Water-cooled screw chiller / heat pump (via SC-EQ card) · BACnet points list

York YS / YS HP / YN Screw Chiller (SC-EQ) BACnet points list

Updated 4 November 2026

Short answer

YS, YS HP and YN screw chillers reach a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can run/stop the unit and write the leaving chilled liquid setpoint, motor current limit, leaving hot water setpoint and operating mode. Read-only points cover water temperatures, refrigerant and oil pressures, slide valve position, solid-state starter values, and multistate operation, safety, cycling and warning codes.

This page lists 51 BACnet objects for the York YS / YS HP / YN Screw Chiller (SC-EQ) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YS / YS HP / YN Screw Chiller (SC-EQ)
Equipment
Water-cooled screw chiller / heat pump (via SC-EQ card)
Equipment type
Chillers
BACnet objects
51 (6 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.2.0.20
Default device instance
5000 + MAC address
Also known as
YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1
Source document
YS, YS HP, YN SC-EQ BAS Points List · rev. Rev 2.3, 2021-12-08
Download CSV 51 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YS / YS HP / YN Screw Chiller (SC-EQ)

Integration in brief

Wire the BAS to the SC-EQ J12 RS-485 port and set the MAC address; the card detects BACnet MS/TP. Start/stop the unit with BV 1 and write the leaving chilled liquid setpoint (AV 1) and motor current limit (AV 2); on YS HP units also the hot water setpoint (AV 3) and mode (AV 4). Read MV 1, BV 5, the leaving water temperature and % FLA, and MV 2/MV 3 for shutdowns.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM START STOP CMDRemote run/stop (1 = run)Command
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 2MOTOR CURRENT REMOTE SPRemote motor current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUSCompressor motor runningRead
MV 5UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
AV 12MOTOR CURRENT PCT FLAMotor current, % FLA (load indication)Read
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read
MV 3UNIT CYCLING FAULT CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM START STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-4 the remote setpoints and mode. MV 5 shows the control source (Local, ISN, Analog, Digital, Modem); it should read ISN for BAS control. The points list has no write-enable point.

Network setup

Watch out for

York YS / YS HP / YN Screw Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

51 of 51 shown
Type
AnalogBinaryMulti-state
Access
Show
York YS / YS HP / YN Screw Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2MOTOR CURRENT REMOTE SPMotor Current Limit Setpoint%Command
AV3HOT WATER REMOTE SPLeaving Heated Liquid SP°FCommand
AV4OPERATIONAL MODERemote operational mode (heat pump units)Command0=Cooling, 1=Heating, 2=Cooling & Heating
BVmin1REM START STOP CMDRemote Run/StopCommand0=Stop, 1=Run
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CH LIQ TEMPReturn Chilled Liquid Temperature°FRead
AV7EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV8CONDENSER PRESSURECondenser PressurePSIGRead
AV9OIL PRESSURE DIFERENTIALOil Pressure DifferentialPSIDRead
AV10ENTERING COND WATER TEMPReturn Condenser Liquid Temperature°FRead
AV11LEAVING COND WATER TEMPLeaving Condenser Liquid Temperature°FRead
AVmin12MOTOR CURRENT PCT FLAMotor Current Percent FLA%Read
AV13PHASE A MOTOR CURRENTSSS Phase A Current (SSS only)AmpsRead
AV14PHASE B MOTOR CURRENTSSS Phase B Current (SSS only)AmpsRead
AV15PHASE C MOTOR CURRENTSSS Phase C Current (SSS only)AmpsRead
AV16PHASE A_B LINE VOLTSSSS Phase A Voltage (SSS only)VoltsRead
AV17PHASE B_C LINE VOLTSSSS Phase B Voltage (SSS only)VoltsRead
AV18PHASE C_A LINE VOLTSSSS Phase C Voltage (SSS only)VoltsRead
AV19LEAVING CHW TEMP ACT SPLeaving Chilled Liquid Setpoint - Active°FRead
AV20MOTOR CURRENT ACTUAL SPMotor Current Limit Setpoint - Selected%Read
AV21EVAP SATURATION TEMPEvaporator Saturation Temperature°FRead
AV22COND SATURATION TEMPCondenser Saturation Temperature°FRead
AV23DISCHARGE TEMPDischarge Temperature°FRead
AV24OIL SUMP TEMPERATUREOil Sump Temperature°FRead
AV26ACCUM OPERATING HOURSUnit Operating HoursHrRead
AV27ACCUM SYSTEM STARTSUnit System StartsRead
BVmin5COMPR MOTOR STATUSMotor Run ContactsRead0=Off, 1=On
BV6OIL RETURN SOLENOIDOil Return SolenoidRead0=Off, 1=On
BV7CHW PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV8STOP SWITCH STATUSPanel stop switch (start enabled / stop)Read0=Off, 1=On
BV9CHW FLOW SWITCH STATChiller Liquid Flow SwitchRead0=Off, 1=On
BV11LOW SEPARATOR OIL SWITCHLow Separator Oil SwitchRead0=Off, 1=On
BV24ICE STORAGE MODEIce Storage ModeRead0=Disabled, 1=Enabled
MVmin1UNIT OPERATION CODEOperation CodeRead1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Chiller Unload Before Shutdown, 12=Unit Lockout Delay, 13=Unit Running- Modified Run, 14=Unit Stopped- Internal Shutdown
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Safety Faults Present, 2=Evaporator - Low Pressure, 3=Evaporator - Transducer Or Leaving Liquid Probe, 4=Evaporator - Transducer Or Temperature Sensor, 5=Condenser - High Pressure Contacts Open, 6=Condenser - High Pressure, 7=Condenser - Pressure Transducer Out Of Range, 8=Auxiliary Safety - Contacts Closed, 9=Discharge - Low Temperature, 10=Discharge - High Temperature, 11=Oil - High Temperature, 12=Oil - Low Differential Pressure, 13=Oil - High Differential Pressure, 14=Oil - Pump Pressure Transducer Out Of Range, 15=Oil - Sump Pressure Transducer Out Of Range, 16=Oil - High Pressure, 17=Oil - Clogged Filter, 18=Oil - Low Differential Seal Pressure, 19=Oil - Differential Pressure Calibration, 20=Oil Separator - Low Level, 21=Oil - Variable Speed Pump - Setpoint Not Achieved, 22=Control Panel - Power Failure, 23=Motor Controller Fault, 24=Motor Or Starter - Current Imbalance, 25=Thrust Bearing - Proximity Probe Clearance, 26=Thrust Bearing - Proximity Probe Uncalibrated, 27=Thrust Bearing - Proximity Probe Out Of Range, 28=High Oil Temperature, 29=Oil Temperature Probe - Out of Range, 39=LCSSS - Phase Rotation, 40=LCSSS - Motor Or Starter - Current Imbalance, 41=LCSSS - 105% Motor Current Overload, 42=LCSSS - High Instantaneous Current, 43=LCSSS - Open SCR, 44=LCSSS - Shorted Phase A SCR, 45=LCSSS - Shorted Phase B SCR, 46=LCSSS - Shorted Phase C SCR, 47=LCSSS - High Phase A Heatsink Temp - Running, 48=LCSSS - High Phase B Heatsink Temp - Running, 49=LCSSS - High Phase C Heatsink Temp- Running, 50=Starter - Invalid Motor Selection, 51=Oil Or Condenser Transducer Error, 52=Evaporator - Low Pressure, 53=Evaporator - Low Pressure - Smart Freeze, 54=Surge Protection - Excess Surge, 57=Thrust Bearing - Proximity Probe Clearance, 58=Thrust Bearing - Limit Switch Open, 59=Motor - Phase Rotation, 60=Motor - High Temperature, 61=Discharge - High Pressure, 62=High Motor Winding Temperature, 63=High Motor Bearing Temperature, 68=Condenser High Pressure Stopped, 69=Motor - Ground Fault, 70=Excessive Bearing Vibration, 71=Low Discharge Superheat, 72=LCSSS - Phase A Open SCR, 73=LCSSS - Phase B Open SCR, 74=LCSSS - Phase C Open SCR
MVmin3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Cycling Faults Present, 2=Multi-Unit Cycling - Contacts Open, 3=System Cycling - Contacts Open, 4=Oil - Low Temperature Differential, 5=Oil - Low Temperature, 6=Control Panel - Power Failure, 7=Leaving Chilled Liquid - Low Temperature, 8=Leaving Chilled Liquid - Flow Switch Open, 9=Condenser - Flow Switch Open, 10=Motor Controller - Contacts Open, 11=Motor Controller - Loss Of Current, 12=Power Fault, 13=Control Panel - Schedule, 14=Starter - Low Supply Line Voltage, 15=Starter - High Supply Line Voltage, 16=Proximity Probe - Low Supply Voltage, 17=Oil - Variable Speed Pump - Drive Contacts Open, 57=LCSSS Initialization Failed, 58=LCSSS Shutdown - Requesting Fault Data…, 59=LCSSS - Low Phase A Temperature Sensor, 60=LCSSS - Low Phase B Temperature Sensor, 61=LCSSS - Low Phase C Temperature Sensor, 62=LCSSS - Phase Locked Loop, 63=LCSSS - Power Fault, 64=LCSSS - High Supply Line Voltage, 65=LCSSS - Low Supply Line Voltage, 66=LCSSS - Invalid Current Scale Selection, 67=LCSSS - Run Signal, 68=LCSSS - Serial Communications, 69=LCSSS - Stop Contacts Open, 70=LCSSS - Invalid FLA, 71=LCSSS - Logic Board Processor, 72=LCSSS - DSP Communication Failure, 73=LCSSS - Logic Board Power Supply, 75=LCSSS - Serial Communications, 76=LCSSS - Phase Loss, 78=Motor High Winding Temperature, 82=SSS Shutdown - Requesting Fault Data…
MV4UNIT WARNING FAULT CODEUnit Warning Fault CodeRead1=No Warnings Present, 2=Real-Time Clock Failure, 3=Setpoint Override, 4=Condenser Or Evaporator Transducer Error, 5=Evaporator - Low Pressure Limit, 6=Condenser - High Pressure Limit, 7=Condenser Transducer Error, 8=Freeze Threat From Operating Chiller, 9=Refrigerant Level Out Of Range, 10=Standby Lube - Low Oil Pressure, 11=Purge - High Pressure, 12=Purge - Float Switch Error, 13=Purge - Excess Purge, 14=Oil - High Temperature, 15=Oil - Low Pressure Limit, 16=Vanes Uncalibrated, 17=Vanes Uncalibrated - Fixed Speed, 21=Oil - Dirty Filter, 22=Discharge - High Pressure Limit, 24=Low Discharge Superheat Limit, 25=Low Discharge Superheat Detected, 26=Seal Lubrication In Process, 27=External I/O - Serial Communications, 28=Slide Valve Uncalibrated, 29=Freeze Threat - Condenser Flow Switch, 30=Surge Protection - Excess Surge Limit, 31=Excess Surge Detected, 32=Purge - Canister #1 Full, 33=Oil Recovery Limit
MVmin5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN, 2=Analog, 3=Digital, 4=Modem
AV32LVNG CHW TEMP ACT SPLeaving Chilled Liquid Temperature SP Active°FRead
AV35ANTI RECYCLE TIME REMAINAnti-Recycle Time RemainingMinRead
AV37SEAL PRESS DIFFERENTIALSeal Pressure DifferentialPSIDRead
AV38FILTER DIFF PRESSUREFilter Pressure DifferentialPSIDRead
AV39LEAV COND HW TEMP ACT SPLeaving Heated Liquid Setpoint - Active°FRead
AV41MIN LOAD CTL MTR FLA LIMMinimum Load Control Motor FLA Limit%Read
AV42SLIDE VALVE POSITIONSlide Valve Position%Read
AV49INPUT POWERInput Power (SSS only)kWRead
AV50INPUT KWHInput Kilowatt Hours (SSS only)kWhRead
AV51INPUT KWH LO SSSInput kWh low part (SSS only)Read
AV52INPUT KWH OFFSET SSSInput kWh offset part (SSS only)Read
Object ID lookup: York YS / YN point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YS / YS HP / YN Screw Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YS / YS HP / YN Screw Chiller (SC-EQ)

How many BACnet points does the York YS / YS HP / YN Screw Chiller (SC-EQ) have?

This list has 51 BACnet objects: 37 analog values, 8 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YS / YS HP / YN Screw Chiller (SC-EQ) BACnet points are writable?

6 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YS / YS HP / YN Screw Chiller (SC-EQ) BACnet documentation?

The source is YS, YS HP, YN SC-EQ BAS Points List, revision Rev 2.3, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/hSI0v36JJxo5NkdS0gNL0w/content.

What are the minimum BACnet points to integrate the York YS / YS HP / YN Screw Chiller (SC-EQ)?

Start with BV 1 REM START STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 MOTOR CURRENT REMOTE SP (Remote motor current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 12 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YS / YS HP / YN Screw Chiller (SC-EQ)?

BV 1 REM START STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-4 the remote setpoints and mode. MV 5 shows the control source (Local, ISN, Analog, Digital, Modem); it should read ISN for BAS control. The points list has no write-enable point.

How do I check these points on the real YS / YS HP / YN Screw Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YS, YS HP, YN SC-EQ BAS Points List · rev. Rev 2.3, 2021-12-08. Object names, instances and units are reproduced as published; descriptions are our own.