Easy BACnet
  1. Home
  2. BACnet points lists
  3. York
  4. YK-EP Centrifugal Chiller (SC-EQ)

Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card) · BACnet points list

York YK-EP Centrifugal Chiller (SC-EQ) BACnet points list

Updated 28 October 2026

Short answer

Same base list as the YK, plus an economizer-compressor block (AV 205-243, BV 205-209): its pressures, motor current and voltage, discharge and saturation temperatures, refrigerant level, run status, hours and starts. The SC-EQ card connects on BACnet MS/TP (or Modbus RTU / N2). Drive points depend on the starter type.

This page lists 170 BACnet objects for the York YK-EP Centrifugal Chiller (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YK-EP Centrifugal Chiller (SC-EQ)
Equipment
Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
Equipment type
Chillers
BACnet objects
170 (5 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.2.0.20
Default device instance
5000 + MAC address
Also known as
YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1
Source document
YKEP SC-EQ BAS Points List · rev. Rev 2.9, 2021-12-08
Download CSV 170 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YK-EP Centrifugal Chiller (SC-EQ)

Integration in brief

Wire the BAS to the SC-EQ J12 RS-485 port, set the MAC address on the DIP switch and let the card detect BACnet MS/TP. Write the remote run/stop, leaving chilled liquid setpoint and current limit, then read main and economizer motor run status, the operation code, leaving chilled liquid temperature, % FLA and the safety fault code. Check MV 5 and MV 10-13 to confirm the chiller is taking its commands from the BAS.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM RUN STOP CMDRemote run/stop (1 = run)Command
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 2REMOTE CURRENT SPRemote motor current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUSCompressor motor runningRead
MV 5UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
AV 12MOTOR CURRENT PCT FLAMotor current, % FLA (load indication)Read
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read
MV 3UNIT CYCLING FAULT CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and the REM AVs are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital, Modem or Remote. MV 10 shows the run/stop source (Local, BAS, Hardwire) and MV 11-13 the cooling setpoint, heating setpoint and current limit sources (Local, BAS, 0-10 V, 4-20 mA, PWM); check they read BAS. The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.

Network setup

Watch out for

York YK-EP Centrifugal Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

170 of 170 shown
Type
AnalogBinaryMulti-state
Access
Show
York YK-EP Centrifugal Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REMOTE CURRENT SPRemote Current Limit Setpoint%Command
AV3REM HEATING SPRemote Heating Setpoint°FCommand
BVmin1REM RUN STOP CMDRemote Run/StopCommand0=Stop, 1=Run
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CH LIQ TEMPEntering Chilled Liquid Temperature°FRead
AV7EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV8CONDENSER PRESSURECondenser PressurePSIGRead
AV9OIL PRESSURE DIFERENTIALOil Pressure DifferentialPSIDRead
AV10ENTERING COND WATER TEMPEntering Condenser Liquid Temperature°FRead
AV11LEAVING COND WATER TEMPLeaving Condenser Liquid Temperature°FRead
AVmin12MOTOR CURRENT PCT FLAMotor % Full Load Amps%Read
AV13VSD PHASE A OUTPUT CURRENT / MOTOR PHASE A CURRENTPhase A current: VSD output (VSD) or motor (SSS)AmpsRead
AV14VSD PHASE B OUTPUT CURRENT / MOTOR PHASE B CURRENTPhase B current: VSD output (VSD) or motor (SSS)AmpsRead
AV15VSD PHASE C OUTPUT CURRENT / MOTOR PHASE C CURRENTPhase C current: VSD output (VSD) or motor (SSS)AmpsRead
AV16VSD RMS INPUT CURRENT L1 / MOTOR PHASE A VOLTAGEVSD L1 input current (Raptyr VSD) or motor phase A voltage (SSS)Amps / VoltsRead
AV17VSD RMS INPUT CURRENT L2 / MOTOR PHASE B VOLTAGEVSD L2 input current (Raptyr VSD) or motor phase B voltage (SSS)Amps / VoltsRead
AV18VSD RMS INPUT CURRENT L3 / MOTOR PHASE C VOLTAGEVSD L3 input current (Raptyr VSD) or motor phase C voltage (SSS)Amps / VoltsRead
AV19LEAVING CH LIQ TEMP ACT SPLeaving Chilled Liquid Setpoint - Selected°FRead
AV20CURRENT LIMIT ACTIVE SPActive Current Limit%Read
AV21EVAP SATURATION TEMPEvaporator Saturation Temperature°FRead
AV22COND SATURATION TEMPCondenser Saturation Temperature°FRead
AV23DISCHARGE TEMPDischarge Temperature°FRead
AV24OIL SUMP TEMPERATUREOil Sump Temperature°FRead
AV25COND REFRIGERANT LEVELCondenser Refrigerant Level%Read
AV26OPERATING HOURSOperating HoursHrRead
AV27NUMBER OF STARTSNumber Of StartsRead
AV28OIL SUMP PRESSUREOil Sump PressurePSIGRead
AV29OIL PUMP PRESSUREOil Pump PressurePSIGRead
BVmin5COMPR MOTOR STATUSMotor RunRead0=Off, 1=On
BV6LIQUID LINE SOLENOIDLiquid Line SolenoidRead0=Off, 1=On
BV7CH LIQ PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV8START STOP SWITCH STATUSPanel Stop SwitchRead0=Off, 1=On
BV9CH LIQ FLOW SWITCH STATChilled Liquid Flow SwitchRead0=Open, 1=Closed
BV10CND FLOW SWITCH STATCondenser Liquid Flow SwitchRead0=Open, 1=Closed
BV11CND LIQ PUMP STATCondenser Liquid PumpRead0=Off, 1=On
BV19VSD COOLING SYS STATVSD Cooling System (VSD only)Read0=Off, 1=On
BV20VSD HARMONIC FILTER INSTHarmonic Filter Installed (VSD only)Read0=False, 1=True
MVmin1UNIT OPERATION CODEUnit Operation CodeRead1=Unit Stopped - Ready to Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Chiller Unload Before Shutdown, 12=Unit Coastdown, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown, 22=Unit Running - Cooling - No Abnormal Condition, 23=Unit Running - Cooling - Warning Active, 24=Unit Running - Cooling - Modified Run, 25=Unit Running - Heating - No Abnormal Condition, 26=Unit Running - Heating - Warning Active, 27=Unit Running - Heating - Modified Run, 28=Unit Running - Cooling & Heating - No Abnormal Condition, 29=Unit Running - Cooling & Heating - Warning Active, 30=Unit Running - Cooling & Heating - Modified Run
AV401UNIT OPERATION CODE AVUnit Operation Code, raw code (MV 1 shows code + 1)Read
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Safety Faults Present; other values (up to 186) are YKEP Safety Fault Code table SC.2 codes plus 1 (182 codes listed in the source doc)
AV402UNIT SAFETY FAULT CODE AVUnit Safety Fault Code, raw code (MV 2 shows code + 1)Read
MVmin3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Cycling Faults Present; other values (up to 211) are YKEP Cycling Fault Code table SC.3 codes plus 1 (205 codes listed in the source doc)
AV403UNIT CYCLING FAULT CODE AVUnit Cycling Fault Code, raw code (MV 3 shows code + 1)Read
MV4UNIT WARNING CODEUnit Warning CodeRead1=No Warnings Present; other values (up to 152) are YKEP Warning Code table SC.4 codes plus 1 (147 codes listed in the source doc)
AV404UNIT WARNING CODE AVUnit Warning Code, raw code (MV 4 shows code + 1)Read
MVmin5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
AV405UNIT CONTROL SOURCE AVUnit Control Source, same codes as MV 5Read0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
MV6UNIT MODIFIED RUN CODEUnit Modified Run CodeRead1=No Modified Run Conditions Present, 5=Motor - Pulldown Limit, 6=Motor - High Current Limit, 7=Motor Controller - Input Pulldown Limit, 8=Motor Controller - High Input Power Limit, 9=Load Control Mode, 10=COMPRESSOR - SUCTION FLOW LIMIT, 11=VSD - DC BUS ACTIVE, 12=VSD - Input Pulldown Limit, 13=VSD - High Input Current Limit, 14=Discharge – Low Superheat Limit, 15=ECON MOTOR – HIGH CURRENT LIMIT, 16=ECON SEAL LUBRICATION IN PROGRESS, 17=ECON ECONOMIZER – RUN DISABLED, 18=ECON ECONOMIZER – NO DEMAND, 19=ECON COMPRESSOR – NO DEMAND (ECON STOPPED), 20=SEAL LUBRICATION IN PROGRESS
AV406UNIT MODIFIED RUN CODE AVUnit Modified Run Code, raw code (MV 6 shows code + 1)Read
MV7UNIT START INHIBIT CODEUnit Start Inhibit CodeRead1=No Inhibit Faults Present, 2=ANTI-RECYCLE, 3=Vane Motor Switch Open, 4=MOTOR CURRENT > 15 %FLA, 5=LCSSS - HIGH PHASE A HEATSINK TEMPERATURE - STOPPED, 6=LCSSS - HIGH PHASE B HEATSINK TEMPERATURE - STOPPED, 7=LCSSS - HIGH PHASE C HEATSINK TEMPERATURE - STOPPED, 8=MOTOR CONTROLLER - INITIALIZATION IN PROGRESS, 9=VSD - FREQUENCY > 0 HZ, 10=MVSSS - HIGH HEATSINK TEMPERATURE - STOPPED, 11=Line Voltage Not Set, 12=Line Frequency Not Set, 13=Oil - High Sump Pressure - Stopped, 14=VGD Actuator - Feedback Not Calibrated, 15=VGD Actuator - Limit Switch Open, 16=PRV Not Calibrated, 17=VGD Actuator - Stroke Not Calibrated, 18=MBC - INITIALIZATION IN PROGRESS, 19=MBC - BEARING CALIBRATION IN PROGRESS, 20=MBC - BEARING CLEARANCE CHECK IN PROGRESS, 21=MVSSS - HIGH HEATSINK 1 TEMPERATURE - STOPPED, 22=MVSSS - HIGH HEATSINK 2 TEMPERATURE - STOPPED, 23=MVSSS - HIGH HEATSINK 3 TEMPERATURE - STOPPED
AV407UNIT START INHIBIT CODE AVUnit Start Inhibit Code, raw code (MV 7 shows code + 1)Read
MV8UNIT INTERNAL FAULT CODEUnit Internal Fault CodeRead1=No Internal Faults Present, 2=Internal Error - No Timer Handles Available, 3=Watchdog - Software Reboot, 4=Internal Error - Cannot Create Task, 6=INTERNAL ERROR - INVALID BRAM
AV408UNIT INTERNAL FAULT CODE AVUnit Internal Fault Code, raw code (MV 8 shows code + 1)Read
AV30PROX SENSOR ACT POSHigh Speed Thrust Bearing Proximity Position (J, K and U Compressors Only)MilsRead
AV31PROX SENSOR REF POSHigh Speed Thrust Bearing Proximity Reference (J, K and U Compressors Only)MilsRead
AV32ANTI RECYCLE TIME REMAINAnti-Recycle Time RemainingMinRead
AV33INPUT CURRENT PCT FLAInput % Full Load Amps (Raptyr VSD only)%Read
AV34VSD OUTPUT VOLTAGEVSD Output Voltage (VSD only)VoltsRead
AV35VSD INPUT POWERVSD Input Power (VSD only)kWRead
AV36VSD INPUT KWHVSD Input Kilowatt Hours (VSD only)kWhRead
AV37VSD DC BUS VOLTAGEVSD DC Bus Voltage (VSD only)VoltsRead
AV38VSD DC BUS CURRENTVSD DC Bus Current (Non-Raptyr LVVSD VSD only)AmpsRead
AV39ACC SURGE COUNTACC Surge Count (VSD only)Read
AV40VSD OUTPUT FREQUENCYVSD Output Frequency (VSD only)HzRead
AV41FILTER MAX VOLTAGE THDHarmonic Filter Max Voltage Total Harmonic Distortion%Read
AV42FILTER MAX CURRENT TDDHarmonic Filter Max Current Total Demand Distortion%Read
AV43FILTER SUPPLY KVAHarmonic Filter Total Supply KVA (LVVSD with Harmonic Filter or Raptyr VSD)kVARead
AV105MTR SHAFT END VIBRMotor Bearing Shaft End Vibration (motor monitoring option)Read
AV106MTR OP SHAFT END VIBRMotor Bearing Opposite Shaft End Vibration (motor monitoring option)Read
AV107MTR SHAFT END TEMPMotor Bearing Shaft End Temperature (motor monitoring option)°FRead
AV108MTR OP SHAFT END TEMPMotor Bearing Opposite Shaft End Temperature (motor monitoring option)°FRead
AV109MTR WINDING AVG TEMPAverage Winding Temperature (motor monitoring option)°FRead
AV110VSD INTERNAL AMBIENT TEMPVSD Internal Ambient Temp (LVVSD only)°FRead
AV111VSD CONVERTER HSINK TEMPVSD Converter Heatsink Temp (LVVSD only)°FRead
AV112PRE ROTATION VANES POSPre Rotation Vanes (PRV) Position (VSD, VGD or HGBP only)%Read
AV113ACC MAP OUTPUT FREQACC Map Output Frequency (VSD only)HzRead
AV114COND REFRIGERANT LEVEL SPCondenser Refrigerant Level Setpoint%Read
AV115DROP LEG REFRIG TEMPDrop Leg Refrigerant Temperature (Drop Leg Temp Enabled only)°FRead
AV116LEAVING HEAT COND LIQ TEMPLeaving Heating Condenser Liquid Temperature (Heat Recovery only)°FRead
AV117HEATING ACTIVE SPActive Heating Setpoint (heat pump or heat recovery hot water)°FRead
AV118HEAT REC HEAD PRESS VLV CMDHeat Recovery/Head Pressure Control Valve Cmd (head pressure control or heat recovery)%Read
AV119INPUT POWERInput Power (SSS only)kWRead
AV120INPUT KWHInput Kilowatt Hours (SSS only)kWhRead
AV121INPUT KWH LO SSS / INPUT KWH LOInput kWh, low part (SSS or VSD)Read
AV122INPUT KWH OFFSET SSS / INPUT KWH OFFSETInput kWh, offset part x 10,000 (SSS or VSD)Read
AV123OPERATING HOURS LOOperating Hours LowRead
AV124OPERATING HOURS OFFSETOperating Hours OffsetRead
AV126HP LEAVING COND LIQ SP LOCALLocal Leaving Condenser Liquid Setpoint (heat pump or heat recovery hot water)°FRead
AV127HOT GAS BYPASS COMMANDHot Gas Bypass Command (Hot Gas Bypass enabled only)%Read
AV128EVAP REFRIGERANT TEMPEvaporator Refrigerant Temperature (Evaporator Refrigerant Temperature enabled only)°FRead
BV105COND REF LEVEL CNTRL MODECondenser Level Control Valve ModeRead0=Auto, 1=Manual
AV130MTR WINDING PH A TEMPMotor Winding Phase A Temperature (motor monitoring option)°FRead
AV131MTR WINDING PH B TEMPMotor Winding Phase B Temperature (motor monitoring option)°FRead
AV132MTR WINDING PH C TEMPMotor Winding Phase C Temperature (motor monitoring option)°FRead
AV133MTR WINDING PH A2 TEMPMotor Winding Phase A2 Temperature (motor monitoring option)°FRead
AV134MTR WINDING PH B2 TEMPMotor Winding Phase B2 Temperature (motor monitoring option)°FRead
AV135MTR WINDING PH C2 TEMPMotor Winding Phase C2 Temperature (motor monitoring option)°FRead
AV136VSD OIL PUMP CMD FREQUENCYVSD Oil Pump Command FrequencyHzRead
AV137ENTERING HEAT COND LIQ TEMPEntering Heating Condenser Liquid Temperature (Heat Recovery only)°FRead
AV138VSD PH A REC BASEPLATE TEMPVSD Phase A Rectifier Baseplate Temperature (Raptyr VSD only)°FRead
AV139VSD PH B REC BASEPLATE TEMPVSD Phase B Rectifier Baseplate Temperature (Raptyr VSD only)°FRead
AV140VSD PH C REC BASEPLATE TEMPVSD Phase C Rectifier Baseplate Temperature (Raptyr VSD only)°FRead
AV141VSD PH A HEATSINK TEMPVSD Phase A Heatsink Temperature / Baseplate Temperature (Non-Raptyr LVVSD VSD only)°FRead
AV142VSD PH B HEATSINK TEMPVSD Phase B Heatsink Temperature (Non-Raptyr LVVSD VSD only)°FRead
AV143VSD PH C HEATSINK TEMPVSD Phase C Heatsink Temperature (Non-Raptyr LVVSD VSD only)°FRead
AV144EVAP SMALL TEMP DIFFEvaporator Small Temp Difference°F (diff)Read
AV145COND SMALL TEMP DIFFCondenser Small Temp Difference°F (diff)Read
AV146DISCHARGE SUPERHEATDischarge Superheat°F (diff)Read
AV147SUBCOOLER EFFECTIVENESSSubcooler Effectiveness (Drop Leg Temp Enabled only)Read
AV148SUBCOOLING TEMPSubcooling Temperature (Drop Leg Temp Enabled only)°F (diff)Read
AV149DELTA P DIV PDelta P / PRead
AV150HEAD PRESSUREHead PressurePSIDRead
AV151STALL VOLTAGEStall VoltageVoltsRead
MV10RUN STOP CTRL SOURCERun/Stop Control SourceRead0=Local, 1=BAS, 2=Hardwire
AV421RUN STOP CTRL SOURCE AVRun/Stop Control Source, same codes as MV 10Read0=Local, 1=BAS, 2=Hardwire
MV11COOL SETP CTRL SOURCECooling Setp Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV422COOL SETP CTRL SOURCE AVCooling Setp Control Source, same codes as MV 11Read0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
MV12HEAT SETP CTRL SOURCEHeating Setp Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV423HEAT SETP CTRL SOURCE AVHeating Setp Control Source, same codes as MV 12Read0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
MV13CURR LIM CTRL SOURCECurrent Limit Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV424CURR LIM CTRL SOURCE AVCurrent Limit Control Source, same codes as MV 13Read0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV152SURGE AVOIDANCE SURGE COUNTSurge Avoidance Surge CountRead
AV153SSS PHASE A TEMPSSS Phase A Temperature (LCSSS only)°FRead
AV154SSS PHASE B TEMPSSS Phase B Temperature (LCSSS only)°FRead
AV155SSS PHASE C TEMPSSS Phase C Temperature (LCSSS only)°FRead
AV205ECONOMIZER PRESSUREEconomizer PressurePSIGRead
AV206ECON COMP OIL PRESSURE DIFERENTIALEconomizer Compressor Oil Pressure DifferentialPSIDRead
AV207ECON MOTOR CURRENT PCT FLAEconomizer Motor Current Percent FLA%Read
AV208ECON MOTOR PHASE A CURRENTEconomizer Motor Phase A CurrentAmpsRead
AV209ECON MOTOR PHASE B CURRENTEconomizer Motor Phase B CurrentAmpsRead
AV210ECON MOTOR PHASE C CURRENTEconomizer Motor Phase C CurrentAmpsRead
AV211ECON MOTOR PHASE A VOLTAGEEconomizer Motor Phase A VoltageVoltsRead
AV212ECON MOTOR PHASE B VOLTAGEEconomizer Motor Phase B VoltageVoltsRead
AV213ECON MOTOR PHASE C VOLTAGEEconomizer Motor Phase C VoltageVoltsRead
AV214ECON CURRENT LIMIT ACTIVE SPEconomizer Active Current Limit%Read
AV215ECON COMP DISCHARGE TEMPEconomizer Compressor Discharge Temperature°FRead
AV216ECON SATURATION TEMP ACT SPEconomizer Active Saturation Temperature Setpoint°FRead
AV217ECON SATURATION TEMPEconomizer Saturation Temperature°FRead
AV218ECON REFRIGERANT LEVEL SPEconomizer Active Level Setpoint%Read
AV219ECON REFRIGERANT LEVELEconomizer Refrigerant Level%Read
AV220ECON COMP OPERATING HOURSEconomizer Compressor Operating HoursHrRead
AV221ECON COMP NUMBER OF STARTSEconomizer Compressor Number of StartsRead
AV222ECON COMP OIL PUMP PRESSUREEconomizer Compressor Oil Pump PressurePSIGRead
AV223ECON COMP ANTI RECYCLE TIME REMAINEconomizer Compressor Anti-Recycle Time RemainingMinRead
AV224ECON ANTI-SURGE MIN TEMPEconomizer Active Anti-Surge Minimum Temperature°FRead
AV225ECON MTR SHAFT END VIBREconomizer Motor Bearing Shaft End Vibration (econ motor monitoring option)Read
AV226ECON MTR OP SHAFT END VIBREconomizer Motor Bearing Opposite Shaft End Vibration (econ motor monitoring option)Read
AV227ECON MTR SHAFT END TEMPEconomizer Motor Bearing Shaft End Temperature (econ motor monitoring option)°FRead
AV228ECON MTR OP SHAFT END TEMPEconomizer Motor Bearing Opposite Shaft End Temperature (econ motor monitoring option)°FRead
AV229ECON MTR WINDING AVG TEMPEconomizer Motor Average Winding Temperature (econ motor monitoring option)°FRead
BV205ECON COMPR MOTOR STATUSEconomizer Compressor Motor RunRead0=Off, 1=On
BV207MOTOR SPACE HEATER STATUSMotor Space Heater (Motor Space Heater Enabled only)Read0=Off, 1=On
BV208ECON MOTOR SPACE HEATER STATEconomizer Motor Space Heater (Econ Motor Space Heater Enabled only)Read0=Off, 1=On
BV209YKEP CONTROL ENABLEYKEP ControlRead0=Off, 1=On
AV230ECON COMP INPUT POWEREconomizer Compressor Input PowerkWRead
AV231ECON COMP INPUT KWHEconomizer Compressor Input Kilowatt HourskWhRead
AV232ECON COMP INPUT KWH LOEconomizer Compressor Input Kilowatt Hours LowRead
AV233ECON COMP INPUT KWH OFFSETEconomizer Compressor Input Kilowatt Hours OffsetRead
AV234ECON COMP OPERATING HOURS LEconomizer Compressor Operating Hours LowRead
AV235ECON COMP OPERATING HOURS OEconomizer Compressor Operating Hours OffsetRead
AV236ECON MTR WINDING PH A TEMPEconomizer Motor Winding Phase A Temperature (econ motor monitoring option)°FRead
AV237ECON MTR WINDING PH B TEMPEconomizer Motor Winding Phase B Temperature (econ motor monitoring option)°FRead
AV238ECON MTR WINDING PH C TEMPEconomizer Motor Winding Phase C Temperature (econ motor monitoring option)°FRead
AV239ECON MTR WINDING PH A2 TEMPEconomizer Motor Winding Phase A2 Temperature (econ motor monitoring option)°FRead
AV240ECON MTR WINDING PH B2 TEMPEconomizer Motor Winding Phase B2 Temperature (econ motor monitoring option)°FRead
AV241ECON MTR WINDING PH C2 TEMPEconomizer Motor Winding Phase C2 Temperature (econ motor monitoring option)°FRead
AV242ECON COMP PRE ROTATION VANES POSEconomizer Compressor Pre Rotation Vanes (PRV) Position%Read
AV243ECON COMP VSD OIL PUMP CMD FREQEconomizer Compressor VSD Oil Pump Command FrequencyHzRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YK-EP Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YK-EP Centrifugal Chiller (SC-EQ)

How many BACnet points does the York YK-EP Centrifugal Chiller (SC-EQ) have?

This list has 170 BACnet objects: 142 analog values, 15 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YK-EP Centrifugal Chiller (SC-EQ) BACnet points are writable?

5 of the 170 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YK-EP Centrifugal Chiller (SC-EQ) BACnet documentation?

The source is YKEP SC-EQ BAS Points List, revision Rev 2.9, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/WBwYCBJ~KihreRSMUxcxcQ/content.

What are the minimum BACnet points to integrate the York YK-EP Centrifugal Chiller (SC-EQ)?

Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE CURRENT SP (Remote motor current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 12 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YK-EP Centrifugal Chiller (SC-EQ)?

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and the REM AVs are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital, Modem or Remote. MV 10 shows the run/stop source (Local, BAS, Hardwire) and MV 11-13 the cooling setpoint, heating setpoint and current limit sources (Local, BAS, 0-10 V, 4-20 mA, PWM); check they read BAS. The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.

How do I check these points on the real YK-EP Centrifugal Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YKEP SC-EQ BAS Points List · rev. Rev 2.9, 2021-12-08. Object names, instances and units are reproduced as published; descriptions are our own.