- Home
- BACnet points lists
- York
- Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
Rooftop unit controller · BACnet points list
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control BACnet points list
Updated 7 November 2026
The IPU controller in YORK Millennium / Series 40 25-40 ton rooftop units serves BACnet MS/TP (BACnet IP through an optional FieldServer gateway) and Modbus. The BAS can command occupancy, unit stop, fan, ventilation, heating and the Y1/Y2/W1/W2 calls, and write zone, supply air, duct static, building pressure and economizer setpoints and a BAS zone temperature. Read-only points cover temperatures, humidity, CO2, static pressures, damper and VFD outputs, compressor and heat stage status, run hours, faults and the unit mode.
This page lists 146 BACnet objects for the York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control — 61 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 146 (61 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 23000 + MAC address
- Also known as
- YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
Set the MAC address on the IPU (the device instance follows as 23000 + MAC), then command occupancy (AV 88) and write the zone or supply air setpoints. Use UNIT_STOP (AV 93) for a BAS shutdown, and read supply fan status, supply and zone temperatures, the unit mode and the fault flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 88 | OCCUPNCY_CMD | Occupancy command (1 = occupied) | Write |
| AV 93 | UNIT_STOP | Unit stop (1 = stopped, 0 = normal) | Write |
| AV 21 | OCC_ZN_COOL | Occupied zone cooling setpoint | Write |
| AV 22 | OCC_ZN_HEAT | Occupied zone heating setpoint | Write |
| AI 58 | UNIT_MODE | Unit mode index | Read |
| BI 59 | SUPPLY_FAN | Supply fan on/off | Read |
| AI 46 | SUP_AIR_TEMP | Supply air temperature | Read |
| AI 60 | ZONE_TEMP | Zone temperature | Read |
| BI 2 | COL_HEAT_FLT | Cooling/heating fault (1 = faulted) | Read |
| BI 54 | SEN_MSC_FLT | Sensor/misc fault (1 = fault) | Read |
Enable & remote start
OCCUPNCY_CMD (AV 88) sets occupied/unoccupied from the BAS and UNIT_STOP (AV 93) shuts the unit down (0 = normal, 1 = stopped). OCC_MODE (BI 35) shows the resulting occupancy.
Sensors & values from the BMS
ZONE_TMP_BAS (AV 40) takes the zone temperature from the BAS when the control method is set to Comm Zone Temp. CO2 inside (AV 43), under-floor temperature and humidity (AV 36/37) and the duct static and supply air resets (AV 5, AV 28) are also BAS inputs; several must be enabled with the Service key first.
Network setup
- The default device instance is 23000 plus the MAC address (MAC 10 gives 23010); a DE modifier address and offset can set another instance.
- The MAC address is set with the IPU MAC switches or the P1 Manual MAC Address parameter (0-127); P1 baud rate 1200 to 76800.
- BACnet IP needs the FieldServer FS-B2010-02-01Y gateway.
Watch out for
- BAS-enabled inputs such as CO2 inside and under-floor values only take effect after they are enabled with the Service key.
- HEAT_ENABLE (AV 83) is inverted: 0 = enabled, 1 = disabled.
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | ACT_DSP_SP | Duct Static Set Point | inH2O | Read | |
| AI | 3 | ACT_MIN_POS | Active Minimum Position | % | Read | |
| AI | 4 | ACT_SAT_SP | Supply Air Setp | °F | Read | |
| AV | 77 | ACT_SLAB_CTL | Active Slab Control | Write | 0=Off, 1=On | |
| BI | 1 | AMORN_WA_ACT | Adapt Morn Warm Up Active | Read | ||
| AI | 5 | BLD_STAT_PRS | Building Static Pres | inH2O | Read | |
| AV | 1 | BUILD_PRES_SP | Building Pressure Sp | inH2O | Write | |
| AI | 6 | BYPASS_DAMPER | Bypass Damper | % | Read | |
| AI | 8 | C02_2_INSIDE | Co2 1 (Inside) | ppm | Read | |
| AV | 43 | C02_INSIDE | CO2 lvl inside value bas | Write | ||
| AI | 7 | CO2_1_OUT | Co2 1 (Outside) | ppm | Read | |
| AV | 2 | CO2_OFFSET | Co2 Offset | ppm | Write | |
| BImin | 2 | COL_HEAT_FLT | Cooling/ Heating Fault | Read | 0=No Fault, 1=Faulted | |
| AV | 78 | COMFORT_VENT | Comfort Ventilation | Write | 0=Off, 1=On | |
| BI | 3 | COMP_1A | Compressor 1A | Read | 0=Off, 1=On | |
| AI | 9 | COMP_1A_OPER | Compressor 1A Oper Hrs | h | Read | |
| BI | 4 | COMP_1B | Compressor 1B | Read | 0=Off, 1=On | |
| AI | 10 | COMP_1B_OPER | Compressor 1B Oper Hrs | h | Read | |
| BI | 5 | COMP_2A | Compressor 2A | Read | 0=Off, 1=On | |
| AI | 11 | COMP_2A_OPER | Compressor 2A Oper Hrs | h | Read | |
| BI | 6 | COMP_2B | Compressor 2B | Read | 0=Off, 1=On | |
| AI | 12 | COMP_2B_OPER | Compressor 2B Oper Hrs | h | Read | |
| BI | 9 | COMP_LPCO_1 | Compressor Lpco 1 | Read | 0=Faulted, 1=No Fault | |
| BI | 10 | COMP_LPCO_2 | Compressor Lpco 2 | Read | 0=Faulted, 1=No Fault | |
| BI | 12 | COMP_STAT_1 | Compressor Status 1 | Read | 0=Faulted, 1=No Fault | |
| BI | 13 | COMP_STAT_2 | Compressor Status 2 | Read | 0=Faulted, 1=No Fault | |
| AV | 79 | CONTINU_VENT | Continuous Ventilation | Write | 0=Off, 1=On | |
| AI | 16 | DCT_ST_PR_RT | Duct Static Pres Rst | % | Read | |
| AI | 17 | DCT_STAT_PRS | Duct Static Pres | inH2O | Read | |
| AV | 80 | DEW_PNT_RST | Dew Point Reset | Write | 0=Off, 1=On | |
| AV | 3 | DSP_HI_LIMIT | Duct Static High Limit | inH2O | Write | |
| AV | 4 | DSP_LO_LIMIT | Duct Static Low Limit | inH2O | Write | |
| AV | 5 | DSP_RST_BAS | Duct Static Pres Rst Bas | % | Write | |
| AI | 18 | ECON_ME_USED | Economizer Method | Read | ||
| AI | 19 | ECON_STATUS | Economizer Suitable Econ Installed | Read | ||
| AV | 81 | ECONO_INSTAL | Economizer Installed | Write | 0=Off, 1=On | |
| AV | 6 | ECONO_METHOD | Economizer Method | Write | ||
| AV | 7 | EL_AIR_TMP_H | Evap Leaving Air Temp High | °F | Write | |
| AV | 8 | EL_AIR_TMP_L | Evap Leaving Air Temp Low | °F | Write | |
| AI | 20 | EVAP_AIR_TMP | Evaporator Air Temp 1 | °F | Read | |
| BI | 21 | EXH_FAN_STAT | Exhaust Fan Status | Read | 0=Verification Circuit Open, 1=Verification Circuit Closed | |
| BI | 22 | EXHAUST_FAN | Exhaust Fan | Read | 0=Off, 1=On | |
| AI | 21 | EXHAUST_OUT | Exhaust Output | % | Read | |
| BI | 23 | FAN_FAULT | Fan Fault | Read | 0=No Fault, 1=Faulted | |
| BI | 24 | FAN_G | Fan(G) | Read | ||
| AV | 82 | FAN_G_BAS | Fan (G) Bas | Write | 0=Off, 1=On | |
| BI | 25 | FILTER_STATS | Filter Status | Read | 0=No Fault, 1=Faulted | |
| BI | 26 | FURN_OUT_1 | Electric Heat Stage 1 Stg Gas Furnace 1 | Read | ||
| BI | 27 | FURN_OUT_2 | Electric Heat Stage 2 Stg Gas Furnace 1 High | Read | ||
| BI | 28 | FURN_OUT_3 | Electric Heat Stage 3 Stg Gas Furnace 2 Low | Read | ||
| BI | 29 | FURN_OUT_4 | Electric Heat Stage 4 Stg Gas Furnace 2 High | Read | ||
| BI | 30 | FURN_OUT_5 | Electric Heat Stage 5 Stg Gas Furnace 3 Low | Read | ||
| BI | 31 | FURN_OUT_6 | Electric Heat Stage 6 Stg Gas Furnace 3 High | Read | ||
| BI | 32 | FURN_OUT_7 | Electric Heat Stage 7 | Read | ||
| AV | 83 | HEAT_ENABLE | Heating Enable | Write | 0=Enabled, 1=Disabled | |
| AI | 22 | HEAT_ENT_TMP | Heat Entering Temp | °F | Read | |
| AI | 23 | HEAT_STAGES | Electric Heat Stages Gas Heat Stages | Read | ||
| AV | 84 | HEAT_VACTION | Heating Valve Action | Write | 0=Direct Acting, 1=Reverse Acting | |
| AV | 9 | HEATING_SAT | Heating Sat | °F | Write | |
| AI | 24 | HEATING_VALV | Heating Valve | % | Read | |
| BI | 33 | HW_FRZ_STAT | Hot Water Frz Status | Read | 0=No Fault, 1=Faulted | |
| BI | 34 | LOCAL_STOP | Local Stop | Read | ||
| AV | 10 | MAX_BYPASS | Maximum Bypass | % | Write | |
| AV | 12 | MECH_LCK_TMP | Mech Clg Lockout Temp | °F | Write | |
| AV | 14 | MIXD_SAT_LIM | Mixed Sat Limit | °F | Write | |
| AV | 85 | MORN_WARM_UP | Morning Warm Up Enable | Write | 0=Enabled, 1=Disabled | |
| AV | 86 | MORN_WUP_CMD | Morning Warm Up Cmnd | Write | 0=Off, 1=On | |
| AV | 15 | MORN_WUP_RAT | Rat Heating Setp | °F | Write | |
| AV | 87 | NIGHT_SETBAC | Night Set Back (For Heating) | Write | 0=Off, 1=On | |
| AV | 16 | OA_DAMP_POS1 | Oa Damper Min Position 1 | % | Write | |
| AV | 17 | OA_DAMP_POS2 | Oa Damper Min Position 2 | % | Write | |
| AI | 25 | OA_DAMPER | Oa Damper | % | Read | |
| AV | 18 | OA_ENTH_LIMT | Outside Air Enthalpy Setpoint | Write | ||
| AI | 26 | OA_ENTHALPY | Outside Air Enthalpy | Read | ||
| AI | 29 | OA_REL_HUMID | Outside Air Humidity | % | Read | |
| AI | 30 | OA_TEMP | Outside Air Temp | °F | Read | |
| AV | 19 | OAT_HIGH_SAT | Oat For High Sat | °F | Write | |
| AV | 20 | OAT_LOW_SAT | Oat For Low Sat | °F | Write | |
| BI | 35 | OCC_MODE | Occupancy Mode | Read | ||
| BI | 36 | OCC_STATE | Occupancy State | Read | ||
| AVmin | 21 | OCC_ZN_COOL | Occupied Zone Cooling Setp | °F | Write | |
| AVmin | 22 | OCC_ZN_HEAT | Occupied Zone Heating Setp | °F | Write | |
| AVmin | 88 | OCCUPNCY_CMD | Occupancy Command | Write | 0=Unoccupied, 1=Occupied | |
| AV | 23 | RAT_COOL_SP | Rat Cooling Setp | °F | Write | |
| AV | 24 | RAT_HIGH_SAT | Rat For High Sat | °F | Write | |
| AV | 25 | RAT_LOW_SAT | Rat For Low Sat | °F | Write | |
| BI | 40 | RDY_RUN_C1A | Ready To Run Comp 1A | Read | ||
| BI | 41 | RDY_RUN_C1B | Ready To Run Comp 1B | Read | ||
| BI | 42 | RDY_RUN_C2A | Ready To Run Comp 2A | Read | ||
| BI | 43 | RDY_RUN_C2B | Ready To Run Comp 2B | Read | ||
| BI | 46 | RDY_STOP_C1A | Ready To Stop Comp 1A | Read | ||
| BI | 47 | RDY_STOP_C1B | Ready To Stop Comp 1B | Read | ||
| BI | 48 | RDY_STOP_C2A | Ready To Stop Comp 2A | Read | ||
| BI | 49 | RDY_STOP_C2B | Ready To Stop Comp 2B | Read | ||
| AI | 37 | RET_AIR_BY_S | Active Bypass Active Sp | % | Read | |
| AI | 38 | RET_AIR_ENTH | Return Air Enthalpy | Read | ||
| AI | 39 | RET_AIR_HUMD | Return Air Humidity | % | Read | |
| AI | 40 | RET_AIR_TEMP | Return Air Temp | °F | Read | |
| AI | 41 | RET_FAN_OUT | Exhaust/ Return Fan Vfd | % | Read | |
| AV | 26 | SAT_HIGH_LIM | Sat High Limit | °F | Write | |
| AV | 27 | SAT_LOW_LIM | Sat Low Limit | °F | Write | |
| AV | 28 | SAT_RST_BAS | Supply Air Temp Rst Bas | Write | ||
| BI | 53 | SAT_TEMPER | Sat Tempering Enable | Read | ||
| BImin | 54 | SEN_MSC_FLT | Sensor/Misc Fault | Read | 0=No Fault, 1=Faulted | |
| BI | 55 | SF_PROV_SW | Sf Proving Switch | Read | ||
| AV | 29 | SF_SPD_H_SAT | Sf Speed For High Sat | % | Write | |
| AV | 30 | SF_SPD_L_SAT | Sf Speed For Low Sat | % | Write | |
| BI | 56 | SMOKE_PUR_1 | Smoke Purge 1 | Read | ||
| BI | 57 | SMOKE_PUR_2 | Smoke Purge 2 | Read | ||
| BI | 58 | SMOKE_PUR_3 | Smoke Purge 3 | Read | ||
| AV | 90 | SMOKE_PUR1_B | Smoke Purge 1 Bas | Write | ||
| AV | 91 | SMOKE_PUR2_B | Smoke Purge 2 Bas | Write | ||
| AV | 92 | SMOKE_PUR3_B | Smoke Purge 3 Bas | Write | ||
| AV | 31 | STG_1_COOL | Stg 1 Cooling | °F | Write | |
| AV | 32 | STG_1_HEAT | Stg 1 Heating | °F | Write | |
| AV | 33 | STG_2_COOL | Stg 2 Cooling | °F | Write | |
| AV | 34 | STG_2_HEAT | Stg 2 Heating | °F | Write | |
| AImin | 46 | SUP_AIR_TEMP | Supply Air Temp | °F | Read | |
| AI | 47 | SUP_AIR_TRST | Supply Air Temp Rst | Read | ||
| AI | 48 | SUP_FAN_VFD | Supply Fan Vfd | % | Read | |
| BImin | 59 | SUPPLY_FAN | Supply Fan | Read | 0=Off, 1=On | |
| AV | 35 | SYSTEM_STOP | System Stop | Write | ||
| AI | 55 | UND_FLR_DEWP | Under Floor Dew Point | °F | Read | |
| AI | 56 | UND_FLR_HUMD | Under Floor Humidity | % | Read | |
| AI | 57 | UND_FLR_TEMP | Under Floor Temp | °F | Read | |
| AV | 36 | UND_HUMD_BAS | Under Floor Humidity Bas | % | Write | |
| AV | 37 | UND_TEMP_BAS | Under Floor Temp Bas | °F | Write | |
| AImin | 58 | UNIT_MODE | Unit Mode | Read | ||
| AVmin | 93 | UNIT_STOP | Unit Stop | Write | 0=Normal operation, 1=Stopped | |
| AV | 38 | UNOCC_ZN_COOL | Unoccupied Zone Cooling | °F | Write | |
| AV | 39 | UNOCC_ZN_HEAT | Unoccupied Zone Heating | °F | Write | |
| BI | 60 | UNSTABLE_SYS | Unstable System | Read | 0=Normal Operation, 1=Unstable Condition | |
| BI | 61 | VAV_HEAT | Vav Heat | Read | ||
| AV | 94 | VENT_CONTROL | Ventilation Control | Write | 0=Fixed Minimum, 1=Demand | |
| AI | 59 | VENT_DEM_OUT | Ventilation Demand P1 Outp | % | Read | |
| AV | 95 | VENT_ENABLE | Ventilation Enable | Write | 0=Off, 1=On | |
| AV | 96 | W1_LO_HEAT_B | W1 Low Heat Bas | Write | 0=Off, 1=On | |
| BI | 62 | W1_LOW_HEAT | W1 Low Heat | Read | ||
| AV | 97 | W2_HI_HEAT_B | W2 High Heat Bas | Write | 0=Off, 1=On | |
| BI | 63 | W2_HIGH_HEAT | W2 High Heat | Read | ||
| AV | 98 | Y1_LO_COOL_B | Y1 Low Cool Bas | Write | 0=Off, 1=On | |
| BI | 64 | Y1_LOW_COOL | Y1 Low Cool | Read | ||
| AV | 99 | Y2_HI_COOL_B | Y2 High Cool Bas | Write | 0=Off, 1=On | |
| BI | 65 | Y2_HIGH_COOL | Y2 Low Cool | Read | ||
| AImin | 60 | ZONE_TEMP | Zone Temp | °F | Read | |
| AV | 40 | ZONE_TMP_BAS | Zone Temp Bas | °F | Write |
No points match these filters.
Object ID lookup: York Millennium 25-40 Ton IPU point IDs by name
AI1ACT_DSP_SPAI3ACT_MIN_POSAI4ACT_SAT_SPAV77ACT_SLAB_CTLBI1AMORN_WA_ACTAI5BLD_STAT_PRSAV1BUILD_PRES_SPAI6BYPASS_DAMPERAI8C02_2_INSIDEAV43C02_INSIDEAI7CO2_1_OUTAV2CO2_OFFSETBI2COL_HEAT_FLTAV78COMFORT_VENTBI3COMP_1AAI9COMP_1A_OPERBI4COMP_1BAI10COMP_1B_OPERBI5COMP_2AAI11COMP_2A_OPERBI6COMP_2BAI12COMP_2B_OPERBI9COMP_LPCO_1BI10COMP_LPCO_2BI12COMP_STAT_1BI13COMP_STAT_2AV79CONTINU_VENTAI16DCT_ST_PR_RTAI17DCT_STAT_PRSAV80DEW_PNT_RSTAV3DSP_HI_LIMITAV4DSP_LO_LIMITAV5DSP_RST_BASAI18ECON_ME_USEDAI19ECON_STATUSAV81ECONO_INSTALAV6ECONO_METHODAV7EL_AIR_TMP_HAV8EL_AIR_TMP_LAI20EVAP_AIR_TMPBI21EXH_FAN_STATBI22EXHAUST_FANAI21EXHAUST_OUTBI23FAN_FAULTBI24FAN_GAV82FAN_G_BASBI25FILTER_STATSBI26FURN_OUT_1BI27FURN_OUT_2BI28FURN_OUT_3BI29FURN_OUT_4BI30FURN_OUT_5BI31FURN_OUT_6BI32FURN_OUT_7AV83HEAT_ENABLEAI22HEAT_ENT_TMPAI23HEAT_STAGESAV84HEAT_VACTIONAV9HEATING_SATAI24HEATING_VALVBI33HW_FRZ_STATBI34LOCAL_STOPAV10MAX_BYPASSAV12MECH_LCK_TMPAV14MIXD_SAT_LIMAV85MORN_WARM_UPAV86MORN_WUP_CMDAV15MORN_WUP_RATAV87NIGHT_SETBACAV16OA_DAMP_POS1AV17OA_DAMP_POS2AI25OA_DAMPERAV18OA_ENTH_LIMTAI26OA_ENTHALPYAI29OA_REL_HUMIDAI30OA_TEMPAV19OAT_HIGH_SATAV20OAT_LOW_SATBI35OCC_MODEBI36OCC_STATEAV21OCC_ZN_COOLAV22OCC_ZN_HEATAV88OCCUPNCY_CMDAV23RAT_COOL_SPAV24RAT_HIGH_SATAV25RAT_LOW_SATBI40RDY_RUN_C1ABI41RDY_RUN_C1BBI42RDY_RUN_C2ABI43RDY_RUN_C2BBI46RDY_STOP_C1ABI47RDY_STOP_C1BBI48RDY_STOP_C2ABI49RDY_STOP_C2BAI37RET_AIR_BY_SAI38RET_AIR_ENTHAI39RET_AIR_HUMDAI40RET_AIR_TEMPAI41RET_FAN_OUTAV26SAT_HIGH_LIMAV27SAT_LOW_LIMAV28SAT_RST_BASBI53SAT_TEMPERBI54SEN_MSC_FLTBI55SF_PROV_SWAV29SF_SPD_H_SATAV30SF_SPD_L_SATBI56SMOKE_PUR_1BI57SMOKE_PUR_2BI58SMOKE_PUR_3AV90SMOKE_PUR1_BAV91SMOKE_PUR2_BAV92SMOKE_PUR3_BAV31STG_1_COOLAV32STG_1_HEATAV33STG_2_COOLAV34STG_2_HEATAI46SUP_AIR_TEMPAI47SUP_AIR_TRSTAI48SUP_FAN_VFDBI59SUPPLY_FANAV35SYSTEM_STOPAI55UND_FLR_DEWPAI56UND_FLR_HUMDAI57UND_FLR_TEMPAV36UND_HUMD_BASAV37UND_TEMP_BASAI58UNIT_MODEAV93UNIT_STOPAV38UNOCC_ZN_COOLAV39UNOCC_ZN_HEATBI60UNSTABLE_SYSBI61VAV_HEATAV94VENT_CONTROLAI59VENT_DEM_OUTAV95VENT_ENABLEAV96W1_LO_HEAT_BBI62W1_LOW_HEATAV97W2_HI_HEAT_BBI63W2_HIGH_HEATAV98Y1_LO_COOL_BBI64Y1_LOW_COOLAV99Y2_HI_COOL_BBI65Y2_HIGH_COOLAI60ZONE_TEMPAV40ZONE_TMP_BAS
Integration notes
- Access is from the READ/WRITE column; descriptions are the user interface names from the table. Points marked FlexSys, VAV or CV only exist on those units.
- Rows the table marks "this feature is not available on this unit" (43 objects, for example 3rd-stage compressors, condenser fans and suction sensors) are left out.
- Fifteen on/off BAS commands (comfort and continuous ventilation, fan G, heating enable and valve action, morning warm-up, smoke purge 1-3, ventilation control, W1/W2 and Y1/Y2 calls) are printed as AV(BV) nn; they are listed here as AV nn.
- The smoke purge BAS commands (AV 90-92) are described as 0 = off, 1 = off in the table; the state text is left blank.
- The Series 40 IOM (LD14136) prints the same table; both documents point to this list.
- Same IPU object map as the Series 100 YPAL lists in this library: every instance here also appears there, but this table drops the objects not available on 25-40 ton units and spells some names differently (for example C02_INSIDE, ZONE_TMP_BAS).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
How many BACnet points does the York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control have?
This list has 146 BACnet objects: 38 analog inputs, 61 analog values, 47 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control BACnet points are writable?
61 of the 146 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control BACnet documentation?
The source is Millenium Packaged Rooftop Units 25-40 Tons with IPU Control - Installation, Operation and Maintenance (Table 6-12, BACnet MS/TP, Modbus, BACnet IP) (Form 100.50-NOM8 (409)), revision 2009-04, published free by York at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/jHl7DLBfzBwL8EpKbeMhag/content.
What are the minimum BACnet points to integrate the York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control?
Start with AV 88 OCCUPNCY_CMD (Occupancy command (1 = occupied)); AV 93 UNIT_STOP (Unit stop (1 = stopped, 0 = normal)); AV 21 OCC_ZN_COOL (Occupied zone cooling setpoint); AV 22 OCC_ZN_HEAT (Occupied zone heating setpoint); AI 58 UNIT_MODE (Unit mode index); BI 59 SUPPLY_FAN (Supply fan on/off); AI 46 SUP_AIR_TEMP (Supply air temperature); AI 60 ZONE_TEMP (Zone temperature); BI 2 COL_HEAT_FLT (Cooling/heating fault (1 = faulted)); BI 54 SEN_MSC_FLT (Sensor/misc fault (1 = fault)).
How do I enable BMS control of the York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control?
OCCUPNCY_CMD (AV 88) sets occupied/unoccupied from the BAS and UNIT_STOP (AV 93) shuts the unit down (0 = normal, 1 = stopped). OCC_MODE (BI 35) shows the resulting occupancy.
Can the BMS supply sensor values to the York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control?
ZONE_TMP_BAS (AV 40) takes the zone temperature from the BAS when the control method is set to Comm Zone Temp. CO2 inside (AV 43), under-floor temperature and humidity (AV 36/37) and the duct static and supply air resets (AV 5, AV 28) are also BAS inputs; several must be enabled with the Service key first.
How do I check these points on the real Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: Millenium Packaged Rooftop Units 25-40 Tons with IPU Control - Installation, Operation and Maintenance (Table 6-12, BACnet MS/TP, Modbus, BACnet IP) · Form 100.50-NOM8 (409) · rev. 2009-04. Object names, instances and units are reproduced as published; descriptions are our own.