Water-cooled screw chiller BACnet interface · BACnet points list

Trane BCI2-C for RTWD / RTUD chillers (CH530) BACnet points list

Updated 12 November 2026

Short answer

The BCI2-C is a non-programmable Trane controller that connects to the CH530 chiller controls over the IPC3 link and serves the chiller data on BACnet MS/TP. This list is the RTWD column of the guide's model tables: 102 objects with low instance numbers. The BAS writes chilled and hot water setpoints and current limit (AO), auto/stop and diagnostic reset (BO) and chiller mode (MO); everything else is read-only water, refrigerant, oil, compressor and electrical data.

This page lists 102 BACnet objects for the Trane BCI2-C for RTWD / RTUD chillers (CH530) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
BCI2-C for RTWD / RTUD chillers (CH530)
Equipment
Water-cooled screw chiller BACnet interface
Equipment type
Chillers
BACnet objects
102 (6 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055
Source document
Integration Guide: BACnet Communication Interface for Chillers (BCI2-C) · BAS-SVP055A-EN · rev. 04/16/2022
Download CSV 102 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane BCI2-C for RTWD / RTUD chillers (CH530)

Integration in brief

Address the BCI2-C on the MS/TP trunk and discover it. Write BO 1 auto/stop, MO 1 mode, AO 1 chilled water setpoint and AO 2 current limit, then read back running state, leaving water temperature and capacity. BI 23 Alarm Present and BI 24 Shutdown Alarm Present are the summary alarms, and BI 25 shows the last diagnostic.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Chiller Auto Stop CommandBMS auto/stop (enable) commandWrite
MO 1Chiller Mode CommandCool/heat/ice mode commandWrite
AO 1Chilled Water SetpointChilled water setpoint from the BMSWrite
AO 2Current Limit SetpointCurrent (capacity) limit from the BMS, %Write
BI 4Chiller Running StateChiller on/off statusRead
BI 2Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 45Evaporator Leaving Water TempLeaving chilled water temperatureRead
AI 5Actual Running CapacityActual running capacity in percentRead
BI 23Alarm PresentAny active alarm on the chillerRead

Enable & remote start

BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto; relinquish default True, i.e. Auto) is the BMS auto/stop. BI 1 Run Enabled shows whether the chiller is available to run, and BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of the BAS setpoints.

Network setup

Watch out for

Trane BCI2-C for RTWD / RTUD chillers (CH530) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

102 of 102 shown
Type
Access
Show
Trane BCI2-C for RTWD / RTUD chillers (CH530) BACnet Points List
DescriptionStates
AI1Active Cool/Heat Setpoint TemperatureActive chiller water or hot water setpointTemperatureRead
AI2Active Current Limit SetpointActive capacity current limit setpointPercentRead
AImin5Actual Running CapacityLevel of capacity that the chiller is currently running atPercentRead
AI7Suction Pressure- Ckt 1Circuit 1 suction pressurePressureRead
AI10Suction Pressure- Ckt 2Circuit 2 suction pressurePressureRead
AI12Evaporator Saturated Refrigerant Temperature- Ckt 1Circuit 1 evaporator refrigerant temperatureTemperatureRead
AI14Evaporator Saturated Refrigerant Temperature- Ckt 2Circuit 2 evaporator refrigerant temperatureTemperatureRead
AI16Condenser Refrigerant Pressure- Ckt 1Circuit 1 condenser refrigerant pressurePressureRead
AI18Condenser Refrigerant Pressure- Ckt 2Circuit 2 condenser refrigerant pressurePressureRead
AI20Condenser Saturated Refrigerant Temperature- Ckt 1Circuit 1 condenser refrigerant temperatureTemperatureRead
AI22Condenser Saturated Refrigerant Temperature- Ckt 2Circuit 2 condenser refrigerant temperatureTemperatureRead
AI24Unit Power ConsumptionThe power being consumed by the chillerPowerRead
AI25Local Atmospheric PressureLocal atmospheric pressurePressureRead
AI26Starts- Compressor 1ANumber of starts for compressor 1ARead
AI27Starts- Compressor 1BNumber of starts for compressor 1BRead
AI28Starts- Compressor 2ANumber of starts for compressor 2ARead
AI29Starts- Compressor 2BNumber of starts for compressor 2BRead
AI34Run Time- Compressor 1ATotal run time of compressor 1ATimeRead
AI35Run Time- Compressor 1BTotal run time of compressor 1BTimeRead
AI36Run Time- Compressor 2ATotal run time of compressor 2ATimeRead
AI37Run Time- Compressor 2BTotal run time of compressor 2BTimeRead
AI44Evaporator Entering Water TempTemperature of the water entering the evaporatorTemperatureRead
AImin45Evaporator Leaving Water TempTemperature of the water leaving the evaporatorTemperatureRead
AI46Condenser Entering Water TempTemperature of the water entering the condenserTemperatureRead
AI47Condenser Leaving Water TempTemperature of the water leaving the condenserTemperatureRead
AI48High Side Oil Pressure- Compressor 1APressure of the oil at the high side of compressor 1APressureRead
AI49High Side Oil Pressure- Compressor 1BPressure of the oil at the high side of compressor 1BPressureRead
AI50High Side Oil Pressure- Compressor 2APressure of the oil at the high side of compressor 2APressureRead
AI51High Side Oil Pressure- Compressor 2BPressure of the oil at the high side of compressor 2BPressureRead
AI57Outdoor Air TemperatureOutdoor air temperatureTemperatureRead
AI58Condenser Control OutputPercentage of condenser water flow being requested by the chillerPercentRead
AI59Phase AB Voltage- Compressor 1APhase AB voltage, compressor 1AVoltageRead
AI60Phase BC Voltage- Compressor 1APhase BC voltage, compressor 1AVoltageRead
AI61Phase CA Voltage- Compressor 1APhase CA voltage, compressor 1AVoltageRead
AI62Phase AB Voltage- Compressor 1BPhase AB voltage, compressor 1BVoltageRead
AI63Phase BC Voltage- Compressor 1BPhase BC voltage, compressor 1BVoltageRead
AI64Phase CA Voltage- Compressor 1BPhase CA voltage, compressor 1BVoltageRead
AI65Phase AB Voltage- Compressor 2APhase AB voltage, compressor 2AVoltageRead
AI66Phase BC Voltage- Compressor 2APhase BC voltage, compressor 2AVoltageRead
AI67Phase CA Voltage- Compressor 2APhase CA voltage, compressor 2AVoltageRead
AI68Phase AB Voltage- Compressor 2BPhase AB voltage, compressor 2BVoltageRead
AI69Phase BC Voltage- Compressor 2BPhase BC voltage, compressor 2BVoltageRead
AI70Phase CA Voltage- Compressor 2BPhase CA voltage, compressor 2BVoltageRead
AI71Line 1 Current (in Amps)- Compressor 1ALine 1 Current (in Amps)- Compressor 1ACurrentRead
AI72Line 2 Current (in Amps)- Compressor 1ALine 2 Current (in Amps)- Compressor 1ACurrentRead
AI73Line 3 Current (in Amps)- Compressor 1ALine 3 Current (in Amps)- Compressor 1ACurrentRead
AI74Line 1 Current (in Amps)- Compressor 1BLine 1 Current (in Amps)- Compressor 1BCurrentRead
AI75Line 2 Current (in Amps)- Compressor 1BLine 2 Current (in Amps)- Compressor 1BCurrentRead
AI76Line 3 Current (in Amps)- Compressor 1BLine 3 Current (in Amps)- Compressor 1BCurrentRead
AI77Line 1 Current (in Amps)- Compressor 2ALine 1 Current (in Amps)- Compressor 2ACurrentRead
AI78Line 2 Current (in Amps)- Compressor 2ALine 2 Current (in Amps)- Compressor 2ACurrentRead
AI79Line 3 Current (in Amps)- Compressor 2ALine 3 Current (in Amps)- Compressor 2ACurrentRead
AI80Line 1 Current (in Amps)- Compressor 2BLine 1 Current (in Amps)- Compressor 2BCurrentRead
AI81Line 2 Current (in Amps)- Compressor 2BLine 2 Current (in Amps)- Compressor 2BCurrentRead
AI82Line 3 Current (in Amps)- Compressor 2BLine 3 Current (in Amps)- Compressor 2BCurrentRead
AI83Line 1 Current (%RLA)- Compressor 1ALine 1 Current (%RLA)- Compressor 1APercentRead
AI84Line 2 Current (%RLA)- Compressor 1ALine 2 Current (%RLA)- Compressor 1APercentRead
AI85Line 3 Current (%RLA)- Compressor 1ALine 3 Current (%RLA)- Compressor 1APercentRead
AI86Line 1 Current (%RLA)- Compressor 1BLine 1 Current (%RLA)- Compressor 1BPercentRead
AI87Line 2 Current (%RLA)- Compressor 1BLine 2 Current (%RLA)- Compressor 1BPercentRead
AI88Line 3 Current (%RLA)- Compressor 1BLine 3 Current (%RLA)- Compressor 1BPercentRead
AI89Line 1 Current (%RLA)- Compressor 2ALine 1 Current (%RLA)- Compressor 2APercentRead
AI90Line 2 Current (%RLA)- Compressor 2ALine 2 Current (%RLA)- Compressor 2APercentRead
AI91Line 3 Current (%RLA)- Compressor 2ALine 3 Current (%RLA)- Compressor 2APercentRead
AI92Line 1 Current (%RLA)- Compressor 2BLine 1 Current (%RLA)- Compressor 2BPercentRead
AI93Line 2 Current (%RLA)- Compressor 2BLine 2 Current (%RLA)- Compressor 2BPercentRead
AI94Line 3 Current (%RLA)- Compressor 2BLine 3 Current (%RLA)- Compressor 2BPercentRead
AI95Number of CircuitsNumber of CircuitsNoneRead
AI96Number of Compressors, Ckt 1Number of Compressors, Ckt 1NoneRead
AI97Number of Compressors, Ckt 2Number of Compressors, Ckt 2NoneRead
AI98Chiller Design CapacityDesign Capacity of the ChillerNoneRead
AOmin1Chilled Water SetpointDesired leaving water temperature if chiller is in cooling modeTemperatureWrite
AOmin2Current Limit SetpointSets the maximum capacity that the chiller can usePercentWrite
AO4Hot Water SetpointDesired leaving water temperature if chiller is in heating modeTemperatureWrite
BI1Run EnabledThe chiller is available to run or is currently runningReadInactive = Stop, Active = Auto
BImin2Local Setpoint ControlThe chiller is being controlled by local setpoints instead of BAS setpointsReadInactive = Remote Control, Active = Local Control
BI3Capacity LimitedConditions may exist that prevent the chiller from reaching setpointReadInactive = Not Limited, Active = Limited
BImin4Chiller Running StateThe chiller is running or stoppedReadInactive = Off, Active = On
BI5Condenser Water Flow StatusCondenser water flow statusReadInactive = No Flow, Active = Flow
BI6Maximum CapacityAll available chiller capacity is being usedReadInactive = Off, Active = On
BI7Head Relief RequestThe chiller is asking an outside system to provide more heat rejectionReadInactive = Off, Active = On
BI9Compressor 1A RunningCompressor 1A is runningReadInactive = Off, Active = Running
BI10Compressor 1B RunningCompressor 1B is runningReadInactive = Off, Active = Running
BI11Compressor 2A RunningCompressor 2A is runningReadInactive = Off, Active = Running
BI12Compressor 2B RunningCompressor 2B is runningReadInactive = Off, Active = Running
BI17Evaporator Water Pump RequestA request from the chiller to turn on the evaporator water pumpReadInactive = Off, Active = On
BI19Condenser Water Pump RequestA request from the chiller to turn on the condenser water pumpReadInactive = Off, Active = On
BI20Noise Reduction ActiveThe chiller is in a state where noise is being reducedReadInactive = Off, Active = On
BI22Evaporator Water Flow StatusWater is flowing through the evaporatorReadInactive = No Flow, Active = Flow
BImin23Alarm PresentAn alarm is activeReadInactive = No Alarm, Active = Alarm
BI24Shutdown Alarm PresentA shutdown alarm is activeReadInactive = No Alarm, Active = Alarm
BI25Last DiagnosticLast diagnostic for the chillerReadInactive = Off, Active = On
BOmin1Chiller Auto Stop CommandAllows the chiller to run if conditions for running are metWriteInactive = Stop, Active = Auto
BO2Remote Diagnostic Reset CommandResets remotely diagnostics that can be resetWriteInactive = No Reset Request, Active = Reset Request
MI1Running ModePrimary running mode of the chillerRead1 = Chiller Off, 2 = Chiller in Start Mode, 3 = Chiller in Run Mode, 4 = Chiller in Pre-shutdown Mode, 5 = Chiller in Service Mode
MI2Operating ModePrimary operating mode of the chillerRead1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (chiller set up for ice making), 4 = Not Used
MI3MP Communication StatusDo Not Use This PointReadDo Not Use This Point
MI4Refrigerant TypeRefrigerant typeRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134A, 6 = R407C, 7 = R-410A
MI5Model InformationModel type of the chillerRead1 = RTA, 2 = CVH, 3 = CVG, 4 = CVR, 5 = CDH, 6 = RTH, 7 = CGW, 8 = CGA, 9 = CCA, 10 = RTW, 11 = RTX, 12 = RTU, 13 = CCU, 14 = CXA, 15 = CGC, 16 = RAU
MI6Cooling TypeCooling type of the condenserRead1 = Water Cooled, 2 = Air Cooled
MI7Manufacturing LocationLocation where chiller was manufacturedRead1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey
MOmin1Chiller Mode CommandMode of operation of the chillerWrite1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (chiller set up for ice making), 4 = Not Used
Object ID lookup: Trane BCI2-C for RTWD / RTUD chillers point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BCI2-C for RTWD / RTUD chillers (CH530) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane BCI2-C for RTWD / RTUD chillers (CH530)

How many BACnet points does the Trane BCI2-C for RTWD / RTUD chillers (CH530) have?

This list has 102 BACnet objects: 71 analog inputs, 3 analog outputs, 18 binary inputs, 2 binary outputs, 7 multi-state inputs, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane BCI2-C for RTWD / RTUD chillers (CH530) BACnet points are writable?

6 of the 102 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane BCI2-C for RTWD / RTUD chillers (CH530) BACnet documentation?

The source is Integration Guide: BACnet Communication Interface for Chillers (BCI2-C) (BAS-SVP055A-EN), revision 04/16/2022, published free by Trane at https://support.trane.com/hc/article_attachments/49472973334925.

What are the minimum BACnet points to integrate the Trane BCI2-C for RTWD / RTUD chillers (CH530)?

Start with BO 1 Chiller Auto Stop Command (BMS auto/stop (enable) command); MO 1 Chiller Mode Command (Cool/heat/ice mode command); AO 1 Chilled Water Setpoint (Chilled water setpoint from the BMS); AO 2 Current Limit Setpoint (Current (capacity) limit from the BMS, %); BI 4 Chiller Running State (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 45 Evaporator Leaving Water Temp (Leaving chilled water temperature); AI 5 Actual Running Capacity (Actual running capacity in percent); BI 23 Alarm Present (Any active alarm on the chiller).

How do I enable BMS control of the Trane BCI2-C for RTWD / RTUD chillers (CH530)?

BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto; relinquish default True, i.e. Auto) is the BMS auto/stop. BI 1 Run Enabled shows whether the chiller is available to run, and BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of the BAS setpoints.

How do I check these points on the real BCI2-C for RTWD / RTUD chillers (CH530)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide: BACnet Communication Interface for Chillers (BCI2-C) · BAS-SVP055A-EN · rev. 04/16/2022. Object names, instances and units are reproduced as published; descriptions are our own.