Water-cooled dual-compressor centrifugal chiller (via SC-EQ card) · BACnet points list

York YD Dual-Compressor Centrifugal Chiller (SC-EQ) BACnet points list

Updated 28 October 2026

Short answer

The YD's SC-EQ card puts the chiller on a BACnet MS/TP trunk (or Modbus RTU / N2). Most motor, vane, oil and drive points come in #1/#2 pairs, one per compressor. Besides run/stop and the setpoints, the BAS can write the compressor operation mode (staged, single, dual) and lock out one compressor.

This page lists 150 BACnet objects for the York YD Dual-Compressor Centrifugal Chiller (SC-EQ) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YD Dual-Compressor Centrifugal Chiller (SC-EQ)
Equipment
Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
150 (6 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.2.0.20
Default device instance
5000 + MAC address
Also known as
YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView
Source document
YD SC-EQ BAS Points List · rev. Rev 2.4, 2021-12-08
Download CSV 150 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: York YD Dual-Compressor Centrifugal Chiller (SC-EQ)

Integration in brief

Wire the BAS to the SC-EQ J12 RS-485 port, set the MAC address on the DIP switch and let the card detect BACnet MS/TP. Write the remote run/stop, leaving chilled liquid setpoint and current limit (optionally the compressor mode and lockout), then read both motor run states, the operation code, leaving chilled liquid temperature, % FLA and the safety fault code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM RUN STOP CMDRemote run/stop (1 = run)Command
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 2REMOTE CURRENT SPRemote motor current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUS 1Compressor 1 motor runningRead
BV 6COMPR MOTOR STATUS 2Compressor 2 motor runningRead
MV 8UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
AV 13MOTOR CURRENT FLA 1Compressor 1 motor current, % FLARead
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read

Enable & remote start

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and AV 1-4 are the remote setpoints and compressor mode/lockout. MV 8 Unit Control Source reports Local, ISN (BAS), Analog, Digital, Modem or Remote. The YD list has no per-function source points and no write-enable point, and it doesn't say how the source is chosen at the chiller panel.

Network setup

Watch out for

York YD Dual-Compressor Centrifugal Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

150 of 150 shown
Type
AnalogBinaryMulti-state
Access
Show
York YD Dual-Compressor Centrifugal Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REMOTE CURRENT SPRemote Unit Current Limit Setpoint%Command
AV3REM COMP OPERATION MODERemote Compressor Operation ModeCommand0=Staged, 1=Single, 2=Dual
AV4REM COMP LOCKOUTRemote Compressor Remote LockoutCommand0=None, 1=Comp #1, 2=Comp #2
BVmin1REM RUN STOP CMDRemote Run/StopCommand0=Stop, 1=Run
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CH LIQ TEMPEntering Chilled Liquid Temperature°FRead
AV7EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV8CONDENSER PRESSURECondenser PressurePSIGRead
AV9OIL DIFERENTL PRESSURE 1Oil Pressure Differential #1PSIDRead
AV10OIL DIFERENTL PRESSURE 2Oil Pressure Differential #2PSIDRead
AV11ENTERING COND WATER TEMPEntering Condenser Liquid Temperature°FRead
AV12LEAVING COND WATER TEMPLeaving Condenser Liquid Temperature°FRead
AVmin13MOTOR CURRENT FLA 1Motor Current Percent FLA #1%Read
AV14MOTOR CURRENT FLA 2Motor Current Percent FLA #2%Read
AV15EVAP REFRIGERANT TEMPEvaporator Refrigerant Temperature°FRead
AV16DROP LEG REFRIG TEMPDrop Leg Refrigerant Temperature (Drop Leg Temp Enabled only)°FRead
AV17LEAVING CH LIQ TEMP ACT SPLeaving Chilled Liquid Setpoint - Selected°FRead
AV18MOTOR CURRENT ACTUAL SPUnit Current Limit Setpoint - Selected%Read
AV19EVAP SATURATION TEMPEvaporator Saturation Temperature°FRead
AV20COND SATURATION TEMPCondenser Saturation Temperature°FRead
AV21DISCHARGE TEMP 1Discharge Temperature #1°FRead
AV22DISCHARGE TEMP 2Discharge Temperature #2°FRead
AV23OIL SUMP TEMPERATUREOil Sump Temperature°FRead
AV24COND REFRIGERANT LEVELCondenser Refrigerant Level%Read
AV25ACCUM OPERATING HOURSUnit Operating HoursHrRead
AV26ACCUM SYSTEM STARTSUnit System StartsRead
AV27OIL SUMP PRESSUREOil Sump Pressure PSIGPSIGRead
AV28OIL PUMP PRESSURE 1Oil Pump Pressure #1 PSIGPSIGRead
AV29OIL PUMP PRESSURE 2Oil Pump Pressure #2 PSIGPSIGRead
BVmin5COMPR MOTOR STATUS 1Motor Run #1Read0=Off, 1=On
BVmin6COMPR MOTOR STATUS 2Motor Run #2Read0=Off, 1=On
BV7CND LIQ PUMP STATCondenser Liquid PumpRead0=Off, 1=On
BV8CH LIQ PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV9START STOP SWITCH STATUSPanel Stop SwitchRead0=Off, 1=On
BV10CH LIQ FLOW SWITCH STATChilled Liquid Flow SwitchRead0=Open, 1=Closed
BV11CND FLOW SWITCH STATCondenser Liquid Flow SwitchRead0=Open, 1=Closed
BV12DISCH HI PRESS SW 1Discharge High Pressure Switch #1Read0=Open, 1=Closed
BV13DISCH HI PRESS SW 2Discharge High Pressure Switch #2Read0=Open, 1=Closed
BV14VANE MOTOR SW 1Vane Motor Switch #1Read0=Open, 1=Closed
BV15VANE MOTOR SW 2Vane Motor Switch #2Read0=Open, 1=Closed
BV16REFRIGERANT LEVEL LOWERRefrigerant Level LowerRead0=Off, 1=On
BV17REFRIGERANT LEVEL RAISERefrigerant Level RaiseRead0=Off, 1=On
BV18OIL RETURN SOLENOIDOil Return SolenoidRead0=Off, 1=On
BV19PRV OPENING 1Pre-Rotation Vane Opening #1Read0=Off, 1=On
BV20PRV OPENING 2Pre Rotation Vane Opening #2Read0=Off, 1=On
BV21PRV CLOSING 1Pre-Rotation Vane Closing #1Read0=Off, 1=On
BV22PRV CLOSING 2Pre-Rotation Vane Closing #2Read0=Off, 1=On
MVmin1UNIT OPERATION CODEUnit Operation CodeRead1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Start Inhibit, 6=Unit Stopped - Cycling Shutdown, 7=Unit Stopped - Safety Shutdown, 8=Unit Stopped - Internal Shutdown, 9=Unit Starting, 10=Unit Running - No Abnormal Condition, 11=Unit Running - Modified Run, 12=Unit Running - Warning Active, 13=Unit Coastdown, 14=Unit Running - Chiller Unload Before Shutdown, 15=Unit Starting - MVVSD Startup - Drive Not Ready
AV401UNIT OPERATION CODE AVUnit Operation Code, raw code (MV 1 shows code + 1)Read
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Safety Faults Present; other values (up to 209) are YD Safety Fault Code table SC.2 codes plus 1 (208 codes listed in the source doc)
AV402UNIT SAFETY FAULT CODE AVUnit Safety Fault Code, raw code (MV 2 shows code + 1)Read
MV3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Cycling Faults Present; other values (up to 282) are YD Cycling Fault Code table SC.3 codes plus 1 (281 codes listed in the source doc)
AV403UNIT CYCLING FAULT CODE AVUnit Cycling Fault Code, raw code (MV 3 shows code + 1)Read
MV4UNIT WARNING CODEUnit Warning CodeRead1=No Warnings Present; other values (up to 90) are YD Warning Code table SC.4 codes plus 1 (85 codes listed in the source doc)
AV404UNIT WARNING CODE AVUnit Warning Code, raw code (MV 4 shows code + 1)Read
MV5UNIT MODIFIED RUN CODEUnit Modified Run CodeRead1=No Modified Run Conditions Present, 2=Leaving Chilled Liquid Control, 3=System Unloading Before Shutdown, 4=Lag Compressor Unloading Before Shutdown, 5=Lead Motor - Pulldown Limit, 6=Lead Motor - High Current Limit, 7=Motor #1 Start Inhibit - Anti-Recycle, 8=Motor #2 Start Inhibit - Anti-Recycle, 9=Vanes #1 Start Inhibit - Motor Switch Open, 10=Vanes #2 Start Inhibit - Motor Switch Open, 11=Lag Compressor Prelube, 12=Lag Compressor Coastdown, 13=System In Lead Compressor Pulldown, 14=Lead VSD – INPUT PULLDOWN LIMIT, 15=Lead VSD – HIGH INPUT CURRENT LIMIT
AV405UNIT MODIFIED RUN CODE AVUnit Modified Run Code, raw code (MV 5 shows code + 1)Read
MV6UNIT START INHIBIT CODEUnit Start Inhibit CodeRead1=No Start Inhibits Present, 2=Motor #1 - Anti-Recycle, 3=Motor #2 - Anti-Recycle, 4=Vanes #1 - Motor Switch Open, 5=Vanes #2 - Motor Switch Open, 6=Motor #1 - Current > 15% Fla, 7=Motor #2 - Current > 15% Fla, 8=VSD #1 - Frequency > 0 Hz, 9=VSD #2 - Frequency > 0 Hz, 10=LINE FREQUENCY NOT SET, 11=PRV #1 NOT CALIBRATED, 12=PRV #2 NOT CALIBRATED, 13=VGD #1 NOT CALIBRATED, 14=VGD #2 NOT CALIBRATED, 15=LINE VOLTAGE NOT SET, 16=MVSSS #1 – HIGH HEATSINK TEMPERATURE – STOPPED, 17=MVSSS #2 – HIGH HEATSINK TEMPERATURE – STOPPED, 18=MVSSS #1 – HIGH HEATSINK 1 TEMPERATURE – STOPPED, 19=MVSSS #2 – HIGH HEATSINK 1 TEMPERATURE – STOPPED, 20=MVSSS #1 – HIGH HEATSINK 2 TEMPERATURE – STOPPED, 21=MVSSS #2 – HIGH HEATSINK 2 TEMPERATURE – STOPPED, 22=MVSSS #1 – HIGH HEATSINK 3 TEMPERATURE – STOPPED, 23=MVSSS #2 – HIGH HEATSINK 3 TEMPERATURE – STOPPED
AV406UNIT START INHIBIT CODE AVUnit Start Inhibit Code, raw code (MV 6 shows code + 1)Read
MV7UNIT INTERNAL FAULT CODEUnit Internal Fault CodeRead1=No Internal Faults Present, 2=Internal Error - No Timer Handles Available, 3=Watchdog - Software Reboot, 4=Internal Error - Cannot Create Task
AV407UNIT INTERNAL FAULT CODE AVUnit Internal Fault Code, raw code (MV 7 shows code + 1)Read
MVmin8UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
AV408UNIT CONTROL SOURCE AVUnit Control Source, same codes as MV 8Read0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
AV30PROX SENSOR ACT POS 1High Speed Thrust Bearing Proximity Position #1MilsRead
AV31PROX SENSOR ACT POS 2High Speed Thrust Bearing Proximity Position #2MilsRead
AV32REFRIGERANT LEVEL SPRefrigerant Level Setpoint%Read
AV33ANTI RECYC TIME REMAIN 1Motor Anti-Recycle Time Remaining #1SecRead
AV34ANTI RECYC TIME REMAIN 2Motor Anti-Recycle Time Remaining #2SecRead
AV35PRV POSITION 1Pre Rotation Vanes Position #1%Read
AV36PRV POSITION 2Pre Rotation Vanes Position #2%Read
AV37VGD POSITION 1VGD Position #1%Read
AV38VGD POSITION 2VGD Position #2%Read
AV39OIL LEVEL SUMPOil Level (Sump)%Read
AV40COMP OP MODECompressor Op ModeRead0=Staged, 1=Single, 2=Dual
AV41COMP REM LOCKOUT MODECompressor Remote LockoutRead0=None, 1=Comp #1, 2=Comp #2
BV25DISCH VLV OPENING 1Discharge Valve Opening #1Read0=Off, 1=On
BV26DISCH VLV OPENING 2Discharge Valve Opening #2Read0=Off, 1=On
BV27DISCH VLV CLOSING 1Discharge Valve Closing #1Read0=Off, 1=On
BV28DISCH VLV CLOSING 2Discharge Valve Closing #2Read0=Off, 1=On
AV44HOT GAS BYPASS COMMANDHot Gas Bypass Command (Hot Gas Bypass enabled only)%Read
AV105MC 1 INPUT POWERInput Power #1 (VSD only)kWRead
AV106MC 2 INPUT POWERInput Power #2 (VSD only)kWRead
AV107MC 1 INPUT KWHInput Kilowatt Hours #1 (VSD only)kWhRead
AV108MC 2 INPUT KWHInput Kilowatt Hours #2 (VSD only)kWhRead
AV109VSD 1 OUTPUT VOLTAGEVSD #1 Output Voltage (VSD only)VoltsRead
AV110VSD 2 OUTPUT VOLTAGEVSD #2 Output Voltage (VSD only)VoltsRead
AV111VSD 1 OUTPUT FREQUENCYVSD #1 Output Frequency (VSD only)HzRead
AV112VSD 2 OUTPUT FREQUENCYVSD #2 Output Frequency (VSD only)HzRead
AV113MOTOR 1 PHASE A CURRENTMotor #1 Phase A Current (VSD only)AmpsRead
AV114MOTOR 2 PHASE A CURRENTMotor #2 Phase A Current (VSD only)AmpsRead
AV115MOTOR 1 PHASE B CURRENTMotor #1 Phase B Current (VSD only)AmpsRead
AV116MOTOR 2 PHASE B CURRENTMotor #2 Phase B Current (VSD only)AmpsRead
AV117MOTOR 1 PHASE C CURRENTMotor #1 Phase C Current (VSD only)AmpsRead
AV118MOTOR 2 PHASE C CURRENTMotor #2 Phase C Current (VSD only)AmpsRead
AV119VSD 1 DC BUS VOLTAGEVSD #1 DC Bus Voltage (VSD only)VoltsRead
AV120VSD 2 DC BUS VOLTAGEVSD #2 DC Bus Voltage (VSD only)VoltsRead
AV121VSD 1 DC BUS CURRENTVSD #1 DC Bus Current (LVVSD only)AmpsRead
AV122VSD 2 DC BUS CURRENTVSD #2 DC Bus Current (LVVSD only)AmpsRead
AV123VSD 1 INTERNAL AMBIENT TEMPVSD #1 Internal Ambient Temperature (LVVSD only)°FRead
AV124VSD 2 INTERNAL AMBIENT TEMPVSD #2 Internal Ambient Temperature (LVVSD only)°FRead
AV125VSD 1 CONVERTER HSINK TEMPVSD #1 Converter Heatsink Temp (LVVSD only)°FRead
AV126VSD 2 CONVERTER HSINK TEMPVSD #2 Converter Heatsink Temp (LVVSD only)°FRead
AV127FILTER 1 SUPPLY KVAHarmonic Filter #1 Total Supply KVA (LVVSD/HF only)kVARead
AV128FILTER 2 SUPPLY KVAHarmonic Filter #2 Total Supply KVA (LVVSD/HF only)kVARead
BV105VSD 1 COOLING SYS RUNVSD #1 Cooling System Run (VSD only)Read0=Not Running, 1=Running
BV106VSD 2 COOLING SYS RUNVSD #2 Cooling System Run (VSD only)Read0=Not Running, 1=Running
BV107VSD 1 HARMONIC FILTER INSTHarmonic Filter #1 Installed (LVVSD only)Read0=False, 1=True
BV108VSD 2 HARMONIC FILTER INSTHarmonic Filter #2 Installed (LVVSD only)Read0=False, 1=True
AV130FILTER 1 MAX VOLTAGE THDHarmonic Filter #1 Max Voltage Total Harmonic Distortion (LVVSD/HF only)%Read
AV131FILTER 2 MAX VOLTAGE THDHarmonic Filter #2 Max Voltage Total Harmonic Distortion (LVVSD/HF only)%Read
AV132FILTER 1 MAX CURRENT TDDHarmonic Filter #1 Max Current Total Demand Distortion (LVVSD/HF only)%Read
AV133FILTER 2 MAX CURRENT TDDHarmonic Filter #2 Max Current Total Demand Distortion (LVVSD/HF only)%Read
AV138MC 1 INPUT KWH LOInput Kilowatt Hours Low #1Read
AV139MC 1 INPUT KWH OFFSETInput Kilowatt Hours Offset #1Read
AV140MC 2 INPUT KWH LOInput Kilowatt Hours Low #2Read
AV141MC 2 INPUT KWH OFFSETInput Kilowatt Hours Offset #2Read
AV142OPERATING HOURS LOOperating Hours LowRead
AV143OPERATING HOURS OFFSETOperating Hours OffsetRead
AV144EVAP SMALL TEMP DIFFEvaporator Small Temp Difference°F (diff)Read
AV145COND SMALL TEMP DIFFCondenser Small Temp Difference°F (diff)Read
AV146DISCHARGE SUPERHEAT 1Discharge Superheat #1°F (diff)Read
AV147DISCHARGE SUPERHEAT 2Discharge Superheat #2°F (diff)Read
AV148SUBCOOLLER EFFECTIVENESSSubcooler EffectivenessRead
AV149SUBCOOLING TEMPSubcooling Temperature (Drop Leg Temp Enabled only)°F (diff)Read
AV150DELTA P DIV PDelta P / PRead
AV151HEAD PRESSUREHead PressurePSIDRead
AV152STALL VOLTAGE 1Stall Voltage #1VoltsRead
AV153STALL VOLTAGE 2Stall Voltage #1VoltsRead
AV154MTR 1 SHAFT END VIBRMotor #1 Bearing Shaft End Vibration (motor monitoring option)Read
AV155MTR 2 SHAFT END VIBRMotor #2 Bearing Shaft End Vibration (motor monitoring option)Read
AV156MTR 1 OP SHAFT END VIBRMotor #1 Bearing Opposite Shaft End Vibration (motor monitoring option)Read
AV157MTR 2 OP SHAFT END VIBRMotor #2 Bearing Opposite Shaft End Vibration (motor monitoring option)Read
AV158MTR 1 SHAFT END TEMPMotor #1 Bearing Shaft End Temperature (motor monitoring option)°FRead
AV159MTR 2 SHAFT END TEMPMotor #2 Bearing Shaft End Temperature (motor monitoring option)°FRead
AV160MTR 1 OP SHAFT END TEMPMotor #1 Bearing Opposite Shaft End Temperature (motor monitoring option)°FRead
AV161MTR 2 OP SHAFT END TEMPMotor #2 Bearing Opposite Shaft End Temperature (motor monitoring option)°FRead
AV162MTR 1 WINDING PH A TEMPMotor #1 Winding Phase A Temperature (motor monitoring option)°FRead
AV163MTR 2 WINDING PH A TEMPMotor #2 Winding Phase A Temperature (motor monitoring option)°FRead
AV164MTR 1 WINDING PH B TEMPMotor #1 Winding Phase B Temperature (motor monitoring option)°FRead
AV165MTR 2 WINDING PH B TEMPMotor #2 Winding Phase B Temperature (motor monitoring option)°FRead
AV166MTR 1 WINDING PH C TEMPMotor #1 Winding Phase C Temperature (motor monitoring option)°FRead
AV167MTR 2 WINDING PH C TEMPMotor #2 Winding Phase C Temperature (motor monitoring option)°FRead
AV168MTR 1 WINDING PH A2 TEMPMotor #1 Winding Phase A2 Temperature (motor monitoring option)°FRead
AV169MTR 2 WINDING PH A2 TEMPMotor #2 Winding Phase A2 Temperature (motor monitoring option)°FRead
AV170MTR 1 WINDING PH B2 TEMPMotor #1 Winding Phase B2 Temperature (motor monitoring option)°FRead
AV171MTR 2 WINDING PH B2 TEMPMotor #2 Winding Phase B2 Temperature (motor monitoring option)°FRead
AV172MTR 1 WINDING PH C2 TEMPMotor #1 Winding Phase C2 Temperature (motor monitoring option)°FRead
AV173MTR 2 WINDING PH C2 TEMPMotor #2 Winding Phase C2 Temperature (motor monitoring option)°FRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YD Dual-Compressor Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YD Dual-Compressor Centrifugal Chiller (SC-EQ)

How many BACnet points does the York YD Dual-Compressor Centrifugal Chiller (SC-EQ) have?

This list has 150 BACnet objects: 114 analog values, 27 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YD Dual-Compressor Centrifugal Chiller (SC-EQ) BACnet points are writable?

6 of the 150 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YD Dual-Compressor Centrifugal Chiller (SC-EQ) BACnet documentation?

The source is YD SC-EQ BAS Points List, revision Rev 2.4, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/ryVLb5Rnf89iVUfsCgygZw/content.

What are the minimum BACnet points to integrate the York YD Dual-Compressor Centrifugal Chiller (SC-EQ)?

Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE CURRENT SP (Remote motor current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS 1 (Compressor 1 motor running); BV 6 COMPR MOTOR STATUS 2 (Compressor 2 motor running); MV 8 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 13 MOTOR CURRENT FLA 1 (Compressor 1 motor current, % FLA); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)).

How do I enable BMS control of the York YD Dual-Compressor Centrifugal Chiller (SC-EQ)?

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and AV 1-4 are the remote setpoints and compressor mode/lockout. MV 8 Unit Control Source reports Local, ISN (BAS), Analog, Digital, Modem or Remote. The YD list has no per-function source points and no write-enable point, and it doesn't say how the source is chosen at the chiller panel.

How do I check these points on the real YD Dual-Compressor Centrifugal Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YD SC-EQ BAS Points List · rev. Rev 2.4, 2021-12-08. Object names, instances and units are reproduced as published; descriptions are our own.