Easy BACnet
  1. Home
  2. BACnet points lists
  3. York
  4. YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)

Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card) · BACnet points list

York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) BACnet points list

Updated 28 October 2026

Short answer

YORK by Johnson Controls YVWH, YVWE and YGWH water-cooled screw units share one SC-EQ list on BACnet MS/TP (or Modbus RTU / N2). A Read/Write block holds start/stop, run mode (cool, ice storage, heat pump, remote), leaving water setpoints per mode and over-current percentages per mode. Read points cover water temperatures, pressures, per-system motor and VSD values, and bit-coded digital I/O and fault words.

This page lists 79 BACnet objects for the York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
Equipment
Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
Equipment type
Chillers
BACnet objects
79 (9 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 3.5.0.11
Default device instance
5000 + MAC address
Also known as
YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump
Source document
YVWH YVWE YGWH SC-EQ BAS Points List · rev. Rev 1.0, 2021-03-15
Download CSV 79 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)

Integration in brief

Select the run mode with MV 1, start/stop with BV 1, and write the setpoint for the active mode (AV 1 cooling, AV 3 heat pump). MV 2 shows whether the unit is under local, remote or communication control. Read leaving water temperatures, % FLA and VSD run status, and alarm on BV 2.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1START|STOPStart/stop command (1 = start)Write
MV 1RUN MODEMode: cool, ice storage, heat pump, remoteWrite
AV 1LEAVING CHILLED LIQUID SETPOINT ACLeaving chilled liquid setpoint, cooling modeWrite
AV 3LEAVING HEAT LIQUID SETPOINT HPLeaving hot liquid setpoint, heat pump modeWrite
AV 21OVER CURRENT PERCENT ACOver-current setting, %, cooling mode (no detail in sheet)Write
MV 2CONTROL MODEControl mode: local, remote or communicationRead
MV 3SYS 1 VSD RUN STATUSCompressor 1 VSD running, stopped or faultRead
AV 9LEAVING CHILLED LIQUID TEMPERATURELeaving chilled liquid temperatureRead
AV 24SYS 1 PERCENT FLACompressor 1 current, % FLARead
BV 2FAULTUnit fault (1 = fault)Read

Enable & remote start

MV 2 reports the control mode (local, remote, communication). The sheet does not say how to select it and gives no write-enable point.

Network setup

Watch out for

York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

79 of 79 shown
Type
AnalogBinaryMulti-state
Access
Show
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) BACnet Points List
DescriptionStates
BVmin1START|STOPStart/StopWrite0=Stop, 1=Start
MVmin1RUN MODERun ModeWrite0=Cool, 1=ice storage, 2=heat pump, 3=remote
AVmin1LEAVING CHILLED LIQUID SETPOINT ACLeaving chilled liquid setpoint, cooling (AC) mode°FWrite
AV2LEAVING CHILLED LIQUID SETPOINT ICSLeaving chilled liquid setpoint, ice storage (ICS) mode°FWrite
AVmin3LEAVING HEAT LIQUID SETPOINT HPLeaving hot liquid setpoint, heat pump (HP) mode°FWrite
AV4LEAVING HEAT LIQUID SETPOINT HTHPLeaving hot liquid setpoint, high-temperature heat pump mode°FWrite
AVmin21OVER CURRENT PERCENT ACOver current percent, cooling (AC) mode%Write
AV22OVER CURRENT PERCENT ICSOver current percent, ice storage (ICS) mode%Write
AV23OVER CURRENT PERCENT HPOver current percent, heat pump (HP) mode%Write
BVmin2FAULTFaultRead0=no fault, 1=fault exist
BV3TIME LIMITATIONTime LimitationRead0=no time limitation, 1=time limitation
BV4PREHEATPreheatRead0=no preheat, 1=preheat
MVmin2CONTROL MODEControl ModeRead0=local, 1=remote, 2=communication
AV5SYS 1 DIGITAL OUTPUTSystem 1 digital outputs, bit-codedReadBit 0=Liquid Pump, Bit 1=Compressor Y Contact, Bit 2=Compressor Δ Contact, Bit 3=Oil Heater, Bit 4=Hot Gas Bypass, Bit 5=Alarm, Bit 6=Liquid Injection Oil Cooling, Bit 7=DO18, Bit 8=Unit Running, Bit 9=Oil Supply Circuit, Bit 12=Slide Stop Load, Bit 13=Slide Stop Unload, Bit 14=Slide Valve Load, Bit 15=Slide Valve Unload (1=on)
AV6SYS 1 DIGITAL INPUTSystem 1 digital inputs, bit-codedReadBit 0=Chilled Liquid Flow Switch, Bit 1=Mode Switch, Bit 2=High Pressure Switch, Bit 3=Low Oil Level Switch, Bit 4=Motor Internal Protect, Bit 5=External Interlock/Power Protect, Bit 6=Starter Running Feedback, Bit 7=Remote Switch, Bit 8=EM Stop, Bit 9=Starter Fault Feedback, Bit 10=Condenser Liquid Flow Switch (1=closed)
AV7LEAVING CONDENSER LIQUID TEMPERATURELeaving Condenser Liquid Temperature°FRead
AV8RETURN CONDENSER LIQUID TEMPERATUREReturn Condenser Liquid Temperature°FRead
AVmin9LEAVING CHILLED LIQUID TEMPERATURELeaving Chilled Liquid Temperature°FRead
AV10RETURN CHILLED LIQUID TEMPERATUREReturn Chilled Liquid Temperature°FRead
AV11SYS 1 DISCHARGE TEMPERATURESys 1 Discharge Temperature°FRead
AV12EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV13CONDENSER PRESSURECondenser PressurePSIGRead
AV14SYS 1 OIL PRESSURESys 1 Oil PressurePSIGRead
AV15SYS 1 MOTOR CURRENTSys 1 Motor CurrentAmpsRead
AV16SYS 1 DIGITAL INPUT FAULTSystem 1 digital input faults, bit-codedReadBit 0=Cycling Stop-Chilled Liquid Flow Switch Open, Bit 1=Cycling Stop-Condenser Liquid Flow Switch Open, Bit 2=Safety Fault-SYS1 High Pressure Contact Open, Bit 3=Safety Fault-Low Level Switch Open, Bit 4=Safety Fault-SYS1 Compressor Motor Protection, Bit 5=Safety Fault-External Interlock Protection, Bit 6=Safety Fault-SYS1 Compressor Start Fail, Bit 7=Safety Fault-Emergency Stop Pressed, Bit 8=Start Inhibit-Oil Heat Over 5 Hour Before Start, Bit 9=Safety Fault-Evaporator Smart Freeze Protection (1=fault)
AV17SYS 1 ANALOG INPUT FAULTSystem 1 analog input (sensor) faults, bit-codedReadBit 0=Safety Fault-Leaving Condenser Temp. Sensor Fault, Bit 1=Safety Fault-Return Condenser Temp. Sensor Fault, Bit 2=Safety Fault-Leaving Chilled Sensor Fault, Bit 3=Safety Fault-Return Chilled Temp. Sensor Fault, Bit 4=Safety Fault-SYS1 Discharge Temp. Sensor Fault, Bit 10=Safety Fault-Leaving Hot Liquid Temp. Sensor Fault, Bit 11=Safety Fault-Return Hot Liquid Temp. Sensor Fault, Bit 12=Safety Fault-Evaporator Pressure Out Of Range Fault, Bit 13=Safety Fault-Condenser Pressure Sensor Fault, Bit 14=Safety Fault-SYS1 Oil Pressure Sensor Fault (1=fault)
AV18SYS 1 FAULTSystem 1 faults, bit-codedReadBit 0=Safety Fault-Condenser High Pressure, Bit 1=Safety Fault-Evaporator Low Pressure, Bit 2=Safety Fault-SYS1 Discharge High Temp., Bit 3=Safety Fault-SYS1 Compressor Over Current, Bit 4=Safety Fault-SYS1 Compressor Low Current, Bit 5=Cycling Stop-Leaving Condenser High Temperature, Bit 6=Cycling Stop-Leaving Chilled Liquid Low Temperature, Bit 7=Safety Fault-SYS1 Oil Low Diff. Pressure, Bit 8=Safety Fault-SYS1 Oil Clogged Filter, Bit 9=Cycling Stop-SYS1 Anti-Recycle, Bit 10=Cycling Stop-Leaving Hot Liquid High Temperature, Bit 11=Safety Fault-SYS1 Oil Supply Fail, Bit 12=Safety Fault-SYS1 Discharge Low Superheat, Bit 13=Safety Fault-SYS1 Motor High Temperature, Bit 14=Cycling Stop-SYS1 Discharge High Temp. (1=fault)
AV19WATER PUMP WORK HOURSWater Pump Work HoursHoursRead
AV20SYS 1 COMPRESSOR WORK HOURSSys 1 Compressor Work HoursHoursRead
AVmin24SYS 1 PERCENT FLASys 1 Percent FLA%Read
AV25EVAPORATOR SATURATION TEMPERATUREEvaporator Saturation Temperature°FRead
AV26CONDENSER SATURATION TEMPERATURECondenser Saturation Temperature°FRead
AV27DISCHARGE SUPERHEATSys 1 Discharge Superheat°F (diff)Read
AV28SYS 1 MOTOR TEMPERATURE ASys 1 Motor Temperature A°FRead
AV29SYS 1 MOTOR TEMPERATURE BSys 1 Motor Temperature B°FRead
AV30SYS 1 MOTOR TEMPERATURE CSys 1 Motor Temperature C°FRead
AV31LIQUID LEVELLiquid Level%Read
AV32LEVEL CONTROL AOLevel Control AO%Read
AV33LEVEL SETPOINTLevel Setpoint%Read
AV34LEVEL CONTROL PBLevel Control Pb%Read
AV35LEVEL CONTROL TNLevel Control TnSecRead
AV36LEVEL CONTROL PERIODLevel Control PeriodSecRead
MVmin3SYS 1 VSD RUN STATUSSys 1 VSD Run StatusRead0=No Communication, 1=Forward Running, 2=Reverse Running, 3=Stopped, 4=Tuned, 5=Fault
AV38SYS 1 FREQUENCY COMMANDSys 1 VSD Frequency CommandHzRead
AV39SYS 1 VSD FREQUENCY RUNNINGSys 1 VSD Frequency RunningHzRead
AV40SYS 1 VSD BUS VOLTAGESys 1 VSD BUS VoltageVoltsRead
AV41SYS 1 VSD OUTPUT VOLTAGESys 1 VSD Output VoltageVoltsRead
AV42SYS 1 VSD OUTPUT CURRENTSys 1 VSD Output CurrentAmpsRead
AV43SYS 1 VSD OUTPUT POWERSys 1 VSD Output PowerkWRead
AV44SYS 1 VSD HEATSINK TEMPERATURESys 1 VSD Heatsink Temperature°FRead
AV45SYS 1 VSD FAULT CODESys 1 VSD Fault CodeRead
AV46SYS 1 FAIL RATESys 1 Fail Rate%Read
AV47VSD COMMAND PERIODVSD Command PeriodSecRead
AV48VSD PBVSD Pb%Read
AV49VSD TNVSD TnSecRead
AV50SYS 2 DIGITAL OUTPUTSystem 2 digital outputs, bit-codedReadBit 1=Compressor Y Contact, Bit 2=Compressor Δ Contact, Bit 6=Liquid Injection Oil Cooling, Bit 9=Oil Supply Circuit, Bit 12=Slide Stop Load, Bit 13=Slide Stop Unload, Bit 14=Slide Valve Load, Bit 15=Slide Valve Unload (1=on)
AV51SYS 2 DIGITAL INPUTSystem 2 digital inputs, bit-codedReadBit 2=High Pressure Switch, Bit 4=Motor Internal Protect, Bit 6=Starter Running Feedback, Bit 9=Starter Fault Feedback (1=closed)
AV52SYS 2 DISCHARGE TEMPERATURESys 2 Discharge Temperature°FRead
AV55SYS 2 OIL PRESSURESys 2 Oil PressurePSIGRead
AV56SYS 2 MOTOR CURRENTSys 2 Motor CurrentAmpsRead
AV57SYS 2 DIGITAL INPUT FAULTSystem 2 digital input faults, bit-codedRead
AV58SYS 2 ANALOG INPUT FAULTSystem 2 analog input faults, bit-codedRead
AV59SYS 2 FAULTSystem 2 faults, bit-codedRead
AV60SYS 2 COMPRESSOR WORK HOURSSys 2 Compressor Work HoursHoursRead
AV61SYS 2 PERCENT FLASys 2 Percent FLA%Read
AV62SYS 2 DISCHARGE SUPERHEATSys 2 Discharge Superheat°F (diff)Read
AV63SYS 2 MOTOR TEMPERATURE ASys 2 Motor Temperature A°FRead
AV64SYS 2 MOTOR TEMPERATURE BSys 2 Motor Temperature B°FRead
AV65SYS 2 MOTOR TEMPERATURE CSys 2 Motor Temperature C°FRead
MV4SYS 2 VSD RUN STATUSSys 2 VSD Run StatusRead0=No Communication, 1=Forward Running, 2=Reverse Running, 3=Stopped, 4=Tuned, 5=Fault
AV67SYS 2 VSD FREQUENCY COMMANDSys 2 VSD Frequency CommandHzRead
AV68SYS 2 VSD FREQUENCY RUNNINGSys 2 VSD Frequency RunningHzRead
AV69SYS 2 VSD BUS VOLTAGESys 2 VSD BUS VoltageVoltsRead
AV70SYS 2 VSD OUTPUT VOLTAGESys 2 VSD Output VoltageVoltsRead
AV71SYS 2 VSD OUTPUT CURRENTSys 2 VSD Output CurrentAmpsRead
AV72SYS 2 VSD OUTPUT POWERSys 2 VSD Output PowerkWRead
AV73SYS 2 VSD HEATSINK TEMPERATURESys 2 VSD Heatsink Temperature°FRead
AV74SYS 2 VSD FAULT CODESys 2 VSD Fault CodeRead
AV75SYS 2 FAIL RATESys 2 Fail Rate%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)

How many BACnet points does the York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) have?

This list has 79 BACnet objects: 71 analog values, 4 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) BACnet points are writable?

9 of the 79 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ) BACnet documentation?

The source is YVWH YVWE YGWH SC-EQ BAS Points List, revision Rev 1.0, 2021-03-15, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/TWAOtmjMD~xxMBlTMLA2QQ/content.

What are the minimum BACnet points to integrate the York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)?

Start with BV 1 START|STOP (Start/stop command (1 = start)); MV 1 RUN MODE (Mode: cool, ice storage, heat pump, remote); AV 1 LEAVING CHILLED LIQUID SETPOINT AC (Leaving chilled liquid setpoint, cooling mode); AV 3 LEAVING HEAT LIQUID SETPOINT HP (Leaving hot liquid setpoint, heat pump mode); AV 21 OVER CURRENT PERCENT AC (Over-current setting, %, cooling mode (no detail in sheet)); MV 2 CONTROL MODE (Control mode: local, remote or communication); MV 3 SYS 1 VSD RUN STATUS (Compressor 1 VSD running, stopped or fault); AV 9 LEAVING CHILLED LIQUID TEMPERATURE (Leaving chilled liquid temperature); AV 24 SYS 1 PERCENT FLA (Compressor 1 current, % FLA); BV 2 FAULT (Unit fault (1 = fault)).

How do I enable BMS control of the York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)?

MV 2 reports the control mode (local, remote, communication). The sheet does not say how to select it and gives no write-enable point.

How do I check these points on the real YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YVWH YVWE YGWH SC-EQ BAS Points List · rev. Rev 1.0, 2021-03-15. Object names, instances and units are reproduced as published; descriptions are our own.