Absorption chiller, steam or hot water (via SC-EQ card) · BACnet points list

York YIA Absorption Chiller (SC-EQ) BACnet points list

Updated 4 November 2026

Short answer

The YIA's SC-EQ card puts the absorption chiller on a BACnet MS/TP trunk (it also speaks Modbus RTU and N2). The BAS can run/stop the chiller and write the leaving chilled water setpoint and load limit. Read-only points cover chilled and condenser water temperatures, generator and purge pressures, strong solution temperature and concentration, steam or hot water supply values, pump status and multistate operation, shutdown, warning and inhibit codes.

This page lists 43 BACnet objects for the York YIA Absorption Chiller (SC-EQ) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YIA Absorption Chiller (SC-EQ)
Equipment
Absorption chiller, steam or hot water (via SC-EQ card)
Equipment type
Chillers
BACnet objects
43 (3 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 3.4.0.12
Default device instance
5000 + MAC address
Also known as
YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1
Source document
YIA SC-EQ BAS Points List · rev. Rev 1.1, 2020-12-18
Download CSV 43 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YIA Absorption Chiller (SC-EQ)

Integration in brief

Wire the BAS to the SC-EQ RS-485 port and set the MAC address; the card detects BACnet MS/TP. Run/stop the chiller with BV 1 and write the leaving chilled water setpoint (AV 1) and load limit (AV 2). Read MV 1 for the operating state, the chilled water temperatures and MV 2/MV 3 for safety and cycling shutdowns. MV 5 shows whether the chiller is under ISN (BAS) control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM RUN STOP CMDRemote run/stop (1 = run)Command
AV 1REM LEAVING CHW TEMP SPRemote leaving chilled water setpointCommand
AV 2REM LOAD LIMIT SPRemote load limit, %Command
MV 1OPERATIONAL CODEOperating state (ready, starting, running)Read
MV 5UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CHW TEMPLeaving chilled water temperatureRead
AV 6ENTERING CHW TEMPReturn chilled water temperatureRead
MV 2SAFETY SHUTDOWN CODESafety shutdown code (1 = none)Read
MV 3CYCLING SHUTDOWN CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop; AV 1 and AV 2 are the remote setpoints. MV 5 shows the control source (Local, ISN, Analog, Digital); it should read ISN for BAS control. The points list has no write-enable point.

Network setup

Watch out for

York YIA Absorption Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

43 of 43 shown
Type
AnalogBinaryMulti-state
Access
Show
York YIA Absorption Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHW TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REM LOAD LIMIT SPRemote Load Limit Setpoint%Command
BVmin1REM RUN STOP CMDRemote Run/StopCommand0=Stop, 1=Run
AVmin5LEAVING CHW TEMPLeaving Chilled Water Temperature°FRead
AVmin6ENTERING CHW TEMPReturn Chilled Water Temperature°FRead
AV7GENERATOR PRESSUREGenerator Shell PressuremmHgRead
AV10LEAVING COND WATER TEMPLeaving Condenser Water Temperature°FRead
AV11ENTERING COND WATER TEMPReturn Condenser Water Temperature°FRead
AV12AUTO DECRYSTLZATION TEMPAutomatic Decrystallization Temperature°FRead
AV13REFRIG TEMP LEAVING CONDRefrigerant Temperature Leaving the Condenser°FRead
AV14STEAM HOT WATER SUP TEMPSteam / Hot Water Supply Temperature°FRead
AV15STEAM SUPPLY PRESSURESteam Supply Pressure (steam units only)PSIARead
AV16STEAM HT WTR ACT VLV POSSteam / Hot Water Actuator Valve Position%Read
AV18PURGE PMP SERV INTRVL SPPurge Pump Service Interval Setpoint - HoursHrRead
AV19LEAVING CHW TEMP ACT SPActive Leaving Chilled Water Setpoint°FRead
AV21REFRIGERANT TEMPRefrigerant Temperature°FRead
AV22STRONG SOLUTION TEMPStrong Solution Temperature°FRead
AV23STRONG SOLUTION CONCStrong Solution Concentation %%Read
AV26ACCUM OPERATING HOURSTotal Operating HoursHrRead
BV5REFRIG MOTOR STATUSRefrigerant Pump Motor StatusRead0=Off, 1=On
BV6COND MOTOR STATUSCondenser Water Pump StatusRead0=Off, 1=On
BV7CHW PUMP STATChilled Water Pump StatusRead0=Off, 1=On
BV10SOLU ABSORB PMP MTR STATSolution / Absorber Pump Motor StatusRead0=Off, 1=On
BV12PURGE PMP MTR STATPurge Pump Motor StatusRead0=Off, 1=On
BV14REFRIG STAB SOL VLV STATRefrigerant Stabilizer Solenoid Valve StatusRead0=Off, 1=On
BV17REFRIG LVL FLO SW STATRefrigerant Level Float Switch StatusRead0=Open, 1=Closed
MVmin1OPERATIONAL CODEOperational CodeRead1=No Unit Operation Conditions Present, 2=System Ready to Start, 3=System Starting, 4=System Running, 5=Safety Shutdown -Reset to Restart, 6=Cycling Shutdown -Autostart-, 7=System Start Inhibited, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 13=Unit Running- Modified Run, 14=Unit Running - Internal Shutdown
MVmin2SAFETY SHUTDOWN CODESafety Shutdown CodeRead1=No Safety Faults Present, 2=Solution Pump Overload -Chk Crystallization-, 3=Solution Pump Overloads Opened, 4=Refrigerant Pump Overloads Opened, 5=Generator hi-Press Digital Switch HP1 Opened, 6=Generator hi-press Analog Switch PT1 >672 mmHg, 7=Low Refrigerant Temp Digital LRT Opened, 8=Low Refrigerant Temp Analog RT8 < 33F (0.56C), 9=Gen Hi-Temp Dig Switch HT1 Opened -Man Reset-, 10=Gen Hi-Temp Analog Switch RT3 > 330F(166C), 11=Auxiliary TB1-31 Device Opened, 12=Manual Restart After Power is Restored, 13=Chilled Liquid Flow Switch Opened, 14=High Steam Supply Temp RT7 > Maximum Allowed, 15=High Hot Water Supply Temp RT7 > Maximum Allowed, 16=Low Motor Coolant Level -MCFL Switch Opened-, 17=Refrigerant Pump Level Switch 3F Failure, 18=Solution Pump Overload Twice -Chk for Cryst-, 19=Ref Pump Overload Twice -Chk for Cryst-, 20=Soln Low Temp & Evap Flow SW Open -Chk Cryst-, 21=Soln Low Temp & Low Ref Temp Shdwn -Chk Cryst-, 22=High Steam Supply Press PT2 > 35PSIA (241.3KPA), 23=RT3 Low Temp While MCFL Shutdown -Chk Cryst-, 24=RT3 Low Temp After Power Failure -Chk Cryst-, 25=Condenser Liquid Flow Switch Opened, 26=High Concentration in Strong Solution, 27=MCFL Switch Opened, LDC Interrumped -Chk Cryst-, 28=Cond Flow Switch Closed During Limited Dilution, 29=Dilution Cycle Interrupted -Switch 3F Opened-, 30=Dilution Cycle Interrupted -Chilled Water Off-, 31=Dilution Cycle Interrupted -Cond Water Off-, 32=Solution Pump Overload Contacts are in Conflict, 33=Refrigerant pump Overload Contacts are in Conflict, 34=Start Prohibited at this Moment
MVmin3CYCLING SHUTDOWN CODECycling Shutdown CodeRead1=No Cycling Faults Present, 2=Power Failure Ocurred, 3=Low Leaving Chilled Liquid Temperature, 4=Unit Shutdown by Remote Device, 5=Unit Shutdown by Multi-Unit Remote, 6=Daily Schedule Programmed Stop, 7=Emergency Power Source Activated
MV4WARNING MESSAGE CODEWarning Message CodeRead1=No Warnings Present, 2=Low ref temp in evap RT8<34.0F(1.1C) –sol pump is off-, 3=Low refrigerant temperature in evap RT8<35.5F(1.9C), 4=Generator High Pressure >517 mmHg -Load set to 30%-, 5=Purge Pump Overloads Opened, 6=Faulty Strong Solution Temp Sensor RT3, 7=High Steam Supply Press PT2>32PSIA (22O.6KPA), 8=High Hot Water Supply Temp RT7 > Warning Temp, 9=High Steam Supply Temp RT7 > Warning Temp, 10=Purge Pump Service Recommended, 11=Autopurge Failure -Purge Tank Press Doesn't Decrease-, 12=Excess Purging in the Last 7 Days -See Setpoint-, 13=Purge Tank Pressure is >100mmHg, 14=Purge Pump Overload Contacts are in Conflict, 15=Purge Transducer PT4 out of Range, 16=8SOL Failure; PT3>100mmHg -Manually Close VP2 & VP4-, 17=Purge Pump Failure -Manually Close VP2 & VP4-, 18=Autopurge Failure; PT3>15mmHg -Check Purge Pump-, 19=Refrigerant Level Switch Conflict -CHK 1F&3F-, 20=Refrigerant from Condenser RT9 or Shell Press PT1 Conflict
MVmin5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN, 2=Analog, 3=Digital
MV6UNIT CONTROL STATUS CODEUnit Control Status CodeRead1=No Modified Run Conditions Present, 2=Cooling Start Sequence Initiated, 3=Unit Load has Reached the Remote Load Limit Setpoint, 4=Leaving Chilled Liquid Temperature Control in Effect, 5=Unit Load is Controlled by Pulldown Demand Limit, 6=Unit Load is Controlled by Rampdown Limit, 7=Unit Load has Reached the Maximum Load Limit Setpoint, 8=Manual Operation Control in Effect, 9=Dilution Cycle is in Progress, 10=Limited Dilution Cycle is in Progress, 11=Unit Load is set to 30%, 12=Unit Load is set to 60%, 13=Manual Dilution Cycle is in Progress, 14=Unit Load is Inhibited by Low Refrigerant Temp. Condition, 15=ADC in Progress -Load set to 50%-, 16=Primary Limited ADC in Progress - Load set to 50%-, 17=Secondary Limited ADC in Progress, 18=Unit in Standby Until Power Supply Recovers, 19=Unit is Unable to Perform a Limited Dilution Cycle, 20=Primary Limited ADC in Progress - Load set to 50%-
MV7UNIT INHIBIT FAULT CODEUnit Inhibit Fault CodeRead1=No Inhibit Faults Present, 2=Generator hi-press Analog Switch PT1 >672 mmHg, 3=Low Refrigerant Temp Analog RT8 < 33F (0.56C), 4=Auxiliary TB1-31 Device Opened, 5=Leaving Chilled Liquid Temp < Setpoint, 6=Unit Shutdown by Remote Device, 7=HW Valve Loaded>10% Close to <9% to Restart, 8=Steam Valve Loaded >10% Close to <9% to Restart, 9=Unit Shutdown by Multi-Unit Remote
MV8UNIT INTERNAL FAULT CODEUnit Internal Fault CodeRead1=No Internal Faults Present, 2=Watchdog - Software Reboot, 3=Internal User Interface Error, 4=User Interface unable to establish comms with control
AV30ACTIVE MAX LOAD LIMIT SPActive Maximum Load Limit Setpoint%Read
AV32WEEKLY PURGE COUNTERWeekly Purge CounterRead
AV33PULLDOWN INTERVAL TIMERPulldown Interval Timer - MinutesMinRead
AV35PULLDOWN DEMAND SP STARTPulldown Demand Setpoint - Start Load Limit%Read
AV36PULLDOWN DEMAND SP STOPPulldown Demand Setpoint - Stop Load Limit%Read
AV37PURGE TANK PRESSUREPurge Tank PressuremmHgRead
AV38PURGE PUMP PRESSUREPurge Pump PressuremmHgRead
AV39STRONG SOLUTION LVG HEAT EXCHStrong Solution Leaving Heat Exchanger°FRead
BV26REFRIG LVL SOLRefrigerant Level SolenoidRead0=Open, 1=Closed
Object ID lookup: York YIA point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YIA Absorption Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YIA Absorption Chiller (SC-EQ)

How many BACnet points does the York YIA Absorption Chiller (SC-EQ) have?

This list has 43 BACnet objects: 26 analog values, 9 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YIA Absorption Chiller (SC-EQ) BACnet points are writable?

3 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YIA Absorption Chiller (SC-EQ) BACnet documentation?

The source is YIA SC-EQ BAS Points List, revision Rev 1.1, 2020-12-18, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/MgPyIEusbCBvjQ2NPPH0uw/content.

What are the minimum BACnet points to integrate the York YIA Absorption Chiller (SC-EQ)?

Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHW TEMP SP (Remote leaving chilled water setpoint); AV 2 REM LOAD LIMIT SP (Remote load limit, %); MV 1 OPERATIONAL CODE (Operating state (ready, starting, running)); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CHW TEMP (Leaving chilled water temperature); AV 6 ENTERING CHW TEMP (Return chilled water temperature); MV 2 SAFETY SHUTDOWN CODE (Safety shutdown code (1 = none)); MV 3 CYCLING SHUTDOWN CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YIA Absorption Chiller (SC-EQ)?

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop; AV 1 and AV 2 are the remote setpoints. MV 5 shows the control source (Local, ISN, Analog, Digital); it should read ISN for BAS control. The points list has no write-enable point.

How do I check these points on the real YIA Absorption Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YIA SC-EQ BAS Points List · rev. Rev 1.1, 2020-12-18. Object names, instances and units are reproduced as published; descriptions are our own.