Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card) · BACnet points list

York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet points list

Updated 4 November 2026

Short answer

YVWA chillers connect to a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the unit, write the chilled liquid setpoint, current limit and heating setpoint, and switch between chiller and heat pump mode. Read-only points cover chilled and condenser liquid temperatures, per-system pressures, % FLA, hours and starts, VSD values, valve positions and multistate operational and fault codes per system.

This page lists 76 BACnet objects for the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
Equipment
Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
Equipment type
Chillers
BACnet objects
76 (6 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 3.3.0.18
Default device instance
5000 + MAC address
Also known as
YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1
Source document
YVWA SC-EQ BAS Points List · rev. Rev 2.1, 2019-11-05
Download CSV 76 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)

Integration in brief

Put the chiller in remote control (BV 20 reads Remote), then start/stop it with BV 1 and write the chilled liquid setpoint (AV 1) and current limit (AV 2); heat pump units also take BV 3 (mode) and AV 4 (heating setpoint). Read BV 5 for chiller run, the leaving chilled liquid temperature, VSD frequency and BV 6 for the chiller alarm; the fault code MVs give the cause.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM START STOP CMDRemote start/stop (1 = run)Command
AV 1REM CHILLED LIQ SETPOINTRemote chilled liquid setpointCommand
AV 2REM CURRENT LIMIT SETPRemote current limit, %Command
BV 5CHILLER RUNChiller runningRead
BV 20LOCAL REMOTE CONTROL MODEMust read Remote (1) for BMS controlRead
AV 5LEAVING CHILLED LIQ TEMPLeaving chilled liquid temperatureRead
AV 27VSD OUTPUT FREQUENCYCompressor VSD frequency (load indication)Read
BV 6CHILLER ALARMChiller alarm activeRead
MV 2SYS 1 FAULT CODE / FAULT CODEFault/inhibit code, Sys 1 or unit (1 = none)Read

Enable & remote start

BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. On heat pump units BV 3 selects chiller or heat pump operation.

Network setup

Watch out for

York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

76 of 76 shown
Type
AnalogBinaryMulti-state
Access
Show
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM CHILLED LIQ SETPOINTRemote Chilled Liquid Setpoint°FCommand
AVmin2REM CURRENT LIMIT SETPRemote Current Limit Setpoint%Command
AV4REM HEATING SETPOINTRemote Heating Setpoint°FCommand
BVmin1REM START STOP CMDRemote Start / Stop CommandCommand0=Stop, 1=Run
BV3REM OPERATING MODERemote Operating ModeCommand0=Chiller, 1=Heatpump
BV4HISTORY REQUESTHistory buffer 1 request (live / history data)Command0=Live Data, 1=History 1 Data
AVmin5LEAVING CHILLED LIQ TEMPLeaving Chilled Liquid Temp°FRead
AV6ENTERING CHILLED LIQ TEMPEntering Chilled Liquid Temp°FRead
AV7VSD INT AMBIENT TEMPVSD Internal Ambient Temp°FRead
AV8LEAVING COND LIQ TEMPLeaving Condenser Liquid Temp°FRead
AV9SYS 1 DISCH TEMPSys 1 Discharge Temperature°FRead
AV11ENTERING COND LIQ TEMPEntering Condenser Liquid Temp°FRead
AV12SYS 1 OIL PRESSSys 1 Oil PressurePSIGRead
AV13SYS 1 EVAP PRESSSys 1 Evaporator PressurePSIGRead
AV14SYS 1 DISCH PRESSSys 1 Discharge PressurePSIGRead
AV15SYS 1 COMP PCT FLASys 1 Compressor % Full Load Amps%Read
AV16SYS 1 HOURSSys 1 Total Run HoursHrRead
AV17SYS 1 STARTSSys 1 Total Number of StartsRead
AV18SYS 1 HIGHEST MOTOR TEMPSys 1 Highest Motor Temp°FRead
AV19SYS 2 HIGHEST MOTOR TEMPSys 2 Highest Motor Temp°FRead
AV20SYS 1 ECON TEMPSys 1 Economizer Temperature°FRead
AV21SYS 2 OIL PRESSSys 2 Oil PressurePSIGRead
AV22SYS 2 EVAP PRESSSys 2 Evaporator PressurePSIGRead
AV23SYS 2 DISCH PRESSSys 2 Discharge PressurePSIGRead
AV24SYS 2 COMP PCT FLASys 2 Compressor % Full Load Amps%Read
AV25SYS 2 HOURSSys 2 Total Run HoursHrRead
AV26SYS 2 STARTSSys 2 Total Number of StartsRead
AVmin27VSD OUTPUT FREQUENCYVSD Output FrequencyHzRead
AV28SYS 1 COND LEVEL VALVE PCTSys 1 Condenser Level Control Valve % Open%Read
AV29SYS 2 COND LEVEL VALVE PCTSys 2 Condenser Level Control Valve % Open%Read
BVmin5CHILLER RUNChiller RunRead0=Off, 1=On
BVmin6CHILLER ALARMChiller Alarm (0=No Alarm, 1=Alarm Active)Read0=No Alarm, 1=Alarm Active
BV7VSD AUX COOLANT PUMPVSD aux coolant pump (aux pump control enabled)Read0=Off, 1=On
BV8EVAP COND PUMP STATUSEvaporator/Condenser Pump StatusRead0=Off, 1=On
BV9SYS 1 COMP RUN STATUSSys 1 Compressor Run StatusRead0=Off, 1=On
BV10SYS 2 COMP RUN STATUSSys 2 Compressor Run StatusRead0=Off, 1=On
BV11SYS 1 VI STEP SOL VALVE 1 STATUSSys 1 VI Step Solenoid Valve 1 StatusRead0=Off, 1=On
BV12SYS 2 VI STEP SOL VALVE 1 STATUSSys 2 VI Step Solenoid Valve 1 StatusRead0=Off, 1=On
BV13SYS 1 VI STEP SOL VALVE 2 STATUSSys 1 VI Step Solenoid Valve 2 StatusRead0=Off, 1=On
BV14SYS 2 VI STEP SOL VALVE 2 STATUSSys 2 VI Step Solenoid Valve 2 StatusRead0=Off, 1=On
BV15SYS 1 OIL LEVEL SWITCH STATUSSys 1 oil level switch status (oil level option)Read0=Off, 1=On
BV16SYS 2 OIL LEVEL SWITCH STATUSSys 2 oil level switch status (oil level option)Read0=Off, 1=On
BV17SYS 1 LIQ REF INJ VALVE STATUSSys 1 Liquid Refrigerant Injection Valve StatusRead0=Off, 1=On
BV18SYS 2 LIQ REF INJ VALVE STATUSSys 2 Liquid Refrigerant Injection Valve StatusRead0=Off, 1=On
BV19COOLING TYPECooling TypeRead0=Water, 1=Glycol
BVmin20LOCAL REMOTE CONTROL MODELocal Remote Control ModeRead0=Local, 1=Remote
BV21DISPLAY UNITSDisplay UnitsRead0=Imperial, 1=SI
BV22SYS 1 HOT GAS BYPASS VALVE STATUSSys 1 hot gas bypass valve status (hot gas option)Read0=Off, 1=On
BV23SYS 2 HOT GAS BYPASS VALVE STATUSSys 2 hot gas bypass valve status (hot gas option)Read0=Off, 1=On
BV24HEATPUMPHeatpumpRead0=No, 1=Yes
MV1SYS 1 OPERATIONAL CODESys 1 Operational CodeRead64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 69=Chilled Evap Water Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Invalid Serial Number, 72=Condenser Liquid Flow Switch Shutdown, 73=VSD Shutdown - Requesting Fault Data, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Evaporator Pressure Limiting, 82=Motor Current Limiting, 83=OPD Mitigation, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temperature Limiting, 89=VSD Internal Ambient Temperature Limiting, 90=Leaving Chilled Liquid Temperaure Limiting, 91=Oil Filter Clogged, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown
AV501SYS 1 OPERATIONAL CODE AVSys 1 Operational Code AVRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 68=Chilled Evap Water Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Invalid Serial Number, 71=Condenser Liquid Flow Switch Shutdown, 72=VSD Shutdown - Requesting Fault Data, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Evaporator Pressure Limiting, 81=Motor Current Limiting, 82=OPD Mitigation, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temperature Limiting, 88=VSD Internal Ambient Temperature Limiting, 89=Leaving Chilled Liquid Temperaure Limiting, 90=Oil Filter Clogged, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown
MVmin2SYS 1 FAULT CODE / FAULT CODESys 1 fault code (two-compressor units) or unit fault code (one-compressor units)ReadTwo-compressor units: 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload, 19=CT Plug Fault, 20=High Leaving Condenser Liquid Temp, 21=VSD Initialization Failure, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Sys Low Evap Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Sys Low Evap Press LCHLT. One-compressor units: 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=High Leaving Condenser Liquid Temp, 8=VSD Communications Failure, 9=VSD Initialization Failure, 10=Filter - High Heatsink Temperature, 11=Filter - High DC Bus Voltage, 12=Filter - High Phase C Current, 13=Filter - High Phase B Current, 14=Filter - High Phase A Current, 15=Filter - Phase Locked Loop, 16=Filter - Logic Board Power Supply, 17=Filter - Precharge - Low DC Bus Voltage 2, 18=Filter - Precharge - Low DC Bus Voltage 1, 19=Filter - Low DC Bus Voltage, 20=Filter - DC Bus Voltage Imbalance, 21=Filter - Input Current Overload, 22=Filter - Run Signal, 23=Filter - DC Current Transformer 1, 24=Filter - DC Current Transformer 2, 25=Filter - High Baseplate Temperature (Vyper), 26=IEEE-519 Filter Fault, 28=High Discharge Pressure (Software), 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=VSD - Precharge - Low DC Bus Voltage 1, 39=VSD - Precharge - DC Bus Voltage Imbalance, 40=VSD - High DC Bus Voltage, 41=VSD - Low DC Bus Voltage, 42=VSD - DC Bus Voltage Imbalance, 43=VSD - 105 % Motor Current Overload, 44=VSD - 105 % Motor Current Overload, 45=VSD - Motor Current Imbalance, 46=VSD - High Inverter Baseplate Temperature, 47=VSD - Single Phase Input Voltage, 48=VSD - Run Signal, 49=High Discharge Press ( HPCO), 50=Low Evaporator Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Low Evap Press LCHLT, 59=VSD - Precharge - Low DC Bus Voltage 2, 60=VSD - Precharge Lockout, 61=VSD - Serial Receive, 62=VSD - High Phase A Motor Current, 63=VSD - High Phase B Motor Current, 101=VSD - High Phase C Motor Current, 102=VSD - Phase A Gate Driver, 103=VSD - Phase B Gate Driver, 104=VSD - Phase C Gate Driver, 105=VSD - High Phase A Inverter Baseplate Temperature, 106=VSD - High Phase B Inverter Baseplate Temperature, 107=VSD - High Phase C Inverter Baseplate Temperature, 108=VSD - High Converter Heatsink Temperature, 109=VSD - Low Inverter Baseplate Temperature, 110=VSD - Low Phase A Inverter Baseplate Temperature, 111=VSD - Low Phase B Inverter Baseplate Temperature, 112=VSD - Low Phase C Inverter Baseplate Temperature, 113=VSD - Low Converter Heatsink Temperature, 114=VSD - High Internal Ambient Temperature, 115=VSD - Logic Board Power Supply, 116=VSD - Invalid Current Scale Selection, 117=VSD - High Phase A Inverter Heatsink Temperature, 118=VSD - High Phase B Inverter Heatsink Temperature, 119=VSD - High Phase C Inverter Heatsink Temperature, 120=VSD - Low Phase A Inverter Heatsink Temperature, 121=VSD - Low Phase B Inverter Heatsink Temperature, 122=VSD - Low Phase C Inverter Heatsink Temperature, 123=VSD - Logic Board Processor, 124=VSD – Undefined Fault
AV502SYS 1 FAULT CODE AV / FAULT CODE AVSys 1 / unit fault code, raw value (see MV 2)ReadTwo-compressor units: 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload, 18=CT Plug Fault, 19=High Leaving Condenser Liquid Temp, 20=VSD Initialization Failure, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Sys Low Evap Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Sys Low Evap Press LCHLT. One-compressor units: 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=High Leaving Condenser Liquid Temp, 7=VSD Communications Failure, 8=VSD Initialization Failure, 9=Filter - High Heatsink Temperature, 10=Filter - High DC Bus Voltage, 11=Filter - High Phase C Current, 12=Filter - High Phase B Current, 13=Filter - High Phase A Current, 14=Filter - Phase Locked Loop, 15=Filter - Logic Board Power Supply, 16=Filter - Precharge - Low DC Bus Voltage 2, 17=Filter - Precharge - Low DC Bus Voltage 1, 18=Filter - Low DC Bus Voltage, 19=Filter - DC Bus Voltage Imbalance, 20=Filter - Input Current Overload, 21=Filter - Run Signal, 22=Filter - DC Current Transformer 1, 23=Filter - DC Current Transformer 2, 24=Filter - High Baseplate Temperature (Vyper), 25=IEEE-519 Filter Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=VSD - Precharge - Low DC Bus Voltage 1, 38=VSD - Precharge - DC Bus Voltage Imbalance, 39=VSD - High DC Bus Voltage, 40=VSD - Low DC Bus Voltage, 41=VSD - DC Bus Voltage Imbalance, 42=VSD - 105 % Motor Current Overload, 43=VSD - 105 % Motor Current Overload, 44=VSD - Motor Current Imbalance, 45=VSD - High Inverter Baseplate Temperature, 46=VSD - Single Phase Input Voltage, 47=VSD - Run Signal, 48=High Discharge Press ( HPCO), 49=Low Evaporator Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Low Evap Press LCHLT, 58=VSD - Precharge - Low DC Bus Voltage 2, 59=VSD - Precharge Lockout, 60=VSD - Serial Receive, 61=VSD - High Phase A Motor Current, 62=VSD - High Phase B Motor Current, 100=VSD - High Phase C Motor Current, 101=VSD - Phase A Gate Driver, 102=VSD - Phase B Gate Driver, 103=VSD - Phase C Gate Driver, 104=VSD - High Phase A Inverter Baseplate Temperature, 105=VSD - High Phase B Inverter Baseplate Temperature, 106=VSD - High Phase C Inverter Baseplate Temperature, 107=VSD - High Converter Heatsink Temperature, 108=VSD - Low Inverter Baseplate Temperature, 109=VSD - Low Phase A Inverter Baseplate Temperature, 110=VSD - Low Phase B Inverter Baseplate Temperature, 111=VSD - Low Phase C Inverter Baseplate Temperature, 112=VSD - Low Converter Heatsink Temperature, 113=VSD - High Internal Ambient Temperature, 114=VSD - Logic Board Power Supply, 115=VSD - Invalid Current Scale Selection, 116=VSD - High Phase A Inverter Heatsink Temperature, 117=VSD - High Phase B Inverter Heatsink Temperature, 118=VSD - High Phase C Inverter Heatsink Temperature, 119=VSD - Low Phase A Inverter Heatsink Temperature, 120=VSD - Low Phase B Inverter Heatsink Temperature, 121=VSD - Low Phase C Inverter Heatsink Temperature, 122=VSD - Logic Board Processor, 123=VSD – Undefined Fault
MV3SYS 2 OPERATIONAL CODESys 2 Operational CodeRead64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 69=Chilled Evap Water Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Invalid Serial Number, 72=Condenser Liquid Flow Switch Shutdown, 73=VSD Shutdown - Requesting Fault Data, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Evaporator Pressure Limiting, 82=Motor Current Limiting, 83=OPD Mitigation, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temperature Limiting, 89=VSD Internal Ambient Temperature Limiting, 90=Leaving Chilled Liquid Temperaure Limiting, 91=Oil Filter Clogged, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown
AV503SYS 2 OPERATIONAL CODE AVSys 2 Operational Code AVRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 68=Chilled Evap Water Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Invalid Serial Number, 71=Condenser Liquid Flow Switch Shutdown, 72=VSD Shutdown - Requesting Fault Data, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Evaporator Pressure Limiting, 81=Motor Current Limiting, 82=OPD Mitigation, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temperature Limiting, 88=VSD Internal Ambient Temperature Limiting, 89=Leaving Chilled Liquid Temperaure Limiting, 90=Oil Filter Clogged, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown
MV4SYS 2 FAULT CODESys 2 Fault CodeRead1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload, 19=CT Plug Fault, 20=High Leaving Condenser Liquid Temp, 21=VSD Initialization Failure, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Sys Low Evap Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Sys Low Evap Press LCHLT
AV504SYS 2 FAULT CODE AVSys 2 Fault Code AVRead0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload, 18=CT Plug Fault, 19=High Leaving Condenser Liquid Temp, 20=VSD Initialization Failure, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Sys Low Evap Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Sys Low Evap Press LCHLT
AV409LEAD SYSTEM NUMBERLead System NumberRead
AV30LOCAL LVG CHILL COND LIQ SETPLocal Leaving Chilled/Condenser Liquid Setpoint°FRead
AV31LOW LEAVING CHILL COND LIQ CUTLow Leaving Chilled/Condenser Liquid Temp Cutout°FRead
AV32SYS 1 ECON VALVE PCTSys 1 Economizer Valve % Open%Read
AV33SYS 2 ECON VALVE PCTSys 2 Economizer Valve % Open%Read
AV34SYS 2 ECON TEMPSys 2 Economizer Temperature°FRead
AV35VSD DC BUS VOLTVSD DC Bus VoltageVoltsRead
AV36REM LVG CHILL COND LIQ SETPRemote Leaving Chilled/Condenser Liquid Setpoint°FRead
AV37SYS 1 SUBCOOLED LIQ REF TEMPSys 1 Subcooled Liquid Refrigerant Temperature°FRead
AV38COOLING HEATING RANGECooling/Heating Range°F (diff)Read
AV39SYS 1 ECON PRESSSys 1 Economizer PressurePSIGRead
AV40SYS 2 ECON PRESSSys 2 Economizer PressurePSIGRead
AV41SYS 2 DISCH TEMPSys 2 Discharge Temperature°FRead
AV42SYS 2 SUBCOOLED LIQ REF TEMPSys 2 Subcooled Liquid Refrigerant Temperature°FRead
BV25SYS 1 LOCKOUTSys 1 LockoutRead0=Off, 1=On
BV26SYS 2 LOCKOUTSys 2 LockoutRead0=Off, 1=On
BV27SYS 1 ECON DRAIN VALVESys 1 economizer drain solenoid valve (CTS compressor)Read0=Off, 1=On
BV28SYS 2 ECON DRAIN VALVESys 2 economizer drain solenoid valve (CTS compressor)Read0=Off, 1=On
Object ID lookup: York YVWA point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)

How many BACnet points does the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) have?

This list has 76 BACnet objects: 45 analog values, 27 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet points are writable?

6 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet documentation?

The source is YVWA SC-EQ BAS Points List, revision Rev 2.1, 2019-11-05, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/GBppk5iQWBiKzUyxqfeOFA/content.

What are the minimum BACnet points to integrate the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)?

Start with BV 1 REM START STOP CMD (Remote start/stop (1 = run)); AV 1 REM CHILLED LIQ SETPOINT (Remote chilled liquid setpoint); AV 2 REM CURRENT LIMIT SETP (Remote current limit, %); BV 5 CHILLER RUN (Chiller running); BV 20 LOCAL REMOTE CONTROL MODE (Must read Remote (1) for BMS control); AV 5 LEAVING CHILLED LIQ TEMP (Leaving chilled liquid temperature); AV 27 VSD OUTPUT FREQUENCY (Compressor VSD frequency (load indication)); BV 6 CHILLER ALARM (Chiller alarm active); MV 2 SYS 1 FAULT CODE / FAULT CODE (Fault/inhibit code, Sys 1 or unit (1 = none)).

How do I enable BMS control of the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)?

BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. On heat pump units BV 3 selects chiller or heat pump operation.

How do I check these points on the real YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.