Easy BACnet
  1. Home
  2. BACnet points lists
  3. York
  4. YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)

Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card) · BACnet points list

York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points list

Updated 4 November 2026

Short answer

The YVAM's SC-EQ card puts the chiller on a BACnet MS/TP trunk (it also speaks Modbus RTU and N2). The BAS can run/stop the chiller and write the leaving chilled liquid setpoint and input current limit. Read-only points cover chilled liquid and ambient temperatures, refrigerant pressures, compressor VSD values and harmonics, magnetic bearing (MBC) status, condenser fan VSD speeds and faults, and operation, fault, warning and inhibit codes as MV objects with AV copies.

This page lists 109 BACnet objects for the York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
Equipment
Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
109 (4 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.7.0.5
Default device instance
5000 + MAC address
Also known as
YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1
Source document
YVAM SC-EQ BAS Points List · rev. Rev 1.5, 2022-09-20
Download CSV 109 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)

Integration in brief

Wire the BAS to the SC-EQ J12 RS-485 port and set the MAC address; the card detects BACnet MS/TP. Run/stop the chiller with BV 1 and write the leaving chilled liquid setpoint (AV 1) and input current limit (AV 2). Read MV 1, BV 5, the leaving water temperature and % FLA, and MV 2/MV 3 for shutdowns. MV 5 shows whether the chiller is under ISN (BAS) control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM RUN STOP CMDRemote run/stop (1 = run)Command
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 2REMOTE INPUT CURRENT SPRemote input current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUSCompressor motor runningRead
MV 5UNIT CONTROL SOURCEControl source; ISN (BAS) for BMS controlRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
AV 24INPUT CURRENT PCT FLAInput current, % FLA (load indication)Read
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read
MV 3UNIT CYCLING FAULT CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-2 the remote setpoints. MV 5 shows the control source (Local, ISN (BAS), Analog, Digital, Modem, Remote); it should read ISN for BAS control. The points list has no write-enable point.

Network setup

Watch out for

York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

109 of 109 shown
Type
AnalogBinaryMulti-state
Access
Show
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REMOTE INPUT CURRENT SPRemote Input Current Limit Setpoint%Command
BVmin1REM RUN STOP CMDRemote Run/StopCommand0=Stop, 1=Run
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CH LIQ TEMPEntering Chilled Liquid Temperature°FRead
AV7SUCTION PRESSURESuction PressurePSIGRead
AV8DISCHARGE PRESSUREDischarge PressurePSIGRead
AV9EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV10CONDENSER PRESSURECondenser PressurePSIGRead
AV11DISCHARGE TEMPDischarge Temperature°FRead
AV12EVAP REFRIGERANT TEMPEvaporator refrigerant temperature (sensor option)°FRead
AV13VSD PHASE A OUTPUT CURRENTVSD Phase A Output Current (RMS)AmpsRead
AV14VSD PHASE B OUTPUT CURRENTVSD Phase B Output Current (RMS)AmpsRead
AV15VSD PHASE C OUTPUT CURRENTVSD Phase C Output Current (RMS)AmpsRead
AV16OUTSIDE AMBIENT AIR TEMPOutside Ambient Air Temp°FRead
AV17VSD RMS INPUT CURRENT L1VSD L1 Input Current (RMS)AmpsRead
AV18VSD RMS INPUT CURRENT L2VSD L2 Input Current (RMS)AmpsRead
AV19VSD RMS INPUT CURRENT L3VSD L3 Input Current (RMS)AmpsRead
AV20LEAVING CH LIQ TEMP ACT SPLeaving Chilled Liquid Setpoint - Selected°FRead
AV21INPUT CURRENT LMT ACTIVEActive Input Current Limit%Read
AV22EVAP SATURATION TEMPEvaporator Saturation Temperature°FRead
AV23COND SATURATION TEMPCondenser Saturation Temperature°FRead
AVmin24INPUT CURRENT PCT FLAInput % Full Load Amps%Read
AV26OPERATING HOURSOperating HoursHrRead
AV27NUMBER OF STARTSNumber Of StartsRead
AV28HOT GAS BYPASS VLV CMDHot Gas Bypass Command%Read
AV29MOTOR CURRENT PCT FLAMotor % Full Load Amps%Read
BVmin5COMPR MOTOR STATUSMotor RunRead0=Off, 1=On
BV6CH LIQ PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV7VSD COOLING SYS STATVSD Cooling SystemRead0=Off, 1=On
BV8RUN PERMISSIVERun PermissiveRead0=Off, 1=On
BV9CH LIQ FLOW SWITCH STATChilled Liquid Flow SwitchRead0=Open, 1=Closed
BV10EVAPORATOR HEATEREvaporator HeaterRead0=Off, 1=On
BV11COND DRAIN VAVLE MODECondenser Drain Valve ModeRead0=Auto, 1=Manual
BV12EVAP FREEZE PROTECTIONEvaporator Freeze ProtectionRead0=Off, 1=On
MVmin1UNIT OPERATION CODEUnit Operation CodeRead1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Soft Shutdown, 12=Unit Coastdown, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown, 16=Unit Running - Active Low Lift - No Abnormal Condition, 17=Unit Running - Active Low Lift - Warning Active, 18=Unit Running - Active Low Lift - Modified Run, 19=Unit Running - Passive Low Lift - No Abnormal Condition, 20=Unit Running - Passive Low Lift - Warning Active, 21=Unit Running - Passive Low Lift - Modified Run, 22=Unit Running - Cooling - No Abnormal Condition, 23=Unit Running - Cooling - Warning Active, 24=Unit Running - Cooling - Modified Run, 25=Unit Running - Heating - No Abnormal Condition, 26=Unit Running - Heating - Warning Active, 27=Unit Running - Heating - Modified Run, 28=Unit Running - Cooling & Heating - No Abnormal Condition, 29=Unit Running - Cooling & Heating - Warning Active, 30=Unit Running - Cooling & Heating - Modified Run
AV401UNIT OPERATION CODE AVUnit Operation Code AVRead0=Unit Stopped - Ready To Start, 1=Unit Stopped - Local Shutdown, 2=Unit Stopped - Remote Shutdown, 3=Unit Stopped - Warning Active, 4=Unit Stopped - Cycling Shutdown, 5=Unit Stopped - Safety Shutdown, 6=Unit Start Inhibit, 7=Unit Starting, 8=Unit Running - No Abnormal Condition, 9=Unit Running - Warning Active, 10=Unit Running - Soft Shutdown, 11=Unit Coastdown, 12=Unit Running - Modified Run, 13=Unit Stopped - Internal Shutdown, 15=Unit Running - Active Low Lift - No Abnormal Condition, 16=Unit Running - Active Low Lift - Warning Active, 17=Unit Running - Active Low Lift - Modified Run, 18=Unit Running - Passive Low Lift - No Abnormal Condition, 19=Unit Running - Passive Low Lift - Warning Active, 20=Unit Running - Passive Low Lift - Modified Run, 21=Unit Running - Cooling - No Abnormal Condition, 22=Unit Running - Cooling - Warning Active, 23=Unit Running - Cooling - Modified Run, 24=Unit Running - Heating - No Abnormal Condition, 25=Unit Running - Heating - Warning Active, 26=Unit Running - Heating - Modified Run, 27=Unit Running - Cooling & Heating - No Abnormal Condition, 28=Unit Running - Cooling & Heating - Warning Active, 29=Unit Running - Cooling & Heating - Modified Run
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Safety Faults Present, 2=EVAPORATOR - LOW PRESSURE, 7=CONDENSER - PRESSURE TRANSDUCER OUT OF RANGE, 8=AUXILIARY SAFETY - CONTACTS CLOSED, 9=DISCHARGE - LOW TEMPERATURE, 10=DISCHARGE - HIGH TEMPERATURE, 11=DISCHARGE - HIGH PRESSURE SWITCH OPEN, 12=DISCHARGE - HIGH PRESSURE, 14=CONDENSER - FAN VSD FAULT 1 & 2, 21=SALES ORDER - INVALID SYSTEM MODEL, 22=CONTROL PANEL - POWER FAILURE, 23=CONTROL PANEL - LOSS OF CONTROL VOLTAGE, 24=UPS - BATTERY NOT CONNECTED, 25=UPS - INVERTER LOW BATTERY VOLTAGE, 31=VSD - 105% MOTOR CURRENT OVERLOAD, 36=VSD - PRECHARGE LOCKOUT, 37=VSD - HIGH MOTOR HARMONICS, 38=VSD - CAPACITOR FAULT, 39=VSD - ELECTRICAL SIGNATURE BOARD, 52=EVAPORATOR - LOW PRESSURE, 53=EVAPORATOR - LOW PRESSURE - SMART FREEZE, 54=SURGE PROTECTION - EXCESS SURGE, 55=SYSTEM - STARTUP FAILURE, 61=MOTOR - LOW WINDING TEMPERATURE, 62=MOTOR - HIGH WINDING TEMPERATURE, 63=MOTOR - HIGH ROTOR TEMPERATURE, 67=VSD - MOTOR CURRENT IMBALANCE, 69=MBC - DSP UNAUTHORIZED ROTATION, 70=MBC - SPV UNAUTHORIZED ROTATION, 71=MBC - AMP COMMUNICATION, 72=MBC - AMP WATCHDOG, 74=MBC - LOW RADIAL OSCILLATOR VOLTAGE, 76=MBC - LOW AXIAL OSCILLATOR VOLTAGE, 77=MBC - ROTOR CONTRACTION, 78=MBC - HIGH INPUT VOLTAGE, 80=MBC - INTERNAL FAULT, 81=VGD ACTUATOR FAULT, 82=VGD POSITIONING FAULT, 83=MBC - POWER FAIL LANDING, 84=MBC - HIGH ROTOR ELONGATION RATE, 95=VSD - HIGH HX APPROACH TEMPERATURE, 96=VSD - LOGIC BOARD PLUG, 97=VSD - INPUT CURRENT OVERLOAD, 98=VSD - HIGH PHASE A INPUT BASEPLATE TEMPERATURE, 99=VSD - HIGH PHASE B INPUT BASEPLATE TEMPERATURE, 100=VSD - HIGH PHASE C INPUT BASEPLATE TEMPERATURE, 101=VSD - HIGH PHASE A MOTOR BASEPLATE TEMPERATURE, 102=VSD - HIGH PHASE B MOTOR BASEPLATE TEMPERATURE, 103=VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATURE, 104=VSD - DC BUS PRE-REGULATION LOCKOUT, 105=VSD - GROUND FAULT, 106=VSD - PHASE A MOTOR DCCT, 107=VSD - PHASE B MOTOR DCCT, 108=VSD - PHASE C MOTOR DCCT, 109=VSD - PHASE A INPUT DCCT, 110=VSD - PHASE B INPUT DCCT, 111=VSD - PHASE C INPUT DCCT, 112=VSD - HIGH TOTAL DEMAND DISTORTION, 113=VSD - HIGH INTERNAL AMBIENT TEMPERATURE, 114=VSD - DC BUS LOCKOUT - DO NOT CYCLE POWER, 115=VSD - INPUT DCCT OFFSET LOCKOUT, 117=VSD - HIGH PHASE A INPUT CURRENT, 118=VSD - HIGH PHASE B INPUT CURRENT, 119=VSD - HIGH PHASE C INPUT CURRENT, 120=VSD - HIGH PHASE A MOTOR CURRENT, 121=VSD - HIGH PHASE B MOTOR CURRENT, 122=VSD - HIGH PHASE C MOTOR CURRENT, 123=VSD - MOTOR CURRENT THD FAULT, 124=VSD - HIGH INPUT CURRENT TDD, 125=VSD - RECTIFIER PROGRAM FAULT, 126=VSD - INVERTER PROGRAM FAULT, 127=MBC - DSP INITIALIZATION, 128=MBC - HIGH AMPLIFIER TEMPERATURE, 129=MBC - HIGH DC/DC TEMPERATURE, 130=MBC - DSP COMMUNICATION, 131=MBC - DSP INTEGRITY, 132=MBC - FLASH MEMORY CLEAR, 133=MBC - FLASH MEMORY WRITE, 134=MBC - EEPROM, 135=MBC - FLASH MEMORY FULL, 136=MBC - INTERNAL FAULT 11, 137=MBC - INTERNAL FAULT 12, 138=MBC - INTERNAL FAULT 13, 139=MBC - INTERNAL FAULT 14, 140=MBC - DSP WATCHDOG, 141=MBC - DATA ACQUISITION FAULT, 142=MBC - HIGH BEARING Z1 TEMPERATURE, 143=MBC - HIGH BEARING Z2 TEMPERATURE, 144=MBC - CABLE FAULT, 145=MBC - SPEED SIGNAL FAULT, 146=MBC - OVERSPEED FAULT, 147=MBC - ROTOR ELONGATION, 148=MBC - HIGH BEARING CURRENT, 149=MBC - OSCILLATOR FAULT, 150=MBC - POWER SUPPLY FAULT, 151=MBC - UNAUTHORIZED ROTATION, 152=MBC - FAULT CODE X, 153=MBC - NO LEVITATION, 155=MBC - EXCESSIVE SHUTDOWNS, 156=SAFETY STOP, 157=MBC - INITIALIZATION FAILED, 158=MBC - CUSTOMER SERIAL LINK DISABLED, 159=MOTOR - HIGH HOUSING TEMPERATURE, 160=SALES ORDER - INVALID COMPRESSOR MODEL, 161=VSD - LINE VOLTAGE PHASE ROTATION, 162=VSD - PHASE LOCKED LOOP, 163=VSD - LOGIC BOARD HARDWARE, 164=ISOLATION VALVES - NOT OPENED
AV402UNIT SAFETY FAULT CODE AVUnit Safety Fault Code AVRead0=No Safety Faults Present, 1=EVAPORATOR - LOW PRESSURE, 6=CONDENSER - PRESSURE TRANSDUCER OUT OF RANGE, 7=AUXILIARY SAFETY - CONTACTS CLOSED, 8=DISCHARGE - LOW TEMPERATURE, 9=DISCHARGE - HIGH TEMPERATURE, 10=DISCHARGE - HIGH PRESSURE SWITCH OPEN, 11=DISCHARGE - HIGH PRESSURE, 13=CONDENSER - FAN VSD FAULT 1 & 2, 20=SALES ORDER - INVALID SYSTEM MODEL, 21=CONTROL PANEL - POWER FAILURE, 22=CONTROL PANEL - LOSS OF CONTROL VOLTAGE, 23=UPS - BATTERY NOT CONNECTED, 24=UPS - INVERTER LOW BATTERY VOLTAGE, 30=VSD - 105% MOTOR CURRENT OVERLOAD, 35=VSD - PRECHARGE LOCKOUT, 36=VSD - HIGH MOTOR HARMONICS, 37=VSD - CAPACITOR FAULT, 38=VSD - ELECTRICAL SIGNATURE BOARD, 51=EVAPORATOR - LOW PRESSURE, 52=EVAPORATOR - LOW PRESSURE - SMART FREEZE, 53=SURGE PROTECTION - EXCESS SURGE, 54=SYSTEM - STARTUP FAILURE, 60=MOTOR - LOW WINDING TEMPERATURE, 61=MOTOR - HIGH WINDING TEMPERATURE, 62=MOTOR - HIGH ROTOR TEMPERATURE, 66=VSD - MOTOR CURRENT IMBALANCE, 68=MBC - DSP UNAUTHORIZED ROTATION, 69=MBC - SPV UNAUTHORIZED ROTATION, 70=MBC - AMP COMMUNICATION, 71=MBC - AMP WATCHDOG, 73=MBC - LOW RADIAL OSCILLATOR VOLTAGE, 75=MBC - LOW AXIAL OSCILLATOR VOLTAGE, 76=MBC - ROTOR CONTRACTION, 77=MBC - HIGH INPUT VOLTAGE, 79=MBC - INTERNAL FAULT, 80=VGD ACTUATOR FAULT, 81=VGD POSITIONING FAULT, 82=MBC - POWER FAIL LANDING, 83=MBC - HIGH ROTOR ELONGATION RATE, 94=VSD - HIGH HX APPROACH TEMPERATURE, 95=VSD - LOGIC BOARD PLUG, 96=VSD - INPUT CURRENT OVERLOAD, 97=VSD - HIGH PHASE A INPUT BASEPLATE TEMPERATURE, 98=VSD - HIGH PHASE B INPUT BASEPLATE TEMPERATURE, 99=VSD - HIGH PHASE C INPUT BASEPLATE TEMPERATURE, 100=VSD - HIGH PHASE A MOTOR BASEPLATE TEMPERATURE, 101=VSD - HIGH PHASE B MOTOR BASEPLATE TEMPERATURE, 102=VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATURE, 103=VSD - DC BUS PRE-REGULATION LOCKOUT, 104=VSD - GROUND FAULT, 105=VSD - PHASE A MOTOR DCCT, 106=VSD - PHASE B MOTOR DCCT, 107=VSD - PHASE C MOTOR DCCT, 108=VSD - PHASE A INPUT DCCT, 109=VSD - PHASE B INPUT DCCT, 110=VSD - PHASE C INPUT DCCT, 111=VSD - HIGH TOTAL DEMAND DISTORTION, 112=VSD - HIGH INTERNAL AMBIENT TEMPERATURE, 113=VSD - DC BUS LOCKOUT - DO NOT CYCLE POWER, 114=VSD - INPUT DCCT OFFSET LOCKOUT, 116=VSD - HIGH PHASE A INPUT CURRENT, 117=VSD - HIGH PHASE B INPUT CURRENT, 118=VSD - HIGH PHASE C INPUT CURRENT, 119=VSD - HIGH PHASE A MOTOR CURRENT, 120=VSD - HIGH PHASE B MOTOR CURRENT, 121=VSD - HIGH PHASE C MOTOR CURRENT, 122=VSD - MOTOR CURRENT THD FAULT, 123=VSD - HIGH INPUT CURRENT TDD, 124=VSD - RECTIFIER PROGRAM FAULT, 125=VSD - INVERTER PROGRAM FAULT, 126=MBC - DSP INITIALIZATION, 127=MBC - HIGH AMPLIFIER TEMPERATURE, 128=MBC - HIGH DC/DC TEMPERATURE, 129=MBC - DSP COMMUNICATION, 130=MBC - DSP INTEGRITY, 131=MBC - FLASH MEMORY CLEAR, 132=MBC - FLASH MEMORY WRITE, 133=MBC - EEPROM, 134=MBC - FLASH MEMORY FULL, 135=MBC - INTERNAL FAULT 11, 136=MBC - INTERNAL FAULT 12, 137=MBC - INTERNAL FAULT 13, 138=MBC - INTERNAL FAULT 14, 139=MBC - DSP WATCHDOG, 140=MBC - DATA ACQUISITION FAULT, 141=MBC - HIGH BEARING Z1 TEMPERATURE, 142=MBC - HIGH BEARING Z2 TEMPERATURE, 143=MBC - CABLE FAULT, 144=MBC - SPEED SIGNAL FAULT, 145=MBC - OVERSPEED FAULT, 146=MBC - ROTOR ELONGATION, 147=MBC - HIGH BEARING CURRENT, 148=MBC - OSCILLATOR FAULT, 149=MBC - POWER SUPPLY FAULT, 150=MBC - UNAUTHORIZED ROTATION, 151=MBC - FAULT CODE X, 152=MBC - NO LEVITATION, 154=MBC - EXCESSIVE SHUTDOWNS, 155=SAFETY STOP, 156=MBC - INITIALIZATION FAILED, 157=MBC - CUSTOMER SERIAL LINK DISABLED, 158=MOTOR - HIGH HOUSING TEMPERATURE, 159=SALES ORDER - INVALID COMPRESSOR MODEL, 160=VSD - LINE VOLTAGE PHASE ROTATION, 161=VSD - PHASE LOCKED LOOP, 162=VSD - LOGIC BOARD HARDWARE, 163=ISOLATION VALVES - NOT OPENED
MVmin3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Cycling Faults Present, 2=MULTIUNIT CYCLING - CONTACTS OPEN, 3=SYSTEM CYCLING - CONTACTS OPEN, 4=SYSTEM - STARTUP FAILURE, 5=OUTSIDE AMBIENT AIR - HIGH TEMPERATURE, 6=CONTROL PANEL - POWER FAILURE, 7=LEAVING CHILLED LIQUID - LOW TEMPERATURE, 8=CHILLED LIQUID - FLOW SWITCH OPEN, 12=REFRIGERANT TYPE NOT SET, 13=CONTROL PANEL - SCHEDULE, 14=CONDENSER - FAN VSD FAULT 1 & 2, 18=VSD - INITIALIZATION FAILED, 19=VSD SHUTDOWN - REQUESTING FAULT DATA..., 20=VGD ACTUATOR - SERIAL COMMUNICATIONS, 21=UPS - LINE LOW BATTERY VOLTAGE, 22=UPS - NOT CHARGING, 26=VSD - SINGLE PHASE INPUT POWER, 27=VSD - HIGH DC BUS VOLTAGE, 28=VSD - LOGIC BOARD POWER SUPPLY, 29=VSD - LOW DC BUS VOLTAGE, 30=VSD - 105% MOTOR CURRENT OVERLOAD, 31=VSD - HIGH INTERNAL AMBIENT TEMPERATURE, 38=VSD - PRECHARGE - LOW DC BUS VOLTAGE 1, 40=VSD - RUN SIGNAL, 41=VSD - SERIAL RECEIVE, 42=VSD - FAULT CONTACTS OPEN, 101=VSD - SERIAL COMMUNICATIONS, 102=MBC - V13 POSITION, 103=MBC - W13 POSITION, 104=MBC - V24 POSITION, 105=MBC - W24 POSITION, 106=MBC - Z12 POSITION, 107=MBC - V13 LOW FREQUENCY DISPLACEMENT, 108=MBC - W13 LOW FREQUENCY DISPLACEMENT, 109=MBC - V24 LOW FREQUENCY DISPLACEMENT, 110=MBC - W24 LOW FREQUENCY DISPLACEMENT, 111=MBC - Z12 LOW FREQUENCY DISPLACEMENT, 112=MBC - VW13 VIBRATION, 113=MBC - VW24 VIBRATION, 114=MBC - Z12 VIBRATION, 115=MBC - HIGH AMPLIFIER TEMPERATURE, 116=MBC - HIGH DC/DC TEMPERATURE, 117=MBC - SERIAL COMMUNICATIONS, 118=MBC - SPEED SIGNAL FAULT, 119=MBC SHUTDOWN - REQUESTING FAULT DATA..., 120=MBC - FAULT CONTACTS OPEN, 122=MBC - UNKNOWN PARAMETER FILE, 123=MBC - LOW INPUT VOLTAGE, 128=EVAPORATOR - LOW PRESSURE - SMART FREEZE, 129=EVAPORATOR - LOW PRESSURE, 130=CONTROL PANEL - LOSS OF CONTROL VOLTAGE, 131=EXPANSION I/O - SERIAL COMMUNICATIONS, 133=VSD - HIGH PHASE A INPUT CURRENT, 134=VSD - HIGH PHASE B INPUT CURRENT, 135=VSD - HIGH PHASE C INPUT CURRENT, 136=VSD - HIGH PHASE A MOTOR CURRENT, 137=VSD - HIGH PHASE B MOTOR CURRENT, 138=VSD - HIGH PHASE C MOTOR CURRENT, 139=VSD - PHASE A INPUT GATE DRIVER, 140=VSD - PHASE B INPUT GATE DRIVER, 141=VSD - PHASE C INPUT GATE DRIVER, 142=VSD - PHASE A MOTOR GATE DRIVER, 143=VSD - PHASE B MOTOR GATE DRIVER, 144=VSD - PHASE C MOTOR GATE DRIVER, 145=VSD - LOW PHASE A INPUT BASEPLATE TEMPERATURE, 146=VSD - LOW PHASE B INPUT BASEPLATE TEMPERATURE, 147=VSD - LOW PHASE C INPUT BASEPLATE TEMPERATURE, 148=VSD - LOW PHASE A MOTOR BASEPLATE TEMPERATURE, 149=VSD - LOW PHASE B MOTOR BASEPLATE TEMPERATURE, 150=VSD - LOW PHASE C MOTOR BASEPLATE TEMPERATURE, 151=VSD – LINE VOLTAGE PHASE ROTATION, 152=VSD - DC BUS PRE-REGULATION, 153=VSD - LOGIC BOARD PROCESSOR, 154=VSD - PHASE LOCKED LOOP, 155=VSD - NOT RUNNING, 156=VSD - PHASE A INPUT DCCT OFFSET, 157=VSD - PHASE B INPUT DCCT OFFSET, 158=VSD - PHASE C INPUT DCCT OFFSET, 159=VSD - PRECHARGE - LOW DC BUS VOLTAGE 2, 160=VSD - INVALID SETPOINTS, 162=ISOLATION VALVES - NOT CLOSED
AV403UNIT CYCLING FAULT CODE AVUnit Cycling Fault Code AVRead0=No Cycling Faults Present, 1=MULTIUNIT CYCLING - CONTACTS OPEN, 2=SYSTEM CYCLING - CONTACTS OPEN, 3=SYSTEM - STARTUP FAILURE, 4=OUTSIDE AMBIENT AIR - HIGH TEMPERATURE, 5=CONTROL PANEL - POWER FAILURE, 6=LEAVING CHILLED LIQUID - LOW TEMPERATURE, 7=CHILLED LIQUID - FLOW SWITCH OPEN, 11=REFRIGERANT TYPE NOT SET, 12=CONTROL PANEL - SCHEDULE, 13=CONDENSER - FAN VSD FAULT 1 & 2, 17=VSD - INITIALIZATION FAILED, 18=VSD SHUTDOWN - REQUESTING FAULT DATA..., 19=VGD ACTUATOR - SERIAL COMMUNICATIONS, 20=UPS - LINE LOW BATTERY VOLTAGE, 21=UPS - NOT CHARGING, 25=VSD - SINGLE PHASE INPUT POWER, 26=VSD - HIGH DC BUS VOLTAGE, 27=VSD - LOGIC BOARD POWER SUPPLY, 28=VSD - LOW DC BUS VOLTAGE, 29=VSD - 105% MOTOR CURRENT OVERLOAD, 30=VSD - HIGH INTERNAL AMBIENT TEMPERATURE, 37=VSD - PRECHARGE - LOW DC BUS VOLTAGE 1, 39=VSD - RUN SIGNAL, 40=VSD - SERIAL RECEIVE, 41=VSD - FAULT CONTACTS OPEN, 100=VSD - SERIAL COMMUNICATIONS, 101=MBC - V13 POSITION, 102=MBC - W13 POSITION, 103=MBC - V24 POSITION, 104=MBC - W24 POSITION, 105=MBC - Z12 POSITION, 106=MBC - V13 LOW FREQUENCY DISPLACEMENT, 107=MBC - W13 LOW FREQUENCY DISPLACEMENT, 108=MBC - V24 LOW FREQUENCY DISPLACEMENT, 109=MBC - W24 LOW FREQUENCY DISPLACEMENT, 110=MBC - Z12 LOW FREQUENCY DISPLACEMENT, 111=MBC - VW13 VIBRATION, 112=MBC - VW24 VIBRATION, 113=MBC - Z12 VIBRATION, 114=MBC - HIGH AMPLIFIER TEMPERATURE, 115=MBC - HIGH DC/DC TEMPERATURE, 116=MBC - SERIAL COMMUNICATIONS, 117=MBC - SPEED SIGNAL FAULT, 118=MBC SHUTDOWN - REQUESTING FAULT DATA..., 119=MBC - FAULT CONTACTS OPEN, 121=MBC - UNKNOWN PARAMETER FILE, 122=MBC - LOW INPUT VOLTAGE, 127=EVAPORATOR - LOW PRESSURE - SMART FREEZE, 128=EVAPORATOR - LOW PRESSURE, 129=CONTROL PANEL - LOSS OF CONTROL VOLTAGE, 130=EXPANSION I/O - SERIAL COMMUNICATIONS, 132=VSD - HIGH PHASE A INPUT CURRENT, 133=VSD - HIGH PHASE B INPUT CURRENT, 134=VSD - HIGH PHASE C INPUT CURRENT, 135=VSD - HIGH PHASE A MOTOR CURRENT, 136=VSD - HIGH PHASE B MOTOR CURRENT, 137=VSD - HIGH PHASE C MOTOR CURRENT, 138=VSD - PHASE A INPUT GATE DRIVER, 139=VSD - PHASE B INPUT GATE DRIVER, 140=VSD - PHASE C INPUT GATE DRIVER, 141=VSD - PHASE A MOTOR GATE DRIVER, 142=VSD - PHASE B MOTOR GATE DRIVER, 143=VSD - PHASE C MOTOR GATE DRIVER, 144=VSD - LOW PHASE A INPUT BASEPLATE TEMPERATURE, 145=VSD - LOW PHASE B INPUT BASEPLATE TEMPERATURE, 146=VSD - LOW PHASE C INPUT BASEPLATE TEMPERATURE, 147=VSD - LOW PHASE A MOTOR BASEPLATE TEMPERATURE, 148=VSD - LOW PHASE B MOTOR BASEPLATE TEMPERATURE, 149=VSD - LOW PHASE C MOTOR BASEPLATE TEMPERATURE, 150=VSD – LINE VOLTAGE PHASE ROTATION, 151=VSD - DC BUS PRE-REGULATION, 152=VSD - LOGIC BOARD PROCESSOR, 153=VSD - PHASE LOCKED LOOP, 154=VSD - NOT RUNNING, 155=VSD - PHASE A INPUT DCCT OFFSET, 156=VSD - PHASE B INPUT DCCT OFFSET, 157=VSD - PHASE C INPUT DCCT OFFSET, 158=VSD - PRECHARGE - LOW DC BUS VOLTAGE 2, 159=VSD - INVALID SETPOINTS, 161=ISOLATION VALVES - NOT CLOSED
MV4UNIT WARNING CODEUnit Warning CodeRead1=No Warnings Present, 2=WARNING - REAL TIME CLOCK FAILURE, 3=WARNING - SETPOINT OVERRIDE, 4=WARNING - CONDENSER OR EVAPORATOR XDCR ERROR, 5=WARNING - EVAPORATOR - LOW PRESSURE LIMIT, 7=WARNING - DISCHARGE - HIGH PRESSURE LIMIT, 8=WARNING - CONTROL PANEL - LOW TEMPERATURE, 9=WARNING - CONTROL PANEL - HIGH TEMPERATURE, 10=WARNING - CONDENSER - FAN VSD FAULT 1, 11=WARNING - CONDENSER - FAN VSD FAULT 2, 12=WARNING - POWER PANEL - LOW TEMPERATURE, 13=WARNING - POWER PANEL - HIGH TEMPERATURE, 21=WARNING - UPS - NOT CHARGING, 22=WARNING - UPS - LINE LOW BATTERY VOLTAGE, 23=WARNING - UPS - BATTERY NOT CONNECTED, 24=WARNING - UPS - CHECK BATTERY CONNECTION, 25=WARNING - UPS - BATTERY TEST FAILED, 30=WARNING - SURGE PROTECTION - EXCESS SURGE LIMIT, 31=WARNING - EXCESS SURGE DETECTED, 41=WARNING - MOTOR - HIGH WINDING TEMPERATURE, 42=WARNING - MOTOR - HIGH ROTOR TEMPERATURE, 45=WARNING - VSD - INPUT VOLTAGE IMBALANCE, 46=WARNING - VSD - HIGH HX APPROACH TEMPERATURE, 49=WARNING - MBC - LANDING COUNTER HIGH, 56=WARNING - MBC - CHECKSUM CENTERING, 57=WARNING - MBC - DSP WATCHDOG, 58=WARNING - MBC - AMP WATCHDOG, 59=WARNING - MBC - INTERNAL ALARM, 60=WARNING - MBC - HIGH RADIAL OSCILLATOR VOLTAGE, 61=WARNING - MBC - HIGH AXIAL OSCILLATOR VOLTAGE, 66=WARNING - MBC - ROTATION MODE OFF, 67=WARNING - MOTOR - HIGH CURRENT LIMIT, 68=WARNING - MOTOR - HIGH HOUSING TEMPERATURE, 69=WARNING - VSD - DC BUS ACTIVE
AV404UNIT WARNING CODE AVUnit Warning Code AVRead0=No Warnings Present, 1=WARNING - REAL TIME CLOCK FAILURE, 2=WARNING - SETPOINT OVERRIDE, 3=WARNING - CONDENSER OR EVAPORATOR XDCR ERROR, 4=WARNING - EVAPORATOR - LOW PRESSURE LIMIT, 6=WARNING - DISCHARGE - HIGH PRESSURE LIMIT, 7=WARNING - CONTROL PANEL - LOW TEMPERATURE, 8=WARNING - CONTROL PANEL - HIGH TEMPERATURE, 9=WARNING - CONDENSER - FAN VSD FAULT 1, 10=WARNING - CONDENSER - FAN VSD FAULT 2, 11=WARNING - POWER PANEL - LOW TEMPERATURE, 12=WARNING - POWER PANEL - HIGH TEMPERATURE, 20=WARNING - UPS - NOT CHARGING, 21=WARNING - UPS - LINE LOW BATTERY VOLTAGE, 22=WARNING - UPS - BATTERY NOT CONNECTED, 23=WARNING - UPS - CHECK BATTERY CONNECTION, 24=WARNING - UPS - BATTERY TEST FAILED, 29=WARNING - SURGE PROTECTION - EXCESS SURGE LIMIT, 30=WARNING - EXCESS SURGE DETECTED, 40=WARNING - MOTOR - HIGH WINDING TEMPERATURE, 41=WARNING - MOTOR - HIGH ROTOR TEMPERATURE, 44=WARNING - VSD - INPUT VOLTAGE IMBALANCE, 45=WARNING - VSD - HIGH HX APPROACH TEMPERATURE, 48=WARNING - MBC - LANDING COUNTER HIGH, 55=WARNING - MBC - CHECKSUM CENTERING, 56=WARNING - MBC - DSP WATCHDOG, 57=WARNING - MBC - AMP WATCHDOG, 58=WARNING - MBC - INTERNAL ALARM, 59=WARNING - MBC - HIGH RADIAL OSCILLATOR VOLTAGE, 60=WARNING - MBC - HIGH AXIAL OSCILLATOR VOLTAGE, 65=WARNING - MBC - ROTATION MODE OFF, 66=WARNING - MOTOR - HIGH CURRENT LIMIT, 67=WARNING - MOTOR - HIGH HOUSING TEMPERATURE, 68=WARNING - VSD - DC BUS ACTIVE
MVmin5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
AV405UNIT CONTROL SOURCE AVUnit Control Source AVRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
MV6UNIT MODIFIED RUN CODEUnit Modified Run CodeRead1=No Modified Run Conditions Present, 5=VSD - INPUT PULLDOWN LIMIT, 6=VSD - HIGH INPUT CURRENT LIMIT
AV406UNIT MODIFIED RUN CODE AVUnit Modified Run Code AVRead0=No Modified Run Conditions Present, 4=VSD - INPUT PULLDOWN LIMIT, 5=VSD - HIGH INPUT CURRENT LIMIT
MV7UNIT START INHIBIT CODEUnit Start Inhibit CodeRead1=No Inhibit Faults Present, 2=ANTI-RECYCLE, 4=VGD STROKE NOT CALIBRATED, 5=VGD FEEDBACK NOT CALIBRATED, 11=PRV NOT CALIBRATED, 13=VGD NOT CALIBRATED, 14=LINE VOLTAGE NOT SET, 15=LINE FREQUENCY NOT SET, 16=MBC - INITIALIZATION IN PROGRESS
AV407UNIT START INHIBIT CODE AVUnit Start Inhibit Code AVRead0=No Inhibit Faults Present, 1=ANTI-RECYCLE, 3=VGD STROKE NOT CALIBRATED, 4=VGD FEEDBACK NOT CALIBRATED, 10=PRV NOT CALIBRATED, 12=VGD NOT CALIBRATED, 13=LINE VOLTAGE NOT SET, 14=LINE FREQUENCY NOT SET, 15=MBC - INITIALIZATION IN PROGRESS
MV8UNIT INTERNAL FAULT CODEUnit Internal Fault CodeRead1=No Internal Faults Present, 2=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 3=WATCHDOG - SOFTWARE REBOOT, 4=INTERNAL ERROR - CANNOT CREATE TASK, 5=INTERNAL ERROR - CANNOT REGISTER CONTROL, 6=INTERNAL ERROR - INVALID BRAM
AV408UNIT INTERNAL FAULT CODE AVUnit Internal Fault Code AVRead0=No Internal Faults Present, 1=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 2=WATCHDOG - SOFTWARE REBOOT, 3=INTERNAL ERROR - CANNOT CREATE TASK, 4=INTERNAL ERROR - CANNOT REGISTER CONTROL, 5=INTERNAL ERROR - INVALID BRAM
AV32ACTIVE ANTI SURGE MIN FREQActive Anti-Surge Minimum FrequencyHzRead
AV33CONDENSER FAN POWERCondenser Fan PowerkWRead
AV34VSD OUTPUT VOLTAGEVSD Output VoltageVoltsRead
AV35COMP VSD INPUT POWERCompressor VSD Input PowerkWRead
AV36VSD INPUT KWHVSD Input Kilowatt HourskWhRead
AV37VSD DC BUS VOLTAGEVSD DC Bus VoltageVoltsRead
AV38VSD INPUT VOLTAGE L1VSD L1 Input Voltage (RMS)VoltsRead
AV39SURGE COUNTSurge CountRead
AV40VSD OUTPUT FREQUENCYVSD Output FrequencyHzRead
AV41VSD INPUT VOLTAGE L2VSD L2 Input Voltage (RMS)VoltsRead
AV42VSD INPUT VOLTAGE L3VSD L3 Input Voltage (RMS)VoltsRead
AV43COND DRAIN VALVE CMDCondenser Drain Valve Command%Read
BV26MBC LEVITATION MODEMBC Levitation ModeRead0=Off, 1=On
BV27MBC ROTATION MODEMBC Rotation ModeRead0=Off, 1=On
AV48MOTOR HOUSING TEMPMotor Housing Temp°FRead
AV107MOTOR COOLING VALVE CMDMotor Cooling Valve Command%Read
AV108VSD INTERNAL AMBIENT TEMP 2VSD Internal Ambient Temperature 2°FRead
AV109MTR WINDING AVG TEMPAverage Motor Winding Temperature°FRead
AV110VSD INTERNAL AMBIENT TEMP 1VSD Internal Ambient Temperature 1°FRead
AV111VGD POSITIONVGD Position%Read
AV113ACT SUBCOOLING SETPActive Subcooling Setpoint°F (diff)Read
AV114COND LIQUID TEMPCondenser Liquid Temperature°FRead
AV115VSD L1 VOLTAGE THDVSD L1 Voltage Total Harmonic Distortion%Read
AV116VSD L2 VOLTAGE THDVSD L2 Voltage Total Harmonic Distortion%Read
AV117VSD L3 VOLTAGE THDVSD L3 Voltage Total Harmonic Distortion%Read
AV118VSD L1 INPUT CURRENT TDDVSD L1 Input Current Total Demand Distortion%Read
AV119VSD L2 INPUT CURRENT TDDVSD L2 Input Current Total Demand Distortion%Read
AV120VSD L3 INPUT CURRENT TDDVSD L3 Input Current Total Demand Distortion%Read
AV121INPUT KWH LOInput kWh low part (kWh = offset x 10,000 + low)Read
AV122INPUT KWH OFFSETInput kWh offset part (kWh = offset x 10,000 + low)Read
AV123OPERATING HOURS LOOperating hours low part (hours = offset x 10,000 + low)Read
AV124OPERATING HOURS OFFSETOperating hours offset part (hours = offset x 10,000 + low)Read
AV125MBC MOTOR SPEEDMBC Motor SpeedHzRead
AV126COND FAN SPEED CMD 1Condenser Fan Speed Command 1%Read
AV127COND FAN SPEED CMD 2Condenser Fan Speed Command 2%Read
AV128COND FAN SPEED CMD 3Condenser Fan Speed Command 3%Read
AV129COND FAN SPEED CMD 4Condenser Fan Speed Command 4%Read
BV105COND FAN VSD RUN 1Condenser Fan VSD Run 1Read0=Off, 1=On
BV106COND FAN VSD RUN 2Condenser Fan VSD Run 2Read0=Off, 1=On
BV107COND FAN VSD FAULT 1Condenser Fan VSD Fault 1Read0=Off, 1=On
BV108COND FAN VSD FAULT 2Condenser Fan VSD Fault 2Read0=Off, 1=On
AV130SUCT SATURATION TEMPSuction Saturation Temperature°FRead
AV131DISCH SATURATION TEMPDischarge Saturation Temperature°FRead
AV132ACT DISCH PRESSURE SETPActive Discharge Pressure SetpointPSIGRead
AV137UPS BATTERY VOLTAGEUPS Battery VoltageVoltsRead
AV138VSD PH A REC BASEPLATE TEMPVSD Phase A Rectifier Baseplate Temperature°FRead
AV139VSD PH B REC BASEPLATE TEMPVSD Phase B Rectifier Baseplate Temperature°FRead
AV140VSD PH C REC BASEPLATE TEMPVSD Phase C Rectifier Baseplate Temperature°FRead
AV141VSD PH A INV BASEPLATE TEMPVSD Phase A Inverter Baseplate Temperature°FRead
AV142VSD PH B INV BASEPLATE TEMPVSD Phase B Inverter Baseplate Temperature°FRead
AV143VSD PH C INV BASEPLATE TEMPVSD Phase C Inverter Baseplate Temperature°FRead
AV144EVAP SMALL TEMP DIFFEvaporator Small Temp Difference°F (diff)Read
AV145COND SMALL TEMP DIFFCondenser Small Temp Difference°F (diff)Read
AV146DISCHARGE SUPERHEATDischarge Superheat°F (diff)Read
AV148SUBCOOLING TEMPSubcooling Temperature°F (diff)Read
AV149DELTA P DIV PDelta P / PRead
AV150HEAD PRESSUREHead PressurePSIDRead
Object ID lookup: York YVAM point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)

How many BACnet points does the York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) have?

This list has 109 BACnet objects: 85 analog values, 15 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points are writable?

4 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet documentation?

The source is YVAM SC-EQ BAS Points List, revision Rev 1.5, 2022-09-20, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/QO052Dm251t6v1FTiH8_iQ/content.

What are the minimum BACnet points to integrate the York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)?

Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE INPUT CURRENT SP (Remote input current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 24 INPUT CURRENT PCT FLA (Input current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)?

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-2 the remote setpoints. MV 5 shows the control source (Local, ISN (BAS), Analog, Digital, Modem, Remote); it should read ISN for BAS control. The points list has no write-enable point.

How do I check these points on the real YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YVAM SC-EQ BAS Points List · rev. Rev 1.5, 2022-09-20. Object names, instances and units are reproduced as published; descriptions are our own.