- Home
- BACnet points lists
- York
- Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
Scroll chiller / heat pump / condensing unit (via SC-EQ card) · BACnet points list
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) BACnet points list
Updated 4 November 2026
This SC-EQ list covers the YORK scroll product family: air- and water-cooled scroll chillers, heat pumps and condensing units. The SC-EQ card serves BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the unit or each system, write setpoints, range, load limit stage and heat pump mode. Several objects change meaning with the unit type (condensing unit, heat pump, YCWL, EEV, refrigerant), so the sheet prints more than one row for them.
This page lists 85 BACnet objects for the York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
- Equipment
- Scroll chiller / heat pump / condensing unit (via SC-EQ card)
- Equipment type
- Chillers
- BACnet objects
- 85 (7 writable)
- Transport
- BACnet MS/TP
- Firmware
- SC-EQ software 3.5.0.11
- Default device instance
- 5000 + MAC address
- Also known as
- YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1
- Source document
- Scroll SC-EQ BAS Points List · rev. Rev 2.4, 2021-01-11
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
Put the unit in remote control (BV 21 reads Remote), then start/stop it with BV 1 and write the remote setpoint (AV 1) and, if needed, the load limit stage (AV 2). Read the leaving chilled liquid temperature, compressor run status, the per-system alarms (BV 5, BV 6) and the per-system operational and fault codes.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | REM START STOP CMD / SYS1 REM START STOP CMD | Remote start/stop (1 = run) | Command |
| AV 1 | REMOTE SETPOINT / SYS 1 REM SETP | Remote cooling setpoint (99 = auto) | Command |
| AV 2 | REM LOAD LIMIT STAGE | Remote load limit stage (0, 1, 2) | Command |
| MV 1 | SYS 1 OPERATIONAL CODE | Sys 1 operating state | Read |
| BV 9 | SYS 1 COMP 1 RUN | Sys 1 compressor 1 running | Read |
| BV 21 | LOCAL REMOTE CONTROL MODE | Must read Remote (1) for BMS control | Read |
| AV 5 | LEAVING CHILLED LIQ TEMP | Leaving chilled liquid temperature | Read |
| BV 5 | SYS 1 ALARM | System 1 alarm | Read |
| BV 6 | SYS 2 ALARM | System 2 alarm | Read |
| MV 2 | SYS 1 FAULT CODE | Sys 1 fault/inhibit code (1 = no fault) | Read |
Enable & remote start
BV 21 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. AV 4 selects panel, cool or heat on heat pump units.
Network setup
- The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.
- The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.
- The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID).
Watch out for
- The remote (commandable) setpoints read as unreliable until the BAS writes them the first time.
- The SC-EQ only exposes the points that apply to the chiller it detects; if it replaces an E-Link, re-discover the device so old non-applicable points don't sit offline.
- Check the unit type before mapping: AV 1, AV 3 and AV 36-39 mean different things on suction-pressure condensing units, heat pumps and chillers.
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REMOTE SETPOINT / SYS 1 REM SETP | Remote setpoint, 99 = auto (°F); or Sys 1 remote setpoint (PSIG) | °F / PSIG | Command | |
| AVmin | 2 | REM LOAD LIMIT STAGE | Remote load limit stage (0, 1 or 2) | Command | ||
| AV | 3 | REM COOLING RANGE / REM HEATING SETP / SYS 2 REM SETP | Remote cooling range, heating setpoint (999 = auto) or Sys 2 setpoint | °F (diff) / °F / PSIG | Command | |
| AV | 4 | REM HEATPUMP MODE | Remote heat pump mode | Command | 0=Panel, 1=Cool, 2=Heat | |
| BVmin | 1 | REM START STOP CMD / SYS1 REM START STOP CMD | Remote start/stop, unit or Sys 1 (sheet prints both) | Command | 0=Stop, 1=Run | |
| BV | 2 | SYS2 REM START STOP CMD | Sys 2 Remote Start / Stop Command | Command | 0=Stop, 1=Run | |
| BV | 4 | HISTORY REQUEST | History buffer 1 request (live / history data) | Command | 0=Live Data, 1=History 1 Data | |
| AVmin | 5 | LEAVING CHILLED LIQ TEMP | Leaving Chilled Liquid Temp | °F | Read | |
| AV | 6 | ENTERING CHILLED LIQ TEMP | Entering Chilled Liquid Temp | °F | Read | |
| AV | 7 | LEAVING LIQ TEMP HOT | Leaving Liquid Temp Hot (YCWL) | °F | Read | |
| AV | 8 | DISCHARGE AIR TEMP / RETURN LIQ TEMP HOT | Discharge air temp (condensing unit) or return hot liquid temp (YCWL) | °F | Read | |
| AV | 9 | SYS 1 SUCT TEMP | Sys 1 Suction Temperature (If EEV or R-410a) | °F | Read | |
| AV | 10 | OUTSIDE AMBIENT AIR TEMP | Outside Ambient Air Temperature | °F | Read | |
| AV | 11 | SYS 1 SUCT SUPERHEAT | Sys 1 Suction Superheat (EEV units) | °F (diff) | Read | |
| AV | 12 | SYS 1 RUN TIME | Sys 1 run time, seconds | Sec | Read | |
| AV | 13 | SYS 1 SUCT PRESS | Sys 1 Suction Pressure | PSIG | Read | |
| AV | 14 | SYS 1 DISCH PRESS | Sys 1 Discharge Pressure | PSIG | Read | |
| AV | 15 | SYS 1 SUCT TEMP COND UNIT / SYS 1 COOLER INLET REF TEMP | Sys 1 suction temp (condensing unit) or cooler inlet refrigerant temp (R-407c) | °F | Read | |
| AV | 16 | SYS 1 DEFROST TEMP | Sys 1 Defrost Temperature (heat pump) | °F | Read | |
| AV | 17 | SYS 1 EEV OUTPUT PCT | Sys 1 EEV Output Percent (EEV units) | % | Read | |
| AV | 18 | SYS 1 ANTI RECYCLE TIMER | Sys 1 anti-recycle timer, seconds | Read | ||
| AV | 19 | ANTI COINCIDENT TIMER | Anti-coincident timer, seconds | Read | ||
| AV | 20 | SYS 2 SUCT TEMP | Sys 2 Suction Temperature | °F | Read | |
| AV | 21 | SYS 2 RUN TIME | Sys 2 run time, seconds | Sec | Read | |
| AV | 22 | SYS 2 SUCT PRESS | Sys 2 Suction Pressure | PSIG | Read | |
| AV | 23 | SYS 2 DISCH PRESS | Sys 2 Discharge Pressure | PSIG | Read | |
| AV | 24 | SYS 2 SUCT TEMP COND UNIT / SYS 2 COOLER INLET REF TEMP | Sys 2 suction temp (condensing unit) or cooler inlet refrigerant temp (R-407c) | °F | Read | |
| AV | 25 | SYS 2 DEFROST TEMP | Sys 2 Defrost Temperature | °F | Read | |
| AV | 26 | SYS 2 SUCT SUPERHEAT | Sys 2 Suction Superheat | °F (diff) | Read | |
| AV | 27 | SYS 2 ANTI RECYCLE TIMER | Sys 2 anti-recycle timer, seconds | Read | ||
| AV | 28 | SYS 2 EEV OUTPUT PCT | Sys 2 EEV Output Percent | % | Read | |
| AV | 29 | NUMBER COMPRESSORS | Number of Compressors | Read | ||
| BVmin | 5 | SYS 1 ALARM | Sys 1 Alarm | Read | 0=No Alarm, 1=Alarm Active | |
| BVmin | 6 | SYS 2 ALARM | Sys 2 Alarm | Read | 0=No Alarm, 1=Alarm Active | |
| BV | 7 | EVAPORATOR HEATER STATUS | Evaporator Heater Status | Read | 0=Off, 1=On | |
| BV | 8 | EVAPORATOR PUMP STATUS | Evaporator Pump Status | Read | 0=Off, 1=On | |
| BVmin | 9 | SYS 1 COMP 1 RUN | Sys 1 Comp 1 Run | Read | 0=Off, 1=On | |
| BV | 10 | SYS 2 COMP 1 RUN | Sys 2 Comp 1 Run | Read | 0=Off, 1=On | |
| BV | 11 | SYS 1 LIQUID LINE SOL VALVE / SYS 1 MODE SOL VALVE | Sys 1 liquid line solenoid, or mode solenoid on heat pumps | Read | 0=Off, 1=On | |
| BV | 12 | SYS 1 HOT GAS BYPASS VALVE | Sys 1 Hot Gas Bypass Valve (If Not Heatpump) | Read | 0=Off, 1=On | |
| BV | 13 | SYS 1 COMP 2 RUN | Sys 1 Comp 2 Run | Read | 0=Off, 1=On | |
| BV | 14 | SYS 2 COMP 2 RUN | Sys 2 Comp 2 Run | Read | 0=Off, 1=On | |
| BV | 15 | SYS 2 LIQUID LINE SOL VALVE / SYS 2 MODE SOL VALVE | Sys 2 liquid line solenoid, or mode solenoid on heat pumps | Read | 0=Off, 1=On | |
| BV | 16 | LEAD SYSTEM NUMBER | Lead System Number | Read | 0=Sys1, 1=Sys2 | |
| BV | 17 | SYS 1 COMP 3 RUN | Sys 1 Comp 3 Run | Read | 0=Off, 1=On | |
| BV | 18 | SYS 2 COMP 3 RUN | Sys 2 Comp 3 Run | Read | 0=Off, 1=On | |
| BV | 19 | COOLING TYPE | Cooling Type | Read | 0=Water, 1=Glycol | |
| BV | 20 | AMBIENT CONTROL MODE | Ambient Control Mode | Read | 0=Standard Ambient, 1=Low Ambient | |
| BVmin | 21 | LOCAL REMOTE CONTROL MODE | Local Remote Control Mode | Read | 0=Local, 1=Remote | |
| BV | 22 | DISPLAY UNITS | Display Units | Read | 0=Imperial, 1=SI | |
| BV | 23 | LEAD LAG CONTROL MODE | Lead Lag Control Mode | Read | 0=Manual, 1=Auto | |
| BV | 24 | SYS 2 HOT GAS BYPASS VALVE | Sys 2 Hot Gas Bypass Valve | Read | 0=Off, 1=On | |
| MVmin | 1 | SYS 1 OPERATIONAL CODE | Sys 1 Operational Code | Read | 1=No Abnormal Condition, 2=Unit Switch Off, 3=System Switch Off, 4=Lockout, 5=Unit Fault, 6=System Fault, 7=Remote Shutdown, 8=Daily Schedule Shutdown, 9=No Run Permissive, 10=No Cool Load, 11=Anti-Coincidence Timer Active, 12=Anti-Recycle Timer Active, 13=Manual Override, 14=Suction Limiting, 15=Discharge Limiting, 16=Current Limiting, 17=Load Limiting, 18=Compressor(s) Running, 19=Heat pump Load Limiting, 20=Pumping Down | |
| AV | 501 | SYS 1 OPERATIONAL CODE AV | Sys 1 Operational Code AV | Read | 0=No Abnormal Condition, 1=Unit Switch Off, 2=System Switch Off, 3=Lockout, 4=Unit Fault, 5=System Fault, 6=Remote Shutdown, 7=Daily Schedule Shutdown, 8=No Run Permissive, 9=No Cool Load, 10=Anti-Coincidence Timer Active, 11=Anti-Recycle Timer Active, 12=Manual Override, 13=Suction Limiting, 14=Discharge Limiting, 15=Current Limiting, 16=Load Limiting, 17=Compressor(s) Running, 18=Heat pump Load Limiting, 19=Pumping Down | |
| MVmin | 2 | SYS 1 FAULT CODE | Sys 1 Fault Code | Read | 1=No Fault, 2=VAC Under Voltage, 3=Low Ambient Temperature, 4=High Ambient Temperature, 5=Low Leaving Chilled Liquid Temp, 6=High Discharge Pressure, 7=High Differential Oil Pressure, 8=Low Suction Pressure, 9=High Motor Current, 10=LLSV Not On, 11=Low Battery Warning, 12=High Oil Temperature, 13=High Discharge Temperature, 14=Improper Phase Rotation, 15=Low Motor Current / MP / HPCO, 16=Motor Current Unbalanced, 17=Low Differential Oil Pressure, 18=Ground Fault, 19=MP/HPCO Fault, 20=Low Evaporator Temperature, 21=Incorrect Refrigerant Programmed, 22=Power Failure, Manual Reset Required, 23=Unit Motor Current, 24=Low Superheat, 25=Sensor Fault, 26=Discharge Inhibit, 27=MP/HPCO Inhibit, 28=Pump Trip, 29=Pump Fail Make Flow, 30=High Ambient Temperature, 31=Anti-Vacuum Low Pressure Cutout, 32=Flow Switch Open, 33=Leaving Chilled Liquid Temperature Sensor Fault | |
| AV | 502 | SYS 1 FAULT CODE AV | Sys 1 Fault Code AV | Read | 0=No Fault, 1=VAC Under Voltage, 2=Low Ambient Temperature, 3=High Ambient Temperature, 4=Low Leaving Chilled Liquid Temp, 5=High Discharge Pressure, 6=High Differential Oil Pressure, 7=Low Suction Pressure, 8=High Motor Current, 9=LLSV Not On, 10=Low Battery Warning, 11=High Oil Temperature, 12=High Discharge Temperature, 13=Improper Phase Rotation, 14=Low Motor Current / MP / HPCO, 15=Motor Current Unbalanced, 16=Low Differential Oil Pressure, 17=Ground Fault, 18=MP/HPCO Fault, 19=Low Evaporator Temperature, 20=Incorrect Refrigerant Programmed, 21=Power Failure, Manual Reset Required, 22=Unit Motor Current, 23=Low Superheat, 24=Sensor Fault, 25=Discharge Inhibit, 26=MP/HPCO Inhibit, 27=Pump Trip, 28=Pump Fail Make Flow, 29=High Ambient Temperature, 30=Anti-Vacuum Low Pressure Cutout, 31=Flow Switch Open, 32=Leaving Chilled Liquid Temperature Sensor Fault | |
| MV | 3 | SYS 2 OPERATIONAL CODE | Sys 2 Operational Code | Read | 1=No Abnormal Condition, 2=Unit Switch Off, 3=System Switch Off, 4=Lockout, 5=Unit Fault, 6=System Fault, 7=Remote Shutdown, 8=Daily Schedule Shutdown, 9=No Run Permissive, 10=No Cool Load, 11=Anti-Coincidence Timer Active, 12=Anti-Recycle Timer Active, 13=Manual Override, 14=Suction Limiting, 15=Discharge Limiting, 16=Current Limiting, 17=Load Limiting, 18=Compressor(s) Running, 19=Heat pump Load Limiting, 20=Pumping Down | |
| AV | 503 | SYS 2 OPERATIONAL CODE AV | Sys 2 Operational Code AV | Read | 0=No Abnormal Condition, 1=Unit Switch Off, 2=System Switch Off, 3=Lockout, 4=Unit Fault, 5=System Fault, 6=Remote Shutdown, 7=Daily Schedule Shutdown, 8=No Run Permissive, 9=No Cool Load, 10=Anti-Coincidence Timer Active, 11=Anti-Recycle Timer Active, 12=Manual Override, 13=Suction Limiting, 14=Discharge Limiting, 15=Current Limiting, 16=Load Limiting, 17=Compressor(s) Running, 18=Heat pump Load Limiting, 19=Pumping Down | |
| MV | 4 | SYS 2 FAULT CODE | Sys 2 Fault Code | Read | 1=No Fault, 2=VAC Under Voltage, 3=Low Ambient Temperature, 4=High Ambient Temperature, 5=Low Leaving Chilled Liquid Temp, 6=High Discharge Pressure, 7=High Differential Oil Pressure, 8=Low Suction Pressure, 9=High Motor Current, 10=LLSV Not On, 11=Low Battery Warning, 12=High Oil Temperature, 13=High Discharge Temperature, 14=Improper Phase Rotation, 15=Low Motor Current / MP / HPCO, 16=Motor Current Unbalanced, 17=Low Differential Oil Pressure, 18=Ground Fault, 19=MP/HPCO Fault, 20=Low Evaporator Temperature, 21=Incorrect Refrigerant Programmed, 22=Power Failure, Manual Reset Required, 23=Unit Motor Current, 24=Low Superheat, 25=Sensor Fault, 26=Discharge Inhibit, 27=MP/HPCO Inhibit, 28=Pump Trip, 29=Pump Fail Make Flow, 30=High Ambient Temperature, 31=Anti-Vacuum Low Pressure Cutout, 32=Flow Switch Open, 33=Leaving Chilled Liquid Temperature Sensor Fault | |
| AV | 504 | SYS 2 FAULT CODE AV | Sys 2 Fault Code AV | Read | 0=No Fault, 1=VAC Under Voltage, 2=Low Ambient Temperature, 3=High Ambient Temperature, 4=Low Leaving Chilled Liquid Temp, 5=High Discharge Pressure, 6=High Differential Oil Pressure, 7=Low Suction Pressure, 8=High Motor Current, 9=LLSV Not On, 10=Low Battery Warning, 11=High Oil Temperature, 12=High Discharge Temperature, 13=Improper Phase Rotation, 14=Low Motor Current / MP / HPCO, 15=Motor Current Unbalanced, 16=Low Differential Oil Pressure, 17=Ground Fault, 18=MP/HPCO Fault, 19=Low Evaporator Temperature, 20=Incorrect Refrigerant Programmed, 21=Power Failure, Manual Reset Required, 22=Unit Motor Current, 23=Low Superheat, 24=Sensor Fault, 25=Discharge Inhibit, 26=MP/HPCO Inhibit, 27=Pump Trip, 28=Pump Fail Make Flow, 29=High Ambient Temperature, 30=Anti-Vacuum Low Pressure Cutout, 31=Flow Switch Open, 32=Leaving Chilled Liquid Temperature Sensor Fault | |
| AV | 406 | SYS 1 COND FAN STAGES RUN | Sys 1 Condenser Fan Stage | Read | ||
| AV | 408 | SYS 2 COND FAN STAGES RUN | Sys 2 Condenser Fan Stage | Read | ||
| MV | 10 | UNIT CONTROL MODE | Unit control mode | Read | 0=Leaving Water, 1=Return Water, 2=Discharge Air, 3=Suction Press, 4=Heatpump Cooling, 5=Heatpump Heating | |
| AV | 505 | UNIT CONTROL MODE AV | Unit control mode (analog copy) | Read | 0=Leaving Water, 1=Return Water, 2=Discharge Air, 3=Suction Press, 4=Heatpump Cooling, 5=Heatpump Heating | |
| AV | 30 | ANTI RECYCLE TIME PROG | Anti-Recycle Time Programmed | Read | ||
| AV | 31 | LOW LEAVING CHILL LIQ CUTOUT | Low Leaving Chilled Liquid Temp Cutout | °F | Read | |
| AV | 32 | LOW AMBIENT TEMP CUTOUT | Low Ambient Temp Cutout | °F | Read | |
| AV | 33 | LOW SUCT PRESS CUTOUT HEATING | Low Suction Press Cutout Heating (heat pump) | PSIG | Read | |
| AV | 34 | LOW SUCT PRESS CUTOUT COOLING | Low Suction Press Cutout Cooling | PSIG | Read | |
| AV | 35 | HIGH DISCH PRESS CUTOUT | High Discharge Press Cutout | PSIG | Read | |
| AV | 36 | COOLING SETPOINT / SYS 1 COOLING SETPOINT | Cooling setpoint, or Sys 1 cooling setpoint (PSIG, SP control) | °F / PSIG | Read | |
| AV | 37 | COOLING RANGE / SYS 1 COOLING RANGE | Cooling range, or Sys 1 cooling range (PSIG, SP control) | °F (diff) / PSIG | Read | |
| AV | 38 | SYS 2 COOLING SETPOINT / HEATING SETPOINT | Sys 2 cooling setpoint (SP control) or heating setpoint (HP) | PSIG / °F | Read | |
| AV | 39 | SYS 2 COOLING RANGE / HEATING RANGE | Sys 2 cooling range (SP control) or heating range (heat pump) | PSIG / °F (diff) | Read | |
| AV | 40 | SYS 1 DISCH TEMP | Sys 1 Discharge Temperature (EEV units) | °F | Read | |
| AV | 41 | SYS 1 DISCH SUPERHEAT | Sys 1 Discharge Superheat (EEV units) | °F (diff) | Read | |
| AV | 42 | SYS 2 DISCH TEMP | Sys 2 Discharge Temperature | °F | Read | |
| AV | 43 | SYS 2 DISCH SUPERHEAT | Sys 2 Discharge Superheat | °F (diff) | Read | |
| BV | 25 | BIVALENT HT SOURCE TRAY HT | Bivalent Heat Source/Tray Heater (heat pump) | Read | 0=Off, 1=On | |
| AV | 116 | SYS 1 COMP 1 RUN HOURS | Sys 1 Comp 1 Run Hours | Hr | Read | |
| AV | 117 | SYS 1 COMP 2 RUN HOURS | Sys 1 Comp 2 Run Hours | Hr | Read | |
| AV | 118 | SYS 1 COMP 3 RUN HOURS | Sys 1 Comp 3 Run Hours | Hr | Read | |
| AV | 125 | SYS 2 COMP 1 RUN HOURS | Sys 2 Comp 1 Run Hours | Hr | Read | |
| AV | 126 | SYS 2 COMP 2 RUN HOURS | Sys 2 Comp 2 Run Hours | Hr | Read | |
| AV | 127 | SYS 2 COMP 3 RUN HOURS | Sys 2 Comp 3 Run Hours | Hr | Read |
No points match these filters.
Object ID lookup: York YORK Scroll (SC-EQ) point IDs by name
AV1REMOTE SETPOINT / SYS 1 REM SETPAV2REM LOAD LIMIT STAGEAV3REM COOLING RANGE / REM HEATING SETP / SYS 2 REM SETPAV4REM HEATPUMP MODEBV1REM START STOP CMD / SYS1 REM START STOP CMDBV2SYS2 REM START STOP CMDBV4HISTORY REQUESTAV5LEAVING CHILLED LIQ TEMPAV6ENTERING CHILLED LIQ TEMPAV7LEAVING LIQ TEMP HOTAV8DISCHARGE AIR TEMP / RETURN LIQ TEMP HOTAV9SYS 1 SUCT TEMPAV10OUTSIDE AMBIENT AIR TEMPAV11SYS 1 SUCT SUPERHEATAV12SYS 1 RUN TIMEAV13SYS 1 SUCT PRESSAV14SYS 1 DISCH PRESSAV15SYS 1 SUCT TEMP COND UNIT / SYS 1 COOLER INLET REF TEMPAV16SYS 1 DEFROST TEMPAV17SYS 1 EEV OUTPUT PCTAV18SYS 1 ANTI RECYCLE TIMERAV19ANTI COINCIDENT TIMERAV20SYS 2 SUCT TEMPAV21SYS 2 RUN TIMEAV22SYS 2 SUCT PRESSAV23SYS 2 DISCH PRESSAV24SYS 2 SUCT TEMP COND UNIT / SYS 2 COOLER INLET REF TEMPAV25SYS 2 DEFROST TEMPAV26SYS 2 SUCT SUPERHEATAV27SYS 2 ANTI RECYCLE TIMERAV28SYS 2 EEV OUTPUT PCTAV29NUMBER COMPRESSORSBV5SYS 1 ALARMBV6SYS 2 ALARMBV7EVAPORATOR HEATER STATUSBV8EVAPORATOR PUMP STATUSBV9SYS 1 COMP 1 RUNBV10SYS 2 COMP 1 RUNBV11SYS 1 LIQUID LINE SOL VALVE / SYS 1 MODE SOL VALVEBV12SYS 1 HOT GAS BYPASS VALVEBV13SYS 1 COMP 2 RUNBV14SYS 2 COMP 2 RUNBV15SYS 2 LIQUID LINE SOL VALVE / SYS 2 MODE SOL VALVEBV16LEAD SYSTEM NUMBERBV17SYS 1 COMP 3 RUNBV18SYS 2 COMP 3 RUNBV19COOLING TYPEBV20AMBIENT CONTROL MODEBV21LOCAL REMOTE CONTROL MODEBV22DISPLAY UNITSBV23LEAD LAG CONTROL MODEBV24SYS 2 HOT GAS BYPASS VALVEMV1SYS 1 OPERATIONAL CODEAV501SYS 1 OPERATIONAL CODE AVMV2SYS 1 FAULT CODEAV502SYS 1 FAULT CODE AVMV3SYS 2 OPERATIONAL CODEAV503SYS 2 OPERATIONAL CODE AVMV4SYS 2 FAULT CODEAV504SYS 2 FAULT CODE AVAV406SYS 1 COND FAN STAGES RUNAV408SYS 2 COND FAN STAGES RUNMV10UNIT CONTROL MODEAV505UNIT CONTROL MODE AVAV30ANTI RECYCLE TIME PROGAV31LOW LEAVING CHILL LIQ CUTOUTAV32LOW AMBIENT TEMP CUTOUTAV33LOW SUCT PRESS CUTOUT HEATINGAV34LOW SUCT PRESS CUTOUT COOLINGAV35HIGH DISCH PRESS CUTOUTAV36COOLING SETPOINT / SYS 1 COOLING SETPOINTAV37COOLING RANGE / SYS 1 COOLING RANGEAV38SYS 2 COOLING SETPOINT / HEATING SETPOINTAV39SYS 2 COOLING RANGE / HEATING RANGEAV40SYS 1 DISCH TEMPAV41SYS 1 DISCH SUPERHEATAV42SYS 2 DISCH TEMPAV43SYS 2 DISCH SUPERHEATBV25BIVALENT HT SOURCE TRAY HTAV116SYS 1 COMP 1 RUN HOURSAV117SYS 1 COMP 2 RUN HOURSAV118SYS 1 COMP 3 RUN HOURSAV125SYS 2 COMP 1 RUN HOURSAV126SYS 2 COMP 2 RUN HOURSAV127SYS 2 COMP 3 RUN HOURS
Integration notes
- Access is inferred: the sheet has no read/write column. The remote block (AV 1-4, BV 1, BV 2, BV 4) is treated as commandable; everything else as read-only.
- AV 1, AV 3, AV 8, AV 15, AV 24, AV 36-39, BV 1, BV 11 and BV 15 have two or three printed rows that depend on unit type (condensing unit with suction pressure control, heat pump, YCWL, refrigerant). They are merged into one row each with all names.
- System 2 points only report on two-system units; EEV, heat pump and condensing unit points only on those units.
- Operational and fault code MVs (MV 1-4) are the printed code + 1, as the sheet says to add 1 for BACnet MSV values; the AV copies (AV 501-504) carry the raw code. MV 10 / AV 505 are shown as printed, from 0; the card may report the printed number + 1.
- This list has no MV 65001 Units object. Units shown are the IP units. Spare objects are left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
How many BACnet points does the York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) have?
This list has 85 BACnet objects: 56 analog values, 24 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) BACnet points are writable?
7 of the 85 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ) BACnet documentation?
The source is Scroll SC-EQ BAS Points List, revision Rev 2.4, 2021-01-11, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/47mW1GA_AXbFLIz2QICYeQ/content.
What are the minimum BACnet points to integrate the York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)?
Start with BV 1 REM START STOP CMD / SYS1 REM START STOP CMD (Remote start/stop (1 = run)); AV 1 REMOTE SETPOINT / SYS 1 REM SETP (Remote cooling setpoint (99 = auto)); AV 2 REM LOAD LIMIT STAGE (Remote load limit stage (0, 1, 2)); MV 1 SYS 1 OPERATIONAL CODE (Sys 1 operating state); BV 9 SYS 1 COMP 1 RUN (Sys 1 compressor 1 running); BV 21 LOCAL REMOTE CONTROL MODE (Must read Remote (1) for BMS control); AV 5 LEAVING CHILLED LIQ TEMP (Leaving chilled liquid temperature); BV 5 SYS 1 ALARM (System 1 alarm); BV 6 SYS 2 ALARM (System 2 alarm); MV 2 SYS 1 FAULT CODE (Sys 1 fault/inhibit code (1 = no fault)).
How do I enable BMS control of the York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)?
BV 21 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. AV 4 selects panel, cool or heat on heat pump units.
How do I check these points on the real Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: Scroll SC-EQ BAS Points List · rev. Rev 2.4, 2021-01-11. Object names, instances and units are reproduced as published; descriptions are our own.