- YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card) · BACnet points list
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet points list
Updated 4 November 2026
YVWA chillers connect to a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the unit, write the chilled liquid setpoint, current limit and heating setpoint, and switch between chiller and heat pump mode. Read-only points cover chilled and condenser liquid temperatures, per-system pressures, % FLA, hours and starts, VSD values, valve positions and multistate operational and fault codes per system.
This page lists 76 BACnet objects for the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
- Equipment
- Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
- Equipment type
- Chillers
- BACnet objects
- 76 (6 writable)
- Transport
- BACnet MS/TP
- Firmware
- SC-EQ software 3.3.0.18
- Default device instance
- 5000 + MAC address
- Also known as
- YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1
- Source document
- YVWA SC-EQ BAS Points List · rev. Rev 2.1, 2019-11-05
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
Put the chiller in remote control (BV 20 reads Remote), then start/stop it with BV 1 and write the chilled liquid setpoint (AV 1) and current limit (AV 2); heat pump units also take BV 3 (mode) and AV 4 (heating setpoint). Read BV 5 for chiller run, the leaving chilled liquid temperature, VSD frequency and BV 6 for the chiller alarm; the fault code MVs give the cause.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | REM START STOP CMD | Remote start/stop (1 = run) | Command |
| AV 1 | REM CHILLED LIQ SETPOINT | Remote chilled liquid setpoint | Command |
| AV 2 | REM CURRENT LIMIT SETP | Remote current limit, % | Command |
| BV 5 | CHILLER RUN | Chiller running | Read |
| BV 20 | LOCAL REMOTE CONTROL MODE | Must read Remote (1) for BMS control | Read |
| AV 5 | LEAVING CHILLED LIQ TEMP | Leaving chilled liquid temperature | Read |
| AV 27 | VSD OUTPUT FREQUENCY | Compressor VSD frequency (load indication) | Read |
| BV 6 | CHILLER ALARM | Chiller alarm active | Read |
| MV 2 | SYS 1 FAULT CODE / FAULT CODE | Fault/inhibit code, Sys 1 or unit (1 = none) | Read |
Enable & remote start
BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. On heat pump units BV 3 selects chiller or heat pump operation.
Network setup
- The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.
- The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.
- The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID).
Watch out for
- The remote (commandable) setpoints read as unreliable until the BAS writes them the first time.
- The SC-EQ only exposes the points that apply to the chiller it detects; if it replaces an E-Link, re-discover the device so old non-applicable points don't sit offline.
- The fault code table differs between one- and two-compressor units; check the compressor count before decoding MV 2.
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REM CHILLED LIQ SETPOINT | Remote Chilled Liquid Setpoint | °F | Command | |
| AVmin | 2 | REM CURRENT LIMIT SETP | Remote Current Limit Setpoint | % | Command | |
| AV | 4 | REM HEATING SETPOINT | Remote Heating Setpoint | °F | Command | |
| BVmin | 1 | REM START STOP CMD | Remote Start / Stop Command | Command | 0=Stop, 1=Run | |
| BV | 3 | REM OPERATING MODE | Remote Operating Mode | Command | 0=Chiller, 1=Heatpump | |
| BV | 4 | HISTORY REQUEST | History buffer 1 request (live / history data) | Command | 0=Live Data, 1=History 1 Data | |
| AVmin | 5 | LEAVING CHILLED LIQ TEMP | Leaving Chilled Liquid Temp | °F | Read | |
| AV | 6 | ENTERING CHILLED LIQ TEMP | Entering Chilled Liquid Temp | °F | Read | |
| AV | 7 | VSD INT AMBIENT TEMP | VSD Internal Ambient Temp | °F | Read | |
| AV | 8 | LEAVING COND LIQ TEMP | Leaving Condenser Liquid Temp | °F | Read | |
| AV | 9 | SYS 1 DISCH TEMP | Sys 1 Discharge Temperature | °F | Read | |
| AV | 11 | ENTERING COND LIQ TEMP | Entering Condenser Liquid Temp | °F | Read | |
| AV | 12 | SYS 1 OIL PRESS | Sys 1 Oil Pressure | PSIG | Read | |
| AV | 13 | SYS 1 EVAP PRESS | Sys 1 Evaporator Pressure | PSIG | Read | |
| AV | 14 | SYS 1 DISCH PRESS | Sys 1 Discharge Pressure | PSIG | Read | |
| AV | 15 | SYS 1 COMP PCT FLA | Sys 1 Compressor % Full Load Amps | % | Read | |
| AV | 16 | SYS 1 HOURS | Sys 1 Total Run Hours | Hr | Read | |
| AV | 17 | SYS 1 STARTS | Sys 1 Total Number of Starts | Read | ||
| AV | 18 | SYS 1 HIGHEST MOTOR TEMP | Sys 1 Highest Motor Temp | °F | Read | |
| AV | 19 | SYS 2 HIGHEST MOTOR TEMP | Sys 2 Highest Motor Temp | °F | Read | |
| AV | 20 | SYS 1 ECON TEMP | Sys 1 Economizer Temperature | °F | Read | |
| AV | 21 | SYS 2 OIL PRESS | Sys 2 Oil Pressure | PSIG | Read | |
| AV | 22 | SYS 2 EVAP PRESS | Sys 2 Evaporator Pressure | PSIG | Read | |
| AV | 23 | SYS 2 DISCH PRESS | Sys 2 Discharge Pressure | PSIG | Read | |
| AV | 24 | SYS 2 COMP PCT FLA | Sys 2 Compressor % Full Load Amps | % | Read | |
| AV | 25 | SYS 2 HOURS | Sys 2 Total Run Hours | Hr | Read | |
| AV | 26 | SYS 2 STARTS | Sys 2 Total Number of Starts | Read | ||
| AVmin | 27 | VSD OUTPUT FREQUENCY | VSD Output Frequency | Hz | Read | |
| AV | 28 | SYS 1 COND LEVEL VALVE PCT | Sys 1 Condenser Level Control Valve % Open | % | Read | |
| AV | 29 | SYS 2 COND LEVEL VALVE PCT | Sys 2 Condenser Level Control Valve % Open | % | Read | |
| BVmin | 5 | CHILLER RUN | Chiller Run | Read | 0=Off, 1=On | |
| BVmin | 6 | CHILLER ALARM | Chiller Alarm (0=No Alarm, 1=Alarm Active) | Read | 0=No Alarm, 1=Alarm Active | |
| BV | 7 | VSD AUX COOLANT PUMP | VSD aux coolant pump (aux pump control enabled) | Read | 0=Off, 1=On | |
| BV | 8 | EVAP COND PUMP STATUS | Evaporator/Condenser Pump Status | Read | 0=Off, 1=On | |
| BV | 9 | SYS 1 COMP RUN STATUS | Sys 1 Compressor Run Status | Read | 0=Off, 1=On | |
| BV | 10 | SYS 2 COMP RUN STATUS | Sys 2 Compressor Run Status | Read | 0=Off, 1=On | |
| BV | 11 | SYS 1 VI STEP SOL VALVE 1 STATUS | Sys 1 VI Step Solenoid Valve 1 Status | Read | 0=Off, 1=On | |
| BV | 12 | SYS 2 VI STEP SOL VALVE 1 STATUS | Sys 2 VI Step Solenoid Valve 1 Status | Read | 0=Off, 1=On | |
| BV | 13 | SYS 1 VI STEP SOL VALVE 2 STATUS | Sys 1 VI Step Solenoid Valve 2 Status | Read | 0=Off, 1=On | |
| BV | 14 | SYS 2 VI STEP SOL VALVE 2 STATUS | Sys 2 VI Step Solenoid Valve 2 Status | Read | 0=Off, 1=On | |
| BV | 15 | SYS 1 OIL LEVEL SWITCH STATUS | Sys 1 oil level switch status (oil level option) | Read | 0=Off, 1=On | |
| BV | 16 | SYS 2 OIL LEVEL SWITCH STATUS | Sys 2 oil level switch status (oil level option) | Read | 0=Off, 1=On | |
| BV | 17 | SYS 1 LIQ REF INJ VALVE STATUS | Sys 1 Liquid Refrigerant Injection Valve Status | Read | 0=Off, 1=On | |
| BV | 18 | SYS 2 LIQ REF INJ VALVE STATUS | Sys 2 Liquid Refrigerant Injection Valve Status | Read | 0=Off, 1=On | |
| BV | 19 | COOLING TYPE | Cooling Type | Read | 0=Water, 1=Glycol | |
| BVmin | 20 | LOCAL REMOTE CONTROL MODE | Local Remote Control Mode | Read | 0=Local, 1=Remote | |
| BV | 21 | DISPLAY UNITS | Display Units | Read | 0=Imperial, 1=SI | |
| BV | 22 | SYS 1 HOT GAS BYPASS VALVE STATUS | Sys 1 hot gas bypass valve status (hot gas option) | Read | 0=Off, 1=On | |
| BV | 23 | SYS 2 HOT GAS BYPASS VALVE STATUS | Sys 2 hot gas bypass valve status (hot gas option) | Read | 0=Off, 1=On | |
| BV | 24 | HEATPUMP | Heatpump | Read | 0=No, 1=Yes | |
| MV | 1 | SYS 1 OPERATIONAL CODE | Sys 1 Operational Code | Read | 64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 69=Chilled Evap Water Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Invalid Serial Number, 72=Condenser Liquid Flow Switch Shutdown, 73=VSD Shutdown - Requesting Fault Data, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Evaporator Pressure Limiting, 82=Motor Current Limiting, 83=OPD Mitigation, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temperature Limiting, 89=VSD Internal Ambient Temperature Limiting, 90=Leaving Chilled Liquid Temperaure Limiting, 91=Oil Filter Clogged, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown | |
| AV | 501 | SYS 1 OPERATIONAL CODE AV | Sys 1 Operational Code AV | Read | 63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 68=Chilled Evap Water Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Invalid Serial Number, 71=Condenser Liquid Flow Switch Shutdown, 72=VSD Shutdown - Requesting Fault Data, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Evaporator Pressure Limiting, 81=Motor Current Limiting, 82=OPD Mitigation, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temperature Limiting, 88=VSD Internal Ambient Temperature Limiting, 89=Leaving Chilled Liquid Temperaure Limiting, 90=Oil Filter Clogged, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown | |
| MVmin | 2 | SYS 1 FAULT CODE / FAULT CODE | Sys 1 fault code (two-compressor units) or unit fault code (one-compressor units) | Read | Two-compressor units: 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload, 19=CT Plug Fault, 20=High Leaving Condenser Liquid Temp, 21=VSD Initialization Failure, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Sys Low Evap Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Sys Low Evap Press LCHLT. One-compressor units: 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=High Leaving Condenser Liquid Temp, 8=VSD Communications Failure, 9=VSD Initialization Failure, 10=Filter - High Heatsink Temperature, 11=Filter - High DC Bus Voltage, 12=Filter - High Phase C Current, 13=Filter - High Phase B Current, 14=Filter - High Phase A Current, 15=Filter - Phase Locked Loop, 16=Filter - Logic Board Power Supply, 17=Filter - Precharge - Low DC Bus Voltage 2, 18=Filter - Precharge - Low DC Bus Voltage 1, 19=Filter - Low DC Bus Voltage, 20=Filter - DC Bus Voltage Imbalance, 21=Filter - Input Current Overload, 22=Filter - Run Signal, 23=Filter - DC Current Transformer 1, 24=Filter - DC Current Transformer 2, 25=Filter - High Baseplate Temperature (Vyper), 26=IEEE-519 Filter Fault, 28=High Discharge Pressure (Software), 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=VSD - Precharge - Low DC Bus Voltage 1, 39=VSD - Precharge - DC Bus Voltage Imbalance, 40=VSD - High DC Bus Voltage, 41=VSD - Low DC Bus Voltage, 42=VSD - DC Bus Voltage Imbalance, 43=VSD - 105 % Motor Current Overload, 44=VSD - 105 % Motor Current Overload, 45=VSD - Motor Current Imbalance, 46=VSD - High Inverter Baseplate Temperature, 47=VSD - Single Phase Input Voltage, 48=VSD - Run Signal, 49=High Discharge Press ( HPCO), 50=Low Evaporator Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Low Evap Press LCHLT, 59=VSD - Precharge - Low DC Bus Voltage 2, 60=VSD - Precharge Lockout, 61=VSD - Serial Receive, 62=VSD - High Phase A Motor Current, 63=VSD - High Phase B Motor Current, 101=VSD - High Phase C Motor Current, 102=VSD - Phase A Gate Driver, 103=VSD - Phase B Gate Driver, 104=VSD - Phase C Gate Driver, 105=VSD - High Phase A Inverter Baseplate Temperature, 106=VSD - High Phase B Inverter Baseplate Temperature, 107=VSD - High Phase C Inverter Baseplate Temperature, 108=VSD - High Converter Heatsink Temperature, 109=VSD - Low Inverter Baseplate Temperature, 110=VSD - Low Phase A Inverter Baseplate Temperature, 111=VSD - Low Phase B Inverter Baseplate Temperature, 112=VSD - Low Phase C Inverter Baseplate Temperature, 113=VSD - Low Converter Heatsink Temperature, 114=VSD - High Internal Ambient Temperature, 115=VSD - Logic Board Power Supply, 116=VSD - Invalid Current Scale Selection, 117=VSD - High Phase A Inverter Heatsink Temperature, 118=VSD - High Phase B Inverter Heatsink Temperature, 119=VSD - High Phase C Inverter Heatsink Temperature, 120=VSD - Low Phase A Inverter Heatsink Temperature, 121=VSD - Low Phase B Inverter Heatsink Temperature, 122=VSD - Low Phase C Inverter Heatsink Temperature, 123=VSD - Logic Board Processor, 124=VSD – Undefined Fault | |
| AV | 502 | SYS 1 FAULT CODE AV / FAULT CODE AV | Sys 1 / unit fault code, raw value (see MV 2) | Read | Two-compressor units: 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload, 18=CT Plug Fault, 19=High Leaving Condenser Liquid Temp, 20=VSD Initialization Failure, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Sys Low Evap Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Sys Low Evap Press LCHLT. One-compressor units: 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=High Leaving Condenser Liquid Temp, 7=VSD Communications Failure, 8=VSD Initialization Failure, 9=Filter - High Heatsink Temperature, 10=Filter - High DC Bus Voltage, 11=Filter - High Phase C Current, 12=Filter - High Phase B Current, 13=Filter - High Phase A Current, 14=Filter - Phase Locked Loop, 15=Filter - Logic Board Power Supply, 16=Filter - Precharge - Low DC Bus Voltage 2, 17=Filter - Precharge - Low DC Bus Voltage 1, 18=Filter - Low DC Bus Voltage, 19=Filter - DC Bus Voltage Imbalance, 20=Filter - Input Current Overload, 21=Filter - Run Signal, 22=Filter - DC Current Transformer 1, 23=Filter - DC Current Transformer 2, 24=Filter - High Baseplate Temperature (Vyper), 25=IEEE-519 Filter Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=VSD - Precharge - Low DC Bus Voltage 1, 38=VSD - Precharge - DC Bus Voltage Imbalance, 39=VSD - High DC Bus Voltage, 40=VSD - Low DC Bus Voltage, 41=VSD - DC Bus Voltage Imbalance, 42=VSD - 105 % Motor Current Overload, 43=VSD - 105 % Motor Current Overload, 44=VSD - Motor Current Imbalance, 45=VSD - High Inverter Baseplate Temperature, 46=VSD - Single Phase Input Voltage, 47=VSD - Run Signal, 48=High Discharge Press ( HPCO), 49=Low Evaporator Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Low Evap Press LCHLT, 58=VSD - Precharge - Low DC Bus Voltage 2, 59=VSD - Precharge Lockout, 60=VSD - Serial Receive, 61=VSD - High Phase A Motor Current, 62=VSD - High Phase B Motor Current, 100=VSD - High Phase C Motor Current, 101=VSD - Phase A Gate Driver, 102=VSD - Phase B Gate Driver, 103=VSD - Phase C Gate Driver, 104=VSD - High Phase A Inverter Baseplate Temperature, 105=VSD - High Phase B Inverter Baseplate Temperature, 106=VSD - High Phase C Inverter Baseplate Temperature, 107=VSD - High Converter Heatsink Temperature, 108=VSD - Low Inverter Baseplate Temperature, 109=VSD - Low Phase A Inverter Baseplate Temperature, 110=VSD - Low Phase B Inverter Baseplate Temperature, 111=VSD - Low Phase C Inverter Baseplate Temperature, 112=VSD - Low Converter Heatsink Temperature, 113=VSD - High Internal Ambient Temperature, 114=VSD - Logic Board Power Supply, 115=VSD - Invalid Current Scale Selection, 116=VSD - High Phase A Inverter Heatsink Temperature, 117=VSD - High Phase B Inverter Heatsink Temperature, 118=VSD - High Phase C Inverter Heatsink Temperature, 119=VSD - Low Phase A Inverter Heatsink Temperature, 120=VSD - Low Phase B Inverter Heatsink Temperature, 121=VSD - Low Phase C Inverter Heatsink Temperature, 122=VSD - Logic Board Processor, 123=VSD – Undefined Fault | |
| MV | 3 | SYS 2 OPERATIONAL CODE | Sys 2 Operational Code | Read | 64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 69=Chilled Evap Water Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Invalid Serial Number, 72=Condenser Liquid Flow Switch Shutdown, 73=VSD Shutdown - Requesting Fault Data, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Evaporator Pressure Limiting, 82=Motor Current Limiting, 83=OPD Mitigation, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temperature Limiting, 89=VSD Internal Ambient Temperature Limiting, 90=Leaving Chilled Liquid Temperaure Limiting, 91=Oil Filter Clogged, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown | |
| AV | 503 | SYS 2 OPERATIONAL CODE AV | Sys 2 Operational Code AV | Read | 63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 68=Chilled Evap Water Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Invalid Serial Number, 71=Condenser Liquid Flow Switch Shutdown, 72=VSD Shutdown - Requesting Fault Data, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Evaporator Pressure Limiting, 81=Motor Current Limiting, 82=OPD Mitigation, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temperature Limiting, 88=VSD Internal Ambient Temperature Limiting, 89=Leaving Chilled Liquid Temperaure Limiting, 90=Oil Filter Clogged, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown | |
| MV | 4 | SYS 2 FAULT CODE | Sys 2 Fault Code | Read | 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload, 19=CT Plug Fault, 20=High Leaving Condenser Liquid Temp, 21=VSD Initialization Failure, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Sys Low Evap Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Sys Low Evap Press LCHLT | |
| AV | 504 | SYS 2 FAULT CODE AV | Sys 2 Fault Code AV | Read | 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload, 18=CT Plug Fault, 19=High Leaving Condenser Liquid Temp, 20=VSD Initialization Failure, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Sys Low Evap Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Sys Low Evap Press LCHLT | |
| AV | 409 | LEAD SYSTEM NUMBER | Lead System Number | Read | ||
| AV | 30 | LOCAL LVG CHILL COND LIQ SETP | Local Leaving Chilled/Condenser Liquid Setpoint | °F | Read | |
| AV | 31 | LOW LEAVING CHILL COND LIQ CUT | Low Leaving Chilled/Condenser Liquid Temp Cutout | °F | Read | |
| AV | 32 | SYS 1 ECON VALVE PCT | Sys 1 Economizer Valve % Open | % | Read | |
| AV | 33 | SYS 2 ECON VALVE PCT | Sys 2 Economizer Valve % Open | % | Read | |
| AV | 34 | SYS 2 ECON TEMP | Sys 2 Economizer Temperature | °F | Read | |
| AV | 35 | VSD DC BUS VOLT | VSD DC Bus Voltage | Volts | Read | |
| AV | 36 | REM LVG CHILL COND LIQ SETP | Remote Leaving Chilled/Condenser Liquid Setpoint | °F | Read | |
| AV | 37 | SYS 1 SUBCOOLED LIQ REF TEMP | Sys 1 Subcooled Liquid Refrigerant Temperature | °F | Read | |
| AV | 38 | COOLING HEATING RANGE | Cooling/Heating Range | °F (diff) | Read | |
| AV | 39 | SYS 1 ECON PRESS | Sys 1 Economizer Pressure | PSIG | Read | |
| AV | 40 | SYS 2 ECON PRESS | Sys 2 Economizer Pressure | PSIG | Read | |
| AV | 41 | SYS 2 DISCH TEMP | Sys 2 Discharge Temperature | °F | Read | |
| AV | 42 | SYS 2 SUBCOOLED LIQ REF TEMP | Sys 2 Subcooled Liquid Refrigerant Temperature | °F | Read | |
| BV | 25 | SYS 1 LOCKOUT | Sys 1 Lockout | Read | 0=Off, 1=On | |
| BV | 26 | SYS 2 LOCKOUT | Sys 2 Lockout | Read | 0=Off, 1=On | |
| BV | 27 | SYS 1 ECON DRAIN VALVE | Sys 1 economizer drain solenoid valve (CTS compressor) | Read | 0=Off, 1=On | |
| BV | 28 | SYS 2 ECON DRAIN VALVE | Sys 2 economizer drain solenoid valve (CTS compressor) | Read | 0=Off, 1=On |
No points match these filters.
Object ID lookup: York YVWA point IDs by name
AV1REM CHILLED LIQ SETPOINTAV2REM CURRENT LIMIT SETPAV4REM HEATING SETPOINTBV1REM START STOP CMDBV3REM OPERATING MODEBV4HISTORY REQUESTAV5LEAVING CHILLED LIQ TEMPAV6ENTERING CHILLED LIQ TEMPAV7VSD INT AMBIENT TEMPAV8LEAVING COND LIQ TEMPAV9SYS 1 DISCH TEMPAV11ENTERING COND LIQ TEMPAV12SYS 1 OIL PRESSAV13SYS 1 EVAP PRESSAV14SYS 1 DISCH PRESSAV15SYS 1 COMP PCT FLAAV16SYS 1 HOURSAV17SYS 1 STARTSAV18SYS 1 HIGHEST MOTOR TEMPAV19SYS 2 HIGHEST MOTOR TEMPAV20SYS 1 ECON TEMPAV21SYS 2 OIL PRESSAV22SYS 2 EVAP PRESSAV23SYS 2 DISCH PRESSAV24SYS 2 COMP PCT FLAAV25SYS 2 HOURSAV26SYS 2 STARTSAV27VSD OUTPUT FREQUENCYAV28SYS 1 COND LEVEL VALVE PCTAV29SYS 2 COND LEVEL VALVE PCTBV5CHILLER RUNBV6CHILLER ALARMBV7VSD AUX COOLANT PUMPBV8EVAP COND PUMP STATUSBV9SYS 1 COMP RUN STATUSBV10SYS 2 COMP RUN STATUSBV11SYS 1 VI STEP SOL VALVE 1 STATUSBV12SYS 2 VI STEP SOL VALVE 1 STATUSBV13SYS 1 VI STEP SOL VALVE 2 STATUSBV14SYS 2 VI STEP SOL VALVE 2 STATUSBV15SYS 1 OIL LEVEL SWITCH STATUSBV16SYS 2 OIL LEVEL SWITCH STATUSBV17SYS 1 LIQ REF INJ VALVE STATUSBV18SYS 2 LIQ REF INJ VALVE STATUSBV19COOLING TYPEBV20LOCAL REMOTE CONTROL MODEBV21DISPLAY UNITSBV22SYS 1 HOT GAS BYPASS VALVE STATUSBV23SYS 2 HOT GAS BYPASS VALVE STATUSBV24HEATPUMPMV1SYS 1 OPERATIONAL CODEAV501SYS 1 OPERATIONAL CODE AVMV2SYS 1 FAULT CODE / FAULT CODEAV502SYS 1 FAULT CODE AV / FAULT CODE AVMV3SYS 2 OPERATIONAL CODEAV503SYS 2 OPERATIONAL CODE AVMV4SYS 2 FAULT CODEAV504SYS 2 FAULT CODE AVAV409LEAD SYSTEM NUMBERAV30LOCAL LVG CHILL COND LIQ SETPAV31LOW LEAVING CHILL COND LIQ CUTAV32SYS 1 ECON VALVE PCTAV33SYS 2 ECON VALVE PCTAV34SYS 2 ECON TEMPAV35VSD DC BUS VOLTAV36REM LVG CHILL COND LIQ SETPAV37SYS 1 SUBCOOLED LIQ REF TEMPAV38COOLING HEATING RANGEAV39SYS 1 ECON PRESSAV40SYS 2 ECON PRESSAV41SYS 2 DISCH TEMPAV42SYS 2 SUBCOOLED LIQ REF TEMPBV25SYS 1 LOCKOUTBV26SYS 2 LOCKOUTBV27SYS 1 ECON DRAIN VALVEBV28SYS 2 ECON DRAIN VALVE
Integration notes
- Access is inferred: the sheet has no read/write column. The remote block (AV 1, AV 2, AV 4, BV 1, BV 3, BV 4) is treated as commandable; everything else as read-only.
- System 2 points only report on two-compressor units. MV 2 / AV 502 are printed twice: Sys 1 fault code on two-compressor units and the unit fault code on one-compressor units, each with its own code table; they are merged here and both tables are given.
- Operational and fault code MVs are the printed code + 1, as the doc's status code tables say; the AV copies (AV 501-504) carry the raw code. Binary states are as printed.
- This list has no MV 65001 Units object. Units shown are the IP units.
- Spare and reserved objects are left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
How many BACnet points does the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) have?
This list has 76 BACnet objects: 45 analog values, 27 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet points are writable?
6 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ) BACnet documentation?
The source is YVWA SC-EQ BAS Points List, revision Rev 2.1, 2019-11-05, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/GBppk5iQWBiKzUyxqfeOFA/content.
What are the minimum BACnet points to integrate the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)?
Start with BV 1 REM START STOP CMD (Remote start/stop (1 = run)); AV 1 REM CHILLED LIQ SETPOINT (Remote chilled liquid setpoint); AV 2 REM CURRENT LIMIT SETP (Remote current limit, %); BV 5 CHILLER RUN (Chiller running); BV 20 LOCAL REMOTE CONTROL MODE (Must read Remote (1) for BMS control); AV 5 LEAVING CHILLED LIQ TEMP (Leaving chilled liquid temperature); AV 27 VSD OUTPUT FREQUENCY (Compressor VSD frequency (load indication)); BV 6 CHILLER ALARM (Chiller alarm active); MV 2 SYS 1 FAULT CODE / FAULT CODE (Fault/inhibit code, Sys 1 or unit (1 = none)).
How do I enable BMS control of the York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)?
BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. On heat pump units BV 3 selects chiller or heat pump operation.
How do I check these points on the real YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: YVWA SC-EQ BAS Points List · rev. Rev 2.1, 2019-11-05. Object names, instances and units are reproduced as published; descriptions are our own.