Water-cooled screw chiller (via SC-EQ card) · BACnet points list
York YR Screw Chiller (OptiView, SC-EQ) BACnet points list
Updated 4 November 2026
YR screw chillers with OptiView controls reach a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can run/stop the chiller and write the leaving chilled liquid setpoint and motor current limit. Read-only points cover water temperatures, refrigerant and oil pressures, slide valve position, solid-state starter values, and multistate operation, safety, cycling and warning codes.
This page lists 43 BACnet objects for the York YR Screw Chiller (OptiView, SC-EQ) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- YR Screw Chiller (OptiView, SC-EQ)
- Equipment
- Water-cooled screw chiller (via SC-EQ card)
- Equipment type
- Chillers
- BACnet objects
- 43 (4 writable)
- Transport
- BACnet MS/TP
- Firmware
- SC-EQ software 4.3.0.x
- Default device instance
- 5000 + MAC address
- Also known as
- YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York YR Screw Chiller (OptiView, SC-EQ)
Wire the BAS to the SC-EQ J12 RS-485 port and set the MAC address; the card detects BACnet MS/TP. Run/stop the chiller with BV 1 and write the leaving chilled liquid setpoint (AV 1) and motor current limit (AV 2). Read MV 1, BV 5, the leaving water temperature and % FLA, and MV 2/MV 3 for shutdowns.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | REM RUN STOP CMD | Remote run/stop (1 = run) | Command |
| AV 1 | REM LEAVING CHL TEMP SP | Remote leaving chilled liquid setpoint | Command |
| AV 2 | MOTOR CURRENT REMOTE SP | Remote motor current limit, % | Command |
| MV 1 | UNIT OPERATION CODE | Operating state (stopped, starting, running) | Read |
| BV 5 | COMPR MOTOR STATUS | Compressor motor running | Read |
| MV 5 | UNIT CONTROL SOURCE | Control source; ISN (BAS) for BMS control | Read |
| AV 5 | LEAVING CH LIQ TEMP | Leaving chilled liquid temperature | Read |
| AV 12 | MOTOR CURRENT PCT FLA | Motor current, % FLA (load indication) | Read |
| MV 2 | UNIT SAFETY FAULT CODE | Safety shutdown code (1 = none) | Read |
| MV 3 | UNIT CYCLING FAULT CODE | Cycling shutdown code (1 = none) | Read |
Enable & remote start
BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-2 the remote setpoints. MV 5 shows the control source (Local, ISN, Analog, Digital, Modem); it should read ISN for BAS control. The points list has no write-enable point.
Network setup
- The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.
- The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.
- The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID).
- MV 65001 Units sets whether the BAS sees IP or SI values, independent of the chiller display; set it to match the chiller.
Watch out for
- The remote (commandable) setpoints read as unreliable until the BAS writes them the first time.
- The SC-EQ only exposes the points that apply to the chiller it detects; if it replaces an E-Link, re-discover the device so old non-applicable points don't sit offline.
York YR Screw Chiller (OptiView, SC-EQ) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REM LEAVING CHL TEMP SP | Remote Leaving Chilled Liquid Setpoint | °F | Command | |
| AVmin | 2 | MOTOR CURRENT REMOTE SP | Motor Current Limit Setpoint | % | Command | |
| BVmin | 1 | REM RUN STOP CMD | Remote Run/Stop | Command | 0=Stop, 1=Run | |
| MV | 65001 | Units | Unit system reported by the SC-EQ | Write | 0=IP (English), 1=SI (Metric) | |
| AVmin | 5 | LEAVING CH LIQ TEMP | Leaving Chilled Liquid Temperature | °F | Read | |
| AV | 6 | ENTERING CH LIQ TEMP | Return Chilled Liquid Temperature | °F | Read | |
| AV | 7 | EVAPORATOR PRESSURE | Evaporator Pressure | PSIG | Read | |
| AV | 8 | CONDENSER PRESSURE | Condenser Pressure | PSIG | Read | |
| AV | 9 | OIL PRESSURE DIFERENTIAL | Oil Pressure Differential | PSIG | Read | |
| AV | 10 | ENTERING COND WATER TEMP | Return Condenser Liquid Temperature | °F | Read | |
| AV | 11 | LEAVING COND WATER TEMP | Leaving Condenser Liquid Temperature | °F | Read | |
| AVmin | 12 | MOTOR CURRENT PCT FLA | Motor Current Percent FLA | % | Read | |
| AV | 13 | PHASE A MOTOR CURRENT | SSS Phase A Current (SSS only) | Amps | Read | |
| AV | 14 | PHASE B MOTOR CURRENT | SSS Phase B Current (SSS only) | Amps | Read | |
| AV | 15 | PHASE C MOTOR CURRENT | SSS Phase C Current (SSS only) | Amps | Read | |
| AV | 16 | PHASE A_B LINE VOLTS | SSS Phase A Voltage (SSS only) | Volts | Read | |
| AV | 17 | PHASE B_C LINE VOLTS | SSS Phase B Voltage (SSS only) | Volts | Read | |
| AV | 18 | PHASE C_A LINE VOLTS | SSS Phase C Voltage (SSS only) | Volts | Read | |
| AV | 19 | LEAVING CHW TEMP ACT SP | Leaving Chilled Liquid Setpoint - Selected | °F | Read | |
| AV | 20 | MOTOR CURRENT ACTUAL SP | Motor Current Limit Setpoint - Selected | % | Read | |
| AV | 21 | EVAP SATURATION TEMP | Evaporator Saturation Temperature | °F | Read | |
| AV | 22 | COND SATURATION TEMP | Condenser Saturation Temperature | °F | Read | |
| AV | 23 | DISCHARGE TEMP | Discharge Temperature | °F | Read | |
| AV | 25 | COND REFRIGERANT LEVEL | Condenser refrigerant level (doc: really refrigerant level position) | % | Read | |
| AV | 26 | ACCUM OPERATING HOURS | Unit Operating Hours | Hr | Read | |
| AV | 27 | ACCUM SYSTEM STARTS | Unit System Starts | Read | ||
| BVmin | 5 | COMPR MOTOR STATUS | Motor Run Contacts | Read | 0=Off, 1=On | |
| BV | 6 | OIL RETURN SOLENOID | Oil Return Solenoid | Read | 0=Off, 1=On | |
| BV | 7 | CHW PUMP STAT | Chilled Liquid Pump | Read | 0=Off, 1=On | |
| BV | 8 | STOP SWITCH STATUS | Panel stop switch (start enabled / stop) | Read | 0=Off, 1=On | |
| BV | 9 | CHW FLOW SWITCH STAT | Chiller Liquid Flow Switch | Read | 0=Off, 1=On | |
| BV | 11 | LOW SEPARATOR OIL SWITCH | Low Separator Oil Switch | Read | 0=Off, 1=On | |
| BV | 24 | ICE STORAGE MODE | Ice Storage Mode | Read | 0=Disabled, 1=Enabled | |
| MVmin | 1 | UNIT OPERATION CODE | Operation Code | Read | 1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Chiller Unload Before Shutdown, 12=Unit Lockout Delay, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown | |
| MVmin | 2 | UNIT SAFETY FAULT CODE | Unit Safety Fault Code | Read | 1=No Abnormal Condition, 2=Evaporator - Low Pressure, 3=Evaporator - Transducer Or Leaving Liquid Probe, 4=Evaporator - Temperature Transducer, 5=Condenser - High Pressure Contacts Open, 6=Condenser - High Pressure, 7=Condenser - Pressure Transducer Out Of Range, 8=Auxiliary Safety - Contacts Closed, 9=Discharge - Low Temperature, 10=Discharge - High Temperature, 11=Oil - High Temperature, 12=Oil - Low Differential Pressure, 16=Oil- High Pressure, 17=Oil- Filter Clogged, 22=Control Panel - Power Failure, 24=Motor Or Starter - Current Imbalance, 25=Thrust Bearing - Proximity Probe Clearance, 26=Thrust Bearing - Proximity Probe Uncalibrated, 27=Thrust Bearing - Proximity Probe Out Of Range, 28=High Oil Temperature, 29=Oil Temperature Probe - Out of Range, 30=VSD - High Heatsink Temperature, 31=VSD - 105% Motor Current Overload, 32=VSD - High Phase A Inverter Heatsink Temperature, 33=VSD - High Phase B Inverter Heatsink Temperature, 34=VSD - High Phase C Inverter Heatsink Temperature, 35=VSD - High Converter Heatsink Temperature, 36=VSD - Precharge Lockout, 37=Harmonic Filter - High Heatsink Temperature, 38=Harmonic Filter - High Total Demand Distortion, 39=LCSSS - Phase Rotation, 40=LCSSS - Motor Or Starter - Current Imbalance, 41=LCSSS - 105% Motor Current Overload, 42=LCSSS - High Instantaneous Current, 43=LCSSS - Open SCR, 44=LCSSS - Shorted Phase A SCR, 45=LCSSS - Shorted Phase B SCR, 46=LCSSS - Shorted Phase C SCR, 47=LCSSS - High Phase A Heatsink Temperature - Running, 48=LCSSS - High Phase B Heatsink Temperature - Running, 49=LCSSS - High Phase C Heatsink Temperature - Running, 50=Starter - Invalid Motor Selection, 51=Oil Or Condenser Transducer Error, 52=Evaporator - Low Pressure, 53=Evaporator - Low Pressure - Smart Freeze, 54=Surge Protection - Excess Surge, 55=VSD - High Inverter Baseplate Temperature, 56=Harmonic Filter - High Baseplate Temperature, 57=Thrust Bearing - Proximity Probe Clearance, 58=Thrust Bearing - Limit Switch Open, 59=Motor - Phase Rotation, 60=Motor - High Temperature, 61=Discharge - High Pressure, 62=High Motor Winding Temperature, 63=High Motor Bearing Temperature, 64=VSD - High Phase A Baseplate Temperature, 65=VSD - High Phase B Baseplate Temperature, 66=VSD - High Phase C Baseplate Temperature, 67=VSD - Current Imbalance, 68=Condenser high Pressure Stopped, 69=Motor - Ground Fault, 70=Excessive Bearing Vibration, 71=Low Discharge Superheat, 72=LCSSS - Phase A Open SCR, 73=LCSSS - Phase B Open SCR, 74=LCSSS - Phase C Open SCR, 75=Motor Lube Not Done, 76=VSD - Low Frequency | |
| MVmin | 3 | UNIT CYCLING FAULT CODE | Unit Cycling Fault Code | Read | 1=No Abnormal Condition, 2=Multi-Unit Cycling - Contacts Open, 3=System Cycling - Contacts Open, 5=Oil - Low Temperature, 6=Control Panel - Power Failure, 7=Leaving Chilled Liquid - Low Temperature, 8=Leaving Chilled Liquid - Flow Switch Open, 9=Condenser - Flow Switch Open, 10=Motor Controller - Contacts Open, 11=Motor Controller - Loss Of Current, 12=Power Fault, 13=Control Panel - Schedule, 14=Starter - Low Supply Line Voltage, 15=Starter - High Supply Line Voltage, 16=Proximity Probe - Low Supply Voltage, 17=Oil - Variable Speed Pump - Drive Contacts Open, 18=VSD Initialization Failed, 19=VSD Shutdown - Requesting Fault Data…, 20=VSD - High Phase A Instananeous Current, 21=VSD - High Phase B Instananeous Current, 22=VSD - High Phase C Instananeous Current, 23=VSD - Phase A Gate Driver, 24=VSD - Phase B Gate Driver, 25=VSD - Phase C Gate Driver, 26=VSD - Single Phase Input Power, 27=VSD - High DC Bus Voltage, 28=VSD - Logic Board Power Supply, 29=VSD - Low DC Bus Voltage, 30=VSD - DC Bus Voltage Imbalance, 31=VSD - High Internal Ambient Temperature, 32=VSD - Invalid Current Scale Selection, 33=VSD - Low Phase A Inverter Heatsink Temperature, 34=VSD - Low Phase B Inverter Heatsink Temperature, 35=VSD - Low Phase C Inverter Heatsink Temperature, 36=VSD - Low Converter Heatsink Temperature, 37=VSD - Precharge - DC Bus Voltage Imbalance, 38=VSD - Precharge - Low DC Bus Voltage, 39=VSD - Logic Board Processor, 40=VSD - Run Signal, 41=VSD - Serial Communications, 42=VSD - Stop Contacts Open, 43=Harmonic Filter - Logic Board Or Communications, 44=Harmonic Filter - High DC Bus Voltage, 45=Harmonic Filter - High Phase A Current, 46=Harmonic Filter - High Phase B Current, 47=Harmonic Filter - High Phase C Current, 48=Harmonic Filter - Phase Locked Loop, 49=Harmonic Filter - Precharge - Low DC Bus Voltage, 50=Harmonic Filter - Low DC Bus Voltage, 51=Harmonic Filter - DC Bus Voltage Imbalance, 52=Harmonic Filter - 110% Input Current Overload, 53=Harmonic Filter - Logic Board Power Supply, 54=Harmonic Filter - Run Signal, 55=Harmonic Filter - DC Current Transformer 1, 56=Harmonic Filter - DC Current Transformer 2, 57=LCSSS Initialization Failed, 58=LCSSS Shutdown - Requesting Fault Data…, 59=LCSSS - Low Phase A Temperature Sensor, 60=LCSSS - Low Phase B Temperature Sensor, 61=LCSSS - Low Phase C Temperature Sensor, 62=LCSSS - Phase Locked Loop, 63=LCSSS - Power Fault, 64=LCSSS - High Supply Line Voltage, 65=LCSSS - Low Supply Line Voltage, 66=LCSSS - Invalid Current Scale Selection, 67=LCSSS - Run Signal, 68=LCSSS - Serial Communications, 69=LCSSS - Stop Contacts Open, 70=LCSSS - Invalid FLA, 71=LCSSS - Logic Board Processor, 72=LCSSS - DSP Communication Failure, 73=LCSSS - Logic Board Power Supply, 74=VSD - Serial Communications, 75=LCSSS - Serial Communications, 76=LCSSS - Phase Loss, 77=VSD - Low Inverter Baseplate Temperature, 78=Motor High Winding Temperature, 79=VSD - Low Phase A Baseplate Temperature, 80=VSD - Low Phase B Baseplate Temperature, 81=VSD - Low Phase C Baseplate Temperature, 82=SSS Shutdown - Requesting Fault Data… | |
| MV | 4 | UNIT WARNING FAULT CODE | Unit Warning Fault Code | Read | 1=No Abnormal Condition, 2=Real-Time Clock Failure, 3=Setpoint Override, 4=Condenser Or Evaporator Transducer Error, 5=Evaporator - Low Pressure Limit, 6=Condenser - High Pressure Limit, 7=Condenser Transducer Error, 8=Freeze Threat From Operating Chiller, 9=Refrigerant Level Out Of Range, 10=Standby Lube - Low Oil Pressure, 11=Purge - High Pressure, 12=Purge - Float Switch Error, 13=Purge - Excess Purge, 14=Oil - High Temperature, 15=Oil - Low Pressure Limit, 16=Vanes Uncalibrated, 17=Vanes Uncalibrated - Fixed Speed, 18=Harmonic Filter - Operation Inhibited, 19=Harmonic Filter - Data Loss, 21=Oil - Dirty Filter, 22=Discharge - High Pressure Limit, 24=Low Discharge Superheat Limit, 25=Low Discharge Superheat Detected, 26=Seal Lubrication In Process, 27=External I/O - Serial Communications, 28=Slide Valve Uncalibrated, 29=Freeze Threat - Condenser Flow Switch, 30=Surge Protection - Excess Surge Limit, 31=Excess Surge Detected, 32=Purge - Canister #1 Full, 33=Oil Recovery Limit, 34=KW Meter Not Calibrated, 35=VGD or Condenser Sensor, 36=VGD - Extreme Stall, 37=Motor Lube Suggested, 38=Motor Lube Required | |
| MVmin | 5 | UNIT CONTROL SOURCE | Unit Control Source | Read | 0=Local, 1=ISN, 2=Analog, 3=Digital, 4=Modem | |
| AV | 35 | ANTI RECYCLE TIME REMAIN | Anti-Recycle Time Remaining | Min | Read | |
| AV | 37 | SEAL PRESS DIFFERENTIAL | Seal Pressure Differential | PSID | Read | |
| AV | 38 | FILTER DIFF PRESSURE | Filter Pressure Differential | PSID | Read | |
| AV | 41 | MIN LOAD CTL MTR FLA LIM | Minimum Load Control Motor FLA Limit | % | Read | |
| AV | 42 | SLIDE VALVE POSITION | Slide Valve Position | % | Read |
No points match these filters.
Object ID lookup: York YR point IDs by name
AV1REM LEAVING CHL TEMP SPAV2MOTOR CURRENT REMOTE SPBV1REM RUN STOP CMDMV65001UnitsAV5LEAVING CH LIQ TEMPAV6ENTERING CH LIQ TEMPAV7EVAPORATOR PRESSUREAV8CONDENSER PRESSUREAV9OIL PRESSURE DIFERENTIALAV10ENTERING COND WATER TEMPAV11LEAVING COND WATER TEMPAV12MOTOR CURRENT PCT FLAAV13PHASE A MOTOR CURRENTAV14PHASE B MOTOR CURRENTAV15PHASE C MOTOR CURRENTAV16PHASE A_B LINE VOLTSAV17PHASE B_C LINE VOLTSAV18PHASE C_A LINE VOLTSAV19LEAVING CHW TEMP ACT SPAV20MOTOR CURRENT ACTUAL SPAV21EVAP SATURATION TEMPAV22COND SATURATION TEMPAV23DISCHARGE TEMPAV25COND REFRIGERANT LEVELAV26ACCUM OPERATING HOURSAV27ACCUM SYSTEM STARTSBV5COMPR MOTOR STATUSBV6OIL RETURN SOLENOIDBV7CHW PUMP STATBV8STOP SWITCH STATUSBV9CHW FLOW SWITCH STATBV11LOW SEPARATOR OIL SWITCHBV24ICE STORAGE MODEMV1UNIT OPERATION CODEMV2UNIT SAFETY FAULT CODEMV3UNIT CYCLING FAULT CODEMV4UNIT WARNING FAULT CODEMV5UNIT CONTROL SOURCEAV35ANTI RECYCLE TIME REMAINAV37SEAL PRESS DIFFERENTIALAV38FILTER DIFF PRESSUREAV41MIN LOAD CTL MTR FLA LIMAV42SLIDE VALVE POSITION
Integration notes
- Access is inferred: the sheet has no read/write column. The remote block (AV 1-2, BV 1) is treated as commandable and MV 65001 as writable; everything else as read-only.
- Starter values (AV 13-18) only report with a solid-state starter (SSS).
- The doc notes that AV 25's label is off: the value is the refrigerant level position.
- Status-code MVs (MV 1-4) are the printed code + 1, as the doc's status code tables say. MV 5 and MV 65001 are shown as printed, from 0; BACnet multistate values start at 1, so the card may report the printed number + 1. Confirm by discovery.
- Units shown are the IP units; with MV 65001 set to SI the card reports °C, kPa and so on.
- Spare objects and empty rows are left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YR Screw Chiller (OptiView, SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York YR Screw Chiller (OptiView, SC-EQ)
How many BACnet points does the York YR Screw Chiller (OptiView, SC-EQ) have?
This list has 43 BACnet objects: 29 analog values, 8 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York YR Screw Chiller (OptiView, SC-EQ) BACnet points are writable?
4 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official York YR Screw Chiller (OptiView, SC-EQ) BACnet documentation?
The source is YR (OptiView) SC-EQ BAS Points List, revision Rev 1.2, 2021-12-15, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/ISru5gO~hseNJRaG8uHiHg/content.
What are the minimum BACnet points to integrate the York YR Screw Chiller (OptiView, SC-EQ)?
Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 MOTOR CURRENT REMOTE SP (Remote motor current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 12 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).
How do I enable BMS control of the York YR Screw Chiller (OptiView, SC-EQ)?
BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-2 the remote setpoints. MV 5 shows the control source (Local, ISN, Analog, Digital, Modem); it should read ISN for BAS control. The points list has no write-enable point.
How do I check these points on the real YR Screw Chiller (OptiView, SC-EQ)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: YR (OptiView) SC-EQ BAS Points List · rev. Rev 1.2, 2021-12-15. Object names, instances and units are reproduced as published; descriptions are our own.