Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card) · BACnet points list

York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points list

Updated 28 October 2026

Short answer

The YMC2's SC-EQ card puts the chiller on a BACnet MS/TP trunk (or Modbus RTU / N2). Besides run/stop, the leaving chilled liquid setpoint and the input current limit, it exposes VSD input and output data, harmonic distortion, magnetic bearing (MBC) levitation and speed, VGD/PRV positions and the operation, fault and warning codes. Some points apply only to Mod A or Mod B chillers.

This page lists 112 BACnet objects for the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
Equipment
Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
112 (5 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.2.0.20
Default device instance
5000 + MAC address
Also known as
YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1
Source document
YMC2 SC-EQ BAS Points List · rev. Rev 2.11, 2021-12-08
Download CSV 112 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)

Integration in brief

Wire the BAS to the SC-EQ J12 RS-485 port, set the MAC address on the DIP switch and let the card detect BACnet MS/TP. Write the remote run/stop, leaving chilled liquid setpoint and input current limit, then read motor run status, the operation code, leaving chilled liquid temperature, % FLA and the safety fault code. Check MV 5 and MV 10-13 to confirm the chiller is taking its commands from the BAS.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM RUN STOP CMDRemote run/stop (1 = run)Command
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 2REMOTE INPUT CURRENT SPRemote input current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUSCompressor motor runningRead
MV 5UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
AV 29MOTOR CURRENT PCT FLAMotor current, % FLA (load indication)Read
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read
MV 3UNIT CYCLING FAULT CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and the REM AVs are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital, Modem or Remote. MV 10 shows the run/stop source (Local, BAS, Hardwire) and MV 11-13 the cooling setpoint, heating setpoint and current limit sources (Local, BAS, 0-10 V, 4-20 mA, PWM); check they read BAS. The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.

Network setup

Watch out for

York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

112 of 112 shown
Type
AnalogBinaryMulti-state
Access
Show
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REMOTE INPUT CURRENT SPRemote Input Current Limit Setpoint%Command
AV3REM HEATING SPRemote Heating Setpoint°FCommand
BVmin1REM RUN STOP CMDRemote Run/StopCommand0=Stop, 1=Run
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CH LIQ TEMPEntering Chilled Liquid Temperature°FRead
AV7LEAVING COND WATER TEMPLeaving Condenser Liquid Temperature°FRead
AV8ENTERING COND WATER TEMPEntering Condenser Liquid Temperature°FRead
AV9EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV10CONDENSER PRESSURECondenser PressurePSIGRead
AV11DISCHARGE TEMPDischarge Temperature°FRead
AV12EVAP REFRIGERANT TEMPEvaporator Refrigerant Temperature (Evaporator Refrigerant Temperature enabled only)°FRead
AV13VSD PHASE A OUTPUT CURRENTVSD Phase A Output Current (RMS)AmpsRead
AV14VSD PHASE B OUTPUT CURRENTVSD Phase B Output Current (RMS)AmpsRead
AV15VSD PHASE C OUTPUT CURRENTVSD Phase C Output Current (RMS)AmpsRead
AV17VSD RMS INPUT CURRENT L1VSD L1 Input Current (RMS)AmpsRead
AV18VSD RMS INPUT CURRENT L2VSD L2 Input Current (RMS)AmpsRead
AV19VSD RMS INPUT CURRENT L3VSD L3 Input Current (RMS)AmpsRead
AV20LEAVING CH LIQ TEMP ACT SPLeaving Chilled Liquid Setpoint - Selected°FRead
AV21INPUT CURRENT LMT ACTIVEActive Input Current Limit%Read
AV22EVAP SATURATION TEMPEvaporator Saturation Temperature°FRead
AV23COND SATURATION TEMPCondenser Saturation Temperature°FRead
AV24INPUT CURRENT PCT FLAInput % Full Load Amps%Read
AV25COND REFRIGERANT LEVELCondenser Refrigerant Level%Read
AV26OPERATING HOURSOperating HoursHrRead
AV27NUMBER OF STARTSNumber Of StartsRead
AV28HOT GAS BYPASS VLV CMDHot Gas Bypass Command (Hot Gas Bypass enabled only)%Read
AVmin29MOTOR CURRENT PCT FLAMotor % Full Load Amps%Read
BVmin5COMPR MOTOR STATUSMotor RunRead0=Off, 1=On
BV6CH LIQ PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV7VSD COOLING SYS STATVSD Cooling SystemRead0=Off, 1=On
BV8RUN PERMISSIVERun PermissiveRead0=Off, 1=On
BV9CH LIQ FLOW SWITCH STATChilled Liquid Flow SwitchRead0=Open, 1=Closed
BV10CND FLOW SWITCH STATCondenser Liquid Flow SwitchRead0=Open, 1=Closed
BV11COND REF LEVEL CNTRL MODECondenser Level Control Valve ModeRead0=Auto, 1=Manual
BV12CND LIQ PUMP STATCondenser Liquid PumpRead0=Off, 1=On
MVmin1UNIT OPERATION CODEUnit Operation CodeRead1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Soft Shutdown, 12=Unit Coastdown, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown, 16=Unit Running - Active Low Lift - No Abnormal Condition, 17=Unit Running - Active Low Lift - Warning Active, 18=Unit Running - Active Low Lift - Modified Run, 19=Unit Running - Passive Low Lift - No Abnormal Condition, 20=Unit Running - Passive Low Lift - Warning Active, 21=Unit Running - Passive Low Lift - Modified Run, 22=Unit Running - Cooling - No Abnormal Condition, 23=Unit Running - Cooling - Warning Active, 24=Unit Running - Cooling - Modified Run, 25=Unit Running - Heating - No Abnormal Condition, 26=Unit Running - Heating - Warning Active, 27=Unit Running - Heating - Modified Run, 28=Unit Running - Cooling & Heating - No Abnormal Condition, 29=Unit Running - Cooling & Heating - Warning Active, 30=Unit Running - Cooling & Heating - Modified Run
AV401UNIT OPERATION CODE AVUnit Operation Code, raw code (MV 1 shows code + 1)Read
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Safety Faults Present; other values (up to 164) are YMC2 Safety Fault Code table SC.2 codes plus 1 (133 codes listed in the source doc)
AV402UNIT SAFETY FAULT CODE AVUnit Safety Fault Code, raw code (MV 2 shows code + 1)Read
MVmin3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Cycling Faults Present; other values (up to 162) are YMC2 Cycling Fault Code table SC.3 codes plus 1 (111 codes listed in the source doc)
AV403UNIT CYCLING FAULT CODE AVUnit Cycling Fault Code, raw code (MV 3 shows code + 1)Read
MV4UNIT WARNING CODEUnit Warning CodeRead1=No Warnings Present, 2=WARNING - REAL TIME CLOCK FAILURE, 3=WARNING - SETPOINT OVERRIDE, 4=WARNING - CONDENSER OR EVAPORATOR XDCR ERROR, 5=WARNING - EVAPORATOR - LOW PRESSURE LIMIT, 6=WARNING - CONDENSER - HIGH PRESSURE LIMIT, 8=WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI, 9=WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI, 10=WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE, 11=WARNING - MBC - LOW AMPLIFIER RESISTANCE, 12=WARNING - MBC - HIGH AMPLIFIER RESISTANCE, 13=WARNING - MBC - LOW AMPLIFIER CURRENT, 14=WARNING - MBC - HIGH AMPLIFIER CURRENT, 15=WARNING - MBC - POSITION SENSOR ERROR, 16=WARNING - MBC - J BEARING SENSOR DISABLED, 17=WARNING - MBC - K BEARING SENSOR DISABLED, 18=WARNING - MBC - H BEARING SENSOR DISABLED, 21=WARNING – UPS – NOT CHARGING, 22=WARNING – UPS – LINE LOW BATTERY VOLTAGE, 23=WARNING – UPS – BATTERY NOT CONNECTED, 24=WARNING – UPS – CHECK BATTERY CONNECTION, 25=WARNING – UPS – BATTERY TEST FAILED, 26=WARNING - SALES ORDER - INVALID SERIAL NUMBER, 30=WARNING - SURGE PROTECTION - EXCESS SURGE LIMIT, 31=WARNING - EXCESS SURGE DETECTED, 35=WARNING - CONDENSER OR VGD SENSOR FAILURE, 36=WARNING - HARMONIC FILTER - INVALID MODEL, 37=WARNING - HARMONIC FILTER - OPERATION INHIBITED, 38=WARNING - HARMONIC FILTER - DATA LOSS, 40=WARNING - HARMONIC FILTER - NOT RUNNING, 41=WARNING - MOTOR - HIGH WINDING TEMPERATURE, 42=WARNING - MOTOR - HIGH ROTOR TEMPERATURE, 45=WARNING - VSD - INPUT VOLTAGE IMBALANCE, 46=WARNING - VSD - HIGH HX APPROACH TEMPERATURE, 49=WARNING - MBC - LANDING COUNTER HIGH, 56=WARNING – MBC – CHECKSUM CENTERING, 57=WARNING – MBC – DSP WATCHDOG, 58=WARNING – MBC – AMP WATCHDOG, 59=WARNING – MBC – INTERNAL ALARM, 60=WARNING – MBC – HIGH RADIAL OSCILLATOR VOLTAGE, 61=WARNING – MBC – HIGH AXIAL OSCILLATOR VOLTAGE, 66=WARNING - MBC - ROTATION MODE OFF, 67=WARNING - MOTOR - HIGH CURRENT LIMIT, 68=WARNING - MOTOR - HIGH HOUSING TEMPERATURE, 69=WARNING - VSD - DC BUS ACTIVE, 70=WARNING - LIQUID LEVEL SETPOINT NOT ACHIEVED, 71=WARNING - LOSS OF SUBCOOLER LIQUID SEAL
AV404UNIT WARNING CODE AVUnit Warning Code, raw code (MV 4 shows code + 1)Read
MVmin5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
AV405UNIT CONTROL SOURCE AVUnit Control Source, same codes as MV 5Read0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
MV6UNIT MODIFIED RUN CODEUnit Modified Run CodeRead1=No Modified Run Conditions Present, 2=VSD - DC BUS ACTIVE, 3=MOTOR - HIGH CURRENT LIMIT, 5=VSD - INPUT PULLDOWN LIMIT, 6=VSD - HIGH INPUT CURRENT LIMIT
AV406UNIT MODIFIED RUN CODE AVUnit Modified Run Code, raw code (MV 6 shows code + 1)Read
MV7UNIT START INHIBIT CODEUnit Start Inhibit CodeRead1=No Start Inhibits Present, 2=ANTI-RECYCLE, 4=VGD STROKE NOT CALIBRATED, 5=VGD FEEDBACK NOT CALIBRATED, 6=MBC - BEARING CALIBRATION IN PROGRESS, 7=MBC - BEARING CLEARANCE CHECK IN PROGRESS, 8=VSD - INITIALIZATION IN PROGRESS, 11=PRV NOT CALIBRATED, 13=VGD NOT CALIBRATED, 14=LINE VOLTAGE NOT SET, 15=LINE FREQUENCY NOT SET, 16=MBC - INITIALIZATION IN PROGRESS
AV407UNIT START INHIBIT CODE AVUnit Start Inhibit Code, raw code (MV 7 shows code + 1)Read
MV8UNIT INTERNAL FAULT CODEUnit Internal Fault CodeRead1=No Internal Faults Present, 2=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 3=WATCHDOG - SOFTWARE REBOOT, 4=INTERNAL ERROR - CANNOT CREATE TASK, 5=INTERNAL ERROR - CANNOT REGISTER CONTROL, 6=INTERNAL ERROR - INVALID BRAM
AV408UNIT INTERNAL FAULT CODE AVUnit Internal Fault Code, raw code (MV 8 shows code + 1)Read
AV30VGD CONTROL STATEVGD Control State (Mod A Chillers only)Read0=[Unused], 1=Probing or Capacity Control, 2=Stall Reacting, 3=Stall Waiting, 4=Surge Reacting, 5=Surge Waiting, 6=Sensor Override, 7=[Unused], 8=PRV Position Override
AV31VGD STALL COUNTVGD Stall Count (Mod A Chillers only)Read
AV32ACTIVE ANTI SURGE MIN FREQActive Anti-Surge Minimum FrequencyHzRead
AV34VSD OUTPUT VOLTAGEVSD Output VoltageVoltsRead
AV35VSD INPUT POWERVSD Input PowerkWRead
AV36VSD INPUT KWHVSD Input Kilowatt HourskWhRead
AV37VSD DC BUS VOLTAGEVSD DC Bus VoltageVoltsRead
AV38VSD INPUT VOLTAGE L1VSD L1 Input Voltage (RMS)VoltsRead
AV39SURGE COUNTSurge CountRead
AV40VSD OUTPUT FREQUENCYVSD Output FrequencyHzRead
AV41VSD INPUT VOLTAGE L2VSD L2 Input Voltage (RMS)VoltsRead
AV42VSD INPUT VOLTAGE L3VSD L3 Input Voltage (RMS)VoltsRead
AV43COND LVL CTRL VLV CMDCondenser Level Control Valve Command%Read
BV26MBC LEVITATION MODEMBC Levitation ModeRead0=Off, 1=On
BV27MBC ROTATION MODEMBC Rotation ModeRead0=Off, 1=On
AV48MOTOR HOUSING TEMPMotor Housing Temp°FRead
AV107MOTOR COOLING VALVE CMDMotor Cooling Valve Command (Mod A FAB comp & Mod B chillers)%Read
AV108VSD INTERNAL AMBIENT TEMP 2VSD Internal Ambient Temperature 2°FRead
AV109MTR WINDING AVG TEMPAverage Motor Winding Temperature°FRead
AV110VSD INTERNAL AMBIENT TEMP 1VSD Internal Ambient Temperature 1°FRead
AV111VGD POSITIONVGD Position%Read
AV112PRE ROTATION VANES POSPre Rotation Vanes (PRV) Position (Mod A chiller FAA comp only)%Read
AV113COND REFRIGERANT LEVEL SPCondenser Active Level Setpoint%Read
AV114DROP LEG REFRIG TEMPDrop Leg Refrigerant Temperature°FRead
AV115VSD L1 VOLTAGE THDVSD L1 Voltage Total Harmonic Distortion%Read
AV116VSD L2 VOLTAGE THDVSD L2 Voltage Total Harmonic Distortion%Read
AV117VSD L3 VOLTAGE THDVSD L3 Voltage Total Harmonic Distortion%Read
AV118VSD L1 INPUT CURRENT TDDVSD L1 Input Current Total Demand Distortion%Read
AV119VSD L2 INPUT CURRENT TDDVSD L2 Input Current Total Demand Distortion%Read
AV120VSD L3 INPUT CURRENT TDDVSD L3 Input Current Total Demand Distortion%Read
AV121INPUT KWH LOInput Kilowatt Hours LowRead
AV122INPUT KWH OFFSETInput Kilowatt Hours OffsetRead
AV123OPERATING HOURS LOOperating Hours LowRead
AV124OPERATING HOURS OFFSETOperating Hours OffsetRead
AV125MBC MOTOR SPEEDMBC Motor SpeedHzRead
AV126MBC LANDING COUNTERMBC Landing Counter (Mod A chillers only)Read
AV127ACTIVE MIN PRV POSActive Minimum PRV Position (Mod A chiller FAA comp only)%Read
AV137UPS BATTERY VOLTAGEUPS Battery Voltage (Mod B Chillers only)VoltsRead
AV138VSD PH A REC BASEPLATE TEMPVSD Phase A Rectifier Baseplate Temperature°FRead
AV139VSD PH B REC BASEPLATE TEMPVSD Phase B Rectifier Baseplate Temperature°FRead
AV140VSD PH C REC BASEPLATE TEMPVSD Phase C Rectifier Baseplate Temperature°FRead
AV141VSD PH A INV BASEPLATE TEMPVSD Phase A Inverter Baseplate Temperature°FRead
AV142VSD PH B INV BASEPLATE TEMPVSD Phase B Inverter Baseplate Temperature°FRead
AV143VSD PH C INV BASEPLATE TEMPVSD Phase C Inverter Baseplate Temperature°FRead
AV144EVAP SMALL TEMP DIFFEvaporator Small Temp Difference°F (diff)Read
AV145COND SMALL TEMP DIFFCondenser Small Temp Difference°F (diff)Read
AV146DISCHARGE SUPERHEATDischarge Superheat°F (diff)Read
AV147SUBCOOLLER EFFECTIVENESSSubcooler EffectivenessRead
AV148SUBCOOLING TEMPSubcooling Temperature°F (diff)Read
AV149DELTA P DIV PDelta P / PRead
AV150HEAD PRESSUREHead PressurePSIDRead
MV10RUN STOP CTRL SOURCERun/Stop Control SourceRead0=Local, 1=BAS, 2=Hardwire
AV421RUN STOP CTRL SOURCE AVRun/Stop Control Source, same codes as MV 10Read0=Local, 1=BAS, 2=Hardwire
MV11COOL SETP CTRL SOURCECooling Setp Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV422COOL SETP CTRL SOURCE AVCooling Setp Control Source, same codes as MV 11Read0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
MV12HEAT SETP CTRL SOURCEHeating Setp Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV423HEAT SETP CTRL SOURCE AVHeating Setp Control Source, same codes as MV 12Read0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
MV13CURR LIM CTRL SOURCECurrent Limit Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV424CURR LIM CTRL SOURCE AVCurrent Limit Control Source, same codes as MV 13Read0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)

How many BACnet points does the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) have?

This list has 112 BACnet objects: 88 analog values, 11 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points are writable?

5 of the 112 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet documentation?

The source is YMC2 SC-EQ BAS Points List, revision Rev 2.11, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/5I6BffzkZybYzhNWLkSq1w/content.

What are the minimum BACnet points to integrate the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)?

Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE INPUT CURRENT SP (Remote input current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 29 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)?

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and the REM AVs are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital, Modem or Remote. MV 10 shows the run/stop source (Local, BAS, Hardwire) and MV 11-13 the cooling setpoint, heating setpoint and current limit sources (Local, BAS, 0-10 V, 4-20 mA, PWM); check they read BAS. The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.

How do I check these points on the real YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YMC2 SC-EQ BAS Points List · rev. Rev 2.11, 2021-12-08. Object names, instances and units are reproduced as published; descriptions are our own.