Easy BACnet
  1. Home
  2. BACnet points lists
  3. York
  4. YVAA Style B Chiller (SC-EQ)

Air-cooled variable-speed screw chiller (via SC-EQ card) · BACnet points list

York YVAA Style B Chiller (SC-EQ) BACnet points list

Updated 28 October 2026

Short answer

YORK by Johnson Controls YVAA Style B chillers connect to a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the chiller and write the cooling setpoint, current limit and sound limit. Read-only points cover chilled liquid and ambient temperatures, per-system pressures, temperatures, % FLA, power and alarms, VSD values, and multistate operational, fault and warning codes per system.

This page lists 102 BACnet objects for the York YVAA Style B Chiller (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YVAA Style B Chiller (SC-EQ)
Equipment
Air-cooled variable-speed screw chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
102 (5 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.9.0.12
Default device instance
5000 + MAC address
Also known as
YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1
Source document
YVAA Style B SC-EQ BAS Points List · rev. Rev 1.8, 2023-03-20
Download CSV 102 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YVAA Style B Chiller (SC-EQ)

Integration in brief

Put the chiller in remote control (BV 20 reads Remote), then start/stop it with BV 1 and write the cooling setpoint (AV 1) and current limit (AV 2). Read BV 5 for chiller run, leaving chilled liquid temperature and VSD frequency, and BV 15/BV 16 for system alarms; the per-system fault codes give the cause.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM START STOP CMDRemote start/stop (1 = run)Command
AV 1REMOTE COOLING SETPRemote leaving chilled liquid setpointCommand
AV 2REM CURRENT LIMIT SETPRemote current limit, %Command
BV 20LOCAL REMOTE CONTROL MODEMust read Remote (1) for BMS controlRead
BV 5CHILLER RUNChiller runningRead
AV 5LEAVING CHILLED LIQ TEMPLeaving chilled liquid temperatureRead
AV 27VSD OUTPUT FREQUENCYCompressor VSD frequency (load indication)Read
BV 15SYS 1 ALARMSystem 1 alarm activeRead
BV 16SYS 2 ALARMSystem 2 alarm activeRead

Enable & remote start

BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point.

Heartbeat & communication loss

The operational code list includes 'Loss of External Communications'; the sheet gives no timeout or heartbeat point.

Network setup

Watch out for

York YVAA Style B Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

102 of 102 shown
Type
AnalogBinaryMulti-state
Access
Show
York YVAA Style B Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REMOTE COOLING SETPRemote Cooling Setpoint°FCommand
AVmin2REM CURRENT LIMIT SETPRemote Current Limit Setpoint%Command
AV3REMOTE SOUND LIMITRemote Sound Limit%Command
BVmin1REM START STOP CMDRemote Start / Stop CommandCommand0=Stop, 1=Run
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CHILLED LIQ TEMPLeaving Chilled Liquid Temp°FRead
AV6ENTERING CHILLED LIQ TEMPEntering Chilled Liquid Temp°FRead
AV7VSD INT AMBIENT TEMPVSD Internal Ambient Temp°FRead
AV8SYS 1 COND TEMPSys 1 Condenser Temperature°FRead
AV9SYS 1 DISCH TEMPSys 1 Discharge Temperature°FRead
AV10OUTSIDE AMBIENT AIR TEMPOutside Ambient Air Temperature°FRead
AV11SYS 1 EDUCTOR TEMPSys 1 Eductor Temperature°FRead
AV12SYS 1 OIL PRESSSys 1 Oil PressurePSIGRead
AV13SYS 1 SUCT PRESSSys 1 Suction PressurePSIGRead
AV14SYS 1 DISCH PRESSSys 1 Discharge PressurePSIGRead
AV15SYS 1 COMP PCT FLASys 1 Compressor % Full Load Amps%Read
AV16SYS 1 HOURSSys 1 Total Run HoursHrRead
AV17SYS 1 STARTSSys 1 Total Number of StartsRead
AV20SYS 2 EDUCTOR TEMPSys 2 Eductor Temperature°FRead
AV21SYS 2 OIL PRESSSys 2 Oil PressurePSIGRead
AV22SYS 2 SUCT PRESSSys 2 Suction PressurePSIGRead
AV23SYS 2 DISCH PRESSSys 2 Discharge PressurePSIGRead
AV24SYS 2 COMP PCT FLASys 2 Compressor % Full Load Amps%Read
AV25SYS 2 HOURSSys 2 Total Run HoursHrRead
AV26SYS 2 STARTSSys 2 Total Number of StartsRead
AVmin27VSD OUTPUT FREQUENCYVSD Output FrequencyHzRead
AV28SYS 1 COND DRAIN VALVE CMDSys 1 Condenser Drain Valve Command%Read
AV29SYS 2 COND DRAIN VALVE CMDSys 2 Condenser Drain Valve Command%Read
BVmin5CHILLER RUNChiller RunRead0=Off, 1=On
BV7EVAPORATOR HEATER STATUSEvaporator Heater StatusRead0=Off, 1=On
BV8EVAPORATOR PUMP STATUSEvaporator Pump StatusRead0=Off, 1=On
BV9SYS 1 COMP RUN STATUSSys 1 Compressor Run StatusRead0=Off, 1=On
BV10SYS 2 COMP RUN STATUSSys 2 Compressor Run StatusRead0=Off, 1=On
BV11SYS 1 VI STEP SOL VALVE 1 STATUSSys 1 VI Step Solenoid Valve 1 StatusRead0=Off, 1=On
BV12SYS 2 VI STEP SOL VALVE 1 STATUSSys 2 VI Step Solenoid Valve 1 StatusRead0=Off, 1=On
BV13SYS 1 VI STEP SOL VALVE 2 STATUSSys 1 VI Step Solenoid Valve 2 StatusRead0=Off, 1=On
BV14SYS 2 VI STEP SOL VALVE 2 STATUSSys 2 VI Step Solenoid Valve 2 StatusRead0=Off, 1=On
BVmin15SYS 1 ALARMSys 1 AlarmRead0=No Alarm, 1=Alarm Active
BVmin16SYS 2 ALARMSys 2 AlarmRead0=No Alarm, 1=Alarm Active
BV17EVAP ANTI-FREEZE FLOW SWITCHEvap anti-freeze flow switch (anti-freeze pump option)Read0=Off, 1=On
BV18EVAP ANTI-FREEZE PUMP RUNEvap anti-freeze pump run (anti-freeze pump option)Read0=Off, 1=On
BV19COOLING TYPECooling TypeRead0=Water, 1=Glycol
BVmin20LOCAL REMOTE CONTROL MODELocal Remote Control ModeRead0=Local, 1=Remote
BV21DISPLAY UNITSDisplay UnitsRead0=Imperial, 1=SI
BV22READY TO STARTReady To StartRead0=Off, 1=On
MV1SYS 1 OPERATIONAL CODESys 1 Operational CodeRead64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 68=Loss of External Communications, 69=Flow Switch Shutdown, 70=VSD Cooling Shutdown, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Suction Pressure Limiting, 82=Motor Current Limiting, 83=Free Cooling, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temp Limiting, 89=VSD Internal Ambient Temp Limiting, 90=Sound Limiting, 91=BAS Sound Limiting, 92=Remote Sound Limiting, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown, 95=Input Current Limiting, 96=BAS Input Current Limiting, 97=Remote Input Current Limiting, 98=Pulldown Input Current Limiting
MV2SYS 1 FAULT CODESys 1 Fault CodeRead1=No Faults/Inhbits Present, 2=Low Ambient Temperature, 3=High Ambient Temperature, 4=Low Chilled Liquid Temperature, 5=VSD Initialization Failure, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload (Hardware), 19=CT Plug Fault, 20=High Harmonic Filter Temperature, 21=Evap Anti-Freeze Pump Fault, 22=Low Heat Exchanger Temperature, 23=Replace RTC Battery, 28=High Discharge Pressure (Software), 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Suction Pressure, 32=High Discharge Temperature, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press, 50=Low Suction Superheat, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Suction Pressure Smart Freeze, 54=Isolation Valve Failed to Close Warning, 55=Isolation Valve Failed to Open Fault, 56=High Discharge Pressure Rate, 57=Condenser Fan VSD Warning, 58=Low Economizer Superheat
MV3SYS 2 OPERATIONAL CODESys 2 Operational CodeRead64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 68=Loss of External Communications, 69=Flow Switch Shutdown, 70=VSD Cooling Shutdown, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Suction Pressure Limiting, 82=Motor Current Limiting, 83=Free Cooling, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temp Limiting, 89=VSD Internal Ambient Temp Limiting, 90=Sound Limiting, 91=BAS Sound Limiting, 92=Remote Sound Limiting, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown, 95=Input Current Limiting, 96=BAS Input Current Limiting, 97=Remote Input Current Limiting, 98=Pulldown Input Current Limiting
MV4SYS 2 FAULT CODESys 2 Fault CodeRead1=No Faults/Inhbits Present, 2=Low Ambient Temperature, 3=High Ambient Temperature, 4=Low Chilled Liquid Temperature, 5=VSD Initialization Failure, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload (Hardware), 19=CT Plug Fault, 20=High Harmonic Filter Temperature, 21=Evap Anti-Freeze Pump Fault, 22=Low Heat Exchanger Temperature, 23=Replace RTC Battery, 28=High Discharge Pressure (Software), 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Suction Pressure, 32=High Discharge Temperature, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press, 50=Low Suction Superheat, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Suction Pressure Smart Freeze, 54=Isolation Valve Failed to Close Warning, 55=Isolation Valve Failed to Open Fault, 56=High Discharge Pressure Rate, 57=Condenser Fan VSD Warning, 58=Low Economizer Superheat
AV405SYS 1 COND FAN STAGESys 1 Condenser Fan Stage (Staged Fans only)Read
AV407SYS 2 COND FAN STAGESys 2 Condenser Fan Stage (Staged Fans only)Read
AV30ACTIVE LEAVING CHILL LIQ SETPActive Leaving Chilled Liquid Setpoint°FRead
AV31LOW LEAVING CHILL LIQ CUTOUTLow Leaving Chilled Liquid Temp Cutout°FRead
AV32SYS 1 ECON VALVE CMDSys 1 Economizer Valve Command%Read
AV33SYS 2 ECON VALVE CMDSys 2 Economizer Valve Command%Read
AV34LOW SUCT PRESS CUTOUTLow Suction Pressure CutoutPSIGRead
AV35VSD DC BUS VOLTVSD DC Bus VoltageVoltsRead
AV37SYS 1 SUBCOOLING TEMP / SYS 1 EVAPORATOR LEVELSys 1 subcooling (microchannel) or evaporator level (round tube)°F (diff) / %Read
AV38COOLING RANGECooling Range°F (diff)Read
AV39SYS 1 DISCH SUPERHEATSys 1 Discharge Superheat°F (diff)Read
AV40SYS 2 COND TEMPSys 2 Condenser Temperature°FRead
AV41SYS 2 DISCH TEMPSys 2 Discharge Temperature°FRead
AV42SYS 2 SUBCOOLING TEMP / SYS 2 EVAPORATOR LEVELSys 2 subcooling (microchannel) or evaporator level (round tube)°F (diff) / %Read
AV43SYS 2 DISCH SUPERHEATSys 2 Discharge Superheat°F (diff)Read
BV25SYS 1 LOCKOUTSys 1 LockoutRead0=Off, 1=On
BV26SYS 2 LOCKOUTSys 2 LockoutRead0=Off, 1=On
BV27FLOW SWITCH STATUSFlow Switch StatusRead0=Off, 1=On
BV28LEAD SYSTEM NUMBERLead System NumberRead0=Sys 1, 1=Sys 2
AV49SYS 1 ECON TEMPSys 1 Economizer Temperature°FRead
AV50SYS 2 ECON TEMPSys 2 Economizer Temperature°FRead
AV51SYS 1 ECON PRESSSys 1 Economizer PressurePSIGRead
AV52SYS 2 ECON PRESSSys 2 Economizer PressurePSIGRead
AV53SYS 1 MOTOR TEMP 1Sys 1 Motor Temperature 1°FRead
AV54SYS 1 MOTOR TEMP 2Sys 1 Motor Temperature 2°FRead
AV55SYS 1 MOTOR TEMP 3Sys 1 Motor Temperature 3°FRead
AV56SYS 2 MOTOR TEMP 1Sys 2 Motor Temperature 1°FRead
AV57SYS 2 MOTOR TEMP 2Sys 2 Motor Temperature 2°FRead
AV58SYS 2 MOTOR TEMP 3Sys 2 Motor Temperature 3°FRead
AV59SYS 1 COND FAN SPEED CMDSys 1 Condenser Fan Speed Command (VSD Fans only)%Read
AV60SYS 2 COND FAN SPEED CMDSys 2 Condenser Fan Speed Command (VSD Fans only)%Read
AV70VSD FREQUENCY COMMANDVSD Frequency CommandHzRead
BV36SOFT SHUTDOWNSoft ShutdownRead0=Disabled, 1=Enabled
BV37REMOTE EVAPORATORRemote EvaporatorRead0=Disabled, 1=Enabled
BV38QUICK STARTQuick StartRead0=Disabled, 1=Enabled
BV44SYS 1 COND FAN VSD FLTSys 1 condenser fan VSD fault (VSD fans)Read0=Off, 1=On
BV45SYS 2 COND FAN VSD FLTSys 2 condenser fan VSD fault (VSD fans)Read0=Off, 1=On
MV13SYS 1 SYSTEM STATESys 1 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
MV14SYS 2 SYSTEM STATESys 2 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AV415SYS 1 SYSTEM STATE AVSys 1 System State AVRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AV416SYS 2 SYSTEM STATE AVSys 2 System State AVRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
MV15SYS 1 WARNING CODESys 1 Warning CodeRead1=No Faults/Inhbits Present, 2=Quarterly Service Required – Contact JCI, 3=Yearly Service Required – Contact JCI, 4=3 Year Service Required – Contact JCI, 5=5 Year Service Required – Contact JCI, 6=Replace Oil filter
MV16SYS 2 WARNING CODESys 2 Warning CodeRead1=No Faults/Inhbits Present, 2=Quarterly Service Required – Contact JCI, 3=Yearly Service Required – Contact JCI, 4=3 Year Service Required – Contact JCI, 5=5 Year Service Required – Contact JCI, 6=Replace Oil filter
AV417SYS 1 WARNING CODE AVSys 1 Warning Code AVRead0=No Faults/Inhbits Present, 1=Quarterly Service Required – Contact JCI, 2=Yearly Service Required – Contact JCI, 3=3 Year Service Required – Contact JCI, 4=5 Year Service Required – Contact JCI, 5=Replace Oil filter
AV418SYS 2 WARNING CODE AVSys 2 Warning Code AVRead0=No Faults/Inhbits Present, 1=Quarterly Service Required – Contact JCI, 2=Yearly Service Required – Contact JCI, 3=3 Year Service Required – Contact JCI, 4=5 Year Service Required – Contact JCI, 5=Replace Oil filter
AV74SYS 1 FAN POWERSys 1 Fan PowerkWRead
AV75SYS 1 COMPRESSOR POWERSys 1 Compressor PowerkWRead
AV76SYS 2 FAN POWERSys 2 Fan PowerkWRead
AV77SYS 2 COMPRESSOR POWERSys 2 Compressor PowerkWRead
AV501SYS 1 OPERATIONAL CODE AVSys 1 Operational Code AVRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 82=Free Cooling, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=BAS Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=Input Current Limiting, 95=BAS Input Current Limiting, 96=Remote Input Current Limiting, 97=Pulldown Input Current Limiting
AV502SYS 1 FAULT CODE AVSys 1 Fault Code AVRead0=No Faults/Inhbits Present, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 4=VSD Initialization Failure, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 19=High Harmonic Filter Temperature, 20=Evap Anti-Freeze Pump Fault, 21=Low Heat Exchanger Temperature, 22=Replace RTC Battery, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press, 49=Low Suction Superheat, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Suction Pressure Smart Freeze, 53=Isolation Valve Failed to Close Warning, 54=Isolation Valve Failed to Open Fault, 55=High Discharge Pressure Rate, 56=Condenser Fan VSD Warning, 57=Low Economizer Superheat
AV503SYS 2 OPERATIONAL CODE AVSys 2 Operational Code AVRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 82=Free Cooling, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=BAS Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=Input Current Limiting, 95=BAS Input Current Limiting, 96=Remote Input Current Limiting, 97=Pulldown Input Current Limiting
AV504SYS 2 FAULT CODE AVSys 2 Fault Code AVRead0=No Faults/Inhbits Present, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 4=VSD Initialization Failure, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 19=High Harmonic Filter Temperature, 20=Evap Anti-Freeze Pump Fault, 21=Low Heat Exchanger Temperature, 22=Replace RTC Battery, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press, 49=Low Suction Superheat, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Suction Pressure Smart Freeze, 53=Isolation Valve Failed to Close Warning, 54=Isolation Valve Failed to Open Fault, 55=High Discharge Pressure Rate, 56=Condenser Fan VSD Warning, 57=Low Economizer Superheat

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVAA Style B Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YVAA Style B Chiller (SC-EQ)

How many BACnet points does the York YVAA Style B Chiller (SC-EQ) have?

This list has 102 BACnet objects: 66 analog values, 27 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YVAA Style B Chiller (SC-EQ) BACnet points are writable?

5 of the 102 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YVAA Style B Chiller (SC-EQ) BACnet documentation?

The source is YVAA Style B SC-EQ BAS Points List, revision Rev 1.8, 2023-03-20, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/Cxf1tNmYudSglP~8DcXK7g/content.

What are the minimum BACnet points to integrate the York YVAA Style B Chiller (SC-EQ)?

Start with BV 1 REM START STOP CMD (Remote start/stop (1 = run)); AV 1 REMOTE COOLING SETP (Remote leaving chilled liquid setpoint); AV 2 REM CURRENT LIMIT SETP (Remote current limit, %); BV 20 LOCAL REMOTE CONTROL MODE (Must read Remote (1) for BMS control); BV 5 CHILLER RUN (Chiller running); AV 5 LEAVING CHILLED LIQ TEMP (Leaving chilled liquid temperature); AV 27 VSD OUTPUT FREQUENCY (Compressor VSD frequency (load indication)); BV 15 SYS 1 ALARM (System 1 alarm active); BV 16 SYS 2 ALARM (System 2 alarm active).

How do I enable BMS control of the York YVAA Style B Chiller (SC-EQ)?

BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point.

Does the York YVAA Style B Chiller (SC-EQ) need a BACnet heartbeat or have a communication timeout?

The operational code list includes 'Loss of External Communications'; the sheet gives no timeout or heartbeat point.

How do I check these points on the real YVAA Style B Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YVAA Style B SC-EQ BAS Points List · rev. Rev 1.8, 2023-03-20. Object names, instances and units are reproduced as published; descriptions are our own.