- ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
Packaged rooftop unit controller (ECO2, 50-130 ton) · BACnet points list
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) BACnet points list
Updated 4 November 2026
The ECO2 controller's IPU 1 microboard speaks BACnet MS/TP and Modbus RTU natively (LON and N2 need an E-Link gateway). The list has read-only analog inputs for air temperatures, static and building pressures, airflows, CO2, refrigerant pressures and the unit mode; binary inputs for compressors, fans, heat stages and faults; and writable analog values for setpoints, limits, BAS reset and sensor inputs, occupancy, unit stop and enable commands.
This page lists 142 BACnet objects for the York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
- Equipment
- Packaged rooftop unit controller (ECO2, 50-130 ton)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 142 (41 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
Connect to the IPU 1 board on BACnet MS/TP (default 38.4K baud). Command occupancy with AV 88, stop or release the unit with AV 93 and write the occupied zone setpoints; feed zone temperature through AV 40 if the control method is set to comm zone temp. Read supply and return air temperatures, the supply fan status, unit mode and the fault inputs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 88 | OCCUPNCY_CMD | Occupancy command (1 = occupied) | Write |
| AV 93 | UNIT_STOP | Unit stop (1 = stopped, 0 = normal) | Write |
| AV 21 | OCC_ZN_COOL | Occupied zone cooling setpoint | Write |
| AV 22 | OCC_ZN_HEAT | Occupied zone heating setpoint | Write |
| AI 58 | UNIT_MODE | Unit mode index, 0-20 | Read |
| BI 59 | SUPPLY_FAN | Supply fan on/off | Read |
| AI 46 | SUP_AIR_TEMP | Supply air temperature | Read |
| AI 60 | ZONE_TEMP | Zone temperature | Read |
| BI 2 | COL/HEAT_FLT | Cooling/heating fault (1 = faulted) | Read |
| BI 54 | SEN/MSC_FLT | Sensor/misc fault (1 = fault) | Read |
Enable & remote start
AV 88 is the occupancy command (0 = unoccupied, 1 = occupied) and AV 93 the unit stop (0 = normal operation, 1 = stopped). BAS reset and BAS sensor inputs (AV 5, AV 28, AV 36, AV 37) must first be enabled at the unit with the service key; AV 40 zone temperature needs the control method set to comm zone temp.
Sensors & values from the BMS
AV 40 ZONE_TMP_BAS feeds zone temperature when the control method is set to comm zone temp. AV 36 and AV 37 feed under-floor humidity and temperature, and AV 5 and AV 28 give BAS duct static and supply air reset; these need enabling with the service key.
Network setup
- BACnet MS/TP default baud rate is 38.4K. Modbus RTU defaults to 9600 and can be set to 19.2K, 38.4K or 57.6K at the keypad.
- LON and N2 need an E-Link gateway; BACnet MS/TP and Modbus RTU are native on the IPU 1.
- See the ECO2 installation and operation manual (form 100.50-NOM3) for setup details.
Watch out for
- Binary commands are AVs that take 0 or 1, not BVs.
- Optional points report only when the option is fitted (see the sales order).
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | ACT_DSP_SP | Active DSP set point | in. WC | Read | |
| AI | 2 | ACT_MIN_FLOW | Active minimum air flow | CFM | Read | |
| AI | 3 | ACT_MIN_POS | Active minimum position | % | Read | |
| AI | 4 | ACT_SAT_SP | Active supply air temp setp | °F | Read | |
| AI | 5 | BLD_STAT_PRS | Building static pres | in. WC | Read | |
| AI | 6 | BYPASS_DAMPR | Bypass damper | % | Read | |
| AI | 7 | CO2_1_OUT | CO2 1 (outside) | PPM | Read | |
| AI | 8 | CO2_2_IN | CO2 2 (inside) | PPM | Read | |
| AI | 9 | COMP_1A_OPER | Compressor 1A oper hrs | h | Read | |
| AI | 10 | COMP_1B_OPER | Compressor 1B oper hrs | h | Read | |
| AI | 11 | COMP_2A_OPER | Compressor 2A oper hrs | h | Read | |
| AI | 12 | COMP_2B_OPER | Compressor 2B oper hrs | h | Read | |
| AI | 13 | COMP_3A_OPER | Compressor 3A oper hrs | h | Read | |
| AI | 14 | COMP_3B_OPER | Compressor 3B oper hrs | h | Read | |
| AI | 15 | COND_FAN_SPD | Condenser fan speed (units printed as hrs) | h | Read | |
| AI | 16 | DCT_ST_PR_RT | Duct static pres rst | % | Read | |
| AI | 17 | DCT_STAT_PRS | Duct static pres | in. WC | Read | |
| AI | 18 | ECON_ME_USED | Economizer method used | Read | 0=Dry bulb, 1=Single enthalpy, 2=Dual enthalpy | |
| AI | 19 | ECON_STATUS | Econo sys status | Read | 0=Installed and inactive, 1=Installed and active, 2=Not installed | |
| AI | 20 | EVAP_AIR_TMP | Evaporator air temp 1 | °F | Read | |
| AI | 21 | EXHAUST_OUT | Exhaust damper | % | Read | |
| AI | 22 | HEAT_ENT_TMP | Heat entering temp | °F | Read | |
| AI | 23 | HEAT_STAGES | Electric or staged gas heat stages available, 1-7 | Read | ||
| AI | 24 | HEATING_VALV | Heating valve | % | Read | |
| AI | 25 | OA_DAMPER | OA damper | % | Read | |
| AI | 26 | OA_ENTHALPY | Outside air enthalpy | BTU/lb | Read | |
| AI | 27 | OA_FLO_PRS_1 | OA flow pressure 1 | in. WC | Read | |
| AI | 28 | OA_FLO_PRS_2 | OA flow pressure 2 | in. WC | Read | |
| AI | 29 | OA_REL_HUMID | OA relative humidity | % | Read | |
| AI | 30 | OA_TEMP | Outside air temp | °F | Read | |
| AI | 31 | PRS_1_DISCH | Pressures 1 discharge | PSI | Read | |
| AI | 32 | PRS_1_SUCTON | Pressures 1 suction | PSI | Read | |
| AI | 33 | PRS_2_DISCH | Pressures 2 discharge | PSI | Read | |
| AI | 34 | PRS_2_SUCTON | Pressures 2 suction | PSI | Read | |
| AI | 35 | PRS_3_DISCH | Pressures 3 discharge | PSI | Read | |
| AI | 36 | PRS_3_SUCTON | Pressures 3 suction | PSI | Read | |
| AI | 37 | RET_AIR_BY_S | Return air bypass active SP | % | Read | |
| AI | 38 | RET_AIR_ENTH | Return air enthalpy | BTU/lb | Read | |
| AI | 39 | RET_AIR_HUMD | RA relative humidity | % | Read | |
| AI | 40 | RET_AIR_TEMP | Return air temp | °F | Read | |
| AI | 41 | RET_FAN_OUT | Exhaust/return fan VFD | % | Read | |
| AI | 42 | RET_FAN_PRES | Return fan pressure | in. WC | Read | |
| AI | 43 | SAT_SUC_TMP1 | Saturated suction temp 1 | °F | Read | |
| AI | 44 | SAT_SUC_TMP2 | Saturated suction temp 2 | °F | Read | |
| AI | 45 | SAT_SUC_TMP3 | Saturated suction temp 3 | °F | Read | |
| AImin | 46 | SUP_AIR_TEMP | Supply air temp | °F | Read | |
| AI | 47 | SUP_AIR_TRST | Supply air temp rst | V DC | Read | |
| AI | 48 | SUP_FAN_VFD | Supply fan VFD | % | Read | |
| AI | 49 | TEMP_1_SUCT | Temperatures 1 suction | °F | Read | |
| AI | 50 | TEMP_1_SUPER | Temperature 1 superheat | °F | Read | |
| AI | 51 | TEMP_2_SUCT | Temperatures 2 suction | °F | Read | |
| AI | 52 | TEMP_2_SUPER | Temperature 2 superheat | °F | Read | |
| AI | 53 | TEMP_3_SUCT | Temperatures 3 suction | °F | Read | |
| AI | 54 | TEMP_3_SUPER | Temperature 3 superheat | °F | Read | |
| AI | 55 | UND_FLR_DEWP | Under floor slab dew point | °F | Read | |
| AI | 56 | UND_FLR_HUMD | Under floor humidity | % | Read | |
| AI | 57 | UND_FLR_TEMP | Under floor temp | °F | Read | |
| AImin | 58 | UNIT_MODE | Unit mode, 0-20 (see ECO2 IOM 100.50-NOM3) | Read | ||
| AI | 59 | VENT_DEM_OUT | Ventilation demand PI outp | % | Read | |
| AImin | 60 | ZONE_TEMP | Zone temp | °F | Read | |
| AI | 61 | OA_FLOW_1 | IAQ dmpr air flows OA flow 1 | CFM | Read | |
| AI | 62 | OA_FLOW_2 | IAQ dmpr air flows OA flow 2 | CFM | Read | |
| AI | 63 | OA_FLOW_TOTL | Outside air flow total | CFM | Read | |
| BI | 1 | AMORN_WA_ACT | Adapt morn warm act | Read | ||
| BImin | 2 | COL/HEAT_FLT | Cooling/heating fault | Read | 0=No fault, 1=Faulted | |
| BI | 3 | COMP_1A | Compressor 1A | Read | 0=Off, 1=On | |
| BI | 4 | COMP_1B | Compressor 1B | Read | 0=Off, 1=On | |
| BI | 5 | COMP_2A | Compressor 2A | Read | 0=Off, 1=On | |
| BI | 6 | COMP_2B | Compressor 2B | Read | 0=Off, 1=On | |
| BI | 7 | COMP_3A | Compressor 3A | Read | 0=Off, 1=On | |
| BI | 8 | COMP_3B | Compressor 3B | Read | 0=Off, 1=On | |
| BI | 9 | COMP_LPCO_1 | Compressor LPCO 1 | Read | 0=Fault, 1=No fault | |
| BI | 10 | COMP_LPCO_2 | Compressor LPCO 2 | Read | 0=Fault, 1=No fault | |
| BI | 11 | COMP_LPCO_3 | Compressor LPCO 3 | Read | 0=Fault, 1=No fault | |
| BI | 12 | COMP_STAT_1 | Compressor status 1 | Read | 0=Fault, 1=No fault | |
| BI | 13 | COMP_STAT_2 | Compressor status 2 | Read | 0=Fault, 1=No fault | |
| BI | 14 | COMP_STAT_3 | Compressor status 3 | Read | 0=Fault, 1=No fault | |
| BI | 15 | COND_FAN_1A | Condenser fan 1A/1 | Read | ||
| BI | 16 | COND_FAN_1B | Condenser fan 1B/2 | Read | ||
| BI | 17 | COND_FAN_2A | Condenser fan 2A/3 | Read | ||
| BI | 18 | COND_FAN_2B | Condenser fan 2B/4 | Read | ||
| BI | 19 | COND_FAN_3A | Condenser fan 3A/5 | Read | ||
| BI | 20 | COND_FAN_3B | Condenser fan 3B/6 | Read | ||
| BI | 21 | EXH_FAN_STAT | Exhaust fan status | Read | 0=Off, 1=On | |
| BI | 22 | EXHAUST_FAN | Exhaust fan | Read | 0=Off, 1=On | |
| BI | 23 | FAN_FAULT | Fan fault | Read | 0=No fault, 1=Fault | |
| BI | 24 | FAN_G | Fan (G) | Read | ||
| BI | 25 | FILTER_STATS | Filter status 1 | Read | 0=No fault, 1=Fault | |
| BI | 26 | FURN_OUT_1 | Electric heat stage 1 / gas furnace 1 low | Read | ||
| BI | 27 | FURN_OUT_2 | Electric heat stage 2 / gas furnace 1 high | Read | ||
| BI | 28 | FURN_OUT_3 | Electric heat stage 3 / gas furnace 2 low | Read | ||
| BI | 29 | FURN_OUT_4 | Electric heat stage 4 / gas furnace 2 high | Read | ||
| BI | 30 | FURN_OUT_5 | Electric heat stage 5 / gas furnace 3 low | Read | ||
| BI | 31 | FURN_OUT_6 | Electric heat stage 6 / gas furnace 3 high | Read | ||
| BI | 32 | FURN_OUT_7 | Electric heat stage 7 / gas furnace spare or 1B | Read | ||
| BI | 33 | HW_FRZ_STAT | Hot water frz status | Read | 0=No fault, 1=Fault | |
| BI | 52 | RET_FAN_STAT | Return fan status | Read | 0=Off, 1=On | |
| BImin | 54 | SEN/MSC_FLT | Sensor/misc fault | Read | 0=No fault, 1=Fault | |
| BI | 55 | SF_PROV_SW | SF proving switch | Read | 0=Run, 1=Stop | |
| BImin | 59 | SUPPLY_FAN | Supply fan | Read | 0=Off, 1=On | |
| BI | 60 | UNSTABLE_SYS | Unstable system | Read | 0=Normal operation, 1=Unstable | |
| AV | 1 | BULD_PRES_SP | Building pressure SP | in. WC | Write | |
| AV | 2 | CO2_OFFSET | CO2 offset | PPM | Write | |
| AV | 3 | DSP_HI_LIMIT | Duct static high limit | in. WC | Write | |
| AV | 4 | DSP_LO_LIMIT | Duct static low limit | in. WC | Write | |
| AV | 5 | DSP_RST_BAS | Duct static pressure reset from BAS (enable with service key) | % | Write | |
| AV | 7 | EL_AIR_TMP_H | Evap leaving air temp high | °F | Write | |
| AV | 8 | EL_AIR_TMP_L | Evap leaving air temp low | °F | Write | |
| AV | 9 | HEATING_SAT | Heating SAT | °F | Write | |
| AV | 10 | MAX_BYPASS | Maximum bypass | % | Write | |
| AV | 11 | MAX_FLOW_DV | Max flow demand ventilation | CFM | Write | |
| AV | 12 | MECH_LCK_TMP | Mech clg lockout temp | °F | Write | |
| AV | 13 | MIN_FLOW_DV | Min flow demand ventilation | CFM | Write | |
| AV | 14 | MIXD_SAT_LIM | Mixed SAT limit | °F | Write | |
| AV | 15 | MORN_WUP_RAT | RAT heating setpoint (morning warm-up) | °F | Write | |
| AV | 16 | OA_DAMP_POS1 | OA damper min position 1 | % | Write | |
| AV | 17 | OA_DAMP_POS2 | OA damper min position 2 | % | Write | |
| AV | 18 | OA_ENTH_LIMT | OA enthalpy limit | BTU/lb | Write | |
| AVmin | 21 | OCC_ZN_COOL | Occupied zone cooling | °F | Write | |
| AVmin | 22 | OCC_ZN_HEAT | Occupied zone heating | °F | Write | |
| AV | 23 | RAT_COOL_SP | RAT cooling setp | °F | Write | |
| AV | 26 | SAT_HIGH_LIM | SAT high limit | °F | Write | |
| AV | 27 | SAT_LOW_LIM | SAT low limit | °F | Write | |
| AV | 28 | SAT_RST_BAS | Supply air reset from BAS (enable with service key) | V DC | Write | |
| AV | 31 | STG_1_COOL | Stg 1 cooling | °F | Write | |
| AV | 32 | STG_1_HEAT | Stg 1 heating | °F | Write | |
| AV | 33 | STG_2_COOL | Stg 2 cooling | °F | Write | |
| AV | 34 | STG_2_HEAT | Stg 2 heating | °F | Write | |
| AV | 35 | SYSTEM_STOP | System stop (compressor systems) | Write | 0=All compressors OK to run | |
| AV | 36 | UND_HUMD_BAS | Under floor humidity from BAS (enable with service key) | % | Write | |
| AV | 37 | UND_TEMP_BAS | Under floor temp from BAS (enable with service key) | °F | Write | |
| AV | 38 | UOCC_ZN_COOL | Un-occupied zone cooling | °F | Write | |
| AV | 39 | UOCC_ZN_HEAT | Un-occupied zone heating | °F | Write | |
| AV | 40 | ZONE_TMP_BAS | Zone temp from BAS (control method = comm zone temp) | °F | Write | |
| AV | 77 | ACT_SLAB_CTL | Active slab control | Write | 0=Off, 1=On | |
| AV | 80 | DEW_PNT_RST | Dew point reset | Write | 0=Off, 1=On | |
| AV | 81 | ECONO_INSTAL | Economizer installed | Write | 0=Off, 1=On | |
| AV | 86 | MORN_WUP_CMD | Morning warm up cmnd | Write | 0=Off, 1=On | |
| AV | 87 | NIGHT_SETBAC | Night set back (for heating) | Write | 0=Off, 1=On | |
| AVmin | 88 | OCCUPNCY_CMD | Occupancy command | Write | 0=Unoccupied, 1=Occupied | |
| AVmin | 93 | UNIT_STOP | Unit stop | Write | 0=Normal operation, 1=Stopped | |
| AV | 95 | VENT_ENABLE | Ventilation enable | Write | 0=Off, 1=On |
No points match these filters.
Object ID lookup: York ECO2 IPU 1 rooftop point IDs by name
AI1ACT_DSP_SPAI2ACT_MIN_FLOWAI3ACT_MIN_POSAI4ACT_SAT_SPAI5BLD_STAT_PRSAI6BYPASS_DAMPRAI7CO2_1_OUTAI8CO2_2_INAI9COMP_1A_OPERAI10COMP_1B_OPERAI11COMP_2A_OPERAI12COMP_2B_OPERAI13COMP_3A_OPERAI14COMP_3B_OPERAI15COND_FAN_SPDAI16DCT_ST_PR_RTAI17DCT_STAT_PRSAI18ECON_ME_USEDAI19ECON_STATUSAI20EVAP_AIR_TMPAI21EXHAUST_OUTAI22HEAT_ENT_TMPAI23HEAT_STAGESAI24HEATING_VALVAI25OA_DAMPERAI26OA_ENTHALPYAI27OA_FLO_PRS_1AI28OA_FLO_PRS_2AI29OA_REL_HUMIDAI30OA_TEMPAI31PRS_1_DISCHAI32PRS_1_SUCTONAI33PRS_2_DISCHAI34PRS_2_SUCTONAI35PRS_3_DISCHAI36PRS_3_SUCTONAI37RET_AIR_BY_SAI38RET_AIR_ENTHAI39RET_AIR_HUMDAI40RET_AIR_TEMPAI41RET_FAN_OUTAI42RET_FAN_PRESAI43SAT_SUC_TMP1AI44SAT_SUC_TMP2AI45SAT_SUC_TMP3AI46SUP_AIR_TEMPAI47SUP_AIR_TRSTAI48SUP_FAN_VFDAI49TEMP_1_SUCTAI50TEMP_1_SUPERAI51TEMP_2_SUCTAI52TEMP_2_SUPERAI53TEMP_3_SUCTAI54TEMP_3_SUPERAI55UND_FLR_DEWPAI56UND_FLR_HUMDAI57UND_FLR_TEMPAI58UNIT_MODEAI59VENT_DEM_OUTAI60ZONE_TEMPAI61OA_FLOW_1AI62OA_FLOW_2AI63OA_FLOW_TOTLBI1AMORN_WA_ACTBI2COL/HEAT_FLTBI3COMP_1ABI4COMP_1BBI5COMP_2ABI6COMP_2BBI7COMP_3ABI8COMP_3BBI9COMP_LPCO_1BI10COMP_LPCO_2BI11COMP_LPCO_3BI12COMP_STAT_1BI13COMP_STAT_2BI14COMP_STAT_3BI15COND_FAN_1ABI16COND_FAN_1BBI17COND_FAN_2ABI18COND_FAN_2BBI19COND_FAN_3ABI20COND_FAN_3BBI21EXH_FAN_STATBI22EXHAUST_FANBI23FAN_FAULTBI24FAN_GBI25FILTER_STATSBI26FURN_OUT_1BI27FURN_OUT_2BI28FURN_OUT_3BI29FURN_OUT_4BI30FURN_OUT_5BI31FURN_OUT_6BI32FURN_OUT_7BI33HW_FRZ_STATBI52RET_FAN_STATBI54SEN/MSC_FLTBI55SF_PROV_SWBI59SUPPLY_FANBI60UNSTABLE_SYSAV1BULD_PRES_SPAV2CO2_OFFSETAV3DSP_HI_LIMITAV4DSP_LO_LIMITAV5DSP_RST_BASAV7EL_AIR_TMP_HAV8EL_AIR_TMP_LAV9HEATING_SATAV10MAX_BYPASSAV11MAX_FLOW_DVAV12MECH_LCK_TMPAV13MIN_FLOW_DVAV14MIXD_SAT_LIMAV15MORN_WUP_RATAV16OA_DAMP_POS1AV17OA_DAMP_POS2AV18OA_ENTH_LIMTAV21OCC_ZN_COOLAV22OCC_ZN_HEATAV23RAT_COOL_SPAV26SAT_HIGH_LIMAV27SAT_LOW_LIMAV28SAT_RST_BASAV31STG_1_COOLAV32STG_1_HEATAV33STG_2_COOLAV34STG_2_HEATAV35SYSTEM_STOPAV36UND_HUMD_BASAV37UND_TEMP_BASAV38UOCC_ZN_COOLAV39UOCC_ZN_HEATAV40ZONE_TMP_BASAV77ACT_SLAB_CTLAV80DEW_PNT_RSTAV81ECONO_INSTALAV86MORN_WUP_CMDAV87NIGHT_SETBACAV88OCCUPNCY_CMDAV93UNIT_STOPAV95VENT_ENABLE
Integration notes
- Access comes from the sheet's Read/Write column. Binary commands (occupancy, unit stop, morning warm-up and so on) are analog values that take 0 or 1.
- Availability is Standard or Optional (see the sales order); optional points only report when the option is fitted.
- BACnet values are always in imperial units, whatever the ECO2 display is set to.
- Rows with no BACnet object (gas heat stages, gas furnace names that share the electric heat BIs, OAT/RAT setpoints for high/low SAT, fan speed setpoints for high/low SAT) are left out; BI 26-32 carry the electric heat or gas furnace stage outputs.
- The AV 35 System Stop comment is cut off in the sheet after 0 = all compressors OK to run; the other values stop compressor systems. The AI 15 condenser fan speed units are printed as hrs.
- The Johnson Controls document portal files this sheet as Series 100 IPU 1 Native BACnet and Modbus.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
How many BACnet points does the York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) have?
This list has 142 BACnet objects: 63 analog inputs, 41 analog values, 38 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) BACnet points are writable?
41 of the 142 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP) BACnet documentation?
The source is ECO 2 Mod-D,E 50-130 Ton Rooftop Native BACnet & Modbus Object Listings (Microboard IPU 1), revision ver J.02, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/q6LHnNOzMSDLOmZUbI44Ug/content.
What are the minimum BACnet points to integrate the York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)?
Start with AV 88 OCCUPNCY_CMD (Occupancy command (1 = occupied)); AV 93 UNIT_STOP (Unit stop (1 = stopped, 0 = normal)); AV 21 OCC_ZN_COOL (Occupied zone cooling setpoint); AV 22 OCC_ZN_HEAT (Occupied zone heating setpoint); AI 58 UNIT_MODE (Unit mode index, 0-20); BI 59 SUPPLY_FAN (Supply fan on/off); AI 46 SUP_AIR_TEMP (Supply air temperature); AI 60 ZONE_TEMP (Zone temperature); BI 2 COL/HEAT_FLT (Cooling/heating fault (1 = faulted)); BI 54 SEN/MSC_FLT (Sensor/misc fault (1 = fault)).
How do I enable BMS control of the York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)?
AV 88 is the occupancy command (0 = unoccupied, 1 = occupied) and AV 93 the unit stop (0 = normal operation, 1 = stopped). BAS reset and BAS sensor inputs (AV 5, AV 28, AV 36, AV 37) must first be enabled at the unit with the service key; AV 40 zone temperature needs the control method set to comm zone temp.
Can the BMS supply sensor values to the York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)?
AV 40 ZONE_TMP_BAS feeds zone temperature when the control method is set to comm zone temp. AV 36 and AV 37 feed under-floor humidity and temperature, and AV 5 and AV 28 give BAS duct static and supply air reset; these need enabling with the service key.
How do I check these points on the real ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: ECO 2 Mod-D,E 50-130 Ton Rooftop Native BACnet & Modbus Object Listings (Microboard IPU 1) · rev. ver J.02. Object names, instances and units are reproduced as published; descriptions are our own.