- YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
Water-cooled centrifugal chiller (via E-Link gateway) · BACnet points list
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) BACnet points list
Updated 6 November 2026
The E-Link gateway reads the YD OptiView microboard over YorkTalk 3 and serves BACnet, N2, LON and Modbus objects: remote setpoint, current limit, compressor operation mode and lockout, run/stop, water temperatures and pressures, per-compressor oil and motor values and the status codes.
This page lists 109 BACnet objects for the York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
- Equipment
- Water-cooled centrifugal chiller (via E-Link gateway)
- Equipment type
- Chillers
- BACnet objects
- 109 (5 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
Put the chiller in remote/ISN control at the panel, then start and stop it with the E-Link remote run/stop object and write the remote setpoint and current limit. Read the operating, safety and warning codes, run status and water temperatures.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | REM RUN STOP CMD | Remote start/stop (1 = run) | Write |
| AV 1 | REM LEAVING CH LIQ TEMP SP | Remote leaving chilled liquid setpoint | Write |
| AV 2 | REM MOTOR CURRENT SP | Remote current limit, % | Write |
| MV 8 | UNIT CONTROL SOURCE | Must read ISN (BAS) for BMS control | Read |
| MV 1 | UNIT OPERATION CODE | Unit operating status code | Read |
| BV 5 | COMPR MOTOR STATUS 1 | Chiller running | Read |
| AV 5 | LEAVING CH LIQ TEMP | Leaving chilled liquid temperature | Read |
| AV 6 | ENTERING CH LIQ TEMP | Entering chilled liquid temperature | Read |
| MV 2 | UNIT SAFETY FAULT CODE | Safety (shutdown) fault code | Read |
| MV 4 | UNIT WARNING CODE | Active warning code | Read |
Enable & remote start
The E-Link remote slots (AV 1-4, BV 1-4) are the BMS commands; the chiller panel must be set for remote (ISN/BAS) control for them to take effect.
Network setup
- The E-Link gateway talks to the chiller microboard over YorkTalk 3 and serves BACnet, N2, LON and Modbus; BACnet addressing is set on the E-Link.
- Check the chiller program version against the sheet's version table; availability codes (S/O/N) are per version.
Watch out for
- Status codes are multistate values offset by 1 from the printed code tables.
- Points marked optional (O) on the sheet report only on units with that option or program version.
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REM LEAVING CH LIQ TEMP SP | Remote Leaving Chilled Liquid Setpoint | °F | Write | |
| AVmin | 2 | REM MOTOR CURRENT SP | Remote Unit Current Limit Setpoint | % | Write | |
| AV | 3 | REM COMP OPERATION MODE | Remote Comp Operation Mode | Write | 0=Staged, 1=Single, 2=Dual | |
| AV | 4 | REM COMP LOCKOUT | Remote Comp Lockout | Write | 0=None, 1=Comp #1, 2=Comp #2 | |
| BVmin | 1 | REM RUN STOP CMD | Remote Run/Stop | Write | 0=Stop, 1=Run | |
| AVmin | 5 | LEAVING CH LIQ TEMP | Leaving Chilled Liquid Temperature | °F | Read | |
| AVmin | 6 | ENTERING CH LIQ TEMP | Entering Chilled Liquid Temperature | °F | Read | |
| AV | 7 | EVAPORATOR PRESSURE | Evaporator Pressure | psig | Read | |
| AV | 8 | CONDENSER PRESSURE | Condenser Pressure | psig | Read | |
| AV | 9 | OIL DIFERENTL PRESSURE 1 | Oil Pressure Differential #1 | psid | Read | |
| AV | 10 | OIL DIFERENTL PRESSURE 2 | Oil Pressure Differential #2 | psid | Read | |
| AV | 11 | ENTERING COND WATER TEMP | Entering Condenser Liquid Temperature | °F | Read | |
| AV | 12 | LEAVING COND WATER TEMP | Leaving Condenser Liquid Temperature | °F | Read | |
| AV | 13 | MOTOR CURRENT FLA 1 | Motor Current Percent FLA #1 | % | Read | |
| AV | 14 | MOTOR CURRENT FLA 2 | Motor Current Percent FLA #2 | % | Read | |
| AV | 15 | EVAP REFRIG TEMP | Evaporator Refrigerant Temperature | °F | Read | |
| AV | 16 | DROP LEG REFRIG TEMP | Drop Leg Refrigerant Temperature | °F | Read | |
| AV | 17 | LEAVING CH LIQ TEMP ACT SP | Leaving Chilled Liquid Setpoint-Selected | °F | Read | |
| AV | 18 | MOTOR CURRENT ACTUAL SP | Unit Current Limit Setpoint-Selected | % | Read | |
| AV | 19 | EVAP SATURATION TEMP | Evaporator Saturation Temp | °F | Read | |
| AV | 20 | COND SATURATION TEMP | Condenser Saturation Temp | °F | Read | |
| AV | 21 | DISCHARGE TEMP 1 | Discharge Temperature #1 | °F | Read | |
| AV | 22 | DISCHARGE TEMP 2 | Discharge Temperature #2 | °F | Read | |
| AV | 23 | OIL SUMP TEMPERATURE | Oil Sump Temperature | °F | Read | |
| AV | 24 | COND REFRIGERANT LEVEL | Condenser Refrigerant Level | % | Read | |
| AV | 25 | ACCUM OPERATING HOURS | Unit Operating Hours | Read | ||
| AV | 26 | ACCUM SYSTEM STARTS | Unit System Starts | Read | ||
| AV | 27 | OIL SUMP PRESSURE | Oil Sump Pressure PSIG | psig | Read | |
| AV | 28 | OIL PUMP PRESSURE 1 | Oil Pump Pressure #1 PSIG | psig | Read | |
| AV | 29 | OIL PUMP PRESSURE 2 | Oil Pump Pressure #2 PSIG | psig | Read | |
| BVmin | 5 | COMPR MOTOR STATUS 1 | Motor Run #1 | Read | 0=Off, 1=On | |
| BV | 6 | COMPR MOTOR STATUS 2 | Motor Run #2 | Read | 0=Off, 1=On | |
| BV | 8 | CH LIQ PUMP STAT | Chilled Liquid Pump | Read | 0=Off, 1=On | |
| BV | 9 | START STOP SWITCH STATUS | Panel Stop Switch | Read | 0=Off, 1=On | |
| BV | 10 | CH LIQ FLOW SWITCH STAT | Chilled Liquid Flow Switch | Read | 0=Open, 1=Closed | |
| BV | 11 | CND FLOW SWITCH STAT | Condenser Liquid Flow Switch | Read | 0=Open, 1=Closed | |
| BV | 12 | DISCH HI PRESS SW 1 | Discharge High Pressure Switch #1 | Read | ||
| BV | 13 | DISCH HI PRESS SW 2 | Discharge High Pressure Switch #2 | Read | ||
| BV | 14 | VANE MOTOR SW 1 | Vane Motor Switch #1 | Read | ||
| BV | 15 | VANE MOTOR SW 2 | Vane Motor Switch #2 | Read | ||
| BV | 16 | REFRIGERANT LEVEL LOWER | Refrigerant Level Lower | Read | 0 = Off, 1 = On | |
| BV | 17 | REFRIGERANT LEVEL RAISE | Refrigerant Level Raise | Read | 0 = Off, 1 = On | |
| BV | 18 | OIL RETURN SOLONOID | Oil Return Solenoid | Read | ||
| BV | 19 | PRV OPENING 1 | Pre-Rotation Vane Opening #1 | Read | ||
| BV | 20 | PRV OPENING 2 | Pre Rotation Vane Opening #2 | Read | ||
| BV | 21 | PRV CLOSING 1 | Pre-Rotation Vane Closing #1 | Read | ||
| BV | 22 | PRV CLOSING 2 | Pre-Rotation Vane Closing #2 | Read | ||
| MVmin | 1 | UNIT OPERATION CODE | Unit Operation Code | Read | ||
| MVmin | 2 | UNIT SAFETY FAULT CODE | Unit Safety Fault Code | Read | ||
| MV | 3 | UNIT CYCLING FAULT CODE | Unit Cycling Fault Code | Read | ||
| MVmin | 4 | UNIT WARNING CODE | Unit Warning Code | Read | ||
| MV | 5 | UNIT MODIFIED RUN CODE | Unit Modified Run Code | Read | ||
| MV | 6 | UNIT START INHIBIT CODE | Unit Start Inhibit Code | Read | ||
| MV | 7 | UNIT INTERNAL FAULT CODE | Unit Internal Fault Code | Read | ||
| MVmin | 8 | UNIT CONTROL SOURCE | Unit Control Source | Read | 0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem | |
| AV | 30 | PROX SENSOR ACT POS 1 | High Speed Thrust Bearing Proximity Position #1 (mils ) | Read | ||
| AV | 31 | PROX SENSOR ACT POS 2 | High Speed Thrust Bearing Proximity Position #2 (mils ) | Read | ||
| AV | 32 | REFRIGERANT LEVEL SP | Refrigerant Level Setpoint | % | Read | |
| AV | 33 | ANTI RECYC TIME REMAIN 1 | Motor Anti-Recycle Time Remaining #1 | Read | ||
| AV | 34 | ANTI RECYC TIME REMAIN 2 | Motor Anti-Recycle Time Remaining #2 | Read | ||
| AV | 35 | PRV POSITION 1 | Pre Rotation Vanes Position #1 | % | Read | |
| AV | 36 | PRV POSITION 2 | Pre Rotation Vanes Position #2 | % | Read | |
| AV | 37 | VGD POSITION 1 | VGD Position #1 | % | Read | |
| AV | 38 | VGD POSITION 2 | VGD Position #2 | % | Read | |
| AV | 39 | OIL LEVEL SUMP | Oil Level (Sump) | % | Read | |
| AV | 40 | COMP OPERATION MODE | Compressor Operation Mode | Read | 0=Staged, 1=Single, 2=Dual | |
| AV | 41 | COMP LOCKOUT MODE | Compressor Lockout Mode | Read | 0=None 1=Comp #1, 2=Comp #2 | |
| BV | 25 | DISCH VLV OPENING 1 | Discharge Valve Opening #1 | Read | ||
| BV | 26 | DISCH VLV OPENING 2 | Discharge Valve Opening #2 | Read | ||
| BV | 27 | DISCH VLV CLOSING 1 | Discharge Valve Closing #1 | Read | ||
| BV | 28 | DISCH VLV CLOSING 2 | Discharge Valve Closing #2 | Read | ||
| AV | 105 | MC 1 INPUT POWER | Input Power #1 (VSD only) | kW | Read | |
| AV | 106 | MC 2 INPUT POWER | Input Power #2 (VSD only) | kW | Read | |
| AV | 107 | MC 1 INPUT KWH | Input Kilowatt Hours #1 (VSD only) | kWh | Read | |
| AV | 108 | MC 2 INPUT KWH | Input Kilowatt Hours #2 (VSD only) | kWh | Read | |
| AV | 109 | VSD 1 OUTPUT VOLTAGE | VSD #1 Output Voltage (VSD only) | Read | ||
| AV | 110 | VSD 2 OUTPUT VOLTAGE | VSD #2 Output Voltage (VSD only) | Read | ||
| AV | 111 | VSD 1 OUTPUT FREQUENCY | VSD #1 Output Frequency (VSD only) | Hz | Read | |
| AV | 112 | VSD 2 OUTPUT FREQUENCY | VSD #2 Output Frequency (VSD only) | Hz | Read | |
| AV | 113 | MOTOR 1 PHASE A CURRENT | Motor #1 Phase A Current (VSD only) | A | Read | |
| AV | 114 | MOTOR 2 PHASE A CURRENT | Motor #2 Phase A Current (VSD only) | A | Read | |
| AV | 115 | MOTOR 1 PHASE B CURRENT | Motor #1 Phase B Current (VSD only) | A | Read | |
| AV | 116 | MOTOR 2 PHASE B CURRENT | Motor #2 Phase B Current (VSD only) | A | Read | |
| AV | 117 | MOTOR 1 PHASE C CURRENT | Motor #1 Phase C Current (VSD only) | A | Read | |
| AV | 118 | MOTOR 2 PHASE C CURRENT | Motor #2 Phase C Current (VSD only) | A | Read | |
| AV | 119 | VSD 1 DC BUS VOLTAGE | VSD #1 DC Bus Voltage (VSD only) | V | Read | |
| AV | 120 | VSD 2 DC BUS VOLTAGE | VSD #2 DC Bus Voltage (VSD only) | V | Read | |
| AV | 121 | VSD 1 DC BUS CURRENT | VSD #1 DC Bus Current (LVVSD only) | A | Read | |
| AV | 122 | VSD 2 DC BUS CURRENT | VSD #2 DC Bus Current (LVVSD only) | A | Read | |
| AV | 123 | VSD 1 INTERNAL AMBIENT TEMP | VSD #1 Internal Ambient Temperature (LVVSD only) | °F | Read | |
| AV | 124 | VSD 2 INTERNAL AMBIENT TEMP | VSD #2 Internal Ambient Temperature (LVVSD only) | °F | Read | |
| AV | 125 | VSD 1 CONVERTER HSINK TEMP | VSD #1 Converter Heatsink Temp (LVVSD only) | °F | Read | |
| AV | 126 | VSD 2 CONVERTER HSINK TEMP | VSD #2 Converter Heatsink Temp (LVVSD only) | °F | Read | |
| AV | 127 | FILTER #1 SUPPLY KVA | Harmonic Filter #1 Total Supply KVA (LVVSD/HF only) | kVA | Read | |
| AV | 128 | FILTER #2 SUPPLY KVA | Harmonic Filter #2 Total Supply KVA (LVVSD/HF only) | kVA | Read | |
| BV | 105 | VSD #1 COOLING SYS RUN | VSD #1 Cooling System Run (VSD only) | Read | 0=Not Running, 1=Running | |
| BV | 106 | VSD #2 COOLING SYS RUN | VSD #2 Cooling System Run (VSD only) | Read | 0=Not Running, 1=Running | |
| BV | 107 | VSD #1 HARMONIC FILTER INST | Harmonic Filter #1 Installed (LVVSD only) | Read | 0=False, 1=True | |
| BV | 108 | VSD #2 HARMONIC FILTER INST | Harmonic Filter #2 Installed (LVVSD only) | Read | 0=False, 1=True | |
| AV | 130 | FILTER #1 MAX VOLTAGE THD | Harmonic Filter #1 Max Voltage Total Harmonic Distortion (LVVSD/HF only) | % | Read | |
| AV | 131 | FILTER #2 MAX VOLTAGE THD | Harmonic Filter #2 Max Voltage Total Harmonic Distortion (LVVSD/HF only) | % | Read | |
| AV | 132 | FILTER #1 MAX CURRENT TDD | Harmonic Filter #1 Max Current Total Demand Distortion (LVVSD/HF only) | % | Read | |
| AV | 133 | FILTER #2 MAX CURRENT TDD | Harmonic Filter #2 Max Current Total Demand Distortion (LVVSD/HF only) | % | Read | |
| AV | 138 | MC 1 INPUT KWH LO | Input Kilowatt Hours Low #1 (see note 21) (VSD only) | Read | ||
| AV | 139 | MC 1 INPUT KWH OFFSET | Input Kilowatt Hours Offset #1 (see note 21) (VSD only) | Read | ||
| AV | 140 | MC 2 INPUT KWH LO | Input Kilowatt Hours Low #2 (see note 21) (VSD only) | Read | ||
| AV | 141 | MC 2 INPUT KWH OFFSET | Input Kilowatt Hours Offset #2 (see note 21) (VSD only) | Read | ||
| AV | 142 | OPERATING HOURS LO | Operating Hours Low (see note 22) | Read | ||
| AV | 143 | OPERATING HOURS OFFSET | Operating Hours Offset (see note 22) | Read |
No points match these filters.
Object ID lookup: York YD E-Link point IDs by name
AV1REM LEAVING CH LIQ TEMP SPAV2REM MOTOR CURRENT SPAV3REM COMP OPERATION MODEAV4REM COMP LOCKOUTBV1REM RUN STOP CMDAV5LEAVING CH LIQ TEMPAV6ENTERING CH LIQ TEMPAV7EVAPORATOR PRESSUREAV8CONDENSER PRESSUREAV9OIL DIFERENTL PRESSURE 1AV10OIL DIFERENTL PRESSURE 2AV11ENTERING COND WATER TEMPAV12LEAVING COND WATER TEMPAV13MOTOR CURRENT FLA 1AV14MOTOR CURRENT FLA 2AV15EVAP REFRIG TEMPAV16DROP LEG REFRIG TEMPAV17LEAVING CH LIQ TEMP ACT SPAV18MOTOR CURRENT ACTUAL SPAV19EVAP SATURATION TEMPAV20COND SATURATION TEMPAV21DISCHARGE TEMP 1AV22DISCHARGE TEMP 2AV23OIL SUMP TEMPERATUREAV24COND REFRIGERANT LEVELAV25ACCUM OPERATING HOURSAV26ACCUM SYSTEM STARTSAV27OIL SUMP PRESSUREAV28OIL PUMP PRESSURE 1AV29OIL PUMP PRESSURE 2BV5COMPR MOTOR STATUS 1BV6COMPR MOTOR STATUS 2BV8CH LIQ PUMP STATBV9START STOP SWITCH STATUSBV10CH LIQ FLOW SWITCH STATBV11CND FLOW SWITCH STATBV12DISCH HI PRESS SW 1BV13DISCH HI PRESS SW 2BV14VANE MOTOR SW 1BV15VANE MOTOR SW 2BV16REFRIGERANT LEVEL LOWERBV17REFRIGERANT LEVEL RAISEBV18OIL RETURN SOLONOIDBV19PRV OPENING 1BV20PRV OPENING 2BV21PRV CLOSING 1BV22PRV CLOSING 2MV1UNIT OPERATION CODEMV2UNIT SAFETY FAULT CODEMV3UNIT CYCLING FAULT CODEMV4UNIT WARNING CODEMV5UNIT MODIFIED RUN CODEMV6UNIT START INHIBIT CODEMV7UNIT INTERNAL FAULT CODEMV8UNIT CONTROL SOURCEAV30PROX SENSOR ACT POS 1AV31PROX SENSOR ACT POS 2AV32REFRIGERANT LEVEL SPAV33ANTI RECYC TIME REMAIN 1AV34ANTI RECYC TIME REMAIN 2AV35PRV POSITION 1AV36PRV POSITION 2AV37VGD POSITION 1AV38VGD POSITION 2AV39OIL LEVEL SUMPAV40COMP OPERATION MODEAV41COMP LOCKOUT MODEBV25DISCH VLV OPENING 1BV26DISCH VLV OPENING 2BV27DISCH VLV CLOSING 1BV28DISCH VLV CLOSING 2AV105MC 1 INPUT POWERAV106MC 2 INPUT POWERAV107MC 1 INPUT KWHAV108MC 2 INPUT KWHAV109VSD 1 OUTPUT VOLTAGEAV110VSD 2 OUTPUT VOLTAGEAV111VSD 1 OUTPUT FREQUENCYAV112VSD 2 OUTPUT FREQUENCYAV113MOTOR 1 PHASE A CURRENTAV114MOTOR 2 PHASE A CURRENTAV115MOTOR 1 PHASE B CURRENTAV116MOTOR 2 PHASE B CURRENTAV117MOTOR 1 PHASE C CURRENTAV118MOTOR 2 PHASE C CURRENTAV119VSD 1 DC BUS VOLTAGEAV120VSD 2 DC BUS VOLTAGEAV121VSD 1 DC BUS CURRENTAV122VSD 2 DC BUS CURRENTAV123VSD 1 INTERNAL AMBIENT TEMPAV124VSD 2 INTERNAL AMBIENT TEMPAV125VSD 1 CONVERTER HSINK TEMPAV126VSD 2 CONVERTER HSINK TEMPAV127FILTER #1 SUPPLY KVAAV128FILTER #2 SUPPLY KVABV105VSD #1 COOLING SYS RUNBV106VSD #2 COOLING SYS RUNBV107VSD #1 HARMONIC FILTER INSTBV108VSD #2 HARMONIC FILTER INSTAV130FILTER #1 MAX VOLTAGE THDAV131FILTER #2 MAX VOLTAGE THDAV132FILTER #1 MAX CURRENT TDDAV133FILTER #2 MAX CURRENT TDDAV138MC 1 INPUT KWH LOAV139MC 1 INPUT KWH OFFSETAV140MC 2 INPUT KWH LOAV141MC 2 INPUT KWH OFFSETAV142OPERATING HOURS LOAV143OPERATING HOURS OFFSET
Integration notes
- Every YorkTalk 3 E-Link sheet uses the same slot skeleton (P03 = AV 1 and so on); only the slots this chiller populates are listed, and slots marked not available on every program version are left out.
- Object names are the E-Link names printed on the sheet; the sheet also gives LON, N2 and Modbus addresses, not reproduced here.
- Access follows the sheet's Modbus function note: the remote slots AV 1-4 and BV 1-4 accept writes; the rest are read-only.
- Status code objects (MV) use the code tables in the sheet; it notes that BACnet multistate values are the printed code + 1. Printed states are shown from 0.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
How many BACnet points does the York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) have?
This list has 109 BACnet objects: 75 analog values, 26 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) BACnet points are writable?
5 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3) BACnet documentation?
The source is YD OptiView BAS E-Link points list, revision 2018-02-27 (Rev K_06f), published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/l7pWhFILYevobk9HZKrdBw/content.
What are the minimum BACnet points to integrate the York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)?
Start with BV 1 REM RUN STOP CMD (Remote start/stop (1 = run)); AV 1 REM LEAVING CH LIQ TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REM MOTOR CURRENT SP (Remote current limit, %); MV 8 UNIT CONTROL SOURCE (Must read ISN (BAS) for BMS control); MV 1 UNIT OPERATION CODE (Unit operating status code); BV 5 COMPR MOTOR STATUS 1 (Chiller running); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 6 ENTERING CH LIQ TEMP (Entering chilled liquid temperature); MV 2 UNIT SAFETY FAULT CODE (Safety (shutdown) fault code); MV 4 UNIT WARNING CODE (Active warning code).
How do I enable BMS control of the York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)?
The E-Link remote slots (AV 1-4, BV 1-4) are the BMS commands; the chiller panel must be set for remote (ISN/BAS) control for them to take effect.
How do I check these points on the real YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: YD OptiView BAS E-Link points list · rev. 2018-02-27 (Rev K_06f). Object names, instances and units are reproduced as published; descriptions are our own.