Air-cooled variable-speed screw chiller · BACnet points list

York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

YORK by Johnson Controls YCAV and YCIV chillers with the 031-03478 microboard have BACnet MS/TP, Modbus RTU and N2 built in, so no gateway is needed. The BAS writes a remote setpoint, current limit, sound limit and start/stop (AV 1-3, BV 1). Everything else is read-only analog and binary inputs: chilled liquid and ambient temperatures, per-system pressures, temperatures, % FLA, hours, starts, flash tank values, operational and fault codes, and alarms.

This page lists 112 BACnet objects for the York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
Equipment
Air-cooled variable-speed screw chiller
Equipment type
Chillers
BACnet objects
112 (4 writable)
Transport
BACnet MS/TP
Firmware
Y.ACS.14.03 to Z.ACS.31.03 (031-03476 program parts listed in the sheet)
Also known as
YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude
Source document
YCAV YCIV Modbus, BACnet MS/TP, N2 Data Map (YCAV_IV Native) · rev. 2017-02-17
Download CSV 112 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)

Integration in brief

Put the chiller in remote control (BI 14 reads Remote), then start/stop it with BV 1 and write the remote setpoint (AV 1) and current limit (AV 2). Read each system's state, the leaving chilled liquid temperature and VSD frequency, and the two alarm inputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1START_STOPRemote start/stop (1 = run)Write
AV 1REM_SETPRemote leaving chilled liquid setpointWrite
AV 2DMD_LIMITRemote current limit, % FLAWrite
BI 14LOCAL_REMOTEMust read Remote (1) for BMS controlRead
AI 86S1_SYS_STATESystem 1 state (stopped, running, faulted)Read
AI 1LCHLTLeaving chilled liquid temperatureRead
AI 45VSD_OUT_FRCompressor VSD frequency (load indication)Read
BI 1S13_ALARMSystems 1/3 alarmRead
BI 2S24_ALARMSystems 2/4 alarmRead

Enable & remote start

BI 14 shows Local or Remote control mode. The sheet gives no point to change it and no write-enable point.

Heartbeat & communication loss

Operational code 67 is 'Loss Of External Communications'; the sheet gives no timeout or heartbeat point.

Network setup

Watch out for

York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

112 of 112 shown
Type
Access
Show
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) BACnet Points List
DescriptionStates
AVmin1REM_SETPRemote Setpoint°FWrite
AVmin2DMD_LIMITRemote Current Limit Setpoint% FLAWrite
AV3SND_LIMITRemote Sound Limit%Write
BVmin1START_STOPRemote Start / Stop CommandWrite0=Stop, 1=Run
AImin1LCHLTLeaving Chilled Liquid Temperature°FRead
AI2ECHLTEntering Chilled Liquid Temperature°FRead
AI3VSD_IA_TEMPVSD Internal Ambient Temperature°FRead
AI4S1_SUCT_TEMPSys 1 Suction Temperature°FRead
AI5S2_SUCT_TEMPSys 2 Suction Temperature°FRead
AI6S3_SUCT_TEMPSys 3 Suction Temperature°FRead
AI7S4_SUCT_TEMPSys 4 Suction Temperature°FRead
AI8S1_DSCH_TEMPSys 1 Discharge Temperature°FRead
AI9S2_DSCH_TEMPSys 2 Discharge Temperature°FRead
AI10S3_DSCH_TEMPSys 3 Discharge Temperature°FRead
AI11S4_DSCH_TEMPSys 4 Discharge Temperature°FRead
AI12OATAmbient Air Temperature°FRead
AI13S1_OIL_TEMPSys 1 Oil Temperature°FRead
AI14S2_OIL_TEMPSys 2 Oil Temperature°FRead
AI15S3_OIL_TEMPSys 3 Oil Temperature°FRead
AI16S4_OIL_TEMPSys 4 Oil Temperature°FRead
AI17S1_OIL_PRESSSys 1 Oil PressurePSIRead
AI18S2_OIL_PRESSSys 2 Oil PressurePSIRead
AI19S3_OIL_PRESSSys 3 Oil PressurePSIRead
AI20S4_OIL_PRESSSys 4 Oil PressurePSIRead
AI21S1_SUCT_PRESSys 1 Suction PressurePSIRead
AI22S2_SUCT_PRESSys 2 Suction PressurePSIRead
AI23S3_SUCT_PRESSys 3 Suction PressurePSIRead
AI24S4_SUCT_PRESSys 4 Suction PressurePSIRead
AI25S1_DSCH_PRESSys 1 Discharge PressurePSIRead
AI26S2_DSCH_PRESSys 2 Discharge PressurePSIRead
AI27S3_DSCH_PRESSys 3 Discharge PressurePSIRead
AI28S4_DSCH_PRESSys 4 Discharge PressurePSIRead
AI29S1_MC_FLASys 1 Motor Current FLA%Read
AI30S2_MC_FLASys 2 Motor Current FLA%Read
AI31S3_MC_FLASys 3 Motor Current FLA%Read
AI32S4_MC_FLASys 4 Motor Current FLA%Read
AI33S1_OP_HRSSys 1 Operating HoursRead
AI34S2_OP_HRSSys 2 Operating HoursRead
AI35S3_OP_HRSSys 3 Operating HoursRead
AI36S4_OP_HRSSys 4 Operating HoursRead
AI37S1_COMP_STSys 1 Compressor StartsRead
AI38S2_COMP_STSys 2 Compressor StartsRead
AI39S3_COMP_STSys 3 Compressor StartsRead
AI40S4_COMP_STSys 4 Compressor StartsRead
AI41S1_HI_MTR_TSys 1 Highest Motor Temperature°FRead
AI42S2_HI_MTR_TSys 2 Highest Motor Temperature°FRead
AI43S3_HI_MTR_TSys 3 Highest Motor Temperature°FRead
AI44S4_HI_MTR_TSys 4 Highest Motor Temperature°FRead
AImin45VSD_OUT_FRVSD Output FrequencyHzRead
AI46S1_FEEDSys 1 Flash Tank Feed Valve %%Read
AI47S2_FEEDSys 2 Flash Tank Feed Valve %%Read
AI48S3_FEEDSys 3 Flash Tank Feed Valve %%Read
AI49S4_FEEDSys 4 Flash Tank Feed Valve %%Read
AI50S1_OP_CODESys 1 Operational CodeRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss Of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 71=Password Shutdown (AGR), 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 83=ISN/BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD Pre-Charging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=ISN Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=System HPCO (Fan Special)
AI51S2_OP_CODESys 2 Operational CodeRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss Of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 71=Password Shutdown (AGR), 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 83=ISN/BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD Pre-Charging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=ISN Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=System HPCO (Fan Special)
AI52S3_OP_CODESys 3 Operational CodeRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss Of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 71=Password Shutdown (AGR), 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 83=ISN/BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD Pre-Charging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=ISN Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=System HPCO (Fan Special)
AI53S4_OP_CODESys 4 Operational CodeRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss Of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 71=Password Shutdown (AGR), 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 83=ISN/BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD Pre-Charging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=ISN Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=System HPCO (Fan Special)
AI54S1_FTL_CODESys 1 Fault CodeRead0=No Fault Code, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage (Unit), 9=Pre-charge DC Bus Voltage Imbalance (Unit), 10=High DC Bus Voltage (Unit), 11=Low DC Bus Voltage (Unit), 12=DC Bus Voltage Imbalance (Unit), 13=High VSD Ambient Temperature, 14=Single Phase Input (Unit), 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 32=High Oil Temperature, 33=Low Suction Superheat, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage (System 1/3, 2/4), 38=Pre-charge DC Bus Voltage Imbalance (System 1/3, 2/4), 39=High DC Bus Voltage (System 1/3, 2/4), 40=Low DC Bus Voltage (System 1/3, 2/4), 41=DC Bus Voltage Imbalance (System 1/3, 2/4), 42=High Motor Current, 43=Motor Current Overload (Software), 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input (System 1/3, 2/4), 47=VSD Run Signal Fault, 48=High Discharge Pressure (Hardware - HPCO), 49=High Flash Tank Level, 50=Control Voltage Fault, 51=Low Discharge Superheat
AI55S2_FLT_CODESys 2 Fault CodeRead0=No Fault Code, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage (Unit), 9=Pre-charge DC Bus Voltage Imbalance (Unit), 10=High DC Bus Voltage (Unit), 11=Low DC Bus Voltage (Unit), 12=DC Bus Voltage Imbalance (Unit), 13=High VSD Ambient Temperature, 14=Single Phase Input (Unit), 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 32=High Oil Temperature, 33=Low Suction Superheat, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage (System 1/3, 2/4), 38=Pre-charge DC Bus Voltage Imbalance (System 1/3, 2/4), 39=High DC Bus Voltage (System 1/3, 2/4), 40=Low DC Bus Voltage (System 1/3, 2/4), 41=DC Bus Voltage Imbalance (System 1/3, 2/4), 42=High Motor Current, 43=Motor Current Overload (Software), 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input (System 1/3, 2/4), 47=VSD Run Signal Fault, 48=High Discharge Pressure (Hardware - HPCO), 49=High Flash Tank Level, 50=Control Voltage Fault, 51=Low Discharge Superheat
AI56S3_FTL_CODESys 3 Fault CodeRead0=No Fault Code, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage (Unit), 9=Pre-charge DC Bus Voltage Imbalance (Unit), 10=High DC Bus Voltage (Unit), 11=Low DC Bus Voltage (Unit), 12=DC Bus Voltage Imbalance (Unit), 13=High VSD Ambient Temperature, 14=Single Phase Input (Unit), 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 32=High Oil Temperature, 33=Low Suction Superheat, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage (System 1/3, 2/4), 38=Pre-charge DC Bus Voltage Imbalance (System 1/3, 2/4), 39=High DC Bus Voltage (System 1/3, 2/4), 40=Low DC Bus Voltage (System 1/3, 2/4), 41=DC Bus Voltage Imbalance (System 1/3, 2/4), 42=High Motor Current, 43=Motor Current Overload (Software), 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input (System 1/3, 2/4), 47=VSD Run Signal Fault, 48=High Discharge Pressure (Hardware - HPCO), 49=High Flash Tank Level, 50=Control Voltage Fault, 51=Low Discharge Superheat
AI57S4_FLT_CODESys 4 Fault CodeRead0=No Fault Code, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage (Unit), 9=Pre-charge DC Bus Voltage Imbalance (Unit), 10=High DC Bus Voltage (Unit), 11=Low DC Bus Voltage (Unit), 12=DC Bus Voltage Imbalance (Unit), 13=High VSD Ambient Temperature, 14=Single Phase Input (Unit), 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 32=High Oil Temperature, 33=Low Suction Superheat, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage (System 1/3, 2/4), 38=Pre-charge DC Bus Voltage Imbalance (System 1/3, 2/4), 39=High DC Bus Voltage (System 1/3, 2/4), 40=Low DC Bus Voltage (System 1/3, 2/4), 41=DC Bus Voltage Imbalance (System 1/3, 2/4), 42=High Motor Current, 43=Motor Current Overload (Software), 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input (System 1/3, 2/4), 47=VSD Run Signal Fault, 48=High Discharge Pressure (Hardware - HPCO), 49=High Flash Tank Level, 50=Control Voltage Fault, 51=Low Discharge Superheat
AI58S1_LEVELSys 1 Flash Tank Level %%Read
AI59S2_LEVELSys 2 Flash Tank Level %%Read
AI60S3_LEVELSys 3 Flash Tank Level %%Read
AI61S4_LEVELSys 4 Flash Tank Level %%Read
AI62S1_FAN_STGSys 1 Condenser Fan StageRead
AI63S2_FAN_STGSys 2 Condenser Fan StageRead
AI64S3_FAN_STGSys 3 Condenser Fan StageRead
AI65S4_FAN_STGSys 4 Condenser Fan StageRead
AI66LEADLead refrigerant system numberRead
AI67LCHLT_SETPLeaving Chilled Liquid Setpoint°FRead
AI68LCHLT_CUTOUTLeaving Chilled Liquid Cutout°FRead
AI69S1_DRAINSys 1 Flash Tank Drain Valve %%Read
AI70S2_DRAINSys 2 Flash Tank Drain Valve %%Read
AI71S3_DRAINSys 3 Flash Tank Drain Valve %%Read
AI72S4_DRAINSys 4 Flash Tank Drain Valve %%Read
AI73SUCT_PRS_CUTSuction Pressure CutoutPSIRead
AI74VSD_DCB_V_13VSD DC Bus Voltage Sys 1/3VoltsRead
AI75VSD_DCB_V_24VSD DC Bus Voltage Sys 2/4VoltsRead
AI76REM_SETPOINTRemote Leaving Chilled Liquid Setpoint°FRead
AI77S1_SUC_SHEATSys 1 Suction Superheat°F (diff)Read
AI78S2_SUC_SHEATSys 2 Suction Superheat°F (diff)Read
AI79S3_SUC_SHEATSys 3 Suction Superheat°F (diff)Read
AI80S4_SUC_SHEATSys 4 Suction Superheat°F (diff)Read
AI81COOLING_RNGCooling Range°FRead
AI82S1_DSC_SHEATSys 1 Discharge Superheat°F (diff)Read
AI83S2_DSC_SHEATSys 2 Discharge Superheat°F (diff)Read
AI84S3_DSC_SHEATSys 3 Discharge Superheat°F (diff)Read
AI85S4_DSC_SHEATSys 4 Discharge Superheat°F (diff)Read
AImin86S1_SYS_STATESys 1 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AI87S2_SYS_STATESys 2 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AI88S3_SYS_STATESys 3 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AI89S4_SYS_STATESys 4 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AI90S1_MTR_OVERSys 1 Motor Current Overload SettingAmpsRead
AI91S2_MTR_OVERSys 2 Motor Current Overload SettingAmpsRead
AI92S3_MTR_OVERSys 3 Motor Current Overload SettingAmpsRead
AI93S4_MTR_OVERSys 4 Motor Current Overload SettingAmpsRead
BImin1S13_ALARMSys 1/3 AlarmRead0=No Alarm, 1=Alarm
BImin2S24_ALARMSys 2/4 AlarmRead0=No Alarm, 1=Alarm
BI3EVAP_HEATEREvaporator Heater StatusRead
BI4EVAP_PUMPEvaporator Pump StatusRead
BI5S1_COMP_RUNSys 1 Compressor Run StatusRead
BI6S2_COMP_RUNSys 2 Compressor Run StatusRead
BI7S3_COMP_RUNSys 3 Compressor Run StatusRead
BI8S4_COMP_RUNSys 4 Compressor Run StatusRead
BI9S1_ECON_SVSys 1 Economizer Solenoid Valve StatusRead
BI10S2_ECON_SVSys 2 Economizer Solenoid Valve StatusRead
BI11S3_ECON_SVSys 3 Economizer Solenoid Valve StatusRead
BI12S4_ECON_SVSys 4 Economizer Solenoid Valve StatusRead
BI13WATER_GLYCOLCooling TypeRead0=Water, 1=Glycol
BImin14LOCAL_REMOTELocal Remote Control ModeRead0=Local, 1=Remote
BI15DISP_UNITSDisplay UnitsRead0=Imperial, 1=SI

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)

How many BACnet points does the York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) have?

This list has 112 BACnet objects: 93 analog inputs, 3 analog values, 15 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) BACnet points are writable?

4 of the 112 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) BACnet documentation?

The source is YCAV YCIV Modbus, BACnet MS/TP, N2 Data Map (YCAV_IV Native), revision 2017-02-17, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/DsvsbvlZNgkCrndB1NvZpg/content.

What are the minimum BACnet points to integrate the York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)?

Start with BV 1 START_STOP (Remote start/stop (1 = run)); AV 1 REM_SETP (Remote leaving chilled liquid setpoint); AV 2 DMD_LIMIT (Remote current limit, % FLA); BI 14 LOCAL_REMOTE (Must read Remote (1) for BMS control); AI 86 S1_SYS_STATE (System 1 state (stopped, running, faulted)); AI 1 LCHLT (Leaving chilled liquid temperature); AI 45 VSD_OUT_FR (Compressor VSD frequency (load indication)); BI 1 S13_ALARM (Systems 1/3 alarm); BI 2 S24_ALARM (Systems 2/4 alarm).

How do I enable BMS control of the York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)?

BI 14 shows Local or Remote control mode. The sheet gives no point to change it and no write-enable point.

Does the York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

Operational code 67 is 'Loss Of External Communications'; the sheet gives no timeout or heartbeat point.

How do I check these points on the real YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.