperature Minimum Cool Limit point being used°FRead
AV11195Economizer Minimum Position Setpoint BAS - ActiveActive value for Economizer Minimum Position Setpoint BAS point being used for%Read
AV11196Economizer Outdoor Air Enthalpy Enable Setpoint BAS - ActiveActive value for Economizer Outdoor Air Enthalpy Enable Setpoint BA point beingBtu/lbRead
AV11197Economizer Outdoor Air Enable Setpoint BAS - ActiveActive value for Economizing Outdoor Air Enable Setpoint point being used for°FRead
AV11198Relief Enable Position Setpoint - ActiveActive value for Relief Enable Position Setpoint point being used for control%Read
AV11199Heating Demand Limit Capacity Enable Setpoint - ActiveActive value for Heating Demand Limit Capacity Enable Setpoint point being used%Read
AV11200Discharge Air Temperature Maximum Cool Limit - ActiveActive value for Discharge Air Temperature Maximum Cool Limit point being used°FRead
AV11202Cool TypeType of cooling in the unitRead
AV11203DCV Min Outdoor Airflow Setpoint - ActiveActive value for DCV Minimum OA CFM Setpoint point being used forcfmRead
AV11204DCV Minimum OA Damper Position at Full Fan Capacity - ActiveActive value for DCV Minimum OA Damper Position at Full Fan Capacity%Read
AV11205DCV Minimum OA Damper Position at Mid Fan Capacity - ActiveActive value for DCV Minimum OA Damper Position at Mid Fan Capacity%Read
AV11206DCV Minimum OA Damper Position at Min Fan Capacity - ActiveActive value for DCV Minimum OA Damper Position at Min Fan Capacity%Read
AV11209Demand Shed Offset Setpoint - ActiveActive value for Demand Shed Offset Setpoint point being used for controlΔ°FRead
AV11210Design Min Outdoor Airflow Setpoint - ActiveActive value for Design Minimum OA CFM Setpoint point being used forcfmRead
AV11211Design Minimum OA Damper Position at Full Fan Capacity - ActiveActive value for Design Minimum OA Damper Position at Full Fan Capacity%Read
AV11212Design Minimum OA Damper Position at Mid Fan Capacity - ActiveActive value for Design Minimum OA Damper Position at Mid Fan Capacity%Read
AV11213Design Minimum OA Damper Position at Min Fan Capacity - ActiveActive value for Design Minimum OA Damper Position at Min Fan Capacity%Read
AV11214Economizer Dry Bulb Disable Return Air OffsetDifferential dry bulb economizer disable offset [Outside Air is Configured as 0-100%]Δ°FWrite
AV11217Filter Runtime Hours Setpoint - ActiveFilter runtime hours setpoint in useRead
AV11218Heat Primary Enable BAS - ActiveHeat primary enable value in use [Primary Heating Source]%Read
AV11219Heating Capacity Setpoint BAS - ActiveActive value for Heating Capacity Setpoint BAS point being used for control [Primary Heating Source Configured]%Read
AV11220Morning Warmup Setpoint BAS - ActiveActive value for Morning Warmup Setpoint BAS point being used for control°FRead
AV11222Outdoor Air Minimum Flow Setpoint BAS - ActiveActive value for Outdoor Air Minimum Flow Setpoint BAS point being usedcfmRead
AV11226Space CO2 High Limit - ActiveActive value for Space CO2 High Limit point being used for controlppmRead
AV11227Space CO2 Low Limit - ActiveActive value for Space CO2 Low Limit point being used for controlppmRead
AV11229Space Static Pressure Setpoint Deadband - ActiveActive value for Space Static Pressure Setpoint Deadband point being used forin. w.c.Read
AV11231Standby Min Outdoor Airflow Setpoint - ActiveActive value for Standby Minimum OA CFM Setpoint point being used forcfmRead
AV11236Discharge Air Cooling Setpoint (Target) - ActiveActive value for Discharge Air Cooling Setpoint (Target) point being used for°FRead
AV11237Discharge Air Heating Setpoint High Limit - ActiveActive value for Discharge Air Heating Setpoint High Limit point being used°FRead
AV11238Duct Static Pressure Reset Time (seconds)Reset time for fan speed on duct static pressure control (seconds) [System Type Configured as VVDA]Write
AV11240Duct Static Pressure Deadband ActiveActive value for Supply Air Pressure Setpoint Deadband point being used forin. w.c.Read
AV11241Heating Reset Start TempDischarge air heating reset start temperature [Heating is Installed and System Type is Configured as VVDA]°FWrite
AV11242Heating Reset End TempDischarge air heating reset end temperature [Heating is Installed and System Type is Configured as VVDA]°FWrite
AV11243Supply Fan Maximum Speed Setpoint - ActiveActive value for Supply Fan Maximum Speed Setpoint point being used for%Read
AV11244Supply Fan Maximum Output Frequency StatusActive value for Supply Fan Maximum Output Frequency point being used forRead
AV11245Supply Fan Minimum Speed Setpoint - ActiveActive value for Supply Fan Minimum Speed Setpoint point being used for%Read
AV11246Supply Fan Minimum Output Frequency StatusActive value for Supply Fan Minimum Output Frequency point being used forRead
AV11247Cooling Demand Limit Capacity Enable Setpoint - ActiveActive value for Cooling Demand Limit Capacity Enable Setpoint point being used%Read
AV11248Economizer Minimum Position Setpoint ActiveEconomizer min position setpoint value resulting from arbitration%Read
AV11249Heating Capacity Secondary StatusUnit secondary heating capacity being utilized [Secondary Heating Source Configured]%Read
AV11250Occupied Standby Cooling Setpoint BAS - ActiveActive value for Occupied Standby Cooling Setpoint BAS°FRead
AV11251Occupied Standby Heating Setpoint BAS - ActiveActive value for Occupied Standby Heating Setpoint BAS°FRead
AV11252Preheat TypeIdentifies the product preheat typeRead
AV11253Reheat TypeIdentifies the product reheat typeRead
AV11254Space CO2 Concentration ActiveActive space CO2 concentration being used by the controller [CO2 Sensor Configured]ppmRead
AV11256Compressor Cooling P-Gain (%/F)Compressor cooling PI gain; row repeated per control type%Write
AV11257Compressor Cooling Reset Time (seconds)Compressor cooling PI reset time; row repeated per control typeWrite
AV11258Economizer Cooling P-Gain - 1 (%/F)Proportional gain for 1st loop Econ PI controller (%/F), for CVZT/VVZT systems%Write
AV11259Economizer Cooling Reset Time - 1 (Seconds)Reset time for 1st loop Econ PI controller (seconds), for CVZT/VVZT systemsWrite
AV11266Auxiliary Heating P-Gain (%/F)Auxiliary heat PI gain; meaning varies by heat type%Write
AV11267Auxiliary Heating Reset Time (seconds)Auxiliary heat PI reset time; meaning varies by heat typeWrite
AV11268Compressor Cooling P-Gain - 1 (%/F)Proportional gain for 1st loop Cooling PI controller (%/F)%Write
AV11269Compressor Cooling Reset Time - 1 (seconds)Reset time for 1st loop Cooling PI controller (second)Write
AV11270Compressor Cooling P-Gain - 2 (%/F)Proportional gain for 2nd loop compressor cooling PI controller (%/F)%Write
AV11271Compressor Cooling Reset Time - 2 (seconds)Reset time for 2nd loop compressor cooling PI controller (second)Write
AV11272Economizer Discharge Air SetpointDischarge Air Setpoint selection to be used for Economizer control on Conventional°FCommand
AV11273Economizer Discharge Air Setpoint - ActiveActive Discharge Air Setpoint used for Economizer control on Conventional Thermostat controlled°FRead
AV11276Space Temperature Setpoint Input ActiveActive space temperature input setpoint as determined by arbitrating the space temperature°FRead
AV11277Space Temperature Cooling Setpoint Input ActiveActive cooling space temperature input setpoint as determined by arbitrating the cooling°FRead
AV11278Supply Fan PowerSupply Fan Drive Output Power [Indoor Fan Type Configured as Multi Speed or Variable Speed]kWRead
AV11279Supply Fan CurrentSupply Fan Drive Output Current [Indoor Fan Type Configured as Multi Speed or Variable Speed]ARead
AV11280Duct Static Pressure Setpoint ActiveDuct static pressure control setpoint value resulting from arbitration [System Type Configured as VVDA]in. w.c.Read
AV11281Dehumidification Control StatusStatus of the unit dehumidification capacity [Hot Gas Reheat is Configured as Installed]%Read
AV11286Motorized Damper Position SetpointMotorized Damper Position Setpoint [Outside Air is Configured as 0-50% Motorized Damper]%Command
AV11287Motorized Damper Position Setpoint - ActiveActive value for Motorized Damper Position Setpoint [Outside Air is Configured as 0-50% Motorized Damper]%Read
AV11288Standby Minimum OA Damper Position at Full Fan CapacityStandby Minimum OA Damper Position at Full Fan Capacity%Command
AV11289Standby Minimum OA Damper Position at Full Fan Capacity - ActiveActive value for Standby Minimum OA Damper Position at Full Fan Capacity%Read
AV11290Standby Minimum OA Damper Position at Mid Fan CapacityStandby Minimum OA Damper Position at Mid Fan Capacity%Command
AV11291Standby Minimum OA Damper Position at Mid Fan Capacity - ActiveActive value for Standby Minimum OA Damper Position at Mid Fan Capacity%Read
AV11292Standby Minimum OA Damper Position at Min Fan CapacityStandby Minimum OA Damper Position at Min Fan Capacity%Command
AV11293Standby Minimum OA Damper Position at Min Fan Capacity - ActiveActive value for Standby Minimum OA Damper Position at Min Fan Capacity%Read
AV11299Return Air Humidity ActiveActive Return Air Humidity sensor used for control [Economizer Type is Configured as Comparative Enthalpy]%Read
AV11300Return Air Humidity ArbitratorArbitrator for Return Air Humidity [Economizer Type is Configured as Comparative Enthalpy]%Write
AV11301Return Air Enthalpy ActiveReturn air enthalpy value being utilized by the unit [Economizer Type is Configured as Comparative Enthalpy]Btu/lbRead
AV11302Relief Enable Position Setpoint StatusOutdoor air damper position to enable Relief sequence [Space Pressure Control is Configured]%Read
AV11307Discharge Air Heating Setpoint (Target) - ActiveActive value for Discharge Air Heating Setpoint (Target) point being used for°FRead
AV11308Duct Static Pressure Setpoint High Limit Setpoint BASDuct Static Pressure Setpoint High Limit is used to limit fan speedin. w.c.Command
AV11309Duct Static Pressure Setpoint High Limit Setpoint BAS - ActiveActive Duct Static Pressure Setpoint High Limit is used to limit fanin. w.c.Read
AV11314Comfort Purge Interval (minutes)User adjustable setpoint used to set the amount of time the compressorWrite
AV11315Reheat Purge Interval (minutes)User adjustable setpoint used to set the amount of time the compressorsWrite
AV11316Reheat P-Gain 1Proportional gain for 1st loop Reheat PI controller (%/F)%Write
AV11317Reheat Reset Time - 1Reset time for 1st loop Reheat PI controller (second)Write
AV11318Reheat P-Gain 2Proportional gain for 2nd loop Reheat PI controller (%/F)%Write
AV11319Reheat Reset Time - 2Reset time for discharge air Reheat PI controller (second)Write
AV11320Space Dew Point Setpoint BASUser adjustable setpoint used to set the maximum Space Dew Point Setpoint°FCommand
AV11321Dew Point Setpoint Offset BASUser adjustable setpoint used to set the maximum Space Dew Point Setpoint°FCommand
AV11323Outdoor Air Dew Point Setpoint BASUser adjustable setpoint used to set the Outdoor Air Dew Point Setpoint°FCommand
AV11325Space Static Pressure Setpoint ActiveActive space static pressure being used by the controller [StatiTrac Space Pressure Control configured.]in. w.c.Read
AV11326Space Dehumidification Setpoint Offset BASSetting for unit to use for applying a % offset to the%Command
AV11327Space Dehumidification Setpoint BASSetting for unit to use to control dehumidification [Hot Gas Reheat is Configured as Installed]%Command
AV11329Space Dehumidification Unoccupied Setpoint BASUsed to define the (occupied) space dehumidification setpoint%Command
AV11330Space Dew Point Unoccupied Setpoint BASUser adjustable setpoint used to set the maximum Space Dew Point Unoccupied°FCommand
AV11331Compressor Dehumid P-Gain 2Proportional Gain for 2nd loop Compressor Dehumid PI controller (%/deg F)°FWrite
AV11332Compressor Dehumid P-Gain 1Proportional gain for 1st loop Compressor Dehumid PI controller (%/F)°FWrite
AV11333Compressor Dehumid Reset Time - 2 (seconds)Reset time for 2nd loop compressor Dehumid PI controller (second)Write
AV11334Compressor Dehumid Reset Time - 1 (seconds)Reset time for 1st loop Dehumid PI controller (second) [Hot Gas Reheat is configured as Installed]Write
AV11335Pre Cool Setpoint BASDefines the space temp above which Pre Cool is enabled°FCommand
AV11336Pre Cool Setpoint BAS - ActiveActive value for Pre Cool Setpoint BAS point being used for control°FRead
AV11337Refrigerant Target Setpoint ActiveRefrigerant target setpoint actively being used for dehumidification control [Hot Gas Reheat is Configured as installed]°FRead
AV11338Space Dew Point Setpoint ActiveOccupied Space Dew Point Setpoint actively being used for dehumidification control°FRead
AV11340Dew Point Setpoint Offset BAS - ActiveDew Point Setpoint Offset actively being used for dehumidification control°FRead
AV11341Outdoor Air Dew Point Setpoint BAS - ActiveOutdoor Air Dew Point Setpoint Offset actively being used for dehumidification control°FRead
AV11342Unoccupied Dehumidification TimerUser adjustable time the space relative humidity is controlled <65% in unoccupiedWrite
AV11343Heating Reset AmountDischarge air heating amount to reset between start and end temperaturesΔ°FWrite
AV11344VAV Box Stroke TimerUser adjustable VAV Box Stroke time that should be allowed for fullWrite
AV11346Economizer Cooling P-Gain (%/F)Proportional gain for VVDA systems Econ PI controller (%/F)%Write
AV11347Economizer Cooling Reset Time (Seconds)Reset time for VVDA systems Econ PI controller (in seconds)Write
AV11348Economizer Cooling P-Gain - 2 (%/F)Proportional gain for 2nd loop Econ PI controller (%/F), for CVZT/VVZT systems%Write
AV11349Economizer Cooling Reset Time - 2 (Seconds)Reset time for 2nd loop Econ PI controller (seconds), for CVZT/VVZT systemsWrite
AV11350Auxiliary Heating P-Gain - 1 (%/F)Space control proportional gain for 1st loop Heating PI controller (%/F)%Write
AV11351Auxiliary Heating Reset Time - 1 (seconds)Space control reset Time for 1st loop Auxiliary Heating PI Controller (inWrite
AV11352Auxiliary Heating P-Gain - 2 (%/F)Space control proportional gain for 2nd loop Heating PI controller (%/F)%Write
AV11353Auxiliary Heating Reset Time - 2 (seconds)Space control reset Time for 2nd loop Auxiliary Heating PI Controller (inWrite
AV11354Discharge Air Heating Setpoint Low LimitDischarge Air Heating Setpoint Low Limit (deg F)°FCommand
AV11355Discharge Air Heating Setpoint Low Limit - ActiveActive value for Discharge Air Heating Setpoint Low Limit point being used°FRead
AV11356Discharge Air Cooling Setpoint StatusActual discharge air cooling setpoint value being used for control [System Type is Configured as VVDA]°FRead
AV11357Discharge Air Heating Setpoint StatusActual discharge air heating setpoint value being used for control°FRead
AV11358Discharge Air Reheating Setpoint High Limit - ActiveActive value for Discharge Air Reheating Setpoint High Limit point being used°FRead
AV11359Discharge Air Reheating Setpoint Low Limit - ActiveActive value for Discharge Air Reheating Setpoint Low Limit point being used°FRead
AV11360Discharge Air Reheating Setpoint High LimitDischarge Air Reheating Setpoint High Limit (deg F)°FCommand
AV11361Discharge Air Reheating Setpoint Low LimitDischarge Air Reheating Setpoint Low Limit (deg F)°FCommand
AV11362Run Time - Gas Heat Manifold 1 Burner 1 (Hours)Gas heat runtimeRead
AV11363Starts - Gas Heat Manifold 1 Burner 1Gas heat startsRead
AV11364Run Time - Gas Heat Manifold 1 Burner 2 (Hours)Gas heat runtime [Gas Heat is installed with a second gas valve on manifold 1.]Read
AV11365Starts - Gas Heat Manifold 1 Burner 2Gas heat starts [Gas Heat is installed with a second gas valve on manifold 1.]Read
AV11366Run Time - Gas Heat Manifold 2 Burner 1 (Hours)Gas heat runtimeRead
AV11367Starts - Gas Heat Manifold 2 Burner 1Gas heat startsRead
AV11368Auxiliary Heating P-Gain Modulating Gas Staging (%/F)Proportional gain for 2nd loop-Staging control for Modulating Gas Heating [Modulating gas heat is configured]%Write
AV11369Auxiliary Heating Reset Time Modulating Gas Staging (seconds)Reset Time for 2nd loop-Staging control for Modulating Gas Heating [Modulating gas heat is configured]Write
AV11370Outdoor Airflow Calibration GainOutdoor airflow Traq measurement Calibration Gain [Outside Air Configured as 0% to 100% w/ TRAQ]Write
AV11371Outdoor Airflow Calibration OffsetOutdoor airflow Traq measurement calibration Offset [Outside Air Configured as 0% to 100% w/ TRAQ]Write
AV11372Outdoor Airflow P-Gain (%/CFM)Proportional gain for outdoor airflow Traq Minimum Position Control%Write
AV11373Outdoor Airflow Reset Time (Seconds)Reset time for Outdoor airflow Traq Minimum Position ControlWrite
AV11374Local Atmospheric PressureLocal atmospheric pressure [Outside Air Configured as 0% to 100% w/ TRAQ]psiWrite
AV11379Space Pressure Control P-Gain (%/IWC)Proportional gain for building static space pressure control [StatiTrac Space Pressure Control configured.]%Write
AV11380Space Pressure Control Reset Time (Seconds)Reset time for building static space pressure control [StatiTrac Space Pressure Control configured.]Write
AV11381Space Pressure Control Feed Forward GainFeed Forward gain for building static space pressure control [StatiTrac Space Pressure Control configured.]%Write
AV11382Relief Air Damper Minimum Position SetpointRelief Air Damper Minimum Position Setpoint [StatiTrac Space Pressure Control configured.]%Write
AV11383Condenser Fan CapacityStatus of the total unit condenser fan capacity%Read
AV11388Control StateControl State StatusRead
BI10105FDD: Unit Economizing When It Should NotDiagnostic: Unit Economizing When It Should Not [Outside Air is Configured as 0-100% Economizer]Readfalse = Inactive, true = Active
BI10106FDD: Unit Not Economizing When It ShouldDiagnostic: Unit Not Economizing When It Should [Outside Air is Configured as 0-100% Economizer]Readfalse = Inactive, true = Active
BI10107FDD: Excessive Outdoor AirDiagnostic: Excessive Air [Outside Air is Configured as 0-100% Economizer]Readfalse = Inactive, true = Active
BI10108FDD: Outdoor Air Damper Not ModulatingDiagnostic: Damper NOT Modulating [Outside Air is Configured as 0-100% Economizer]Readfalse = Inactive, true = Active
BI10121Relief Fan Output StatusStatus of the Relief fan output on the controller [Space Pressure Control is Configured]Readfalse = Off, true = On
BI10143VAV Box CommandWhether the associated VAV boxes should be AUTO or forced openReadfalse = Off, true = On
BI10170Condensate Overflow InputStatus of the condensate overflow input [Condensate Overflow Switch is Configured as Installed]Readfalse = Open, true = Closed
BI10172Occupancy InputStatus of the wired occupancy inputReadfalse = Occupied, true = Unoccupied
BI10210Equipment Shutdown Input StatusStatus of the equipment shutdown function of the unitReadfalse = Equipment Run, true = Equipment Shutdown
BI10211External Auto Stop Input StatusStatus of the externally-wired auto/stop input [External Auto/Stop Configured as Installed]Readfalse = Stop, true = Auto
BI10219Economizer Airside StatusStatus of airside economizing [Outside Air is Configured as 0-100%]Readfalse = Inactive, true = Active
BImin10226Supply Fan StatusStatus of the supply fan output of the controllerReadfalse = Off, true = On
BI11100Compressor 1 Command StatusCompressor 1 Run Command Status [Efficiency is not Configured as High]Readfalse = Off, true = On
BI11101Circuit 1 LPC StatusCircuit 1 LPC Input StatusReadfalse = Open, true = Closed
BI11102Compressor 1 Proving StatusStatus of input for monitoring Compressor 1 proof of operation circuitReadfalse = Not Proved, true = Proved
BI11103Compressor 2 Command StatusCompressor 2 Run Command Status [Multi-Compressor Systems]Readfalse = Off, true = On
BI11105Compressor 2 Proving StatusStatus of input for monitoring Compressor 2 proof of operation circuit [Multi-Compressor Systems]Readfalse = Not Proved, true = Proved
BI11106Compressor 3 Command StatusCompressor 3 Run Command StatusReadfalse = Off, true = On
BI11108Compressor 3 Proving StatusStatus of input for monitoring Compressor 3 proof of operation circuitReadfalse = Not Proved, true = Proved
BI11113Demand Limit InputConfigurable, hardwired input to command Demand Limit [Demand Management Configured as Demand Limit]Readfalse = Not Limited, true = Limited
BI11114Demand Shed InputConfigurable, hardwired input to command Demand Shed [Demand Management Configured as Demand Shed]Readfalse = Off, true = On
BI11115Phase Monitor StatusStatus of local Phase Monitor InputReadfalse = Tripped, true = Okay
BI11116Condenser Fan 1 Command StatusCondenser Fan 1 Run Command StatusReadfalse = Off, true = On
BI11117Condenser Fan 2 Command StatusCondenser Fan 2 Run Command Status [Dual Condenser Fan Systems]Readfalse = Off, true = On
BI11120Thermostat G InputThermostat Fan Request [Space Controller Configured as Conventional TStat]Readfalse = Open, true = Closed
BI11121Thermostat W1/O InputThermostat Heat Stage 1 Request or Thermostat Heat/Cool Mode Request for HPReadfalse = Open, true = Closed
BI11122Thermostat W2 InputThermostat Heat Stage 2 Request (or Emergency Heat) [Space Controller Configured as Conventional TStat]Readfalse = Open, true = Closed
BI11123Thermostat X2 InputThermostat Emergency Heat Request [Space Controller Configured as Conventional TStat]Readfalse = Open, true = Closed
BI11124Thermostat Y1 InputThermostat Compressor Stage 1 Request [Space Controller Configured as Conventional TStat]Readfalse = Open, true = Closed
BI11125Thermostat Y2 InputThermostat Compressor Stage 2 Request [Space Controller Configured as Conventional TStat]Readfalse = Open, true = Closed
BI11127FroStat InputStatus of Hardwired Frostat Input [FroStat Configured as Installed]Readfalse = Open, true = Closed
BI11128Electric Heat Stage 1 StatusStatus of Electric Heat Stage 1 command [One or more stages of Staged Electric Heat configured]Readfalse = Off, true = On
BI11129Electric Heat Stage 2 StatusStatus of Electric Heat Stage 2 command [Two or more stages of Staged Electric Heat configured]Readfalse = Off, true = On
BI11130Clogged Filter InputStatus of Hardwired Clogged Filter Input [Clogged Filter Configured as Installed]Readfalse = Clean, true = Dirty Filter
BI11131Condenser Fan 3 Command StatusCondenser Fan 3 Run Command StatusReadfalse = Off, true = On
BI11133Ventilation Override Exhaust StatusHardwired input VOM Exhaust [Ventilation Override Configured as Installed]Readfalse = Open, true = Closed
BI11134Ventilation Override Pressurize StatusHardwired input VOM Pressurize [Ventilation Override Configured as Installed]Readfalse = Open, true = Closed
BI11135Ventilation Override Purge StatusHardwired input VOM Purge [Ventilation Override Configured as Installed]Readfalse = Open, true = Closed
BI11143Reheat Humidistat InputHardwired input to support dehumidification requests on hot gas reheat units [Humidistat is Configured as Installed]Readfalse = Open, true = Closed
BI11144Diagnostic: VFD Fault Supply Fan - 1Diagnostic: VFD Fault Supply Fan - 1Readfalse = Inactive, true = Active
BI11145Diagnostic: VFD Supply Fan Ground Fault - 1Diagnostic: VFD Supply Fan Ground Fault - 1Readfalse = Inactive, true = Active
BI11147Diagnostic: VFD Supply Fan Motor Current Overload - 1Diagnostic: VFD Supply Fan Motor Current Overload - 1Readfalse = Inactive, true = Active
BI11148Diagnostic: VFD Supply Fan Short Circuit - 1Diagnostic: VFD Supply Fan Short Circuit - 1Readfalse = Inactive, true = Active
BI11149Fan Mode - Air-FiSupply Fan Mode as set from a wireless sensor connected to theReadfalse = Cycling, true = Continuous
BI11150Occupancy Input - Air-FiLocal Occupancy Input as detected by a wireless sensor connected to theReadfalse = Occupied, true = Unoccupied
BI11151Fan Mode InputSupply Fan Mode as set from a wired sensor connected to theReadfalse = Cycling, true = Continuous
BI11154Gas Heat Stage 1 StatusStatus of gas heat Stage 1Readfalse = Off, true = On
BI11155Gas Heat Stage 2 StatusStatus of gas heat Stage 2Readfalse = Off, true = On
BI11187Reheat Pumpout Solenoid StatusReheat Pumpout Solenoid IMC Command Status [Hot Gas Reheat is Configured as Installed]Readfalse = Off, true = On
BI11188Reheat Valve 2 Fault StatusReheat Valve 2 (Cooling) Fault Status [Hot Gas Reheat is Configured as Installed]Readfalse = Inactive, true = Active
BI11189Reheat Valve 1 Fault StatusReheat Valve 1 Fault Status [Hot Gas Reheat is Configured as Installed]Readfalse = Inactive, true = Active
BI11190Reheat Valve 1 Calibration StatusReheat Valve 1 Calibration Status from Stepper Motor Module [Hot Gas Reheat is Configured as Installed]Readfalse = Inactive, true = Active
BI11191Reheat Valve 2 Calibration StatusReheat Valve 2 (Cooling) Calibration Status from Stepper Motor ModuleReadfalse = Inactive, true = Active
BI11192VAV Changeover InputVAV Changeover Request [System Type is Configured as VVDA]Readfalse = Open, true = Closed
BI11194Diagnostic: VFD Supply Fan Broken Belt - 1Diagnostic: VFD Supply Fan Broken Belt - 1Readfalse = Inactive, true = Active
BI11195Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 1Modulating gas heat ignition controller [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11196Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 2Modulating gas heat ignition controller [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11197Diagnostic: Modulating Gas Invalid ID Plug Manifold 1Gas heat ignition controller detected an invalid or failed ID Plug [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11198Diagnostic: Modulating Gas Heat Configuration InvalidUnit controller configuration does not match gas heat ignition controller ID PlugReadfalse = Inactive, true = Active
BI11199Diagnostic: Gas Heat Weak Flame Manif 1 Burner 1Weak flame or aged flame rod detected on burner 1 [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11200Diagnostic: Gas Heat Weak Flame Manif 1 Burner 2Weak flame or aged flame rod detected on burner 2 [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11201Diagnostic: Gas Heat Insufficient Combustion AirGas heat is being derated/reduced due to insufficient combustion air [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11202Diagnostic: Modulating Gas Primary Limit Open Manifold 1Gas heat failure, primary limit detected open [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11203Diagnostic: Modulating Gas Heat Open Fuse Manifold 1Gas heat failure, fuse detected open [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11204Diagnostic: Gas Heat Failed Ignition Manifold 1Gas heat is locked out for one hour due to failed ignitionReadfalse = Inactive, true = Active
BI11205Diagnostic: Modulating Gas Valve Failure Manifold 1Modulating gas valve did not reach park or full On position [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11206Diagnostic: Modulating Gas Control Board Failure Manifold 1Ignition control board failure during startup self test [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11207Diagnostic: Gas Heat Unexpected Flame Manifold 1Staged gas heat ignition controller [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11208Diagnostic: Staged Gas Heat Invalid ID Plug Manifold 1Gas heat ignition controller detected an invalid or failed ID Plug [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11209Diagnostic: Staged Gas Heat Configuration Invalid Manifold 1Unit controller configuration does not match gas heat ignition controller ID PlugReadfalse = Inactive, true = Active
BI11210Diagnostic: Staged Gas Heat Primary Limit Open Manifold 1Gas heat failure, primary limit detected open [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11211Diagnostic: Staged Gas Heat Open Fuse Manifold 1Gas heat failure, fuse detected open [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11212Diagnostic: Heat Failed Ignition Manifold 1Gas heat is locked out for one hour due to failed ignitionReadfalse = Disabled, true = Enabled
BI11213Diagnostic: Staged Gas Heat Valve Failure Manifold 1Gas valve state is low when it should be high [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11214Diagnostic: Gas Heat Inducer High Pressure Manifold 1Gas heat inducer air pressure switch high is open when it isReadfalse = Inactive, true = Active
BI11215Diagnostic: Gas Heat Valve Short Manifold 1Gas heat valve shorted to 24V, ignition control failure or faulty wiringReadfalse = Inactive, true = Active
BI11216Diagnostic: Gas Heat Flame Loss Manifold 1Gas heat locked out due to flame loss occurring three times [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11217Diagnostic: Staged Gas Heat Control Board Failure Manifold 1Ignition control board failure during startup self test [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11218Diagnostic: Gas Heat Start Failure Manifold 1Ignition controller checks at startup failed or flame circuitry idle state isReadfalse = Inactive, true = Active
BI11219Diagnostic: Gas Heat Unexpected Flame Manifold 2Staged gas heat ignition controllerReadfalse = Inactive, true = Active
BI11220Diagnostic: Staged Gas Heat Invalid ID Plug Manifold 2Gas heat ignition controller detected an invalid or failed ID PlugReadfalse = Inactive, true = Active
BI11221Diagnostic: Staged Gas Heat Configuration Invalid Manifold 2Unit controller configuration does not match gas heat ignition controller ID PlugReadfalse = Inactive, true = Active
BI11222Diagnostic: Staged Gas Heat Primary Limit Open Manifold 2Gas heat failure, primary limit detected openReadfalse = Inactive, true = Active
BI11223Diagnostic: Staged Gas Heat Open Fuse Manifold 2Gas heat failure, fuse detected openReadfalse = Inactive, true = Active
BI11224Diagnostic: Heat Failed Ignition Manifold 2Gas heat is locked out for one hour due to failed ignitionReadfalse = Inactive, true = Active
BI11225Diagnostic: Staged Gas Heat Valve Failure Manifold 2Gas valve state is low when it should be highReadfalse = Inactive, true = Active
BI11226Diagnostic: Gas Heat Inducer High Pressure Manifold 2Gas heat inducer air pressure switch high is open when it isReadfalse = Inactive, true = Active
BI11227Diagnostic: Gas Heat Valve Short Manifold 2Gas heat valve shorted to 24V, ignition control failure or faulty wiringReadfalse = Inactive, true = Active
BI11228Diagnostic: Gas Heat Flame Loss Manifold 2Gas heat locked out due to flame loss occurring three timesReadfalse = Inactive, true = Active
BI11229Diagnostic: Staged Gas Heat Control Board Failure Manifold 2Ignition control board failure during startup self testReadfalse = Inactive, true = Active
BI11230Diagnostic: Gas Heat Start Failure Manifold 2Ignition controller checks at startup failed or flame circuitry idle state isReadfalse = Inactive, true = Active
BI11231Diagnostic: Gas Heat Lockout Manifold 1Gas heat ignition controller locked out (modulating or staged gas)Readfalse = Inactive, true = Active
BI11232Diagnostic: Gas Heat Lockout Manifold 2Staged gas heat ignition controller is operation locked out on manifold 2Readfalse = Inactive, true = Active
BI11233Diagnostic: Gas Heat Flame Rod Aged Manifold 1Weak flame or aged flame rod detected on manifold 1 [Staged Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11234Diagnostic: Gas Heat Flame Rod Aged Manifold 2Weak flame or aged flame rod detected on manifold 1 [800 MBH Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11235Diagnostic: Gas Heat Failed Ignition Manifold 1 Burner 2Modulating gas heat ignition controller burner 2 operation failed ignition [Modulating gas heat configured]Readfalse = Inactive, true = Active
BI11236Reheat LPC StatusReheat LPC Status [Modulating Hot Gas Reheat on Voyager 3]Readfalse = Open, true = Closed
BI11241Diagnostic: Gas Heat Air Pressure Sensor Reading LowModulating gas heat ignition controller, air pressure sensor is reading low [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11242Diagnostic: Gas Heat Air Pressure Sensor Reading HighModulating gas heat ignition controller, air pressure sensor is reading high [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11243Diagnostic: Gas Heat Loss of Inducer Motor ControlModulating gas heat ignition controller, loss of inducer motor control [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11244Diagnostic: Gas Heat Air Sensor Null Pressure CheckModulating gas heat ignition controller [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11245Diagnostic: Gas Heat Limited Low FireModulating gas heat ignition controller [Modulating Gas Heat is Configured]Readfalse = Inactive, true = Active
BI11247Diagnostic: Refrigerant Concentration Sensor ADiagnostic point that is be active when Refrigerant Leak Sensor is in [Refrigerant Type is R454B]Readfalse = Inactive, true = Active
BI11248Refrigerant Leak Detection System InputActive state will be maintained for the duration of the alarm state [Refrigerant Type is R454B]Readfalse = Inactive, true = Active
BI11249Diagnostic: Refrigerant Leak Sensor Failure Sensor ADiagnostic point that shall be active when the refrigerant sensor reports a [Refrigerant Type is R454B]Readfalse = Inactive, true = Active
BV10103Heat Lockout CommandNormally used by the BMS to command the unit to prevent heating [Primary Heating Source Installed]Commandfalse = Normal, true = Locked out
BV10104Supply Fan Configuration CommandUsed to command the supply fan configuration as either cycling or continuousWritefalse = Cycling, true = Continuous
BV10106Dehumidification Enable CommandNormally used by the BMS to disable unit dehumidification [Hot Gas Reheat is Configured as Installed]Commandfalse = Disabled, true = Auto
BV10109Filter Timer ResetCommands the unit to reset the accumulated filter run hoursWritefalse = Accumulating, true = Reset
BV10110Reset DiagnosticUsed to initiate a request to reset any controller diagnosticsWritefalse = Normal, true = Reset
BV10111Daytime Warmup Enable CommandUsed to enable daytime warmup [System Type is Configured as VVDA and Primary Heat is Configured.]Commandfalse = Disabled, true = Enabled
BV10112Morning Warmup Enable CommandNormally used by the BMS to enable morning warmupCommandfalse = Disabled, true = Enabled
BV10113Occupancy Input BASNormally used by the BMS to provide the requested occupancy state toWritefalse = Occupied, true = Unoccupied
BV10115Cooling Lockout BASUsed to prevent all mechanical coolingCommandfalse = Normal, true = Locked out
BV10119Supply Air Tempering EnableUsed to enable the supply (discharge) air tempering feature of the unitCommandfalse = Disabled, true = Enabled
BVmin11100Alarm Indicator StatusState of the controller alarm outputReadfalse = Off, true = On
BV11111Compressor Lockout StatusOne or more compressors are locked out with no diagnosticReadfalse = Normal, true = Locked out
BVmin11113Unit Stop CommandPoint used to force the unit into an immediate stop conditionWritefalse = Auto, true = Stop
BV11114Supply Fan Speed Command EnableEnables the unit to use Supply Fan Speed Command to override theCommandfalse = Disabled, true = Enabled
BV11115Cooling Capacity Setpoint Enable BASCommands the unit to use Cooling Capacity Setpoint BAS value to overrideCommandfalse = Disabled, true = Enabled
BV11116Heating Capacity Setpoint Enable BASCommands the unit to use Heating Capacity Setpoint BAS value to override [Primary Heating Source Installed]Commandfalse = Disabled, true = Enabled
BV11119Supply Fan CompensationCommands the unit to utilize "Economizer Minimum Position Setpoint BAS" instead ofCommandfalse = Disabled, true = Enabled
BV11121Compressor 1 Run Time ResetCompressor 1 Runtime ResetWritefalse = Accumulating, true = Reset
BV11122Compressor 1 Starts ResetCompressor 1 Starts ResetWritefalse = Accumulating, true = Reset
BV11123Compressor 2 Run Time ResetCompressor 2 Runtime Reset [Multi-Compressor Systems]Writefalse = Accumulating, true = Reset
BV11124Compressor 2 Starts ResetCompressor 2 Starts Reset [Multi-Compressor Systems]Writefalse = Accumulating, true = Reset
BV11125Compressor 3 Run Time ResetCompressor 3 Runtime ResetWritefalse = Accumulating, true = Reset
BV11126Compressor 3 Starts ResetCompressor 3 Starts ResetWritefalse = Accumulating, true = Reset
BV11127Condenser Fan 1 Run Time ResetCondenser fan 1 runtime resetWritefalse = Accumulating, true = Reset
BV11128Condenser Fan 1 Starts ResetCondenser fan 1 starts resetWritefalse = Accumulating, true = Reset
BV11129Condenser Fan 2 Run Time ResetCondenser Fan 2 Runtime Reset [Dual Condenser Fan Systems]Writefalse = Accumulating, true = Reset
BV11130Condenser Fan 2 Starts ResetCondenser Fan 2 Starts Reset [Dual Condenser Fan Systems]Writefalse = Accumulating, true = Reset
BV11131Condenser Fan 3 Run Time ResetCondenser Fan 3 Runtime ResetWritefalse = Accumulating, true = Reset
BV11132Condenser Fan 3 Starts ResetCondenser Fan 3 Starts ResetWritefalse = Accumulating, true = Reset
BV11133Relief Fan Run Time ResetRelief Fan Runtime Reset [Space Pressure Control is Configured]Writefalse = Accumulating, true = Reset
BV11134Relief Fan Starts ResetRelief Fan Starts Reset [Space Pressure Control is Configured]Writefalse = Accumulating, true = Reset
BV11135Electric Heat Stage 1 Run Time ResetElectric Heat Stage 1 Runtime Reset [One or more stages of Staged Electric Heat configured]Writefalse = Accumulating, true = Reset
BV11136Electric Heat Stage 1 Starts ResetElectric Heat Stage 1 Starts Reset [One or more stages of Staged Electric Heat configured]Writefalse = Accumulating, true = Reset
BV11137Electric Heat Stage 2 Run Time ResetElectric Heat Stage 2 Runtime Reset [Two or more stages of Staged Electric Heat configured]Writefalse = Accumulating, true = Reset
BV11138Electric Heat Stage 2 Starts ResetElectric Heat Stage 2 Starts Reset [Two or more stages of Staged Electric Heat configured]Writefalse = Accumulating, true = Reset
BV11139Supply Fan Run Time ResetSupply Fan Runtime ResetWritefalse = Accumulating, true = Reset
BV11140Supply Fan Starts ResetSupply Fan Starts ResetWritefalse = Accumulating, true = Reset
BV11141Diagnostic: Supply Fan FailureDiagnostic: Fan Failure [Indoor Fan Type Configured as Multi Speed or Variable Speed]Readfalse = Inactive, true = Active
BV11143Diagnostic: Duct Static Pressure Limit TripDiagnostic: Duct Static Pressure Limit Trip [System Type is Configured as VVDA]Readfalse = Inactive, true = Active
BV11144Diagnostic: Filter Change RequiredDiagnostic: Dirty Filter [Clogged Filter Configured as Installed]Readfalse = Inactive, true = Active
BV11145Diagnostic: Condensate Overflow LockoutCondensate Drain Pan Overflow Lockout [Condensate Overflow Switch is Configured as Installed]Readfalse = Inactive, true = Active
BV11146Diagnostic: FroStat TripDiagnostic: FroStat Trip [FroStat Configured as Installed]Readfalse = Inactive, true = Active
BV11155Diagnostic: Comp 1 Proving TripDiagnostic: Comp 1 Proving TripReadfalse = Inactive, true = Active
BV11156Diagnostic: Comp 2 Proving TripDiagnostic: Comp 2 Proving Trip [Multi-Compressor Systems]Readfalse = Inactive, true = Active
BV11157Diagnostic: Comp 3 Proving TripDiagnostic: Comp 3 Proving TripReadfalse = Inactive, true = Active
BV11158Diagnostic: Circuit 1 LPC TripDiagnostic: Circuit 1 LPC TripReadfalse = Inactive, true = Active
BV11161Diagnostic: Compressor 1 Contactor FailureDiagnostic: Compressor 1 Contactor Fail LockoutReadfalse = Inactive, true = Active
BV11162Diagnostic: Circuit 1 LPC LockoutDiagnostic: Circuit 1 LPC LockoutReadfalse = Inactive, true = Active
BV11166VVZT DAT Control ModeDetermines Auto or Manual mode for discharge air temperature control for VVZTCommandfalse = Auto, true = Manual
BV11172Diagnostic: Compressor 1 Proving LockoutDiagnostic: Compressor 1 Proving LockoutReadfalse = Inactive, true = Active
BV11173Occupancy Input ActiveOccupancy Input being actively used for status determinationReadfalse = Occupied, true = Unoccupied
BV11174Diagnostic: Compressor 2 Contactor FailureDiagnostic: Compressor 2 Contactor Fail Lockout [Multi-Compressor Systems]Readfalse = Inactive, true = Active
BV11175Diagnostic: Circuit 2 LPC LockoutDiagnostic: Circuit 2 LPC Lockout [Multi-Compressor Systems]Readfalse = Inactive, true = Active
BV11176Diagnostic: Compressor 2 Proving LockoutDiagnostic: Compressor 2 Proving Lockout [Multi-Compressor Systems]Readfalse = Inactive, true = Active
BV11190Diagnostic: Maintenance RequiredDiagnostic: Maintenance RequiredReadfalse = Inactive, true = Active
BV11192Diagnostic: Unit Communications FailureDiagnostic: Unit Communications FailureReadfalse = Inactive, true = Active
BV11199Supply Fan Configuration StatusSupply fan configurationReadfalse = Cycling, true = Continuous
BV11200Timed Override Timer Is ActiveWhether or not the timed override timer is activeReadfalse = Inactive, true = Active
BV11201Supply Fan Speed Command Enable - ActiveActive value for Supply Fan Speed Command Enable point being used forReadfalse = Disabled, true = Enabled
BV11202Cooling Capacity Setpoint Enable BAS - ActiveActive value for Cooling Capacity Setpoint Enable BAS point being used forReadfalse = Disabled, true = Enabled
BV11203Cooling Lockout BAS - ActiveActive value for Cooling Lockout BAS point being used for controlReadfalse = Normal, true = Locked out
BV11204Heating Capacity Setpoint Enable BAS - ActiveActive value for Heating Capacity Setpoint Enable point being used for control [Primary Heating Source Installed]Readfalse = Disabled, true = Enabled
BV11205Daytime Warmup Enable Command - ActiveActive value for Daytime Warmup Enable Command point being used for controlReadfalse = Disabled, true = Enabled
BV11208Supply Fan Compensation - ActiveActive value for Supply Fan Compensation point being used for controlReadfalse = Disabled, true = Enabled
BV11209Dehumidification Enable Command - ActiveActive value for Dehumidification Enable Command point being used for controlReadfalse = Disabled, true = Auto
BV11211VVZT DAT Control Mode - ActiveActive value for VVZT DAT Control Mode point being used for controlReadfalse = Auto, true = Manual
BV11216Heat Lockout Command - ActiveActive value for Heat Lockout Command point being used for control [Primary Heating Source Installed]Readfalse = Normal, true = Locked out
BV11217Morning Warmup Enable Command - ActiveActive value for Morning Warmup Enable Command point being used for controlReadfalse = Disabled, true = Enabled
BV11221Supply Air Tempering StatusStatus of the Supply Air Tempering function [Supply Air Tempering Configured as Enabled]Readfalse = Disabled, true = Enabled
BV11222Supply Air Tempering Enable - ActiveActive value for Supply Air Tempering Enable point being used for controlReadfalse = Disabled, true = Enabled
BV11224Occupancy Input ArbitratorStatus of the arbitrated occupancy inputsWritefalse = Occupied, true = Unoccupied
BV11226Demand Limit Request BASUsed to demand limit the unit remotely [Demand Management Configured as Demand Limit]Writefalse = Not Limited, true = Limited
BV11227Demand Limit Request - ActiveActive Demand Limit Request value used by the equipment [Demand Management Configured as Demand Limit]Readfalse = Not Limited, true = Limited
BV11228Diagnostic: Compressor 3 Contactor FailureDiagnostic: Compressor 3 Contactor Fail LockoutReadfalse = Inactive, true = Active
BV11229Diagnostic: Compressor 3 Proving LockoutDiagnostic: Compressor 3 Proving LockoutReadfalse = Inactive, true = Active
BV11231Daytime Warmup ActiveWhether daytime warmup is currently activeReadfalse = Inactive, true = Active
BV11232Morning Warmup ActiveWhether morning warmup is activeReadfalse = Inactive, true = Active
BV11235Occupied Standby Supply Fan Configuration CommandSupply fan mode in Occupied Standby [zone sensor configured]Commandfalse = Cycling, true = Continuous
BV11236Occupied Standby Supply Fan Configuration Command - ActiveOccupied Standby Fan Mode settingReadfalse = Cycling, true = Continuous
BV11248Diagnostic: High Condensate Level DetectedDiagnostic: High Condensate Level Detected [Condensate Overflow Switch is Configured as Installed]Readfalse = Inactive, true = Active
BV11249Diagnostic: Morning Warmup Mode Exceeded 120 MinutesDiagnostic: Morning Warmup Mode Exceeded 120 MinutesReadfalse = Inactive, true = Active
BV11250Diagnostic: Pre Cool Mode Exceeded 120 MinutesDiagnostic: Precool Mode Exceeded 120 MinutesReadfalse = Inactive, true = Active
BV11251Diagnostic: Night Purge Mode Exceeded 120 MinutesDiagnostic: Night Purge Mode Exceeded 120 MinutesReadfalse = Inactive, true = Active
BV11252Diagnostic: Circuit 3 LPC LockoutDiagnostic: Circuit 3 LPC LockoutReadfalse = Inactive, true = Active
BV11255Dehumidification StatusActive state showing whether dehumidification is active or inactive [Hot Gas Reheat is Configured as Installed]Readfalse = Inactive, true = Active
BV11256Pre Cool Enable CommandNormally used by the BMS to enable pre CoolCommandfalse = Disabled, true = Enabled
BV11257Pre Cool Enable Command - ActiveActive value for Pre Cool Enable Command point being used for controlReadfalse = Disabled, true = Enabled
BV11258Pre Cool ActiveWhether Pre Cool is activeReadfalse = Inactive, true = Active
BV11259Occupied Dehumidification Enable BASSetting for unit to use "Enable" or "Disable" for Occupied Dehumidification ControlCommandfalse = Disabled, true = Enabled
BV11260Occupied Dehumidification Enable BAS - ActiveActive value for Dehumidification Enable BAS point being used for controlReadfalse = Disabled, true = Enabled
BV11261Unoccupied Dehumidification Enable BASSetting for unit to use "Enable" or "Disable" for Occupied Dehumidification ControlCommandfalse = Disabled, true = Enabled
BV11262Unoccupied Dehumidification Enable BAS - ActiveActive value for Dehumidification Enable BAS point being used for controlReadfalse = Disabled, true = Enabled
BV11263Diagnostic: Duct Static Pressure Limit LockoutDiagnostic: Duct Static Pressure Limit Lockout [System Type is configured as VVDA]Readfalse = Inactive, true = Active
BV11265Diagnostic: Duct Static Pressure Local LockoutDiagnostic: Duct Static Pressure Local Lockout [System Type is configured as VVDA]Readfalse = Inactive, true = Active
BV11266Gas Heat Manifold 1 Burner 1 Run Time ResetGas heat runtime resetWritefalse = Accumulating, true = Reset
BV11267Gas Heat Manifold 1 Burner 1 Starts ResetGas heat starts counter resetWritefalse = Accumulating, true = Reset
BV11268Gas Heat Manifold 1 Burner 2 Run Time ResetGas heat runtime reset [Gas Heat is installed with a second gas valve on manifold 1.]Writefalse = Accumulating, true = Reset
BV11269Gas Heat Manifold 1 Burner 2 Starts ResetGas heat starts reset counterWritefalse = Accumulating, true = Reset
BV11270Gas Heat Manifold 2 Burner 1 Run Time ResetGas heat runtime resetWritefalse = Accumulating, true = Reset
BV11271Gas Heat Manifold 2 Burner 1 Starts ResetGas heat starts counter resetWritefalse = Accumulating, true = Reset
BV11276Diagnostic: Supply Fan Bypass EnableDiagnostic: Supply Fan VFD Bypass Enable [Unit has Supply Fan VFD Bypass feature installed.]Readfalse = Inactive, true = Active
BV11277Diagnostic: Reheat Valve 1 FaultDiagnostic: Reheat Valve 1 Fault [Hot Gas Reheat is Configured as Installed]Readfalse = Inactive, true = Active
BV11278Diagnostic: Reheat Valve 2 FaultDiagnostic: Reheat Valve 2 Fault [Hot Gas Reheat is Configured as Installed]Readfalse = Inactive, true = Active
BV11279Diagnostic: Outdoor Airflow Pressure Calibration LimitDiagnostic: Outdoor Airflow Pressure Calibration Limit (Traq) [Economizer with Fresh Air Measurement and Control (Traq) Installed.]Readfalse = Inactive, true = Active
BV11280Diagnostic: Space Pressure Calibration LimitDiagnostic: Space Pressure Calibration Limit (Statitrac) [Space Pressure Control (Statitrac) is configured.]Readfalse = Inactive, true = Active
BV11281Diagnostic: Reheat LPC TripDiagnostic: Reheat LPC Trip [Modulating Hot Gas Reheat on Voyager 3]Readfalse = Inactive, true = Active
BV11282Diagnostic: Reheat LPC LockoutDiagnostic: Reheat LPC Lockout [Modulating Hot Gas Reheat on Voyager 3]Readfalse = Inactive, true = Active
BV11283Refrigerant Mitigation ActiveActive when the Symbio 700 controller is in a mitigation state for [Refrigerant Type is R454B]Readfalse = Inactive, true = Active
MImin10101Heat Cool Mode StatusCurrent heat cool mode of the controllerRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MI10144Economizer System StatusOperating state of the airside economizer systemRead1 = Disabled, 2 = Enabled, 3 = Not Present
MI11100System Mode Switch Air-FiStatus of the wireless system mode switch connected to the controllerRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MI11101Timed Override Air-FiStatus of the Timed Override wireless inputRead1 = Idle, 2 = On, 3 = Cancel
MI11102System Mode Switch InputStatus of the wired system mode switch connected to the controllerRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MI11103Timed Override InputStatus of the Timed Override wired inputRead1 = Idle, 2 = On, 3 = Cancel
MV10101Cooling Reset Type StatusType of cooling reset used by the controller [System Type is Configured as VVDA]Read1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air
MV10102Emergency Override BASUsed to command the unit into an emergency mode of operationCommand1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV10103Economizer Airside Enable BASNormally provided by the BAS to enable airside economizingCommand1 = Disabled, 2 = Enabled, 3 = Auto
MV10104Heat Cool Mode RequestUsed to command the unit into a heat/cool modeCommand1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MVmin10106Occupancy RequestNormally used by the BMS to command the unit into an occupancyCommand1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV10110Timed Override RequestUsed to request a temporary timed override during unoccupiedWrite1 = Idle, 2 = On, 3 = Cancel
MV11100Arbitration Method RequestSetting for unit to use "Enable External/BAS Control" or "Standalone Control" dataWrite1 = Enable External/BAS Control, 2 = Standalone Control
MV11101Customer Options Module Communication StatusCommunication Status of the Customer Options Module [Customer Options Module Installed and In-Use]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11102Economizer TypeGeneral description of the type of economizer systemRead1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/ Sensor, 9 = Waterside Economizer and TRAQ Damper/Sensor, 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor
MV11103Fresh Air Options Module Communication StatusCommunication Status of the Fresh Air Options Module [Fresh Air Options Module Installed and In-Use]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11105Indoor Options Module Communication StatusCommunication Status of the Indoor Options Module [Indoor Options Module Installed and In-Use]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11106On-Board I/O Communication StatusCommunication Status of the On-Board Inputs and OutputsRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11110Service Test State RequestRequests a service test stepWrite1 = Inactive; the remaining test steps depend on unit configuration
MV11111Cooling Reset TypeSelectable discharge air cooling reset type based on outdoor, space [System Type is Configured as VVDA]Write1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air
MV11112System Mode Switch LocalStatus of the system mode switch connected to the controller as arbitratedRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MV11113Timed Override StatusStatus of the timed override requestRead1 = Idle, 2 = On, 3 = Cancel
MV11114Trane Unit TypeEquipment type according to the manufacturer's classificationRead1 = 1 Heat/1 Cool, 2 = Heat Pump, 3 = Blower Coil, 4 = Unit Ventilator, 5 = Fan Coil, 6 = Rooftop, 7 = Air Handler, 8 = Vertical Self Contained, 9 = Unitary, 10 = VAV Box
MV11115Unit Stop SourceSource of the stop command that turned off the equipmentRead1 = None, 2 = Emergency Stop, 3 = Drain Pan Overflow, 4 = Local HI, 5 = Remote HI, 6 = External Auto Stop, 7 = Phase Monitor, 8 = Emergency Override, 9 = Supply Fan Fault, 10 = Equipment Shutdown Input, 11 = Smoke Detector, 12 = Equipment Limit, 13 = Sensor Failure
MV11116Emergency Override BAS - ActiveActive value for Emergency Override BAS point being used for controlRead1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV11118Economizer Decision MethodUsed to indicate the method of enabling airside economizing [Outside Air is configured as 0-100%]Read1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy, 5 = Differential Dry Bulb
MV11119Refrigerant TypeType of refrigerant used in the equipmentRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E), 17 = R-454B
MV11120Economizer Airside Enable BAS - ActiveActive value for Economizer Airside Enable BAS point being used for controlRead1 = Disabled, 2 = Enabled, 3 = Auto
MV11121Heat Cool Mode Request - ActiveActive value for Heat Cool Mode Request point being used for controlRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MVmin11123Occupancy StatusActive occupancy mode of the controllerRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV11124Supply Fan VFD Communication StatusModbus supply fan VFD comm status [multi/variable speed fan]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11125Occupancy Request ActiveActive Occupancy mode being requested of the unitRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV11128Gas Heat Ignition Module 1 Communication StatusCommunication Status of the Modbus Gas Heat Ignition Module 1Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11129Gas Heat Ignition Module 2 Communication StatusCommunication Status of the Modbus Gas Heat Ignition Module 2 [800 MBH Gas Heat is Configured]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11130Emergency Override StatusActive Emergency Override mode in control of the equipmentRead1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV11133Stepper Motor Communication StatusCommunication Status of the Stepper Motor Inputs and Outputs [Stepper Motor Module Installed and In-Use]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11136Heating Reset TypeSelectable discharge air heating reset type of outdoor, spaceWrite1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air
MV11137Heating Reset Type StatusDischarge air heating reset type status [System Type is Configured as VVDA]Read1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air
MV11139Refrigerant Leak Sensor Communication Status Sensor ACommunication status of the Modbus communicating refrigerant detection system [Refrigerant Type is R-454B]Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
Object ID lookup: Trane Symbio 700 Voyager 3 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 700 Voyager 3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 700 Voyager 3

How many BACnet points does the Trane Symbio 700 Voyager 3 have?

This list has 568 BACnet objects: 56 analog inputs, 260 analog values, 105 binary inputs, 108 binary values, 6 multi-state inputs, 33 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 700 Voyager 3 BACnet points are writable?

198 of the 568 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane Symbio 700 Voyager 3 BACnet documentation?

The source is Integration Guide: BACnet and Modbus Integration to Voyager 3 Packaged Rooftop Air-Conditioners with Symbio 700 Controls (BAS-SVP066B-EN), revision April 2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP066B-EN_04132024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 700 Voyager 3?

Start with MV 10106 Occupancy Request (Occupancy command (occupied/unoccupied/standby)); BV 11113 Unit Stop Command (BMS stop/auto of the whole unit); AV 10159 Occupied Cooling Setpoint BAS (Occupied cooling setpoint (dual-setpoint units)); AV 10160 Occupied Heating Setpoint BAS (Occupied heating setpoint (dual-setpoint units)); AV 10127 Space Temperature Setpoint BAS (Single-setpoint alternative to the two setpoints above); MI 10101 Heat Cool Mode Status (Current heat/cool operating mode); MV 11123 Occupancy Status (Confirms the occupancy the unit is running in); BI 10226 Supply Fan Status (Supply fan on/off status); AV 11178 Space Temperature Active (Space temperature the unit is actually controlling to); BV 11100 Alarm Indicator Status (Unit alarm output; on when the controller is in alarm).

How do I enable BMS control of the Trane Symbio 700 Voyager 3?

MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the default: the controller weighs BAS, Air-Fi and wired sources. 'Standalone Control' ignores all BAS input and is meant for troubleshooting. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.

Does the Trane Symbio 700 Voyager 3 need a BACnet heartbeat or have a communication timeout?

The sensor BAS points (AV 10113 Outdoor Air Temperature BAS, AV 10114 Space Temperature BAS, AV 10116-10119, AV 11103 Return Air Humidity BAS, AV 11119 Return Air Temperature BAS) have a 900 s heartbeat in the tables, so the BMS must keep rewriting them. The setpoint and command points have no heartbeat.

Can the BMS supply sensor values to the Trane Symbio 700 Voyager 3?

Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it; the '... Arbitrator' object shows which source wins and the '... Active' object reports the value in use. Space setpoints go to AV 10127 (single setpoint) or AV 10159/10160 (dual setpoint). BV 10113 Occupancy Input BAS is the communicated occupancy input.

How do I check these points on the real Symbio 700 Voyager 3?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide: BACnet and Modbus Integration to Voyager 3 Packaged Rooftop Air-Conditioners with Symbio 700 Controls · BAS-SVP066B-EN · rev. April 2024. Object names, instances and units are reproduced as published; descriptions are our own.