Water-cooled centrifugal chiller (via SC-EQ card) · BACnet points list

York YT Centrifugal Chiller (SC-EQ) BACnet points list

Updated 28 October 2026

Short answer

YORK by Johnson Controls YT centrifugal chillers reach a BAS through the SC-EQ communication card, which serves BACnet MS/TP (or Modbus RTU / N2) and replaced the older E-Link gateway. The SC-EQ list has four remote commands (start/stop, leaving chilled liquid setpoint, current limit, VSD fixed-speed select), temperatures, pressures, starter and VSD values, and multistate operation, safety, cycling and warning codes with matching analog copies.

This page lists 71 BACnet objects for the York YT Centrifugal Chiller (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YT Centrifugal Chiller (SC-EQ)
Equipment
Water-cooled centrifugal chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
71 (5 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.2.0.20
Default device instance
5000 + MAC address
Also known as
YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1
Source document
YT SC-EQ BAS Points List · rev. Rev 2.5, 2021-12-08
Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YT Centrifugal Chiller (SC-EQ)

Integration in brief

Start and stop it with BV 1 and write the leaving chilled liquid setpoint (AV 1) and current limit (AV 2). Read MV 1 for the operating state, BV 5 for motor run, the leaving water temperature and % FLA, and MV 2/MV 3 for safety and cycling shutdowns.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM START STOP CMDRemote start/stop (1 = start)Command
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 2REMOTE CURRENT SPRemote motor current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUSCompressor motor runningRead
MV 5UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
AV 12MOTOR CURRENT PCT FLAMotor current, % FLA (load indication)Read
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read
MV 3UNIT CYCLING FAULT CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM START STOP CMD (0 = Stop, 1 = Start) is the BAS start/stop, and AV 1-2 are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital or Modem; check it reads ISN (BAS). The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.

Network setup

Watch out for

York YT Centrifugal Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

71 of 71 shown
Type
AnalogBinaryMulti-state
Access
Show
York YT Centrifugal Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REMOTE CURRENT SPRemote Current Limit Setpoint%Command
BVmin1REM START STOP CMDRemote Start/StopCommand0=Stop, 1=Start
BV3VSD FIXED SPEED SELECTVariable Speed Drive Fixed SpeedCommand0=Auto, 1=Fixed
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CHW TEMPReturn Chilled Liquid Temperature°FRead
AV7EVAPORATOR PRESSUREEvaporator PressurePSIARead
AV8CONDENSER PRESSURECondenser PressurePSIARead
AV9OIL PRESSURE DIFERENTIALOil Pressure DifferentialPSIDRead
AV10ENTERING COND WATER TEMPReturn Condenser Liquid Temperature°FRead
AV11LEAVING COND WATER TEMPLeaving Condenser Liquid Temperature°FRead
AVmin12MOTOR CURRENT PCT FLAMotor Current Percent FLA%Read
AV13VSD PHASE A MOTOR CURRENT / SSS PHASE A MOTOR CURRENTPhase A motor current (VSD or solid-state starter)AmpsRead
AV14VSD PHASE B MOTOR CURRENT / SSS PHASE B MOTOR CURRENTPhase B motor current (VSD or solid-state starter)AmpsRead
AV15VSD PHASE C MOTOR CURRENT / SSS PHASE C MOTOR CURRENTPhase C motor current (VSD or solid-state starter)AmpsRead
AV16PHASE A_B LINE VOLTSSolid State Starter Phase A Voltage (SSS only)VoltsRead
AV17PHASE B_C LINE VOLTSSolid State Starter Phase B Voltage (SSS only)VoltsRead
AV18PHASE C_A LINE VOLTSSolid State Starter Phase C Voltage (SSS only)VoltsRead
AV19LEAVING CH LIQ TEMP ACT SPLeaving Chilled Liquid Setpoint - Selected°FRead
AV20MOTOR CURRENT ACTUAL SPMotor Current Limit Setpoint - Selected%Read
AV21EVAP SATURATION TEMPEvaporator Saturation Temp°FRead
AV22COND SATURATION TEMPCondenser Saturation Temp°FRead
AV23DISCHARGE TEMPDischarge Temperature°FRead
AV24OIL SUMP TEMPERATUREOil Sump Temperature°FRead
AV25PURGE PRESSUREPurge PressurePSIARead
AV26ACCUM OPERATING HOURSUnit Operating HoursHrRead
AV27ACCUM SYSTEM STARTSUnit System StartsRead
BVmin5COMPR MOTOR STATUSMotor Run ContactsRead0=Off, 1=On
BV6VENT LINE SOLENOIDVent Line SolenoidRead0=Off, 1=On
BV7CHW PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV8STOP SWITCH STATUSPanel Stop SwitchRead0=Start Enabled, 1=Stop
BV9CHW FLOW SWITCH STATChilled Liquid Flow SwitchRead0=Open, 1=Closed
BV17ACC VALVE SURGE MAPAdaptive Capacity Control Valid Surge Map (VSD only)Read0=False, 1=True
BV18ACC NEW SURGE POINTAdaptive Capacity Control New Surge Point (VSD only)Read0=False, 1=True
BV19VSD COOL PUMP RUN RELAYVariable Speed Drive Water Pump Relay (VSD only)Read0=Off, 1=On
BV20VSD HARMONIC FILTER INSTHarmonic Filter Installed (VSD only)Read0=False, 1=True
BV21ACC SURGE DETECTION TYPEAdaptive Capacity Control Surge Type (VSD only)Read0=Delta P/P, 1=Current
MVmin1UNIT OPERATION CODEUnit Operation CodeRead1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Chiller Unload Before Shutdown, 12=Unit Coastdown
AV401UNIT OPERATION CODE AVUnit Operation Code AVRead0=Unit Stopped - Ready To Start, 1=Unit Stopped - Local Shutdown, 2=Unit Stopped - Remote Shutdown, 3=Unit Stopped - Warning Active, 4=Unit Stopped - Cycling Shutdown, 5=Unit Stopped - Safety Shutdown, 6=Unit Start Inhibit, 7=Unit Starting, 8=Unit Running - No Abnormal Condition, 9=Unit Running - Warning Active, 10=Unit Running - Chiller Unload Before Shutdown, 11=Unit Coastdown
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Abnormal Condition, 2=Evaporator - Low Pressure, 3=Evaporator - Transducer Or Leaving Liquid Probe, 4=Evaporator - Temperature Transducer, 5=Condenser - High Pressure Contacts Open, 6=Condenser - High Pressure, 7=Condenser - Pressure Transducer Out Of Range, 8=Auxiliary Safety - Contacts Closed, 9=Discharge - Low Temperature, 10=Discharge - High Temperature, 11=Oil - High Temperature, 12=Oil - Low Differential Pressure, 13=Oil - High Differential Pressure, 22=Control Panel - Power Failure, 24=Motor Or Starter - Current Imbalance, 30=VSD - High Heatsink Temperature, 31=VSD - 105% Motor Current Overload, 32=VSD - High Phase A Inverter Heatsink Temperature, 33=VSD - High Phase B Inverter Heatsink Temperature, 34=VSD - High Phase C Inverter Heatsink Temperature, 35=VSD - High Converter Heatsink Temperature, 36=VSD - Precharge Lockout, 37=Harmonic Filter - High Heatsink Temperature, 38=Harmonic Filter - High Total Demand Distortion, 39=LCSSS - Phase Loss, 40=LCSSS - Current Imbalance, 41=LCSSS - 105% Motor Current Overload, 42=LCSSS - High Current, 43=LCSSS - Open SCR, 44=LCSSS - Shorted Phase A SCR, 45=LCSSS - Shorted Phase B SCR, 46=LCSSS - Shorted Phase C SCR, 47=LCSSS - High Phase A Temperature - Running, 48=LCSSS - High Phase B Temperature - Running, 49=LCSSS - High Phase C temperature - Running, 50=Starter - Invalid Motor Selection, 52=Evaporator - Low Pressure, 53=Evaporator - Low Pressure - Smart Freeze
AV402UNIT SAFETY FAULT CODE AVUnit Safety Fault Code AVRead0=No Abnormal Condition, 1=Evaporator - Low Pressure, 2=Evaporator - Transducer Or Leaving Liquid Probe, 3=Evaporator - Temperature Transducer, 4=Condenser - High Pressure Contacts Open, 5=Condenser - High Pressure, 6=Condenser - Pressure Transducer Out Of Range, 7=Auxiliary Safety - Contacts Closed, 8=Discharge - Low Temperature, 9=Discharge - High Temperature, 10=Oil - High Temperature, 11=Oil - Low Differential Pressure, 12=Oil - High Differential Pressure, 21=Control Panel - Power Failure, 23=Motor Or Starter - Current Imbalance, 29=VSD - High Heatsink Temperature, 30=VSD - 105% Motor Current Overload, 31=VSD - High Phase A Inverter Heatsink Temperature, 32=VSD - High Phase B Inverter Heatsink Temperature, 33=VSD - High Phase C Inverter Heatsink Temperature, 34=VSD - High Converter Heatsink Temperature, 35=VSD - Precharge Lockout, 36=Harmonic Filter - High Heatsink Temperature, 37=Harmonic Filter - High Total Demand Distortion, 38=LCSSS - Phase Loss, 39=LCSSS - Current Imbalance, 40=LCSSS - 105% Motor Current Overload, 41=LCSSS - High Current, 42=LCSSS - Open SCR, 43=LCSSS - Shorted Phase A SCR, 44=LCSSS - Shorted Phase B SCR, 45=LCSSS - Shorted Phase C SCR, 46=LCSSS - High Phase A Temperature - Running, 47=LCSSS - High Phase B Temperature - Running, 48=LCSSS - High Phase C temperature - Running, 49=Starter - Invalid Motor Selection, 51=Evaporator - Low Pressure, 52=Evaporator - Low Pressure - Smart Freeze
MVmin3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Abnormal Condition, 2=Multi-Unit Cycling - Contacts Open, 3=System Cycling - Contacts Open, 5=Oil - Low Temperature, 6=Control Panel - Power Failure, 7=Leaving Chilled Liquid - Low Temperature, 8=Leaving Chilled Liquid - Flow Switch Open, 9=Condenser - Flow Switch Open, 10=Motor Controller - Contacts Open, 11=Motor Controller - Loss Of Current, 12=Power Fault, 13=Control Panel - Schedule, 14=Starter - Low Supply Line Voltage, 15=Starter - High Supply Line Voltage, 18=VSD Initialization Failure, 19=VSD Shutdown - Requesting Fault Data, 20=VSD - High Phase A Instantaneous Current, 21=VSD - High Phase B Instantaneous Current, 22=VSD - High Phase C Instantaneous Current, 23=VSD - Phase A Gate Driver, 24=VSD - Phase B Gate Driver, 25=VSD - Phase C Gate Driver, 26=VSD - Single Phase Input Power, 27=VSD - High DC Bus Voltage, 28=VSD - Logic Board Power Supply, 29=VSD - Low DC Bus Voltage, 30=VSD - DC Bus Voltage Imbalance, 31=VSD - High Internal Ambient Temperature, 32=VSD - Invalid Current Scale Selection, 33=VSD - Low Phase A Inverter Heatsink Temperature, 34=VSD - Low Phase B Inverter Heatsink Temperature, 35=VSD - Low Phase C Inverter Heatsink Temperature, 36=VSD - Low Converter Heatsink Temperature, 37=VSD - Precharge - DC Bus Voltage Imbalance, 38=VSD - Precharge - Low DC Bus Voltage, 39=VSD - Logic Board Processor, 40=VSD - Run Signal, 41=VSD - Serial Communications, 42=VSD - Stop Contacts Open, 43=Harmonic Filter - Logic Board Or Communications, 44=Harmonic Filter - High DC Bus Voltage, 45=Harmonic Filter - High Phase A Instantaneous Current, 47=Harmonic Filter - High Phase C Instantaneous Current, 48=Harmonic Filter - Phase Locked Loop, 49=Harmonic Filter - Precharge - Low DC Bus Voltage, 50=Harmonic Filter - Low DC Bus Voltage, 51=Harmonic Filter - DC Bus Voltage Imbalance, 52=Harmonic Filter - 110% Input Current Overload, 53=Harmonic Filter - Logic Board Power Supply, 54=Harmonic Filter - Run Signal, 55=Harmonic Filter - DC Current Transformer 1, 56=Harmonic Filter - DC Current Transformer 2, 57=LCSSS Initialization Failure, 58=LCSSS Shutdown - Requesting Fault Data, 59=LCSSS - Low Phase A Heatsink Temperature, 60=LCSSS - Low Phase B Heatsink Temperature, 61=LCSSS - Low Phase C Heatsink Temperature, 62=LCSSS - Phase Locked Loop, 63=LCSSS - Power Fault, 64=LCSSS - High Supply Line Voltage, 65=LCSSS - Low Supply Line Voltage, 66=LCSSS - Invalid Model Selection, 67=LCSSS - Run Signal, 68=LCSSS - Serial Communications, 69=LCSSS - Stop Contacts Open, 71=LCSSS - Logic Board Processor, 73=LCSSS - Power Fail, 74=VSD - Serial Communications, 75=LCSSS - Serial Communications, 76=LCSSS - Phase Loss
AV403UNIT CYCLING FAULT CODE AVUnit Cycling Fault Code AVRead0=No Abnormal Condition, 1=Multi-Unit Cycling - Contacts Open, 2=System Cycling - Contacts Open, 4=Oil - Low Temperature, 5=Control Panel - Power Failure, 6=Leaving Chilled Liquid - Low Temperature, 7=Leaving Chilled Liquid - Flow Switch Open, 8=Condenser - Flow Switch Open, 9=Motor Controller - Contacts Open, 10=Motor Controller - Loss Of Current, 11=Power Fault, 12=Control Panel - Schedule, 13=Starter - Low Supply Line Voltage, 14=Starter - High Supply Line Voltage, 17=VSD Initialization Failure, 18=VSD Shutdown - Requesting Fault Data, 19=VSD - High Phase A Instantaneous Current, 20=VSD - High Phase B Instantaneous Current, 21=VSD - High Phase C Instantaneous Current, 22=VSD - Phase A Gate Driver, 23=VSD - Phase B Gate Driver, 24=VSD - Phase C Gate Driver, 25=VSD - Single Phase Input Power, 26=VSD - High DC Bus Voltage, 27=VSD - Logic Board Power Supply, 28=VSD - Low DC Bus Voltage, 29=VSD - DC Bus Voltage Imbalance, 30=VSD - High Internal Ambient Temperature, 31=VSD - Invalid Current Scale Selection, 32=VSD - Low Phase A Inverter Heatsink Temperature, 33=VSD - Low Phase B Inverter Heatsink Temperature, 34=VSD - Low Phase C Inverter Heatsink Temperature, 35=VSD - Low Converter Heatsink Temperature, 36=VSD - Precharge - DC Bus Voltage Imbalance, 37=VSD - Precharge - Low DC Bus Voltage, 38=VSD - Logic Board Processor, 39=VSD - Run Signal, 40=VSD - Serial Communications, 41=VSD - Stop Contacts Open, 42=Harmonic Filter - Logic Board Or Communications, 43=Harmonic Filter - High DC Bus Voltage, 44=Harmonic Filter - High Phase A Instantaneous Current, 46=Harmonic Filter - High Phase C Instantaneous Current, 47=Harmonic Filter - Phase Locked Loop, 48=Harmonic Filter - Precharge - Low DC Bus Voltage, 49=Harmonic Filter - Low DC Bus Voltage, 50=Harmonic Filter - DC Bus Voltage Imbalance, 51=Harmonic Filter - 110% Input Current Overload, 52=Harmonic Filter - Logic Board Power Supply, 53=Harmonic Filter - Run Signal, 54=Harmonic Filter - DC Current Transformer 1, 55=Harmonic Filter - DC Current Transformer 2, 56=LCSSS Initialization Failure, 57=LCSSS Shutdown - Requesting Fault Data, 58=LCSSS - Low Phase A Heatsink Temperature, 59=LCSSS - Low Phase B Heatsink Temperature, 60=LCSSS - Low Phase C Heatsink Temperature, 61=LCSSS - Phase Locked Loop, 62=LCSSS - Power Fault, 63=LCSSS - High Supply Line Voltage, 64=LCSSS - Low Supply Line Voltage, 65=LCSSS - Invalid Model Selection, 66=LCSSS - Run Signal, 67=LCSSS - Serial Communications, 68=LCSSS - Stop Contacts Open, 70=LCSSS - Logic Board Processor, 72=LCSSS - Power Fail, 73=VSD - Serial Communications, 74=LCSSS - Serial Communications, 75=LCSSS - Phase Loss
MV4UNIT WARNING CODEUnit Warning CodeRead1=No Abnormal Condition, 2=Real-Time Clock Failure, 3=Default Setpoints Loaded, 4=Evaporator Or Condenser Transducer Error, 5=Evaporator - Low Pressure Limit, 6=Condenser - High Pressure Limit, 11=Purge - High Pressure, 12=Purge - Float Switch Error, 13=Purge - Excess Purge, 15=Motor - High Current Limit, 16=Vanes Uncalibrated, 17=Vanes Uncalibrated - Fixed Speed Operation, 18=Harmonic Filter - Operation Inhibited, 19=Harmonic Filter - Data Loss, 20=Harmonic Filter - Input Frequency Out Of Range, 27=External I/O Board Serial Communications
AV404UNIT WARNING CODE AVUnit Warning Code AVRead0=No Abnormal Condition, 1=Real-Time Clock Failure, 2=Default Setpoints Loaded, 3=Evaporator Or Condenser Transducer Error, 4=Evaporator - Low Pressure Limit, 5=Condenser - High Pressure Limit, 10=Purge - High Pressure, 11=Purge - Float Switch Error, 12=Purge - Excess Purge, 14=Motor - High Current Limit, 15=Vanes Uncalibrated, 16=Vanes Uncalibrated - Fixed Speed Operation, 17=Harmonic Filter - Operation Inhibited, 18=Harmonic Filter - Data Loss, 19=Harmonic Filter - Input Frequency Out Of Range, 26=External I/O Board Serial Communications
MVmin5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem
AV405UNIT CONTROL SOURCE AVUnit control source (analog copy)Read0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem
AV32VSD ANTI RECYCLE TIME REMAINVariable Speed Drive Anti-Recycle Time Remaining (VSD only)MinRead
AV33ACC MAP PRV POSAdaptive Capacity Control Map PRV Position (VSD only)%Read
AV34VSD OUTPUT VOLTAGEVariable Speed Drive Output Voltage (VSD only)VoltsRead
AV35VSD INPUT KW / SSS ANTI RECYCLE TIME REMAINVSD: input power, kW. SSS/EM starter: anti-recycle time, minkW / MinRead
AV36VSD INPUT KWH / PRE ROTATION VANE POSVSD: input kWh. SSS/EM starter: pre-rotation vane position, %kWh / %Read
AV37VSD DC LINK VOLTAGEVariable Speed Drive DC Bus Voltage (VSD only)VoltsRead
AV38VSD DC LINK CURRENTVariable Speed Drive Inverter Link Current (VSD only)AmpsRead
AV39VSD SURGE COUNTAdaptive Capacity Control Surge Count (VSD only)Read
AV40VSD OUTPUT FREQUENCYVariable Speed Drive Output Frequency (VSD only)HzRead
AV41VSD MAX VOLTAGE THDHarmonic Filter Maximum Voltage Total Harmonic Distortion (VSD only)%Read
AV42VSD MAX CURRENT TDDHarmonic Filter Maximum Current Total Demand Distortion (VSD only)%Read
AV43FILTER SUPPLY KVAHarmonic Filter Total Supply KVA (VSD only)kVARead
AV110VSD INTERNAL AMBIENT TEMPVSD Internal Ambient Temp (VSD only)°FRead
AV111VSD CONVERTER HSINK TEMPVSD Converter Heatsink Temp (VSD only)°FRead
AV112VSD PRE ROTATION VANE POSVariable Speed Drive Pre Rotation Vanes Position (VSD only)%Read
AV113ACC MAP OUTPUT FREQACC Map Output Frequency (VSD only)HzRead
AV114REFRIGERANT LEVEL SPRefrigerant Level Setpoint (VSD only)%Read
AV115DROP LEG REFRIG TEMPDrop Leg Refrigerant Temperature (VSD only)°FRead
AV120INPUT KWHInput Kilowatt Hours (SSS only)kWhRead
AV121INPUT KWH LO SSS / INPUT KWH LOInput kWh low part (kWh modulo 10,000)Read
AV122INPUT KWH OFFSET SSS / INPUT KWH OFFSETInput kWh offset part (kWh divided by 10,000)Read
AV123OPERATING HOURS LOOperating hours low part (hours modulo 10,000)Read
AV124OPERATING HOURS OFFSETOperating hours offset part (hours divided by 10,000)Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YT Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YT Centrifugal Chiller (SC-EQ)

How many BACnet points does the York YT Centrifugal Chiller (SC-EQ) have?

This list has 71 BACnet objects: 53 analog values, 12 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YT Centrifugal Chiller (SC-EQ) BACnet points are writable?

5 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YT Centrifugal Chiller (SC-EQ) BACnet documentation?

The source is YT SC-EQ BAS Points List, revision Rev 2.5, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/qySCXKFcGaJK93xZ8jJBmA/content.

What are the minimum BACnet points to integrate the York YT Centrifugal Chiller (SC-EQ)?

Start with BV 1 REM START STOP CMD (Remote start/stop (1 = start)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE CURRENT SP (Remote motor current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 12 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YT Centrifugal Chiller (SC-EQ)?

BV 1 REM START STOP CMD (0 = Stop, 1 = Start) is the BAS start/stop, and AV 1-2 are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital or Modem; check it reads ISN (BAS). The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.

How do I check these points on the real YT Centrifugal Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YT SC-EQ BAS Points List · rev. Rev 2.5, 2021-12-08. Object names, instances and units are reproduced as published; descriptions are our own.