Fan coil, blower coil and unit ventilator controller · BACnet points list

Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator BACnet points list

Updated 6 November 2026

Short answer

The Symbio 400-B/500 is Trane's programmable unit controller, BTL listed as a B-BC. For fan coil, blower coil and unit ventilator applications it exposes about 115 objects: local and BAS sensor values, occupancy, heat/cool mode and fan speed requests, valve, damper and heat outputs, setpoint limits and diagnostics. Symbio UI sets the protocol and chooses BAS or local per sensor and setpoint.

This page lists 116 BACnet objects for the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Equipment
Fan coil, blower coil and unit ventilator controller
Equipment type
VAV boxes & fan coils
BACnet objects
116 (62 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN
Source document
Integration Guide - Symbio 400-B/500 Programmable Controller for Fan Coil, Blower Coil and Unit Ventilator · BAS-SVP060A-EN · rev. October 2022
Download CSV 116 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator

Integration in brief

Set the rotary address, then use Symbio UI (USB, http://198.80.18.1) BAS Control Selection to pick BAS or Local for each sensor and setpoint. Schedule with MV 6 Occupancy Request, write AV 27 Space Temperature Setpoint BAS, MV 4 Heat Cool Mode Request and MV 8 fan speed, and refresh any BAS sensor objects at least every 15 minutes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6Occupancy RequestOccupancy command from the BMS scheduleWrite
MV 4Heat Cool Mode RequestHeat/cool mode commandWrite
MV 8Supply Fan Speed BASFan speed command (1 = Auto)Write
AV 27Space Temperature Setpoint BASSpace setpoint from the BMSWrite
BV 2Reset Diagnostic RequestReset diagnostics (self-clears)Write
MV 7Occupancy StatusConfirms the occupancy in effectRead
MV 5Heat Cool Mode StatusHeat/cool mode in effectRead
BI 5Supply Fan StatusFan running (1 = on)Read
AV 59Space Temperature ActiveSpace temperature the unit controls toRead
AI 4Discharge Air TemperatureDischarge air temperatureRead

Enable & remote start

The BAS controls the unit by writing values and putting points in or out of service. BAS Control Selection in Symbio UI chooses BAS or Local per sensor and setpoint. MV 9 Emergency Override BAS shuts the unit down for any value other than 1 = Normal.

Heartbeat & communication loss

BAS-supplied sensor objects (Space Temperature BAS, Outdoor Air Temperature BAS, Space Humidity BAS, Entering Water Temperature BAS) must be rewritten at least every 15 minutes. If no write is seen in time the object goes to fault and the unit falls back to its own sensor; at power-up they start in fault until written.

Sensors & values from the BMS

Put the BAS sensor objects in service (they are out of service by default), then write AV 14 Space Temperature BAS, AV 1 Outdoor Air Temperature BAS, AV 2 Space Humidity BAS, AV 4 Entering Water Temperature BAS or AV 112 Space CO2 Concentration BAS. The matching Active objects (AV 59, AV 3, AV 6, AV 5, AV 113) show the value in use.

Network setup

Watch out for

Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

116 of 116 shown
Type
Access
Show
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator BACnet Points List
DescriptionStates
AI1Space Temperature LocalLocal zone temperature or return air temperature°FRead
AI2Space Temperature Setpoint LocalLocal zone sensor setpoint°FRead
AI3Space Humidity LocalLocal relative humidity sensor value%Read
AImin4Discharge Air TemperatureDischarge air temperature from equipment°FRead
AI5Entering Water Temperature LocalLocal sensor entering water temperature°FRead
AI8Outside Air Temperature LocalLocal outside air temperature sensor°FRead
AI20Face and Bypass Damper Position StatusFace and bypass damper position, % of strokeRead
AI21Space CO2 Concentration LocalLocal carbon dioxide concentrationppmRead
AO1Outdoor Air Damper PositionAnalog outdoor air damper output commandRead
AO2Chilled Water Valve CommandAnalog chilled water valve command 0% closedRead
AO3Heating Valve CommandAnalog heating valve output command 0% closedRead
AO4Electric Heat CommandAnalog electric heat output commandRead
AV1Outdoor Air Temperature BASCommunicated outdoor air temperature°FWrite
AV2Space Humidity BASCommunicated space relative humidity%Write
AV3Outdoor Air Temperature ActiveOutdoor air temperature in use°FRead
AV4Entering Water Temperature BASCommunicated entering water temperature°FWrite
AV5Entering Water Temperature ActiveActively used entering water temperature°FRead
AV6Space Humidity ActiveActively used space relative humidity%Read
AV8Economizer Minimum Position Setpoint BASCommunicated value for minimum economizer position setpoint%Write
AV9Fan Off Delay TimeFan off delay timesecondsWrite
AV10Compressor Enable BASCompressor capacity limit; 0 % disables compressors%Write
AV12Filter Runtime Hours SetpointFan run hours before a filter maintenance diagnostic; 0 disableshoursWrite
AV14Space Temperature BASCommunicated space temperature°FWrite
AV16Economizer RequestEconomizer position request for manual override%Write
AV18Cool Valve RequestCool valve position request for manual override%Write
AV19DX Cool RequestDX compressor output request for manual override%Write
AV20Heat Valve RequestHeat valve position request for manual override%Write
AV21Discharge Air Temperature Low Limit SetpointDischarge air low limit; trips freeze protection after 3 min°FWrite
AV22Electric Heat RequestElectric heat request for manual override%Write
AV23Unoccupied Cooling SetpointCooling setpoint used in unoccupied mode°FWrite
AV24Unoccupied Heating SetpointHeating setpoint used in unoccupied mode°FWrite
AVmin27Space Temperature Setpoint BASCommunicated space temperature setpoint°FWrite
AV28Space Temperature Setpoint ActiveThe currently used space temperature setpoint°FRead
AV29Freeze Avoidance SetpointFreeze avoidance setpoint°FWrite
AV30Occupied OffsetOffset from the setpoint for occupied heat/cool setpoints°FWrite
AV31Economizer Minimum Position Setpoint LocalMinimum outside air damper position during occupied mode%Write
AV32Economizer Enable Minimum Outdoor Air Temperature SetpointEconomizing is allowed only above this outdoor air temperature°FWrite
AV33Occupied Bypass TimeOccupied bypass time remainingminutesRead
AV34Standby OffsetOffset from the setpoint for standby heat/cool setpoints°FWrite
AV35Exhaust fan Enable PositionEconomizer position that turns the exhaust fan on (default 10 %)%Write
AV36Space Dehumidification Setpoint BASSpace humidity setpoint for dehumidification%Write
AV37Space Temperature Setpoint DefaultFallback space setpoint when no valid setpoint exists°FWrite
AV38Filter Runtime HoursFan run hours since the filter timer was resethoursRead
AV58Standby Minimum Position SetpointMinimum position in occupied standby mode%Write
AVmin59Space Temperature ActiveThe currently used space temperature°FRead
AV60Occupied Low Fan Min Position SetpointMinimum position in occupied with low fan speed%Write
AV63Supply Fan Speed RequestSupply fan speed request; below the low limit counts as off%Write
AV64Fan Capacity Low LimitMinimum fan speed as a fraction of maximum speed%Write
AV65Compressor Lockout SetpointOutdoor air temperature that locks out the compressors°FWrite
AV67Auxiliary Heat Control RequestAuxiliary heat capacity limit; 0 % disables auxiliary heat%Write
AV68Space Relative Humidity OffsetDehumidification stops at setpoint minus this offset (default 8 %)%Write
AV69Economizer Minimum Position Setpoint ActiveCurrent minimum allowed economizer position%Read
AV71Face and Bypass Damper RequestFace and bypass damper capacity after curve and diagnostics%Read
AV73Supply Fan Speed StatusSupply fan speed; discrete fans show 0/33/66/100 %%Read
AV74Heating Capacity PrimaryPrimary heating source heat capacity%Read
AV75Heating Capacity SecondarySecondary heating source heat capacity%Read
AV76Cooling Capacity StatusCooling source cool capacity%Read
AV77Discharge Air Temperature Maximum Heat LimitHeating capacity is limited to keep discharge air below this°FWrite
AV78Discharge Air Temperature Minimum Cool LimitCooling capacity is limited to keep discharge air above this°FWrite
AV81Electric Heat Stage 1 Fan OutputMinimum fan speed with electric heat stage 1%Write
AV82Electric Heat Stage 2 Fan OutputMinimum fan speed with electric heat stage 2%Write
AV87Cooling Setpoint High LimitUpper limit for the cooling setpoint°FWrite
AV88Cooling Setpoint Low LimitLower limit for the cooling setpoint°FWrite
AV89Heating Setpoint High LimitUpper limit for the heating setpoint°FWrite
AV90Heating Setpoint Low LimitLower limit for the heating setpoint°FWrite
AV96Discharge Air Temperature Design Cool LimitFan speeds up to hold discharge air above this in cooling°FWrite
AV97Discharge Air Temperature Design Heat LimitFan speeds up to hold discharge air below this in heating°FWrite
AV108DCV Minimum Economizer Position at Max Fan SpeedDamper position with fan speed at maximum%Write
AV109DCV Minimum Economizer Position at Min Fan SpeedDamper position with fan speed at minimum%Write
AV110Space CO2 LimitCO2 Maximum SetpointppmWrite
AV111Space CO2 Low LimitCO2 Minimum SetpointppmWrite
AV112Space CO2 Concentration BASBAS communicated CO2 valueppmWrite
AV113Space CO2 Concentration ActiveArbitrated BAS and Local CO2 valueppmRead
BI1Occupancy InputNormally open inputRead0=Occupied, 1=Unoccupied
BI2Condensate Overflow InputNormally closed inputRead0=Overflow, 1=Normal
BI3Low Coil Temperature DetectionNormally closed inputRead0=Low temperature, 1=Normal
BI4Frost Detection InputNormally closed inputRead
BImin5Supply Fan StatusNormally open inputRead0=Off, 1=On
BO2Exhaust Fan Start Stop CommandExhaust fan start/stop outputRead0=Off, 1=Running
BO4Chilled Water Valve Command BinaryBinary chilled water commandRead
BO5Compressor 2 CommandCompressor 2 commandRead
BO6Heating Valve Command BinaryBinary heating valve outputRead
BO7Reversing Valve OutputReversing valve outputReadOn=Cooling, Off=Heating
BO8Outside Air Damper Binary OutputBinary outdoor air damper output commandRead
BV1Supply Fan Configuration CommandOccupied fan mode: cycle with capacity or run continuouslyWrite
BVmin2Reset Diagnostic RequestReset all diagnostics except filter; self-clearsWrite1=Reset
BV3Diagnostic: Discharge Air Temperature Low LimitFreeze protection: discharge air below low limitRead0=Inactive, 1=Active
BV4Diagnostic: Condensate OverflowCondensate overflow diagnostic (latching)Read0=Inactive, 1=Active
BV5Diagnostic: Low Coil Temperature DetectLow coil temperature detection diagnosticRead0=Inactive, 1=Active
BV6Diagnostic: Low Air Flow- Supply Fan FailureLow airflow / supply fan failure diagnosticRead
BV7Diagnostic: Freeze Avoidance ModeFreeze avoidance active (hydronic units)Read0=Inactive, 1=Active
BV8Diagnostic: Filter Change RequiredFilter change required (fan run hours)Read0=Inactive, 1=Active
BV10Exhaust Fan EnableExhaust fan enableWrite0=Disable, 1=Enable
BV11Dehumidification StatusDehumidification activeRead0=Not active, 1=Dehumidification active
BV12Filter Timer Reset RequestReset the filter runtime timer; self-clearsWrite1=Reset
BV13Reversing Valve RequestReversing valve request for manual overrideWrite
BV14Predicted Occupied Heat Cool Mode StatusPredicted heat/cool mode for the next occupied periodRead
BV15Demand Control Ventilation EnableEnables Demand Control VentilationWrite
MI1Supply Fan Speed LocalLocal fan speed settingRead
MI2Timed Override StatusTimed override request from zone sensorRead
MI3Communication StatusCommunication statusRead1=Comm Up, 2=Comm Down, 3=No Parent Configured
MI4IMC StatusECM fan module (IMC) statusRead1=ok, 2=commLoss, 3=newConfig, 4=hwMismatch, 5=swMismatch, 6=hwVersion, 7=swVersion, 8=nvDataMismatch, 9=dupRotarySwitch, 10=extraDevice, 11=rotarySwitchNotFound
MO1Supply Fan Speed BASFan speed output (1-, 2- or 3-speed fan)Read2=Off, 3=Low, 4=Medium, 5=High (1-speed fan: 2/5; 2-speed fan: 2/3/5)
MV1Supply Fan Speed ActiveActive supply fan speed for discrete fan speedRead
MV2Cooling Fan Speed DefaultDo not use (per the guide)Write
MVmin4Heat Cool Mode RequestHeat/cool mode commandWrite1=Auto, 2=Heat, 3=Morning warm-up, 4=Cool, 5=Night Purge (treated as Auto), 6=Pre-Cool, 7=Off, 8=Test (status only), 9=Emergency Heat (treated as Auto), 10=Fan Only (economizer at min), 11=Free Cool
MVmin5Heat Cool Mode StatusActual heat/cool mode statusRead
MVmin6Occupancy RequestOccupancy commandWrite1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby, 5=Auto
MVmin7Occupancy StatusOccupancy in effectRead1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby
MVmin8Supply Fan Speed BASFan speed command from the BASWrite1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MV9Emergency Override BASEmergency override; anything but Normal shuts the unit downWrite1=Normal, 2=Pressurize, 3=Depressurize, 4=Purge, 5=Shutdown, 6=Fire (all but Normal treated as shutdown)
MV10Economizer Airside Enable BASAirside economizer enable/disable/auto from the BASWrite1=Disabled, 2=Enabled, 3=Auto
MV11Number of Fan SpeedsNumber of fan speeds configuredWrite1=Zero, 2=One, 3=Two, 4=Three, 5=Variable Speed
MV13Outdoor Air Damper StatusOutdoor air damper position statusRead1=At or Below Minimum Position, 2=Above Minimum Position, 3=Economizer Not Present
MV22Fan Operating Mode RequestECM fan operating mode: energy efficient or acousticalWrite1=Energy Efficient Mode, 2=Acoustical Mode
MV23First Stage Compressor Minimum Fan SpeedMinimum fan speed with the first compressor stage onWrite1=Low, 2=Medium, 3=High (default)
Object ID lookup: Trane Symbio 400-B/500 FC/BC/UV point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator

How many BACnet points does the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator have?

This list has 116 BACnet objects: 8 analog inputs, 4 analog outputs, 61 analog values, 5 binary inputs, 6 binary outputs, 14 binary values, 4 multi-state inputs, 1 multi-state output, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator BACnet points are writable?

62 of the 116 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator BACnet documentation?

The source is Integration Guide - Symbio 400-B/500 Programmable Controller for Fan Coil, Blower Coil and Unit Ventilator (BAS-SVP060A-EN), revision October 2022, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP060A-EN_10082022.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator?

Start with MV 6 Occupancy Request (Occupancy command from the BMS schedule); MV 4 Heat Cool Mode Request (Heat/cool mode command); MV 8 Supply Fan Speed BAS (Fan speed command (1 = Auto)); AV 27 Space Temperature Setpoint BAS (Space setpoint from the BMS); BV 2 Reset Diagnostic Request (Reset diagnostics (self-clears)); MV 7 Occupancy Status (Confirms the occupancy in effect); MV 5 Heat Cool Mode Status (Heat/cool mode in effect); BI 5 Supply Fan Status (Fan running (1 = on)); AV 59 Space Temperature Active (Space temperature the unit controls to); AI 4 Discharge Air Temperature (Discharge air temperature).

How do I enable BMS control of the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator?

The BAS controls the unit by writing values and putting points in or out of service. BAS Control Selection in Symbio UI chooses BAS or Local per sensor and setpoint. MV 9 Emergency Override BAS shuts the unit down for any value other than 1 = Normal.

Does the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator need a BACnet heartbeat or have a communication timeout?

BAS-supplied sensor objects (Space Temperature BAS, Outdoor Air Temperature BAS, Space Humidity BAS, Entering Water Temperature BAS) must be rewritten at least every 15 minutes. If no write is seen in time the object goes to fault and the unit falls back to its own sensor; at power-up they start in fault until written.

Can the BMS supply sensor values to the Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator?

Put the BAS sensor objects in service (they are out of service by default), then write AV 14 Space Temperature BAS, AV 1 Outdoor Air Temperature BAS, AV 2 Space Humidity BAS, AV 4 Entering Water Temperature BAS or AV 112 Space CO2 Concentration BAS. The matching Active objects (AV 59, AV 3, AV 6, AV 5, AV 113) show the value in use.

How do I check these points on the real Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide - Symbio 400-B/500 Programmable Controller for Fan Coil, Blower Coil and Unit Ventilator · BAS-SVP060A-EN · rev. October 2022. Object names, instances and units are reproduced as published; descriptions are our own.