Air-cooled variable-speed screw chiller (via E-Link gateway) · BACnet points list

York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) BACnet points list

Updated 6 November 2026

Short answer

The E-Link gateway reads the YCAV/YCIV microboard over YorkTalk 2 (4800 baud) and serves BACnet, N2, LON and Modbus objects named by YorkTalk page: remote setpoint, ISN current and sound limits, start/stop, chilled liquid temperatures, per-system pressures, temperatures, run hours and starts, VSD values and status codes.

This page lists 114 BACnet objects for the York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
Equipment
Air-cooled variable-speed screw chiller (via E-Link gateway)
Equipment type
Chillers
BACnet objects
114 (5 writable)
Transport
—
Firmware
Not stated
Also known as
YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478
Source document
YCAV_YCIV BAS E-Link points list · rev. 2014-08-25 (Rev K_03g)
Download CSV 114 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)

Integration in brief

Put the chiller in remote/ISN control at the panel, then start and stop it with the E-Link remote run/stop object and write the remote setpoint and current limit. Read the operating, safety and warning codes, run status and water temperatures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1YT2_S01_P07Remote start/stop (1 = run)Write
AV 1YT2_S01_P03Remote leaving chilled liquid setpointWrite
AV 2YT2_S01_P04Remote current limit, %Write
BV 20YT2_S01_P51Must read Remote (1) for BMS controlRead
MV 1YT2_S01_P56System 1 operating codeRead
BV 5YT2_S01_P36Chiller runningRead
AV 5YT2_S01_P11Leaving chilled liquid temperatureRead
AV 6YT2_S01_P12Entering chilled liquid temperatureRead
MV 2YT2_S01_P57System 1 fault codeRead
BV 6YT2_S01_P37Chiller alarm (1 = alarm)Read

Enable & remote start

The E-Link remote slots (AV 1-4, BV 1-4) are the BMS commands; the chiller panel must be set for remote (ISN/BAS) control for them to take effect.

Network setup

Watch out for

York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

114 of 114 shown
Type
AnalogBinaryMulti-state
Access
Show
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) BACnet Points List
DescriptionStates
AVmin1YT2_S01_P03Setpoint ( Start command must be active to take effect)°FWrite
AVmin2YT2_S01_P04ISN Current Limit Start command must be active to take effect%Write
AV3YT2_S01_P05ISN Sound Limit ( RSL Option must be enabled or this point ignored)%Write
BVmin1YT2_S01_P07Start / Stop CommandWrite
BV4YT2_S01_P10History Buffer 1 RequestWrite
AVmin5YT2_S01_P11Leaving Chilled Liquid Temp°FRead
AVmin6YT2_S01_P12Return Chilled Liquid Temp°FRead
AV7YT2_S01_P13VSD Internal Ambient Temp°FRead
AV8YT2_S01_P14Sys 1 Suction Temperature°FRead
AV9YT2_S01_P15Sys 1 Discharge Temperature°FRead
AV10YT2_S01_P16Outside Ambient Air Temperature°FRead
AV11YT2_S01_P17Sys 1 Oil Temperature°FRead
AV12YT2_S01_P18Sys 1 Oil Pressure (gauge)psiRead
AV13YT2_S01_P19Sys 1 Suction Pressure (gauge)psiRead
AV14YT2_S01_P20Sys 1 Discharge Pressure (gauge)psiRead
AV15YT2_S01_P21Sys 1 Compressor % Full Load Amps%Read
AV16YT2_S01_P22Sys 1 Total Run HourshoursRead
AV17YT2_S01_P23Sys 1 Total Number of StartsRead
AV18YT2_S01_P24Sys 1 Highest Motor Temp°FRead
AV19YT2_S01_P25Sys 2 Highest Motor Temp°FRead
AV20YT2_S01_P26Sys 2 Oil Temperature°FRead
AV21YT2_S01_P27Sys 2 Oil Pressure (gauge)psiRead
AV22YT2_S01_P28Sys 2 Suction Pressure (gauge)psiRead
AV23YT2_S01_P29Sys 2 Discharge Pressure (gauge)psiRead
AV24YT2_S01_P30Sys 2 Compressor % Full Load Amps%Read
AV25YT2_S01_P31Sys 2 Total Run HourshoursRead
AV26YT2_S01_P32Sys 2 Total Number of StartsRead
AV27YT2_S01_P33VSD Output FrequencyHzRead
AV28YT2_S01_P34Sys 1 Flash Tank Feed Valve % Open%Read
AV29YT2_S01_P35Sys 2 Flash Tank Feed Valve % Open%Read
BVmin5YT2_S01_P36Chiller RunRead
BVmin6YT2_S01_P37Chiller AlarmRead0=no alarm, 1=alarm
BV7YT2_S01_P38Evaporator Heater StatusRead
BV8YT2_S01_P39Evaporator Pump StatusRead
BV9YT2_S01_P40Sys 1 Compressor Run StatusRead
BV10YT2_S01_P41Sys 2 Compressor Run StatusRead
BV11YT2_S01_P42Sys 1 Economizer Solenoid Valve StatusRead
BV12YT2_S01_P43Sys 2 Economizer Solenoid Valve StatusRead
BV19YT2_S01_P50S1-1 Cooling TypeRead0=Water, 1=Glycol
BVmin20YT2_S01_P51Local/Remote Control ModeRead0=Local, 1=Remote
BV21YT2_S01_P52Display Units ModeRead0=Imperial, 1=SI
MVmin1YT2_S01_P56Sys 1 Operational CodeRead
MVmin2YT2_S01_P57Sys 1 Fault CodeRead
MV3YT2_S01_P58Sys 2 Operational CodeRead
MV4YT2_S01_P59Sys 2 Fault CodeRead
MV5YT2_S01_P60Sys 1 Flash Tank Level (%)Read
MV6YT2_S01_P61Sys 1 Condenser Fan Stages Running (0-7)Read
MV7YT2_S01_P62Sys 2 Flash Tank Level (%)Read
MV8YT2_S01_P63Sys 2 Condenser Fan Stages Running (0-7)Read
MV9YT2_S01_P64Lead System NumberRead
AV30YT2_S01_P66Local Leaving Chilled Liquid Setpoint°FRead
AV31YT2_S01_P67Low Leaving Chilled Liquid Temp Cutout°FRead
AV32YT2_S01_P68Sys 1 Flash Tank Drain Valve % Open%Read
AV33YT2_S01_P69Sys 2 Flash Tank Drain Valve % Open%Read
AV34YT2_S01_P70Low Suction Pressure CutoutpsiRead
AV35YT2_S01_P71VSD DC Bus VoltageVRead
AV36YT2_S01_P72Remote Leaving Chilled Liquid Setpoint°FRead
AV37YT2_S01_P73Sys 1 Suction Superheat°FRead
AV38YT2_S01_P74Cooling Range°FRead
AV39YT2_S01_P75Sys 1 Discharge Superheat°FRead
AV40YT2_S01_P76Sys 2 Suction Temperature°FRead
AV41YT2_S01_P77Sys 2 Discharge Temperature°FRead
AV42YT2_S01_P78Sys 2 Suction Superheat°FRead
AV43YT2_S01_P79Sys 2 Discharge Superheat°FRead
BV25YT2_S01_P80Sys 1 LockoutRead
BV26YT2_S01_P81Sys 2 LockoutRead
AV105YT2_S02_P11Leaving Chilled Liquid Temp°FRead
AV106YT2_S02_P12Return Chilled Liquid Temp°FRead
AV107YT2_S02_P13VSD Internal Ambient Temp 2°FRead
AV108YT2_S02_P14Sys 3 Suction Temperature°FRead
AV109YT2_S02_P15Sys 3 Discharge Temperature°FRead
AV111YT2_S02_P17Sys 3 Oil Temperature°FRead
AV112YT2_S02_P18Sys 3 Oil PressurepsiRead
AV113YT2_S02_P19Sys 3 Suction PressurepsiRead
AV114YT2_S02_P20Sys 3 Discharge PressurepsiRead
AV115YT2_S02_P21Sys 3 Compressor % Full Load Amps%Read
AV116YT2_S02_P22Sys 3 Total Run HourshoursRead
AV117YT2_S02_P23Sys 3 Total # of StartsRead
AV118YT2_S02_P24Sys 3 Highest Motor Temp°FRead
AV119YT2_S02_P25Sys 4 Highest Motor Temp°FRead
AV120YT2_S02_P26Sys 4 Oil Temperature°FRead
AV121YT2_S02_P27Sys 4 Oil PressurepsiRead
AV122YT2_S02_P28Sys 4 Suction PressurepsiRead
AV123YT2_S02_P29Sys 4 Discharge PressurepsiRead
AV124YT2_S02_P30Sys 4 Compressor % Full Load Amps%Read
AV125YT2_S02_P31Sys 4 Total Run HourshoursRead
AV126YT2_S02_P32Sys 4 Total # of StartsRead
AV127YT2_S02_P33VSD Output Frequency 2HzRead
AV128YT2_S02_P34Sys 3 Flask Tank Feed Valve % Open%Read
AV129YT2_S02_P35Sys 4 Flask Tank Feed Valve % Open%Read
BV109YT2_S02_P40Sys 3 Compressor Run StatusRead
BV110YT2_S02_P41Sys 4 Compressor Run StatusRead
BV111YT2_S02_P42Sys 3 Economizer Solenoid Valve StatusRead
BV112YT2_S02_P43Sys 4 Economizer Solenoid Valve StatusRead
MV101YT2_S02_P56Sys 3 Operational CodeRead
MV102YT2_S02_P57Sys 3 Fault CodeRead
MV103YT2_S02_P58Sys 4 Operational CodeRead
MV104YT2_S02_P59Sys 4 Fault CodeRead
MV105YT2_S02_P60Sys 3 Flash Tank Level %Read
MV106YT2_S02_P61Sys 3 Condenser Fan Stage ( 0-7 )Read
MV107YT2_S02_P62Sys 4 Flash Tank Level %Read
MV108YT2_S02_P63Sys 4 Condenser Fan Stage ( 0-7)Read
MV110YT2_S02_P65Sys 3 & 4 Debug CodeRead
AV132YT2_S02_P68Sys 3 Flash Tank Drain Valve % Open%Read
AV133YT2_S02_P69Sys 4 Flash Tank Drain Valve % Open%Read
AV135YT2_S02_P71VSD DC Bus Voltage 2VRead
AV137YT2_S02_P73Sys 3 Suction Superheat°FRead
AV139YT2_S02_P75Sys 3 Discharge Superheat°FRead
AV140YT2_S02_P76Sys 4 Suction Temperature°FRead
AV141YT2_S02_P77Sys 4 Discharge Temperature°FRead
AV142YT2_S02_P78Sys 4 Suction Superheat°FRead
AV143YT2_S02_P79Sys 4 Discharge Superheat°FRead
BV125YT2_S02_P80Sys 3 LockoutRead
BV126YT2_S02_P81Sys 4 LockoutRead
Object ID lookup: York YCAV / YCIV E-Link point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)

How many BACnet points does the York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) have?

This list has 114 BACnet objects: 75 analog values, 21 binary values, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) BACnet points are writable?

5 of the 114 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2) BACnet documentation?

The source is YCAV_YCIV BAS E-Link points list, revision 2014-08-25 (Rev K_03g), published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/F5MxE~19WRFrMvSKgqKvYA/content.

What are the minimum BACnet points to integrate the York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)?

Start with BV 1 YT2_S01_P07 (Remote start/stop (1 = run)); AV 1 YT2_S01_P03 (Remote leaving chilled liquid setpoint); AV 2 YT2_S01_P04 (Remote current limit, %); BV 20 YT2_S01_P51 (Must read Remote (1) for BMS control); MV 1 YT2_S01_P56 (System 1 operating code); BV 5 YT2_S01_P36 (Chiller running); AV 5 YT2_S01_P11 (Leaving chilled liquid temperature); AV 6 YT2_S01_P12 (Entering chilled liquid temperature); MV 2 YT2_S01_P57 (System 1 fault code); BV 6 YT2_S01_P37 (Chiller alarm (1 = alarm)).

How do I enable BMS control of the York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)?

The E-Link remote slots (AV 1-4, BV 1-4) are the BMS commands; the chiller panel must be set for remote (ISN/BAS) control for them to take effect.

How do I check these points on the real YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.