Water-cooled scroll chiller BACnet interface · BACnet points list

Trane BCI2-C for CGWN / CCUN chillers (CH530) BACnet points list

Updated 12 November 2026

Short answer

The BCI2-C is a non-programmable Trane controller that connects to the CH530 chiller controls over the IPC3 link and serves the chiller data on BACnet MS/TP. This list is the CGWN/CCUN column of the guide's model tables: 62 objects with low instance numbers covering water temperatures, suction and discharge pressures, compressor starts and run times, flow and alarm status. The commands are BO 1 auto/stop, BO 2 diagnostic reset and MO 1 chiller mode.

This page lists 62 BACnet objects for the Trane BCI2-C for CGWN / CCUN chillers (CH530) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
BCI2-C for CGWN / CCUN chillers (CH530)
Equipment
Water-cooled scroll chiller BACnet interface
Equipment type
Chillers
BACnet objects
62 (3 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055
Source document
Integration Guide: BACnet Communication Interface for Chillers (BCI2-C) · BAS-SVP055A-EN · rev. 04/16/2022
Download CSV 62 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane BCI2-C for CGWN / CCUN chillers (CH530)

Integration in brief

Address the BCI2-C on the MS/TP trunk and discover it. Write BO 1 auto/stop and MO 1 mode, then read back running state, leaving water temperature and capacity. BI 23 Alarm Present and BI 24 Shutdown Alarm Present are the summary alarms, BI 25 shows the last diagnostic, and BO 2 resets diagnostics remotely.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Chiller Auto Stop CommandBMS auto/stop (enable) commandWrite
MO 1Chiller Mode CommandCool/heat/ice mode commandWrite
BI 4Chiller Running StateChiller on/off statusRead
BI 2Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 45Evaporator Leaving Water TempLeaving chilled water temperatureRead
AI 5Actual Running CapacityActual running capacity in percentRead
BI 23Alarm PresentAny active alarm on the chillerRead

Enable & remote start

BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto; relinquish default True, i.e. Auto) is the BMS auto/stop. BI 1 Run Enabled shows whether the chiller is available to run, and BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of the BAS setpoints. No BAS setpoint objects are listed for this model.

Network setup

Watch out for

Trane BCI2-C for CGWN / CCUN chillers (CH530) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

62 of 62 shown
Type
Analog
Access
Show
Trane BCI2-C for CGWN / CCUN chillers (CH530) BACnet Points List
DescriptionStates
AI1Active Cool/Heat Setpoint TemperatureActive chiller water or hot water setpointTemperatureRead
AI3Active Demand Limit SetpointActive demand limit setpointPercentRead
AImin5Actual Running CapacityLevel of capacity that the chiller is currently running atPercentRead
AI8Suction Pressure- Ckt 1Circuit 1 suction pressurePressureRead
AI11Suction Pressure- Ckt 2Circuit 2 suction pressurePressureRead
AI13Suction Saturated Refrigerant Temperature- Ckt 1Circuit 1 suction refrigerant temperatureTemperatureRead
AI15Suction Saturated Refrigerant Temperature- Ckt 2Circuit 2 suction refrigerant temperatureTemperatureRead
AI17Discharge Pressure- Ckt 1Circuit 1 discharge pressurePressureRead
AI21Discharge Saturated Refrigerant Temperature- Ckt 1Circuit 1 discharge refrigerant temperatureTemperatureRead
AI23Discharge Saturated Refrigerant Temperature- Ckt 2Circuit 2 discharge refrigerant temperatureTemperatureRead
AI25Local Atmospheric PressureLocal atmospheric pressurePressureRead
AI26Starts- Compressor 1ANumber of starts for compressor 1ARead
AI27Starts- Compressor 1BNumber of starts for compressor 1BRead
AI30Starts- Compressor 1CNumber of starts for compressor 1CRead
AI31Starts- Compressor 2ANumber of starts for compressor 2ARead
AI32Starts- Compressor 2BNumber of starts for compressor 2BRead
AI33Starts- Compressor 2CNumber of starts for compressor 2CRead
AI34Run Time- Compressor 1ATotal run time of compressor 1ATimeRead
AI35Run Time- Compressor 1BTotal run time of compressor 1BTimeRead
AI38Run Time- Compressor 1CTotal run time of compressor 1CTimeRead
AI39Run Time- Compressor 2ATotal run time of compressor 2ATimeRead
AI40Run Time- Compressor 2BTotal run time of compressor 2BTimeRead
AI41Run Time- Compressor 2CTotal run time of compressor 2CTimeRead
AI42Airflow Percentage- Circuit 1Approximate airflow percentage of circuit 1PercentRead
AI43Airflow Percentage- Circuit 2Approximate airflow percentage of circuit 2PercentRead
AI44Evaporator Entering Water TempTemperature of the water entering the evaporatorTemperatureRead
AImin45Evaporator Leaving Water TempTemperature of the water leaving the evaporatorTemperatureRead
AI46Condenser Entering Water TempTemperature of the water entering the condenserTemperatureRead
AI47Condenser Leaving Water TempTemperature of the water leaving the condenserTemperatureRead
AI57Outdoor Air TemperatureOutdoor air temperatureTemperatureRead
AI95Number of CircuitsNumber of CircuitsNoneRead
AI96Number of Compressors, Ckt 1Number of Compressors, Ckt 1NoneRead
AI97Number of Compressors, Ckt 2Number of Compressors, Ckt 2NoneRead
AI98Chiller Design CapacityDesign Capacity of the ChillerNoneRead
BI1Run EnabledThe chiller is available to run or is currently runningReadInactive = Stop, Active = Auto
BImin2Local Setpoint ControlThe chiller is being controlled by local setpoints instead of BAS setpointsReadInactive = Remote Control, Active = Local Control
BI3Capacity LimitedConditions may exist that prevent the chiller from reaching setpointReadInactive = Not Limited, Active = Limited
BImin4Chiller Running StateThe chiller is running or stoppedReadInactive = Off, Active = On
BI5Condenser Water Flow StatusCondenser water flow statusReadInactive = No Flow, Active = Flow
BI6Maximum CapacityAll available chiller capacity is being usedReadInactive = Off, Active = On
BI9Compressor 1A RunningCompressor 1A is runningReadInactive = Off, Active = Running
BI10Compressor 1B RunningCompressor 1B is runningReadInactive = Off, Active = Running
BI13Compressor 1C RunningCompressor 1C is runningReadInactive = Off, Active = Running
BI14Compressor 2A RunningCompressor 2A is runningReadInactive = Off, Active = Running
BI15Compressor 2B RunningCompressor 2B is runningReadInactive = Off, Active = Running
BI16Compressor 2C RunningCompressor 2C is runningReadInactive = Off, Active = Running
BI17Evaporator Water Pump RequestA request from the chiller to turn on the evaporator water pumpReadInactive = Off, Active = On
BI19Condenser Water Pump RequestA request from the chiller to turn on the condenser water pumpReadInactive = Off, Active = On
BI22Evaporator Water Flow StatusWater is flowing through the evaporatorReadInactive = No Flow, Active = Flow
BImin23Alarm PresentAn alarm is activeReadInactive = No Alarm, Active = Alarm
BI24Shutdown Alarm PresentA shutdown alarm is activeReadInactive = No Alarm, Active = Alarm
BI25Last DiagnosticLast diagnostic for the chillerReadInactive = Off, Active = On
BOmin1Chiller Auto Stop CommandAllows the chiller to run if conditions for running are metWriteInactive = Stop, Active = Auto
BO2Remote Diagnostic Reset CommandResets remotely diagnostics that can be resetWriteInactive = No Reset Request, Active = Reset Request
MI1Running ModePrimary running mode of the chillerRead1 = Chiller Off, 2 = Chiller in Start Mode, 3 = Chiller in Run Mode, 4 = Chiller in Pre-shutdown Mode, 5 = Chiller in Service Mode
MI2Operating ModePrimary operating mode of the chillerRead1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (chiller set up for ice making), 4 = Not Used
MI3MP Communication StatusDo Not Use This PointReadDo Not Use This Point
MI4Refrigerant TypeRefrigerant typeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134A, 6 = R407C, 7 = R-410A
MI5Model InformationModel type of the chillerRead1 = RTA, 2 = CVH, 3 = CVG, 4 = CVR, 5 = CDH, 6 = RTH, 7 = CGW, 8 = CGA, 9 = CCA, 10 = RTW, 11 = RTX, 12 = RTU, 13 = CCU, 14 = CXA, 15 = CGC, 16 = RAU
MI6Cooling TypeCooling type of the condenserRead1 = Water Cooled, 2 = Air Cooled
MI7Manufacturing LocationLocation where chiller was manufacturedRead1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey
MOmin1Chiller Mode CommandMode of operation of the chillerWrite1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (chiller set up for ice making), 4 = Not Used
Object ID lookup: Trane BCI2-C for CGWN / CCUN chillers point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BCI2-C for CGWN / CCUN chillers (CH530) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane BCI2-C for CGWN / CCUN chillers (CH530)

How many BACnet points does the Trane BCI2-C for CGWN / CCUN chillers (CH530) have?

This list has 62 BACnet objects: 34 analog inputs, 18 binary inputs, 2 binary outputs, 7 multi-state inputs, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane BCI2-C for CGWN / CCUN chillers (CH530) BACnet points are writable?

3 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane BCI2-C for CGWN / CCUN chillers (CH530) BACnet documentation?

The source is Integration Guide: BACnet Communication Interface for Chillers (BCI2-C) (BAS-SVP055A-EN), revision 04/16/2022, published free by Trane at https://support.trane.com/hc/article_attachments/49472973334925.

What are the minimum BACnet points to integrate the Trane BCI2-C for CGWN / CCUN chillers (CH530)?

Start with BO 1 Chiller Auto Stop Command (BMS auto/stop (enable) command); MO 1 Chiller Mode Command (Cool/heat/ice mode command); BI 4 Chiller Running State (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 45 Evaporator Leaving Water Temp (Leaving chilled water temperature); AI 5 Actual Running Capacity (Actual running capacity in percent); BI 23 Alarm Present (Any active alarm on the chiller).

How do I enable BMS control of the Trane BCI2-C for CGWN / CCUN chillers (CH530)?

BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto; relinquish default True, i.e. Auto) is the BMS auto/stop. BI 1 Run Enabled shows whether the chiller is available to run, and BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of the BAS setpoints. No BAS setpoint objects are listed for this model.

How do I check these points on the real BCI2-C for CGWN / CCUN chillers (CH530)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide: BACnet Communication Interface for Chillers (BCI2-C) · BAS-SVP055A-EN · rev. 04/16/2022. Object names, instances and units are reproduced as published; descriptions are our own.