Air-cooled variable-speed screw chiller (via SC-EQ card) · BACnet points list

York YVAA / YVFA / YAGK Chiller (SC-EQ) BACnet points list

Updated 4 November 2026

Short answer

YVAA, YVFA and YAGK chillers connect to a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the chiller, write the cooling setpoint, current limit and sound limit, and inhibit the free cooling valve. Read-only points cover chilled liquid and ambient temperatures, per-system pressures, temperatures, % FLA, kW and lockouts, VSD values, condenser fan data, free cooling (YVFA) values, and multistate operational, fault and warning codes per system. This is the standard list; separate lists exist for the YT3 panel and the YVAA Style B.

This page lists 109 BACnet objects for the York YVAA / YVFA / YAGK Chiller (SC-EQ) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YVAA / YVFA / YAGK Chiller (SC-EQ)
Equipment
Air-cooled variable-speed screw chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
109 (8 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ software 4.8.0.25
Default device instance
5000 + MAC address
Also known as
YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1
Source document
YVAA / YVFA / YAGK SC-EQ BAS Points List · rev. Rev 2.16, 2023-01-03
Download CSV 109 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YVAA / YVFA / YAGK Chiller (SC-EQ)

Integration in brief

Put the chiller in remote control (BV 20 reads Remote), then start/stop it with BV 1 and write the cooling setpoint (AV 1) and current limit (AV 2). Read BV 5 for chiller run, the leaving chilled liquid temperature and VSD frequency, BV 6 for the chiller alarm and the per-system fault codes for the cause.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM START STOP CMDRemote start/stop (1 = run)Command
AV 1REMOTE SETPOINTRemote leaving chilled liquid setpointCommand
AV 2REM CURRENT LIMIT SETPRemote current limit, %Command
BV 5CHILLER RUNChiller runningRead
BV 20LOCAL REMOTE CONTROL MODEMust read Remote (1) for BMS controlRead
AV 5LEAVING CHILLED LIQ TEMPLeaving chilled liquid temperatureRead
AV 27VSD OUTPUT FREQUENCYCompressor VSD frequency (load indication)Read
BV 6CHILLER ALARMChiller alarm activeRead
MV 2SYS 1 FAULT CODESys 1 fault/inhibit code (1 = none)Read
MV 4SYS 2 FAULT CODESys 2 fault/inhibit code (1 = none)Read

Enable & remote start

BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point.

Heartbeat & communication loss

The operational code list includes 'Loss of External Communications'; the sheet gives no timeout or heartbeat point.

Network setup

Watch out for

York YVAA / YVFA / YAGK Chiller (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

109 of 109 shown
Type
AnalogBinaryMulti-state
Access
Show
York YVAA / YVFA / YAGK Chiller (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REMOTE SETPOINTRemote Setpoint°FCommand
AVmin2REM CURRENT LIMIT SETPRemote Current Limit Setpoint%Command
AV3REMOTE SOUND LIMITRemote Sound Limit%Command
BVmin1REM START STOP CMDRemote Start / Stop CommandCommand0=Stop, 1=Run
BV2REM FC VALVE OPEN INHIBITRemote free cooling valve open inhibitCommand0=Disabled, 1=Enabled
BV3REM FC VALVE CLOSE INHIBITRemote free cooling valve close inhibitCommand0=Disabled, 1=Enabled
BV4HISTORY REQUESTHistory buffer 1 request (live / history data)Command0=Live Data, 1=History 1 Data
MV65001UnitsUnit system reported by the SC-EQWrite0=IP (English), 1=SI (Metric)
AVmin5LEAVING CHILLED LIQ TEMPLeaving Chilled Liquid Temp°FRead
AV6ENTERING CHILLED LIQ TEMPEntering Chilled Liquid Temp°FRead
AV7VSD INT AMBIENT TEMPVSD Internal Ambient Temp°FRead
AV8SYS 1 COND TEMPSys 1 Condenser Temperature°FRead
AV9SYS 1 DISCH TEMPSys 1 Discharge Temperature°FRead
AV10OUTSIDE AMBIENT AIR TEMPOutside Ambient Air Temperature°FRead
AV11SYS 1 EDUCTOR TEMPSys 1 Eductor Temperature°FRead
AV12SYS 1 OIL PRESSSys 1 Oil PressurePSIGRead
AV13SYS 1 SUCT PRESSSys 1 Suction PressurePSIGRead
AV14SYS 1 DISCH PRESSSys 1 Discharge PressurePSIGRead
AV15SYS 1 COMP PCT FLASys 1 Compressor % Full Load Amps%Read
AV16SYS 1 HOURSSys 1 Total Run HoursHrRead
AV17SYS 1 STARTSSys 1 Total Number of StartsRead
AV18SYS 1 HIGHEST MOTOR TEMPSys 1 Highest Motor Temp°FRead
AV19SYS 2 HIGHEST MOTOR TEMPSys 2 Highest Motor Temp°FRead
AV20SYS 2 EDUCTOR TEMPSys 2 Eductor Temperature°FRead
AV21SYS 2 OIL PRESSSys 2 Oil PressurePSIGRead
AV22SYS 2 SUCT PRESSSys 2 Suction PressurePSIGRead
AV23SYS 2 DISCH PRESSSys 2 Discharge PressurePSIGRead
AV24SYS 2 COMP PCT FLASys 2 Compressor % Full Load Amps%Read
AV25SYS 2 HOURSSys 2 Total Run HoursHrRead
AV26SYS 2 STARTSSys 2 Total Number of StartsRead
AVmin27VSD OUTPUT FREQUENCYVSD Output FrequencyHzRead
AV28SYS 1 COND DRAIN VALVE PCTSys 1 Condenser Drain Valve % Open%Read
AV29SYS 2 COND DRAIN VALVE PCTSys 2 Condenser Drain Valve % Open%Read
BVmin5CHILLER RUNChiller RunRead0=Off, 1=On
BVmin6CHILLER ALARMChiller AlarmRead0=No Alarm, 1=Alarm Active
BV7EVAPORATOR HEATER STATUSEvaporator Heater StatusRead0=Off, 1=On
BV8EVAPORATOR PUMP STATUSEvaporator Pump StatusRead0=Off, 1=On
BV9SYS 1 COMP RUN STATUSSys 1 Compressor Run StatusRead0=Off, 1=On
BV10SYS 2 COMP RUN STATUSSys 2 Compressor Run StatusRead0=Off, 1=On
BV11SYS 1 VI STEP SOL VALVE 1 STATUSSys 1 VI Step Solenoid Valve 1 StatusRead0=Off, 1=On
BV12SYS 2 VI STEP SOL VALVE 1 STATUSSys 2 VI Step Solenoid Valve 1 StatusRead0=Off, 1=On
BV13SYS 1 VI STEP SOL VALVE 2 STATUSSys 1 VI Step Solenoid Valve 2 StatusRead0=Off, 1=On
BV14SYS 2 VI STEP SOL VALVE 2 STATUSSys 2 VI Step Solenoid Valve 2 StatusRead0=Off, 1=On
BV17EVAP ANTI-FREEZE FLOW SWITCHEvap anti-freeze flow switchRead0=Off, 1=On
BV18EVAP ANTI-FREEZE PUMP RUNEvap anti-freeze pump runRead0=Off, 1=On
BV19COOLING TYPECooling TypeRead0=Water, 1=Glycol
BVmin20LOCAL REMOTE CONTROL MODELocal Remote Control ModeRead0=Local, 1=Remote
BV21DISPLAY UNITSDisplay UnitsRead0=Imperial, 1=SI
BV22READY TO STARTReady To StartRead0=Off, 1=On
MV1SYS 1 OPERATIONAL CODESys 1 Operational CodeRead64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 68=Loss of External Communications, 69=Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Serial Number Shutdown, 73=Discharge Superheat Recovery, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Suction Pressure Limiting, 82=Motor Current Limiting, 83=Free Cooling, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Pumping Down, 87=VSD PreCharging, 88=VSD Baseplate Temp Limiting, 89=VSD Internal Ambient Temp Limiting, 90=Sound Limiting, 91=BAS Sound Limiting, 92=Remote Sound Limiting, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown, 95=Input Current Limiting, 96=BAS (ISN) Input Current Limiting, 97=Remote Input Current Limiting, 98=Pulldown Input Current Limiting
MVmin2SYS 1 FAULT CODESys 1 Fault CodeRead1=No Faults/Inhbits Present, 2=Low Ambient Temperature, 3=High Ambient Temperature, 4=Low Chilled Liquid Temperature, 5=VSD Initialization Failure, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload (Hardware), 19=CT Plug Fault, 20=High Harmonic Filter Temperature, 21=Evap Anti-Freeze Pump Fault, 22=Low Heat Exchanger Temperature, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Suction Pressure, 32=High Discharge Temperature, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Low Suction Superheat, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Suction Pressure Smart Freeze, 54=Isolation Valve Failed to Close Warning, 55=Isolation Valve Failed to Open Fault, 56=High Discharge Pressure Rate, 57=Condenser Fan VSD Fault Warning
MV3SYS 2 OPERATIONAL CODESys 2 Operational CodeRead64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 68=Loss of External Communications, 69=Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Serial Number Shutdown, 73=Discharge Superheat Recovery, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Suction Pressure Limiting, 82=Motor Current Limiting, 83=Free Cooling, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Pumping Down, 87=VSD PreCharging, 88=VSD Baseplate Temp Limiting, 89=VSD Internal Ambient Temp Limiting, 90=Sound Limiting, 91=BAS Sound Limiting, 92=Remote Sound Limiting, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown, 95=Input Current Limiting, 96=BAS (ISN) Input Current Limiting, 97=Remote Input Current Limiting, 98=Pulldown Input Current Limiting
MVmin4SYS 2 FAULT CODESys 2 Fault CodeRead1=No Faults/Inhbits Present, 2=Low Ambient Temperature, 3=High Ambient Temperature, 4=Low Chilled Liquid Temperature, 5=VSD Initialization Failure, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload (Hardware), 19=CT Plug Fault, 20=High Harmonic Filter Temperature, 21=Evap Anti-Freeze Pump Fault, 22=Low Heat Exchanger Temperature, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Suction Pressure, 32=High Discharge Temperature, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Low Suction Superheat, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Suction Pressure Smart Freeze, 54=Isolation Valve Failed to Close Warning, 55=Isolation Valve Failed to Open Fault, 56=High Discharge Pressure Rate, 57=Condenser Fan VSD Fault Warning
AV405SYS 1 COND FAN STAGES RUNSys 1 condenser fan stage, 0-14 (staged fans)Read
AV406SYS 1 COND FAN SPEED PCTSys 1 condenser fan speed (VSD fans)%Read
AV407SYS 2 COND FAN STAGES RUNSys 2 condenser fan stage, 0-14 (staged fans)Read
AV408SYS 2 COND FAN SPEED PCTSys 2 condenser fan speed (VSD fans)%Read
AV409LEAD SYSTEM NUMBERLead System NumberRead
AV30LOCAL LEAVING CHILL LIQ SETPLocal Leaving Chilled Liquid Setpoint°FRead
AV31LOW LEAVING CHILL LIQ CUTOUTLow Leaving Chilled Liquid Temp Cutout°FRead
AV32SYS 1 ECON VALVE PCTSys 1 Economizer Valve % Open%Read
AV33SYS 2 ECON VALVE PCTSys 2 Economizer Valve % Open%Read
AV34LOW SUCT PRESS CUTOUTLow Suction Pressure CutoutPSIGRead
AV35VSD DC BUS VOLTVSD DC Bus VoltageVoltsRead
AV36REM LEAVING CHILL LIQ SETPRemote Leaving Chilled Liquid Setpoint°FRead
AV37SYS 1 SUBCOOLING / SYS 1 EVAPORATOR LEVELSys 1 subcooling (microchannel) or evaporator level (round tube)°F (diff) / %Read
AV38COOLING RANGECooling Range°F (diff)Read
AV39SYS 1 DISCH SUPERHEATSys 1 Discharge Superheat°F (diff)Read
AV40SYS 2 COND TEMPSys 2 Condenser Temperature°FRead
AV41SYS 2 DISCH TEMPSys 2 Discharge Temperature°FRead
AV42SYS 2 SUBCOOLING / SYS 2 EVAPORATOR LEVELSys 2 subcooling (microchannel) or evaporator level (round tube)°F (diff) / %Read
AV43SYS 2 DISCH SUPERHEATSys 2 Discharge Superheat°F (diff)Read
BV25SYS 1 LOCKOUTSys 1 LockoutRead0=Off, 1=On
BV26SYS 2 LOCKOUTSys 2 LockoutRead0=Off, 1=On
BV27FLOW SWITCH STATUSFlow Switch StatusRead0=Off, 1=On
AV48EVAP ENTER LIQ TEMPEvaporator Entering Liquid Temp (If Free Cooling Enabled)°FRead
AV49COOLING COIL TEMPCooling Coil Temperature°FRead
AV50HEAT EXCH LEAVE TEMPHeat Exchanger Leaving Temperature°FRead
AV51HEAT EXCH ENTER TEMPHeat Exchanger Entering Temperature°FRead
AV52GLY PMP SPDGlycol Pump Speed%Read
AV53COOLING COIL VALVECooling Coil Valve%Read
AV54COOLING COIL BYP VALVECooling Coil Bypass Valve%Read
AV63SYS 1 XL COND FAN SPD CMDSys 1 XL condenser fan speed command (Opt. Enh XL fans)%Read
AV64SYS 2 XL COND FAN SPD CMDSys 2 XL condenser fan speed command (Opt. Enh XL fans)%Read
AV70VSD COMMAND FREQUENCYVSD Command FrequencyHzRead
BV35FREE COOLING VALVEFree Cooling Valve (If Free Cooling Enabled)Read0=Off, 1=On
BV36SOFT SHUTDOWNSoft ShutdownRead0=Disabled, 1=Enabled
BV37REMOTE EVAPORATORRemote EvaporatorRead0=Disabled, 1=Enabled
BV38QUICK STARTQuick StartRead0=Disabled, 1=Enabled
BV40GLYCOL PUMP RUNGlycol Pump Run:Read0=Off, 1=On
BV41GLYCOL HEATERGlycol Heater:Read0=Off, 1=On
BV44SYS 1 COND FAN VSD FLTSys 1 condenser fan VSD fault (VSD fan control types)Read0=Off, 1=On
BV45SYS 2 COND FAN VSD FLTSys 2 condenser fan VSD fault (VSD fan control types)Read0=Off, 1=On
MV12FREE COOLING MODEFree Cooling Mode (If Free Cooling Enabled)Read0=Mechanical, 1=Free Cooling, 2=Hybrid
MV13SYS 1 SYSTEM STATESys 1 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
MV14SYS 2 SYSTEM STATESys 2 System StateRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AV415SYS 1 SYSTEM STATE AVSys 1 System State AVRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AV416SYS 2 SYSTEM STATE AVSys 2 System State AVRead0=Stopped, 1=Running, 2=Faulted, 4=Locked Out, 5=Pre-Run
AV417SYS 1 WARNING CODESys 1 Warning CodeRead0=No Faults/Inhbits Present, 1=Quarterly Service Required – Contact JCI, 2=Yearly Service Required – Contact JCI, 3=3 Year Service Required – Contact JCI, 4=5 Year Service Required – Contact JCI, 5=Replace Oil filter, 6=Free Cooling Valve Opening Inhibited, 7=Free Cooling Valve Closing Inhibited
AV418SYS 2 WARNING CODESys 2 Warning CodeRead0=No Faults/Inhbits Present, 1=Quarterly Service Required – Contact JCI, 2=Yearly Service Required – Contact JCI, 3=3 Year Service Required – Contact JCI, 4=5 Year Service Required – Contact JCI, 5=Replace Oil filter, 6=Free Cooling Valve Opening Inhibited, 7=Free Cooling Valve Closing Inhibited
AV74SYS 1 FAN KWSys 1 Fan KwkWRead
AV75SYS 1 COMPRESSOR KWSys 1 Compressor KwkWRead
AV76SYS 2 FAN KWSys 2 Fan KwkWRead
AV77SYS 2 COMPRESSOR KWSys 2 Compressor KwkWRead
AV501SYS 1 OPERATIONAL CODE AVSys 1 Operational Code AVRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 72=Discharge Superheat Recovery, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 82=Free Cooling, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Pumping Down, 86=VSD PreCharging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=BAS Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=Input Current Limiting, 95=BAS (ISN) Input Current Limiting, 96=Remote Input Current Limiting, 97=Pulldown Input Current Limiting
AV502SYS 1 FAULT CODE AVSys 1 Fault Code AVRead0=No Faults/Inhbits Present, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 4=VSD Initialization Failure, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 19=High Harmonic Filter Temperature, 20=Evap Anti-Freeze Pump Fault, 21=Low Heat Exchanger Temperature, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Low Suction Superheat, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Suction Pressure Smart Freeze, 53=Isolation Valve Failed to Close Warning, 54=Isolation Valve Failed to Open Fault, 55=High Discharge Pressure Rate, 56=Condenser Fan VSD Fault Warning
AV503SYS 2 OPERATIONAL CODE AVSys 2 Operational Code AVRead63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 67=Loss of External Communications, 68=Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Serial Number Shutdown, 72=Discharge Superheat Recovery, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Suction Pressure Limiting, 81=Motor Current Limiting, 82=Free Cooling, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Pumping Down, 86=VSD PreCharging, 87=VSD Baseplate Temp Limiting, 88=VSD Internal Ambient Temp Limiting, 89=Sound Limiting, 90=BAS Sound Limiting, 91=Remote Sound Limiting, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown, 94=Input Current Limiting, 95=BAS (ISN) Input Current Limiting, 96=Remote Input Current Limiting, 97=Pulldown Input Current Limiting
AV504SYS 2 FAULT CODE AVSys 2 Fault Code AVRead0=No Faults/Inhbits Present, 1=Low Ambient Temperature, 2=High Ambient Temperature, 3=Low Chilled Liquid Temperature, 4=VSD Initialization Failure, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload (Hardware), 18=CT Plug Fault, 19=High Harmonic Filter Temperature, 20=Evap Anti-Freeze Pump Fault, 21=Low Heat Exchanger Temperature, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Suction Pressure, 31=High Discharge Temperature, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Low Suction Superheat, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Suction Pressure Smart Freeze, 53=Isolation Valve Failed to Close Warning, 54=Isolation Valve Failed to Open Fault, 55=High Discharge Pressure Rate, 56=Condenser Fan VSD Fault Warning
AV450FREE COOLING MODE AVFree Cooling Mode AV (If Free Cooling Enabled)Read0=Mechanical, 1=Free Cooling, 2=Hybrid
Object ID lookup: York YVAA / YVFA / YAGK point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YVAA / YVFA / YAGK Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YVAA / YVFA / YAGK Chiller (SC-EQ)

How many BACnet points does the York YVAA / YVFA / YAGK Chiller (SC-EQ) have?

This list has 109 BACnet objects: 70 analog values, 31 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YVAA / YVFA / YAGK Chiller (SC-EQ) BACnet points are writable?

8 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YVAA / YVFA / YAGK Chiller (SC-EQ) BACnet documentation?

The source is YVAA / YVFA / YAGK SC-EQ BAS Points List, revision Rev 2.16, 2023-01-03, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/v3G3YemU0Ic3bTVhJD0MOw/content.

What are the minimum BACnet points to integrate the York YVAA / YVFA / YAGK Chiller (SC-EQ)?

Start with BV 1 REM START STOP CMD (Remote start/stop (1 = run)); AV 1 REMOTE SETPOINT (Remote leaving chilled liquid setpoint); AV 2 REM CURRENT LIMIT SETP (Remote current limit, %); BV 5 CHILLER RUN (Chiller running); BV 20 LOCAL REMOTE CONTROL MODE (Must read Remote (1) for BMS control); AV 5 LEAVING CHILLED LIQ TEMP (Leaving chilled liquid temperature); AV 27 VSD OUTPUT FREQUENCY (Compressor VSD frequency (load indication)); BV 6 CHILLER ALARM (Chiller alarm active); MV 2 SYS 1 FAULT CODE (Sys 1 fault/inhibit code (1 = none)); MV 4 SYS 2 FAULT CODE (Sys 2 fault/inhibit code (1 = none)).

How do I enable BMS control of the York YVAA / YVFA / YAGK Chiller (SC-EQ)?

BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point.

Does the York YVAA / YVFA / YAGK Chiller (SC-EQ) need a BACnet heartbeat or have a communication timeout?

The operational code list includes 'Loss of External Communications'; the sheet gives no timeout or heartbeat point.

How do I check these points on the real YVAA / YVFA / YAGK Chiller (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YVAA / YVFA / YAGK SC-EQ BAS Points List · rev. Rev 2.16, 2023-01-03. Object names, instances and units are reproduced as published; descriptions are our own.