Air-cooled variable-speed screw chiller (via E-Link gateway) · BACnet points list

York YVAA / YVFA / YAGK E-Link (YorkTalk 2) BACnet points list

Updated 28 October 2026

Short answer

Before the SC-EQ card, YORK by Johnson Controls YVAA-family chillers reached a BAS through the E-Link gateway, which reads the microboard over YorkTalk 2 (4800 baud) and serves BACnet, N2, LON and Modbus objects. Objects are named by YorkTalk page (YT2_S01_P03 and so on). Section 1 holds the remote commands and core chiller data; section 2 (instances from 101) holds free cooling, Aggreko, power and option points that depend on the microboard program.

This page lists 114 BACnet objects for the York YVAA / YVFA / YAGK E-Link (YorkTalk 2) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YVAA / YVFA / YAGK E-Link (YorkTalk 2)
Equipment
Air-cooled variable-speed screw chiller (via E-Link gateway)
Equipment type
Chillers
BACnet objects
114 (5 writable)
Transport
—
Firmware
C.ACS.20.03 / Y.ACS.20.01 to Y.ACS.20.18 (chiller program)
Also known as
YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478
Source document
YVAA, YVFA, YAGK York Talk 2 (E-Link) points list, boards 031-02478 / 031-03478 · rev. 2021-04-16 (program Y.ACS.20.18)
Download CSV 114 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YVAA / YVFA / YAGK E-Link (YorkTalk 2)

Integration in brief

Put the chiller in remote control (BV 20 reads Remote), then start/stop it with BV 1 and write the remote setpoint (AV 1) and current limit (AV 2) through the E-Link. Read BV 5 for chiller run, the leaving chilled liquid temperature and VSD frequency, and BV 6 for the chiller alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1YT2_S01_P07Remote start/stop (1 = run)Write
AV 1YT2_S01_P03Remote leaving chilled liquid setpointWrite
AV 2YT2_S01_P04Remote current limit, %Write
BV 20YT2_S01_P51Must read Remote (1) for BMS controlRead
BV 5YT2_S01_P36Chiller runningRead
AV 5YT2_S01_P11Leaving chilled liquid temperatureRead
AV 27YT2_S01_P33Compressor VSD frequency (load indication)Read
BV 6YT2_S01_P37Chiller alarm (1 = alarm)Read

Enable & remote start

BV 20 shows Local or Remote control mode. The sheet gives no point to change it and no write-enable point.

Heartbeat & communication loss

Operational code 67 is 'Loss of External Communications'; the sheet gives no timeout or heartbeat point.

Network setup

Watch out for

York YVAA / YVFA / YAGK E-Link (YorkTalk 2) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

114 of 114 shown
Type
AnalogBinaryMulti-state
Access
Show
York YVAA / YVFA / YAGK E-Link (YorkTalk 2) BACnet Points List
DescriptionStates
AVmin1YT2_S01_P03Remote Setpoint°FWrite
AVmin2YT2_S01_P04Remote Current Limit Setpoint%Write
AV3YT2_S01_P05Remote Sound Limit%Write
BVmin1YT2_S01_P07Remote Start/Stop CommandWrite0=Stop, 1=Run
BV4YT2_S01_P10History buffer 1 request (0 = live data, 1 = history data)Write0=Live Data, 1=History 1 Data
AVmin5YT2_S01_P11Leaving Chilled Liquid Temp°FRead
AV6YT2_S01_P12Entering Chilled Liquid Temp°FRead
AV7YT2_S01_P13VSD Internal Ambient Temp°FRead
AV8YT2_S01_P14Sys 1 Condenser Temperature°FRead
AV9YT2_S01_P15Sys 1 Discharge Temperature°FRead
AV10YT2_S01_P16Outside Ambient Air Temperature°FRead
AV11YT2_S01_P17Sys 1 Eductor Temperature (Aggreko disabled)°FRead
AV12YT2_S01_P18Sys 1 Oil PressurePSIRead
AV13YT2_S01_P19Sys 1 Suction PressurePSIRead
AV14YT2_S01_P20Sys 1 Discharge PressurePSIRead
AV15YT2_S01_P21Sys 1 Compressor % Full Load Amps%Read
AV16YT2_S01_P22Sys 1 Total Run HoursRead
AV17YT2_S01_P23Sys 1 Total Number of StartsRead
AV18YT2_S01_P24Sys 1 Highest Motor Temp°FRead
AV19YT2_S01_P25Sys 2 Highest Motor Temp°FRead
AV20YT2_S01_P26Sys 2 Eductor Temperature (Aggreko disabled)°FRead
AV21YT2_S01_P27Sys 2 Oil PressurePSIRead
AV22YT2_S01_P28Sys 2 Suction PressurePSIRead
AV23YT2_S01_P29Sys 2 Discharge PressurePSIRead
AV24YT2_S01_P30Sys 2 Compressor % Full Load Amps%Read
AV25YT2_S01_P31Sys 2 Total Run HoursRead
AV26YT2_S01_P32Sys 2 Total Number of StartsRead
AVmin27YT2_S01_P33VSD Output FrequencyHzRead
AV28YT2_S01_P34Sys 1 Condenser Drain Valve % Open%Read
AV29YT2_S01_P35Sys 2 Condenser Drain Valve % Open%Read
BVmin5YT2_S01_P36Chiller RunRead
BVmin6YT2_S01_P37Chiller AlarmRead0=No Alarm, 1=Alarm
BV7YT2_S01_P38Evaporator Heater StatusRead
BV8YT2_S01_P39Evaporator Pump StatusRead
BV9YT2_S01_P40Sys 1 Compressor Run StatusRead
BV10YT2_S01_P41Sys 2 Compressor Run StatusRead
BV11YT2_S01_P42Sys 1 VI Step Solenoid Valve 1 StatusRead
BV12YT2_S01_P43Sys 2 VI Step Solenoid Valve 1 StatusRead
BV13YT2_S01_P44Sys 1 VI Step Solenoid Valve 2 StatusRead
BV14YT2_S01_P45Sys 2 VI Step Solenoid Valve 2 StatusRead
BV19YT2_S01_P50Cooling TypeRead0=Water, 1=Glycol
BVmin20YT2_S01_P51Local Remote Control ModeRead0=Local, 1=Remote
BV21YT2_S01_P52Display UnitsRead0=Imperial, 1=SI
MV1YT2_S01_P56Sys 1 Operational CodeRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch Off, 66=Remote Controlled Shutdown, 67=Loss of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 72=Discharge Superheat Recovery (Remote Evaporator), 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch Off, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 82=Free Cooling, 83=BAS/ISN Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD Precharging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=BAS/ISN Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=Input Current Limiting, 95=ISN Input Current Limiting, 96=Remote Input Current Limiting, 97=Pulldown Input Current Limiting
MV2YT2_S01_P57Sys 1 Fault CodeRead0=No Fault Code, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 4=VSD Initialization Failure, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Precharge Low DC Bus Voltage (Unit), 9=Precharge DC Bus Voltage Imbalance (Unit), 10=High DC Bus Voltage (Unit), 11=Low DC Bus Voltage (Unit), 12=DC Bus Voltage Imbalance (Unit), 13=High VSD Ambient Temperature, 14=Single Phase Input (Unit), 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 19=High Harmonic Filter Temperature, 20=Evap Anti-Freeze Pump Fault, 21=Low Heat Exchanger Temperature, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Precharge Low DC Bus Voltage (System, Frame E/F), 38=Precharge DC Bus Voltage Imbalance (System, Frame E/F), 39=High DC Bus Voltage (System, Frame E/F), 40=Low DC Bus Voltage (System, Frame E/F), 41=DC Bus Voltage Imbalance (System, Frame E/F), 42=High Motor Current, 43=Motor Current Overload (Software), 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input (System, Frame E/F), 47=VSD Run Signal Fault, 48=High Discharge Pressure (Hardware/HPCO), 49=Low Suction Suerheat, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Suction Pressure Smart Freeze, 53=Isolation Valve Failed to Close Warning, 54=Isolation Valve Failed to Open Fault, 55=High Discharge Pressure Rate, 56=Condenser Fan VSD Warning
MV3YT2_S01_P58Sys 2 Operational CodeRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch Off, 66=Remote Controlled Shutdown, 67=Loss of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 72=Discharge Superheat Recovery (Remote Evaporator), 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch Off, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 82=Free Cooling, 83=BAS/ISN Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD Precharging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=BAS/ISN Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=Input Current Limiting, 95=ISN Input Current Limiting, 96=Remote Input Current Limiting, 97=Pulldown Input Current Limiting
MV4YT2_S01_P59Sys 2 fault code (sheet labels it Sys 1)Read0=No Fault Code, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 4=VSD Initialization Failure, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Precharge Low DC Bus Voltage (Unit), 9=Precharge DC Bus Voltage Imbalance (Unit), 10=High DC Bus Voltage (Unit), 11=Low DC Bus Voltage (Unit), 12=DC Bus Voltage Imbalance (Unit), 13=High VSD Ambient Temperature, 14=Single Phase Input (Unit), 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 19=High Harmonic Filter Temperature, 20=Evap Anti-Freeze Pump Fault, 21=Low Heat Exchanger Temperature, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Precharge Low DC Bus Voltage (System, Frame E/F), 38=Precharge DC Bus Voltage Imbalance (System, Frame E/F), 39=High DC Bus Voltage (System, Frame E/F), 40=Low DC Bus Voltage (System, Frame E/F), 41=DC Bus Voltage Imbalance (System, Frame E/F), 42=High Motor Current, 43=Motor Current Overload (Software), 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input (System, Frame E/F), 47=VSD Run Signal Fault, 48=High Discharge Pressure (Hardware/HPCO), 49=Low Suction Suerheat, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Suction Pressure Smart Freeze, 53=Isolation Valve Failed to Close Warning, 54=Isolation Valve Failed to Open Fault, 55=High Discharge Pressure Rate, 56=Condenser Fan VSD Warning
MV5YT2_S01_P60Sys 1 Condenser Fan StageRead
MV6YT2_S01_P61Sys 1 Condenser Fan SpeedRead
MV7YT2_S01_P62Sys 2 Condenser Fan StageRead
MV8YT2_S01_P63Sys 2 Condenser Fan SpeedRead
MV9YT2_S01_P64Lead System NumberRead
AV30YT2_S01_P66Local Leaving Chilled Liquid Setpoint°FRead
AV31YT2_S01_P67Low Leaving Chilled Liquid Temp Cutout°FRead
AV32YT2_S01_P68Sys 1 Economizer Valve % Open%Read
AV33YT2_S01_P69Sys 2 Economizer Valve % Open%Read
AV34YT2_S01_P70Low Suction Pressure CutoutPSIRead
AV35YT2_S01_P71VSD DC Bus VoltageVoltsRead
AV36YT2_S01_P72Remote Leaving Chilled Liquid Setpoint°FRead
AV37YT2_S01_P73Sys 1 subcooling (microchannel) or condenser level (round tube)°F (diff) / %Read
AV38YT2_S01_P74Cooling Range°FRead
AV39YT2_S01_P75Sys 1 Discharge Superheat°F (diff)Read
AV40YT2_S01_P76Sys 2 Condenser Temperature°FRead
AV41YT2_S01_P77Sys 2 Discharge Temperature°FRead
AV42YT2_S01_P78Sys 2 subcooling (microchannel) or condenser level (round tube)°F (diff) / %Read
AV43YT2_S01_P79Sys 2 Discharge Superheat°F (diff)Read
BV25YT2_S01_P80Sys 1 LockoutRead
BV26YT2_S01_P81Sys 2 LockoutRead
BV27YT2_S01_P82Flow Switch StatusRead
BV29YT2_S01_P84SCC Auto Detect AvailableRead
AV105YT2_S02_P11Evaporator Entering Liquid Temp (Free Cooling)°FRead
AV106YT2_S02_P12Cooling coil temperature (free cooling closed loop) or unit input current°F / -Read
AV107YT2_S02_P13Heat Exchanger Leaving Temp (Free Cooling Closed Loop)°FRead
AV108YT2_S02_P14Heat Exchanger Entering Temp (Free Cooling Closed Loop)°FRead
AV109YT2_S02_P15Glycol Pump Speed (Free Cooling Closed Loop)%Read
AV110YT2_S02_P16Cooling Coil Valve (Free Cooling Closed Loop)%Read
AV111YT2_S02_P17Cooling Coil Bypass Valve (Free Cooling Closed Loop)%Read
AV112YT2_S02_P18Sys 1 Suction Temperature (Aggreko)°FRead
AV113YT2_S02_P19Sys 1 Sat Suction Temperature (Aggreko)°FRead
AV114YT2_S02_P20Sys 1 Suction Superheat (Aggreko)°F (diff)Read
AV115YT2_S02_P21Sys 1 flash tank drain valve % (Aggreko)%Read
AV116YT2_S02_P22Sys 2 Suction Temperature (Aggreko)°FRead
AV117YT2_S02_P23Sys 2 Sat Suction Temperature (Aggreko)°FRead
AV118YT2_S02_P24Sys 2 Suction Superheat (Aggreko)°F (diff)Read
AV119YT2_S02_P25Sys 2 flash tank drain valve % (Aggreko)%Read
AV127YT2_S02_P33VSD Command FrequencyHzRead
BV105YT2_S02_P36Option IndicatorRead0=Disabled, 1=Enabled
BV106YT2_S02_P37Free cooling valve (free cooling open loop)Read0=Off, 1=On
BV107YT2_S02_P38Soft ShutdownRead0=Disabled, 1=Enabled
BV108YT2_S02_P39Remote EvaporatorRead0=Disabled, 1=Enabled
BV109YT2_S02_P40Quick StartRead0=Disabled, 1=Enabled
BV111YT2_S02_P42Glycol pump run (free cooling closed loop)Read0=Off, 1=On
BV112YT2_S02_P43Glycol heater (free cooling closed loop)Read0=Off, 1=On
BV117YT2_S02_P48Frame E/FRead0=Disabled, 1=Enabled
BV118YT2_S02_P49Sound Limit OptionRead0=Disabled, 1=Enabled
BV119YT2_S02_P50SCC Auto Detect Digit 1Read
BV120YT2_S02_P51SCC Auto Detect Digit 2Read
BV121YT2_S02_P52SCC Auto Detect Digit 3Read
BV122YT2_S02_P53SCC Auto Detect Digit 4Read
BV123YT2_S02_P54SCC Auto Detect Digit 5Read
BV124YT2_S02_P55SCC Auto Detect Digit 6Read
MV101YT2_S02_P56Condenser Fan Control TypeRead1=Std. VSD, 2=Opt. VSD, 3=Std. Staged, 4=Opt. Staged
MV102YT2_S02_P57Free cooling mode (free cooling option)Read0=Mechanical, 1=Free cooling, 2=Hybrid
MV103YT2_S02_P58Free cooling control programmed (free cooling option)Read0=Disabled, 1=OL, 2=CL
MV104YT2_S02_P59Sys 1 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
MV105YT2_S02_P60Sys 2 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
MV106YT2_S02_P61Sys 1 Warning CodeRead0=No Warning Set, 1=Quarterly Service Required - Contact JCI, 2=Yearly Service Required - Contact JCI, 3=3 Year Service Required - Contact JCI, 4=5 Year Service Required - Contact JCI, 5=Replace Oil Filter
MV107YT2_S02_P62Sys 2 Warning CodeRead0=No Warning Set, 1=Quarterly Service Required - Contact JCI, 2=Yearly Service Required - Contact JCI, 3=3 Year Service Required - Contact JCI, 4=5 Year Service Required - Contact JCI, 5=Replace Oil Filter
AV131YT2_S02_P67Sys 1 Fan KwRead
AV132YT2_S02_P68Sys 1 Compressor KwRead
AV133YT2_S02_P69Sys 2 Fan KwRead
AV134YT2_S02_P70Sys 2 Compressor KwRead
AV135YT2_S02_P71DC Bus Voltage 2 (Frame E/F)VoltsRead
BV129YT2_S02_P84UnitsRead0=Imperial, 1=Metric

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVAA / YVFA / YAGK E-Link (YorkTalk 2) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YVAA / YVFA / YAGK E-Link (YorkTalk 2)

How many BACnet points does the York YVAA / YVFA / YAGK E-Link (YorkTalk 2) have?

This list has 114 BACnet objects: 63 analog values, 35 binary values, 16 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YVAA / YVFA / YAGK E-Link (YorkTalk 2) BACnet points are writable?

5 of the 114 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York YVAA / YVFA / YAGK E-Link (YorkTalk 2) BACnet documentation?

The source is YVAA, YVFA, YAGK York Talk 2 (E-Link) points list, boards 031-02478 / 031-03478, revision 2021-04-16 (program Y.ACS.20.18), published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/HryI9wyjlbuFpbuVIk9XrA/content.

What are the minimum BACnet points to integrate the York YVAA / YVFA / YAGK E-Link (YorkTalk 2)?

Start with BV 1 YT2_S01_P07 (Remote start/stop (1 = run)); AV 1 YT2_S01_P03 (Remote leaving chilled liquid setpoint); AV 2 YT2_S01_P04 (Remote current limit, %); BV 20 YT2_S01_P51 (Must read Remote (1) for BMS control); BV 5 YT2_S01_P36 (Chiller running); AV 5 YT2_S01_P11 (Leaving chilled liquid temperature); AV 27 YT2_S01_P33 (Compressor VSD frequency (load indication)); BV 6 YT2_S01_P37 (Chiller alarm (1 = alarm)).

How do I enable BMS control of the York YVAA / YVFA / YAGK E-Link (YorkTalk 2)?

BV 20 shows Local or Remote control mode. The sheet gives no point to change it and no write-enable point.

Does the York YVAA / YVFA / YAGK E-Link (YorkTalk 2) need a BACnet heartbeat or have a communication timeout?

Operational code 67 is 'Loss of External Communications'; the sheet gives no timeout or heartbeat point.

How do I check these points on the real YVAA / YVFA / YAGK E-Link (YorkTalk 2)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.