Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 BACnet points list
Updated 7 November 2026
Trane Horizon outdoor air units are controlled by a Tracer UC600 that talks BACnet MS/TP or BACnet IP. This list covers program V12: occupancy and heat/cool mode requests, BAS inputs for space and outdoor conditions, temperature, humidity, airflow, static pressure and CO2 setpoints, supply and exhaust fan, damper, compressor, condenser fan, heat pump, reheat and energy wheel status and commands, refrigerant leak detection inputs and the diagnostic BVs. Which points exist depends on unit type and options.
This page lists 268 BACnet objects for the Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 — 52 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Horizon Outdoor Air Unit, Tracer UC600 program V12
- Equipment
- DOAS / outdoor air unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 268 (52 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Horizon program V12
- Also known as
- Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Write the occupancy request and heat/cool mode request, the occupied or discharge setpoints and, where used, BAS values for space temperature, humidity, CO2 and static pressure. Read operating mode status, discharge air temperature and the lockout/diagnostic BVs; reset manual diagnostics with Alarm Reset.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | Occupancy Request | Occupancy request from the BMS | Write |
| MV 3 | Heat Cool Mode Request | Heat/cool mode request | Write |
| BV 59 | AUTO/STOP | Manual stop (0 = Auto, 1 = Stop) | Write |
| AV 1 | Occupied Cooling Setpoint | Occupied cooling setpoint | Write |
| AV 2 | Occupied Heating Setpoint | Occupied heating setpoint | Write |
| AV 30 | Discharge Air Cooling Setpoint | Discharge air cooling setpoint | Write |
| BV 16 | Alarm Reset | Reset manual-reset diagnostics | Write |
| MV 44 | Operating Mode Status Active | Operating mode status | Read |
| AI 11 | Discharge Air Temperature Local | Discharge air temperature | Read |
| BV 17 | System Lockout - Manual Reset | Manual-reset lockout active | Read |
Enable & remote start
BV 59 AUTO/STOP stops the unit from the network (1 = Stop) and releases it (0 = Auto). Occupancy Request (MV 1) and Heat Cool Mode Request (MV 3) drive normal operation.
Sensors & values from the BMS
The BAS can write Space Temperature BAS (AV 20), Space Temperature Setpoint BAS (AV 25), Space Humidity BAS (AV 8), Space CO2 Concentration BAS (AV 42), Space Static Pressure BAS (AV 73), Duct Static Pressure BAS (AV 64), Outdoor Air Temperature BAS (AV 75), Outdoor Air Humidity BAS (AV 81) and Discharge Air Temperature Setpoint BAS (AV 67); the guide ties each to the matching control program type.
Network setup
- The Tracer UC600 supports BACnet MS/TP and BACnet IP; the device ID examples are in the guide (Tables 5-7).
- Check the program revision first: the guide lists BACnet points that report the program version (Table 2).
Watch out for
- Point availability depends on equipment type (DX, ASHP, WSHP, chilled water), program control type and options.
- Manual-reset diagnostics stay latched until Alarm Reset (BV 16) is written; auto-reset ones clear on their own.
- Diagnostic: Fire Shutdown (BV 8) is written by the BAS and shuts the unit down until it returns to normal.
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 11 | Discharge Air Temperature Local | °F | Read | ||
| AI | 23 | Duct Static Pressure Local | in H2O | Read | ||
| AI | 9 | Exhaust Fan Piezo Pressure Local | in H2O | Read | ||
| AI | 13 | Exhaust Leaving Temperature Local | °F | Read | ||
| AI | 15 | Indoor Coil Leaving Air Temperature Local | °F | Read | ||
| AI | 18 | Liquid Line Pressure Circuit 1 Local | psi | Read | ||
| AI | 19 | Liquid Line Pressure Circuit 2 Local | psi | Read | ||
| AI | 7 | Outdoor Air Damper Position Status Local | % | Read | ||
| AI | 10 | Outdoor Air Flow Local | cfm | Read | ||
| AI | 22 | Outdoor Air Relative Humidity Local | % | Read | ||
| AI | 21 | Outdoor Air Temperature Local | °F | Read | ||
| AI | 25 | Preheat Leaving Temperature Local | °F | Read | ||
| AI | 14 | Return Air Humidity Local | % | Read | ||
| AI | 6 | Return Air Temperature Local | °F | Read | ||
| AI | 4 | Return Static Pressure Local | in H2O | Read | ||
| AI | 8 | Space CO2 Concentration Local | ppm | Read | ||
| AI | 2 | Space Humidity Local | % | Read | ||
| AI | 12 | Space Static Pressure Local | in H2O | Read | ||
| AI | 1 | Space Temperature Local | °F | Read | ||
| AI | 20 | Space Temperature Setpoint Local | °F | Read | ||
| AI | 24 | Split Exhaust-Return Pressure Differential Local | in H2O | Read | ||
| AI | 28 | Suction Line Pressure Circuit 1 Local | psi | Read | ||
| AI | 16 | Suction Line Pressure Circuit 2 Local | psi | Read | ||
| AI | 3 | Supply Fan Piezo Pressure Local | in H2O | Read | ||
| AO | 9 | Chilled Water Valve Command | % | Read | ||
| AO | 3 | Compressor Speed Command Circuit 1 | % | Read | ||
| AO | 8 | Compressor Speed Command Circuit 2 | % | Read | ||
| AO | 7 | Condenser Fan Speed Command | % | Read | ||
| AO | 13 | Energy Recovery Exhaust Bypass Command | % | Read | ||
| AO | 6 | Energy Recovery Outdoor Bypass Command | % | Read | ||
| AO | 10 | Energy Recovery Wheel Speed Command | % | Read | ||
| AO | 4 | Exhaust Fan Speed Command | % | Read | ||
| AO | 11 | Heating Output Command | % | Read | ||
| AO | 1 | Hot Gas Reheat Valve Command | % | Read | ||
| AO | 5 | Outdoor Air Damper Position Command | % | Read | ||
| AO | 14 | Outdoor Coil Water Valve Command Circuit 1 | % | Read | ||
| AO | 15 | Outdoor Coil Water Valve Command Circuit 2 | % | Read | ||
| AO | 2 | Supply Fan Speed Command | % | Read | ||
| AV | 85 | Cabinet Tonnage | tons | Read | ||
| AV | 51 | Compressor Control P-Gain | Write | |||
| AV | 21 | Compressor Cooling Ambient Lockout Setpoint | °F | Write | ||
| AV | 18 | Compressor Heating Capacity Status Active | % | Read | ||
| AV | 86 | Compressor Modulating Capacity | % | Read | ||
| AV | 91 | Compressor Stage Down Delay Remaining | Read | |||
| AV | 90 | Compressor Stage Up Delay Remaining | Read | |||
| AV | 88 | Condenser Fan P-Gain | Write | |||
| AV | 52 | Cooling Capacity Status Active | % | Read | ||
| AV | 19 | Damper Control P-Gain | Read | |||
| AV | 5 | Dehumidification Temperature Active | °F | Read | ||
| AV | 14 | Dehumidification Temperature Setpoint | °F | Write | ||
| AV | 77 | Dehumidification Temperature Setpoint Active | °F | Read | ||
| AVmin | 30 | Discharge Air Cooling Setpoint | °F | Write | ||
| AV | 32 | Discharge Air Heating Setpoint | °F | Write | ||
| AV | 84 | Discharge Air Temperature Active | °F | Read | ||
| AV | 66 | Discharge Air Temperature Setpoint Active | °F | Read | ||
| AV | 67 | Discharge Air Temperature Setpoint BAS | °F | Write | ||
| AV | 45 | Discharge Air Temperature Setpoint Maximum | °F | Write | ||
| AV | 43 | Discharge Air Temperature Setpoint Minimum | °F | Write | ||
| AV | 65 | Duct Static Pressure Active | in H2O | Read | ||
| AV | 64 | Duct Static Pressure BAS | in H2O | Write | ||
| AV | 46 | Duct Static Pressure Setpoint | in H2O | Write | ||
| AV | 55 | Economizer Outdoor Air Enable Setpoint | °F | Write | ||
| AV | 63 | Economizer Outdoor Air Enthalpy Enable Setpoint | BTU/lb | Write | ||
| AV | 54 | Exhaust Fan Air Flow Active | cfm | Read | ||
| AV | 57 | Exhaust Fan Air Flow Setpoint | cfm | Write | ||
| AV | 40 | Exhaust Fan Speed Setpoint - Constant Speed | % | Write | ||
| AV | 12 | Exhaust Fan Tracking Offset Setpoint | % | Write | ||
| AV | 89 | Frost Avoidance Setpoint Active | °F | Read | ||
| AV | 44 | Heating Capacity Primary Status Active | % | Read | ||
| AV | 61 | Heat Control P-Gain | Write | |||
| AV | 92 | Heat Cool Switch Delay Time Remaining | minutes | Read | ||
| AV | 4 | Heat Pump Disable Temperature Setpoint | °F | Write | ||
| AV | 80 | Hot Gas Reheat Capacity Status Active | % | Read | ||
| AV | 60 | Mixed Air Temperature Active | Read | |||
| AVmin | 1 | Occupied Cooling Setpoint | °F | Write | ||
| AVmin | 2 | Occupied Heating Setpoint | °F | Write | ||
| AV | 16 | Occupied Offset | Δ°F | Write | ||
| AV | 11 | Outdoor Air Dewpoint Active | °F | Read | ||
| AV | 10 | Outdoor Air Dewpoint Enable Setpoint | °F | Write | ||
| AV | 68 | Outdoor Air Enthalpy Active | Read | |||
| AV | 38 | Outdoor Air Flow Active | cfm | Read | ||
| AV | 71 | Outdoor Air Flow Setpoint | cfm | Write | ||
| AV | 6 | Outdoor Air Heating Enable Setpoint Active | °F | Read | ||
| AV | 93 | Outdoor Air Heating Enable Setpoint Request | °F | Write | ||
| AV | 82 | Outdoor Air Humidity Active | % | Read | ||
| AV | 81 | Outdoor Air Humidity BAS | % | Write | ||
| AV | 76 | Outdoor Air Temperature Active | °F | Read | ||
| AV | 75 | Outdoor Air Temperature BAS | °F | Write | ||
| AV | 47 | Outdoor Damper Max Position Setpoint | % | Write | ||
| AV | 48 | Outdoor Damper Min Position Setpoint | % | Write | ||
| AV | 36 | Return Air Dewpoint Active | °F | Read | ||
| AV | 72 | Return Air Enthalpy Active | Read | |||
| AV | 69 | Return Dewpoint Dehum Enable Setpoint | °F | Write | ||
| AV | 83 | Return Humidity Dehum Enable Setpoint | % | Write | ||
| AV | 3 | Return Static Pressure Setpoint | in H2O | Write | ||
| AV | 78 | Saturated Suction Temp Circuit 1 Active | °F | Read | ||
| AV | 79 | Saturated Suction Temp Circuit 2 Active | °F | Read | ||
| AV | 50 | Space CO2 Concentration Setpoint | ppm | Write | ||
| AV | 62 | Space CO2 Concentration Active | ppm | Read | ||
| AV | 42 | Space CO2 Concentration BAS | ppm | Write | ||
| AV | 87 | Space Dehumidification Setpoint | % | Write | ||
| AV | 35 | Space Dewpoint Active | °F | Read | ||
| AV | 34 | Space Dewpoint Calculated Setpoint Active | °F | Read | ||
| AV | 7 | Space Humidity Active | % | Read | ||
| AV | 8 | Space Humidity BAS | % | Write | ||
| AV | 70 | Space Static Pressure Active | in H2O | Read | ||
| AV | 73 | Space Static Pressure BAS | in H2O | Write | ||
| AV | 56 | Space Static Pressure Setpoint | in H2O | Write | ||
| AV | 23 | Space Temperature Active | °F | Read | ||
| AV | 20 | Space Temperature BAS | °F | Write | ||
| AV | 37 | Space Temperature Setpoint Active | °F | Read | ||
| AV | 25 | Space Temperature Setpoint BAS | °F | Write | ||
| AV | 41 | Supply Air Flow Active | cfm | Read | ||
| AV | 59 | Supply Air Flow Min Setpoint - Cooling | cfm | Read | ||
| AV | 13 | Supply Air Flow Min Setpoint - Heating | cfm | Read | ||
| AV | 74 | Supply Air Flow Min Setpoint Active | cfm | Read | ||
| AV | 39 | Supply Air Flow Setpoint | Write | |||
| AV | 22 | Supply Air Flow Setpoint Active | cfm | Read | ||
| AV | 17 | Supply Fan Speed Setpoint - Constant Speed | % | Write | ||
| AV | 26 | Unoccupied Cooling Enable Setpoint | °F | Write | ||
| AV | 27 | Unoccupied Heating Enable Setpoint | °F | Write | ||
| AV | 28 | Unoccupied Humidity Enable Setpoint | % | Write | ||
| AV | 33 | Ventilation Deadband High Setpoint | °F | Write | ||
| AV | 29 | Ventilation Deadband Low Setpoint | °F | Write | ||
| AV | 24 | Ventilation Setpoint High Active | °F | Read | ||
| AV | 49 | Ventilation Setpoint Low Active | °F | Read | ||
| BI | 17 | Compressor 1 Status Local | Read | 0=Not Proven, 1=Proven | ||
| BI | 23 | Compressor 1 VFD Status Local | Read | 0=Alarm, 1=Normal | ||
| BI | 18 | Compressor 2 Status Local | Read | 0=Not Proven, 1=Proven | ||
| BI | 19 | Compressor 3 Status Local | Read | 0=Not Proven, 1=Proven | ||
| BI | 20 | Compressor 4 Status Local | Read | 0=Not Proven, 1=Proven | ||
| BI | 10 | Condensate Detection Input | Read | 0=Normal, 1=In Alarm | ||
| BI | 5 | Damper End Switch Status Local | Read | 0=Not Proven, 1=Proven | ||
| BI | 2 | Emergency Stop | Read | 0=Normal, 1=ESTOP | ||
| BI | 12 | Energy Wheel OA Filter Status Local | Read | 0=Clean, 1=Clogged | ||
| BI | 11 | Energy Wheel RA Filter Status Local | Read | 0=Clean, 1=Clogged | ||
| BI | 15 | Energy Wheel Rotation Status Local | Read | 0=Not Proven, 1=Proven | ||
| BI | 7 | Exhaust Damper End Switch | Read | 0=Not Proven, 1=Proven | ||
| BI | 14 | Exhaust Fan Status | Read | 0=Not Proven, 1=Proven | ||
| BI | 6 | Heat On Off Status Local | Read | 0=Off, 1=On | ||
| BI | 16 | Hot Water Freezestat Local | Read | 0=Normal, 1=Freezing | ||
| BI | 3 | Indoor Coil Filter Status Local | Read | 0=Clean, 1=Clogged | ||
| BI | 4 | Occupancy Input | Read | 0=Unocc., 1=Occupied | ||
| BI | 9 | Outdoor Coil Water Safety Circuit Local | Read | 0=Open, 1=Closed | ||
| BI | 8 | Phase Monitor Status Local | Read | 0=Normal, 1=Tripped | ||
| BI | 24 | Refrigerant Leak Detection System Input-Airstream | Read | 0=Alarm, 1=Normal | ||
| BI | 25 | Refrigerant Leak Detection System Input-Control Cabinet | Read | 0=Alarm, 1=Normal | ||
| BI | 1 | Supply Fan Status | Read | 0=Not Proven, 1=Proven | ||
| BO | 11 | Compressor 1 Command | Read | 0=Off, 1=On | ||
| BO | 12 | Compressor 2 Command | Read | 0=Off, 1=On | ||
| BO | 5 | Compressor 3 Command | Read | 0=Off, 1=On | ||
| BO | 6 | Compressor 4 Command | Read | 0=Off, 1=On | ||
| BO | 19 | Condenser Fan 4 Start Stop Command | Read | 0=Off, 1=On | ||
| BO | 21 | Condenser Fan 5 Start Stop Command | Read | 0=Off, 1=On | ||
| BO | 14 | Condenser Fan VFD Start Stop Command | Read | 0=Off, 1=On | ||
| BO | 2 | Damper Open Close Command | Read | 0=Closed, 1=Open | ||
| BO | 15 | Energy Recovery Wheel Start Stop Command | Read | 0=Off, 1=On | ||
| BO | 9 | Exhaust Damper Open Close Command | Read | 0=Off, 1=On | ||
| BO | 10 | Exhaust Fan Start Stop Command | Read | 0=Off, 1=On | ||
| BO | 3 | Heat 1 Command | Read | 0=Off, 1=On | ||
| BO | 7 | Heat 2 Command | Read | 0=Off, 1=On | ||
| BO | 8 | Heat 3 Command | Read | 0=Off, 1=On | ||
| BO | 4 | Inducer High Speed Command | Read | 0=Off, 1=On | ||
| BO | 13 | Pre-Heat Enable | Read | 0=Off, 1=On | ||
| BO | 16 | Reversing Valve Command Circuit 1 | Read | 0=Heating, 1=Cooling | ||
| BO | 17 | Reversing Valve Command Circuit 2 | Read | 0=Heating, 1=Cooling | ||
| BO | 18 | Split Exhaust-Return Damper Open Close Command | Read | 0=Closed, 1=Open | ||
| BO | 1 | Supply Fan Start Stop Command | Read | 0=Off, 1=On | ||
| BVmin | 16 | Alarm Reset | Write | 0=Normal, 1=Reset | ||
| BVmin | 59 | AUTO/STOP | Write | 0=AUTO, 1=STOP | ||
| BV | 62 | Compressor Cooling Allowed | Read | 0=Not Allowed, 1=Allowed | ||
| BV | 61 | Compressor Heating Allowed | Read | 0=Not Allowed, 1=Allowed | ||
| BV | 64 | Compressor Low Ambient Lockout Active | Read | 0=Inactive, 1=Active | ||
| BV | 39 | Condenser Fan Pre-Start | Read | 0=Off, 1=On | ||
| BV | 9 | Economizer Mode | Read | 0=Not Econ., 1=Econ. | ||
| BV | 41 | Energy Recovery Frost Avoidance Status | Read | 0=Normal, 1=Active | ||
| BV | 44 | Free Cooling Mode | Read | 0=Off, 1=On | ||
| BV | 4 | Heat Pump Defrost Mode | Read | 0=Off, 1=On | ||
| BV | 5 | Hot Gas Reheat Purge Mode | Read | 0=Off, 1=On | ||
| BV | 23 | Interlock | Read | 0=Off, 1=On | ||
| BV | 32 | Oil Boost Cycle Circuit 1 | Read | 0=Off, 1=On | ||
| BV | 68 | Refrigerant Leak Mitigation Active | Read | 0=Inactive, 1=Alarm | ||
| BV | 12 | Safety Check | Read | 0=Failed, 1=Passed | ||
| BV | 30 | System Lockout - Auto Reset | Read | 0=Normal, 1=Lockout | ||
| BVmin | 17 | System Lockout - Manual Reset | Read | 0=Normal, 1=Lockout | ||
| BV | 43 | Ventilation Mode | Read | 0=Disabled, 1=Enabled | ||
| MV | 22 | Cabinet Size | Read | 1=OAB, 2=OAD, 3=OAG, 4=OAK, 5=OAN Rev 5, 6=OAN Rev 6 | ||
| MV | 14 | Circuit 1 Status | Read | 1=Off, 2=Partial Capacity, 3=Full Capacity | ||
| MV | 15 | Circuit 2 Status | Read | 1=Off, 2=Partial Capacity, 3=Full Capacity | ||
| MV | 19 | Compressor 1 Status Active | Read | |||
| MV | 20 | Compressor 2 Status Active | Read | |||
| MV | 21 | Compressor 3 Status Active | Read | |||
| MV | 23 | Compressor 4 Status Active | Read | |||
| MV | 36 | Compressor Arrangement Circuit 1 | Read | |||
| MV | 37 | Compressor Arrangement Circuit 2 | Read | |||
| MV | 33 | Compressor Count | Read | |||
| MV | 39 | Compressor Sequencing | Read | 1=1-2-3-4, 2=1-3-2-4 | ||
| MV | 27 | Control Package | Read | 1=Standard, 2=Critical (Lab) | ||
| MV | 47 | Damper Configuration | Read | |||
| MV | 5 | Discharge Setpoint Source Active | Read | |||
| MV | 16 | Economizer Decision Method | Read | |||
| MV | 26 | Energy Wheel Status Active | Read | |||
| MV | 28 | Entering Air Conditions Status Active | Read | 1=100% Outdoor Air (No ERV), 2=Mixed Air or ERV Conditioned Air, 3=100% Return Air | ||
| MV | 8 | Equipment Type | Read | 1=Standard DX, 2=ASHP, 3=WSHP, 4=No Cooling, 5=Chilled Water | ||
| MV | 17 | Exhaust Fan Control Source Active | Read | |||
| MV | 11 | Exhaust Fan Control Type | Read | |||
| MV | 12 | Exhaust Fan Wheel Size | Read | |||
| MVmin | 3 | Heat Cool Mode Request | Write | |||
| MV | 4 | Heat Cool Mode Status | Read | |||
| MV | 40 | Heat Pump Availability Status Active | Read | |||
| MV | 41 | Heat Pump Defrost Mode Status | Read | 1=Not ASHP, 2=Disabled, 3=Demand Defrost, 4=Defrost Fault, 5=Oil Boost, 6=Low Suction | ||
| MV | 9 | Heat Type | Read | |||
| MVmin | 1 | Occupancy Request | Write | 1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby, 5=Auto | ||
| MV | 2 | Occupancy Status Active | Read | 1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby, 5=Unknown | ||
| MVmin | 44 | Operating Mode Status Active | Read | |||
| MV | 32 | Outdoor Damper Control Source Active | Read | |||
| MV | 31 | Outdoor Dehumidification Control Type | Read | 1=Disabled, 2=Outdoor Air Dewpoint Enable Setpoint | ||
| MV | 13 | Program Control Type | Read | 1=Space Control, 2=Discharge Control, 3=Single Zone VAV, 4=Multi Zone VAV | ||
| MV | 46 | Refrigerant Type | Read | 0=Not Used, 7=410A, 17=454B | ||
| MV | 38 | Reheat Sources Active | Read | 1=None, 2=HGRH, 3=HGRH & Hot Water, 4=HGRH & Electric, 5=Hot Water, 6=Electric | ||
| MV | 29 | Return Dehumidification Control Type | Read | 1=Disabled, 2=Return Dewpoint Dehum Enable Setpoint, 3=Return Humidity Dehum Enable Setpoint | ||
| MV | 43 | Space Control Room Size | Read | 1=Small, 2=Medium, 3=Large | ||
| MV | 30 | Space Dehumidification Control Type | Read | |||
| MV | 7 | Space Temp Setpoint Source Active | Read | |||
| MV | 24 | Supply Fan Control Source Active | Read | |||
| MV | 25 | Supply Fan Control Type | Read | |||
| MV | 10 | Supply Fan Wheel Size | Read | |||
| MV | 6 | Unoccupied Control Request | Write | 1=Disabled, 2=Cool & Heat, 3=Cool, Heat, & Dehum | ||
| MV | 45 | Unoccupied Mode Status Active | Read | |||
| BV | 1 | Diagnostic: Supply Fan Failure | Read | 0=Normal, 1=Fail | ||
| BV | 25 | Diagnostic: Supply Fan Control Request Configuration | Read | 0=Normal, 1=Alarm | ||
| BV | 2 | Diagnostic: Exhaust Fan Control Request Configuration | Read | 0=Normal, 1=Alarm | ||
| BV | 24 | Diagnostic: Exhaust Fan Failure | Read | 0=Normal, 1=Fail | ||
| BV | 31 | Diagnostic: Reversing Valve Fault | Read | 0=Normal, 1=Fail | ||
| BV | 46 | Diagnostic: Not Economizing When It Should Be Economizing | Read | 0=Normal, 1=Fail | ||
| BV | 48 | Diagnostic: Damper Not Modulating | Read | 0=Normal, 1=Fail | ||
| BV | 49 | Diagnostic: Econ Mixed Air Low Limit Active | Read | 0=Normal, 1=Active | ||
| BV | 20 | Diagnostic: Energy Wheel OA Filter Status | Read | 0=Normal, 1=Clogged | ||
| BV | 21 | Diagnostic: Energy Wheel RA Filter Status | Read | 0=Normal, 1=Clogged | ||
| BV | 60 | Diagnostic: Energy Recovery Wheel Rotation Failure | Read | 0=Normal, 1=Fail | ||
| BV | 3 | Diagnostic: Damper End Switch | Read | 0=Normal, 1=Fail | ||
| BV | 6 | Diagnostic: Heat Fail Unit Lockout | Read | 0=Normal, 1=Lockout | ||
| BV | 7 | Diagnostic: Liquid Pressure Source Failure Circuit 1 | Read | 0=Normal, 1=Fail | ||
| BV | 8 | Diagnostic: Fire Shutdown | Write | 0=Normal, 1=Alarm | ||
| BV | 10 | Diagnostic: Low Discharge Air Temp Lockout | Read | 0=Normal, 1=Fail | ||
| BV | 11 | Diagnostic: Space Temperature Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 13 | Diagnostic: Outdoor Air Temperature Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 14 | Diagnostic: Outdoor Air Humidity Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 15 | Diagnostic: High Discharge Air Temp Lockout | Read | 0=Normal, 1=Fail | ||
| BV | 18 | Diagnostic: Program Control Request Configuration | Read | 0=Normal, 1=Alarm | ||
| BV | 19 | Diagnostic: Space Humidity Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 22 | Diagnostic: Compressor Heat or Cool Fail Unit Lockout | Read | 0=Normal, 1=Fail | ||
| BV | 26 | Diagnostic: Indoor Coil Filter Status | Read | 0=Normal, 1=Clogged | ||
| BV | 28 | Diagnostic: Condensate Overflow Unit Lockout | Read | 0=Normal, 1=Fail | ||
| BV | 29 | Diagnostic: Suction Pressure Source Fail Circuit 2 | Read | 0=Normal, 1=Fail | ||
| BV | 33 | Diagnostic: Outdoor Coil Water Safety Circuit Open | Read | 0=Normal, 1=Fail | ||
| BV | 35 | Diagnostic: Compressor 1 Proving Status | Read | 0=Normal, 1=Fail | ||
| BV | 36 | Diagnostic: Duct Static Pressure Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 37 | Diagnostic: Liquid Pressure Source Failure Circuit 2 | Read | 0=Normal, 1=Fail | ||
| BV | 38 | Diagnostic: Suction Pressure Source Fail Circuit 1 | Read | 0=Normal, 1=Fail | ||
| BV | 42 | Diagnostic: Heat Failure | Read | 0=Normal, 1=Fail | ||
| BV | 50 | Diagnostic: Space CO2 Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 52 | Diagnostic: Compressor 2 Proving Status | Read | 0=Normal, 1=Fail | ||
| BV | 53 | Diagnostic: Compressor 3 Proving Status | Read | 0=Normal, 1=Fail | ||
| BV | 54 | Diagnostic: Compressor 4 Proving Status | Read | 0=Normal, 1=Fail | ||
| BV | 55 | Diagnostic: Space Static Pressure Source Failure | Read | 0=Normal, 1=Fail | ||
| BV | 65 | Diagnostic: Refrigerant Leak Detected - Airstream | Read | 0=Normal, 1=Alarm | ||
| BV | 66 | Diagnostic-Refrigerant Leak Detected – Control Cabinet | Read | 0=Normal, 1=Alarm |
No points match these filters.
Object ID lookup: Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 point IDs by name
AI11Discharge Air Temperature LocalAI23Duct Static Pressure LocalAI9Exhaust Fan Piezo Pressure LocalAI13Exhaust Leaving Temperature LocalAI15Indoor Coil Leaving Air Temperature LocalAI18Liquid Line Pressure Circuit 1 LocalAI19Liquid Line Pressure Circuit 2 LocalAI7Outdoor Air Damper Position Status LocalAI10Outdoor Air Flow LocalAI22Outdoor Air Relative Humidity LocalAI21Outdoor Air Temperature LocalAI25Preheat Leaving Temperature LocalAI14Return Air Humidity LocalAI6Return Air Temperature LocalAI4Return Static Pressure LocalAI8Space CO2 Concentration LocalAI2Space Humidity LocalAI12Space Static Pressure LocalAI1Space Temperature LocalAI20Space Temperature Setpoint LocalAI24Split Exhaust-Return Pressure Differential LocalAI28Suction Line Pressure Circuit 1 LocalAI16Suction Line Pressure Circuit 2 LocalAI3Supply Fan Piezo Pressure LocalAO9Chilled Water Valve CommandAO3Compressor Speed Command Circuit 1AO8Compressor Speed Command Circuit 2AO7Condenser Fan Speed CommandAO13Energy Recovery Exhaust Bypass CommandAO6Energy Recovery Outdoor Bypass CommandAO10Energy Recovery Wheel Speed CommandAO4Exhaust Fan Speed CommandAO11Heating Output CommandAO1Hot Gas Reheat Valve CommandAO5Outdoor Air Damper Position CommandAO14Outdoor Coil Water Valve Command Circuit 1AO15Outdoor Coil Water Valve Command Circuit 2AO2Supply Fan Speed CommandAV85Cabinet TonnageAV51Compressor Control P-GainAV21Compressor Cooling Ambient Lockout SetpointAV18Compressor Heating Capacity Status ActiveAV86Compressor Modulating CapacityAV91Compressor Stage Down Delay RemainingAV90Compressor Stage Up Delay RemainingAV88Condenser Fan P-GainAV52Cooling Capacity Status ActiveAV19Damper Control P-GainAV5Dehumidification Temperature ActiveAV14Dehumidification Temperature SetpointAV77Dehumidification Temperature Setpoint ActiveAV30Discharge Air Cooling SetpointAV32Discharge Air Heating SetpointAV84Discharge Air Temperature ActiveAV66Discharge Air Temperature Setpoint ActiveAV67Discharge Air Temperature Setpoint BASAV45Discharge Air Temperature Setpoint MaximumAV43Discharge Air Temperature Setpoint MinimumAV65Duct Static Pressure ActiveAV64Duct Static Pressure BASAV46Duct Static Pressure SetpointAV55Economizer Outdoor Air Enable SetpointAV63Economizer Outdoor Air Enthalpy Enable SetpointAV54Exhaust Fan Air Flow ActiveAV57Exhaust Fan Air Flow SetpointAV40Exhaust Fan Speed Setpoint - Constant SpeedAV12Exhaust Fan Tracking Offset SetpointAV89Frost Avoidance Setpoint ActiveAV44Heating Capacity Primary Status ActiveAV61Heat Control P-GainAV92Heat Cool Switch Delay Time RemainingAV4Heat Pump Disable Temperature SetpointAV80Hot Gas Reheat Capacity Status ActiveAV60Mixed Air Temperature ActiveAV1Occupied Cooling SetpointAV2Occupied Heating SetpointAV16Occupied OffsetAV11Outdoor Air Dewpoint ActiveAV10Outdoor Air Dewpoint Enable SetpointAV68Outdoor Air Enthalpy ActiveAV38Outdoor Air Flow ActiveAV71Outdoor Air Flow SetpointAV6Outdoor Air Heating Enable Setpoint ActiveAV93Outdoor Air Heating Enable Setpoint RequestAV82Outdoor Air Humidity ActiveAV81Outdoor Air Humidity BASAV76Outdoor Air Temperature ActiveAV75Outdoor Air Temperature BASAV47Outdoor Damper Max Position SetpointAV48Outdoor Damper Min Position SetpointAV36Return Air Dewpoint ActiveAV72Return Air Enthalpy ActiveAV69Return Dewpoint Dehum Enable SetpointAV83Return Humidity Dehum Enable SetpointAV3Return Static Pressure SetpointAV78Saturated Suction Temp Circuit 1 ActiveAV79Saturated Suction Temp Circuit 2 ActiveAV50Space CO2 Concentration SetpointAV62Space CO2 Concentration ActiveAV42Space CO2 Concentration BASAV87Space Dehumidification SetpointAV35Space Dewpoint ActiveAV34Space Dewpoint Calculated Setpoint ActiveAV7Space Humidity ActiveAV8Space Humidity BASAV70Space Static Pressure ActiveAV73Space Static Pressure BASAV56Space Static Pressure SetpointAV23Space Temperature ActiveAV20Space Temperature BASAV37Space Temperature Setpoint ActiveAV25Space Temperature Setpoint BASAV41Supply Air Flow ActiveAV59Supply Air Flow Min Setpoint - CoolingAV13Supply Air Flow Min Setpoint - HeatingAV74Supply Air Flow Min Setpoint ActiveAV39Supply Air Flow SetpointAV22Supply Air Flow Setpoint ActiveAV17Supply Fan Speed Setpoint - Constant SpeedAV26Unoccupied Cooling Enable SetpointAV27Unoccupied Heating Enable SetpointAV28Unoccupied Humidity Enable SetpointAV33Ventilation Deadband High SetpointAV29Ventilation Deadband Low SetpointAV24Ventilation Setpoint High ActiveAV49Ventilation Setpoint Low ActiveBI17Compressor 1 Status LocalBI23Compressor 1 VFD Status LocalBI18Compressor 2 Status LocalBI19Compressor 3 Status LocalBI20Compressor 4 Status LocalBI10Condensate Detection InputBI5Damper End Switch Status LocalBI2Emergency StopBI12Energy Wheel OA Filter Status LocalBI11Energy Wheel RA Filter Status LocalBI15Energy Wheel Rotation Status LocalBI7Exhaust Damper End SwitchBI14Exhaust Fan StatusBI6Heat On Off Status LocalBI16Hot Water Freezestat LocalBI3Indoor Coil Filter Status LocalBI4Occupancy InputBI9Outdoor Coil Water Safety Circuit LocalBI8Phase Monitor Status LocalBI24Refrigerant Leak Detection System Input-AirstreamBI25Refrigerant Leak Detection System Input-Control CabinetBI1Supply Fan StatusBO11Compressor 1 CommandBO12Compressor 2 CommandBO5Compressor 3 CommandBO6Compressor 4 CommandBO19Condenser Fan 4 Start Stop CommandBO21Condenser Fan 5 Start Stop CommandBO14Condenser Fan VFD Start Stop CommandBO2Damper Open Close CommandBO15Energy Recovery Wheel Start Stop CommandBO9Exhaust Damper Open Close CommandBO10Exhaust Fan Start Stop CommandBO3Heat 1 CommandBO7Heat 2 CommandBO8Heat 3 CommandBO4Inducer High Speed CommandBO13Pre-Heat EnableBO16Reversing Valve Command Circuit 1BO17Reversing Valve Command Circuit 2BO18Split Exhaust-Return Damper Open Close CommandBO1Supply Fan Start Stop CommandBV16Alarm ResetBV59AUTO/STOPBV62Compressor Cooling AllowedBV61Compressor Heating AllowedBV64Compressor Low Ambient Lockout ActiveBV39Condenser Fan Pre-StartBV9Economizer ModeBV41Energy Recovery Frost Avoidance StatusBV44Free Cooling ModeBV4Heat Pump Defrost ModeBV5Hot Gas Reheat Purge ModeBV23InterlockBV32Oil Boost Cycle Circuit 1BV68Refrigerant Leak Mitigation ActiveBV12Safety CheckBV30System Lockout - Auto ResetBV17System Lockout - Manual ResetBV43Ventilation ModeMV22Cabinet SizeMV14Circuit 1 StatusMV15Circuit 2 StatusMV19Compressor 1 Status ActiveMV20Compressor 2 Status ActiveMV21Compressor 3 Status ActiveMV23Compressor 4 Status ActiveMV36Compressor Arrangement Circuit 1MV37Compressor Arrangement Circuit 2MV33Compressor CountMV39Compressor SequencingMV27Control PackageMV47Damper ConfigurationMV5Discharge Setpoint Source ActiveMV16Economizer Decision MethodMV26Energy Wheel Status ActiveMV28Entering Air Conditions Status ActiveMV8Equipment TypeMV17Exhaust Fan Control Source ActiveMV11Exhaust Fan Control TypeMV12Exhaust Fan Wheel SizeMV3Heat Cool Mode RequestMV4Heat Cool Mode StatusMV40Heat Pump Availability Status ActiveMV41Heat Pump Defrost Mode StatusMV9Heat TypeMV1Occupancy RequestMV2Occupancy Status ActiveMV44Operating Mode Status ActiveMV32Outdoor Damper Control Source ActiveMV31Outdoor Dehumidification Control TypeMV13Program Control TypeMV46Refrigerant TypeMV38Reheat Sources ActiveMV29Return Dehumidification Control TypeMV43Space Control Room SizeMV30Space Dehumidification Control TypeMV7Space Temp Setpoint Source ActiveMV24Supply Fan Control Source ActiveMV25Supply Fan Control TypeMV10Supply Fan Wheel SizeMV6Unoccupied Control RequestMV45Unoccupied Mode Status ActiveBV1Diagnostic: Supply Fan FailureBV25Diagnostic: Supply Fan Control Request ConfigurationBV2Diagnostic: Exhaust Fan Control Request ConfigurationBV24Diagnostic: Exhaust Fan FailureBV31Diagnostic: Reversing Valve FaultBV46Diagnostic: Not Economizing When It Should Be EconomizingBV48Diagnostic: Damper Not ModulatingBV49Diagnostic: Econ Mixed Air Low Limit ActiveBV20Diagnostic: Energy Wheel OA Filter StatusBV21Diagnostic: Energy Wheel RA Filter StatusBV60Diagnostic: Energy Recovery Wheel Rotation FailureBV3Diagnostic: Damper End SwitchBV6Diagnostic: Heat Fail Unit LockoutBV7Diagnostic: Liquid Pressure Source Failure Circuit 1BV8Diagnostic: Fire ShutdownBV10Diagnostic: Low Discharge Air Temp LockoutBV11Diagnostic: Space Temperature Source FailureBV13Diagnostic: Outdoor Air Temperature Source FailureBV14Diagnostic: Outdoor Air Humidity Source FailureBV15Diagnostic: High Discharge Air Temp LockoutBV18Diagnostic: Program Control Request ConfigurationBV19Diagnostic: Space Humidity Source FailureBV22Diagnostic: Compressor Heat or Cool Fail Unit LockoutBV26Diagnostic: Indoor Coil Filter StatusBV28Diagnostic: Condensate Overflow Unit LockoutBV29Diagnostic: Suction Pressure Source Fail Circuit 2BV33Diagnostic: Outdoor Coil Water Safety Circuit OpenBV35Diagnostic: Compressor 1 Proving StatusBV36Diagnostic: Duct Static Pressure Source FailureBV37Diagnostic: Liquid Pressure Source Failure Circuit 2BV38Diagnostic: Suction Pressure Source Fail Circuit 1BV42Diagnostic: Heat FailureBV50Diagnostic: Space CO2 Source FailureBV52Diagnostic: Compressor 2 Proving StatusBV53Diagnostic: Compressor 3 Proving StatusBV54Diagnostic: Compressor 4 Proving StatusBV55Diagnostic: Space Static Pressure Source FailureBV65Diagnostic: Refrigerant Leak Detected - AirstreamBV66Diagnostic-Refrigerant Leak Detected – Control Cabinet
Integration notes
- Points come from the guide's complete points list (Tables 33-39) plus the diagnostic BVs that are only printed in the diagnostics table (Table 32).
- Not all points exist on every unit; availability depends on equipment type, control program type and options.
- Multistate state texts are given where the guide prints a clean list; for the other MVs (mode status, source and fan-type objects) see Table 39 of the guide.
- BI 24 and BI 25 (refrigerant leak detection inputs) are footnoted in the guide.
- Our separate "Tracer UC600 Packaged Outdoor Air Unit" list (BAS-SVP18E) covers the older program; this V12 guide adds about 150 objects.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Horizon Outdoor Air Unit, Tracer UC600 program V12 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
How many BACnet points does the Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 have?
This list has 268 BACnet objects: 24 analog inputs, 14 analog outputs, 88 analog values, 22 binary inputs, 20 binary outputs, 57 binary values, 43 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 BACnet points are writable?
52 of the 268 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Trane Horizon Outdoor Air Unit, Tracer UC600 program V12 BACnet documentation?
The source is Horizon Tracer UC600 Programming V12 (Integration Guide) (OAU-SVP002A-EN), revision 2025-01, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/OAU-SVP002A-EN_01122025.pdf.
What are the minimum BACnet points to integrate the Trane Horizon Outdoor Air Unit, Tracer UC600 program V12?
Start with MV 1 Occupancy Request (Occupancy request from the BMS); MV 3 Heat Cool Mode Request (Heat/cool mode request); BV 59 AUTO/STOP (Manual stop (0 = Auto, 1 = Stop)); AV 1 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 2 Occupied Heating Setpoint (Occupied heating setpoint); AV 30 Discharge Air Cooling Setpoint (Discharge air cooling setpoint); BV 16 Alarm Reset (Reset manual-reset diagnostics); MV 44 Operating Mode Status Active (Operating mode status); AI 11 Discharge Air Temperature Local (Discharge air temperature); BV 17 System Lockout - Manual Reset (Manual-reset lockout active).
How do I enable BMS control of the Trane Horizon Outdoor Air Unit, Tracer UC600 program V12?
BV 59 AUTO/STOP stops the unit from the network (1 = Stop) and releases it (0 = Auto). Occupancy Request (MV 1) and Heat Cool Mode Request (MV 3) drive normal operation.
Can the BMS supply sensor values to the Trane Horizon Outdoor Air Unit, Tracer UC600 program V12?
The BAS can write Space Temperature BAS (AV 20), Space Temperature Setpoint BAS (AV 25), Space Humidity BAS (AV 8), Space CO2 Concentration BAS (AV 42), Space Static Pressure BAS (AV 73), Duct Static Pressure BAS (AV 64), Outdoor Air Temperature BAS (AV 75), Outdoor Air Humidity BAS (AV 81) and Discharge Air Temperature Setpoint BAS (AV 67); the guide ties each to the matching control program type.
How do I check these points on the real Horizon Outdoor Air Unit, Tracer UC600 program V12?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Horizon Tracer UC600 Programming V12 (Integration Guide) · OAU-SVP002A-EN · rev. 2025-01. Object names, instances and units are reproduced as published; descriptions are our own.