- Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
Packaged rooftop unit controller (Series 100, 50-65 ton) · BACnet points list
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet points list
Updated 6 November 2026
The 50-65 ton Series 100 rooftop's IPU control board speaks BACnet MS/TP on Port 1 and Modbus on Port 4. The table lists about 240 objects: air temperatures, pressures, airflows, CO2, unit mode and ten active fault and three warning codes as AIs; compressor, fan, heat and fault BIs; setpoints, limits and BAS inputs (zone, outdoor temperature and humidity) as AVs; and 0/1 BAS commands published as both AVs and BVs. Hot gas reheat points are included.
This page lists 243 BACnet objects for the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) — 98 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
- Equipment
- Packaged rooftop unit controller (Series 100, 50-65 ton)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 243 (98 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 23000 + MAC address
- Also known as
- YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
Connect to Port 1 of the IPU control board on BACnet MS/TP. Command occupancy with OCCUPNCY_CMD, stop or release the unit with UNIT_STOP and write the occupied zone setpoints; feed zone temperature through AV 40 if the control method is set to comm zone temp. Read supply air and zone temperatures, supply fan status, unit mode and the fault inputs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 88 | OCCUPNCY_CMD | Occupancy command (1 = occupied) | Write |
| AV 93 | UNIT_STOP | Unit stop (1 = stopped, 0 = normal) | Write |
| AV 21 | OCC_ZN_COOL | Occupied zone cooling setpoint | Write |
| AV 22 | OCC_ZN_HEAT | Occupied zone heating setpoint | Write |
| AI 58 | UNIT_MODE | Current operating mode index | Read |
| BI 59 | SUPPLY_FAN | Supply fan on/off | Read |
| AI 46 | SUP_AIR_TEMP | Supply air temperature | Read |
| AI 60 | ZONE_TEMP | Zone temperature | Read |
| BI 2 | COL/HEAT_FLT | Cooling/heating fault (1 = faulted) | Read |
| AI 71 | FAULT_1 | Active fault code 1 | Read |
Enable & remote start
OCCUPNCY_CMD (AV 88 or BV 12) puts the unit in occupied (1) or unoccupied (0) mode and UNIT_STOP (AV 93 or BV 17) stops it (1) or returns it to normal operation (0). BAS reset and BAS sensor inputs must first be enabled at the unit with the SERVICE key; AV 40 zone temperature needs the control method set to comm zone temp.
Sensors & values from the BMS
AV 40 ZONE_TEMP_BAS feeds zone temperature when the control method is set to comm zone temp. AV 55 OAT_CURR_BAS, AV 56 OAH_CURR_BAS and AV 61 HUM_LVL_BAS feed outdoor temperature, outdoor humidity and zone humidity once enabled in the unit. AV 43 CO2_INSIDE and the BAS reset values (duct static, supply air) must be enabled with the SERVICE key before they are used.
Network setup
- Port 1 carries BACnet MS/TP (P1 PROTOCOL = BACNET); baud 1200 to 76800 is set with the SERVICE key.
- MAC address 0-127 from the IPU DIP switches or P1 MANUAL MAC ADDRESS; the device instance defaults to 23000 + MAC, or DE MODIFIER ADDRESS x 100 + DE MODIFIER OFFSET.
- Cycle main power after changing the MAC address or port settings.
- The Ethernet port is not functional; BACnet IP needs a gateway (the manual suggests a JCI NCE).
- LON and N2 need an E-Link gateway on Port 1.
Watch out for
- Each 0/1 command is listed as both an AV and a BV with the same name; use one of them, not both.
- Points marked FlexSys, VAV, CV or 70-150 ton only report only on those units.
- Setpoint and status AIs report in imperial units.
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | ACT_DSP_SP | Duct static press active SP | Read | ||
| AI | 2 | ACT_MIN_FLOW | Active minimum airflow | Read | ||
| AI | 3 | ACT_MIN_POS | Active minimum position | Read | ||
| AI | 4 | ACT_SAT_SP | Active supply air temp SP | Read | ||
| AV | 77 | ACT_SLAB_CTL | Active slab control (FLEXSYS only) | Write | ||
| BV | 1 | ACT_SLAB_CTL | Active slab control (FLEXSYS only) | Write | ||
| BI | 1 | AMORN_WA_ACT | Adaptive morning warmup status (only used with internal time clock) | Read | ||
| AI | 5 | BLD_STAT_PRS | Building pressure current | Read | ||
| AV | 1 | BULD_PRES_SP | Bldg press SP | Write | ||
| AI | 6 | BYPASS_DAMPER | Bypass damper position (FLEXSYS only) | Read | ||
| AI | 7 | CO2_1_OUT | CO2 level of the outside air | Read | ||
| AI | 8 | CO2_2_IN | CO2 level of the inside air | Read | ||
| AV | 43 | CO2_INSIDE | CO2 lvl inside value BAS | Write | ||
| AV | 2 | CO2_OFFSET | CO2 offset SP | Write | ||
| BImin | 2 | COL/HEAT_FLT | Cooling/heating fault status | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| AV | 78 | COMFORT_VENT | Comfort ventilation (constant volume) | Write | 0=OFF, 1=ON | |
| BV | 2 | COMFORT_VENT | Comfort ventilation (constant volume) | Write | 0=OFF, 1=ON | |
| BI | 3 | COMP_1A | Compressor 1A status | Read | 0=OFF, 1=ON | |
| AI | 9 | COMP_1A_OPER | Comp 1A operating HRS | hours | Read | |
| BI | 4 | COMP_1B | Compressor 1B status | Read | 0=OFF, 1=ON | |
| AI | 10 | COMP_1B_OPER | Comp 1B operating HRS | hours | Read | |
| BI | 5 | COMP_2A | Compressor 2A status | Read | 0=OFF, 1=ON | |
| AI | 11 | COMP_2A_OPER | Comp 2A operating HRS | hours | Read | |
| BI | 6 | COMP_2B | Compressor 2B status | Read | 0=OFF, 1=ON | |
| AI | 12 | COMP_2B_OPER | Comp 2B operating HRS | hours | Read | |
| BI | 7 | COMP_3A | Compressor 3A status (70-150 ton only) | Read | 0=OFF, 1=ON | |
| AI | 13 | COMP_3A_OPER | Comp 3A operating HRS (70-150 ton only) | hours | Read | |
| BI | 8 | COMP_3B | Compressor 3B status (70-150 ton only) | Read | 0=OFF, 1=ON | |
| AI | 14 | COMP_3B_OPER | Comp 3B operating HRS (70-150 ton only) | hours | Read | |
| BI | 9 | COMP_LPCO_1 | Safety input LPCO CKT 1 status | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| BI | 10 | COMP_LPCO_2 | Safety input LPCO CKT 2 status | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| BI | 11 | COMP_LPCO_3 | Safety input LPCO CKT 3 status (70-150 ton only) | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| BI | 12 | COMP_STAT_1 | Safety chain CKT 1 status | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| BI | 13 | COMP_STAT_2 | Safety chain CKT 2 status | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| BI | 14 | COMP_STAT_3 | Safety chain CKT 3 status (70-150 ton only) | Read | 0=Normal (OKAY), 1=Fault(ed) | |
| BI | 15 | COND_FAN_1A | Cond fan 1A/1 status | Read | 0=OFF, 1=ON | |
| BI | 16 | COND_FAN_1B | Cond fan 1B/2 status | Read | 0=OFF, 1=ON | |
| BI | 17 | COND_FAN_2A | Cond fan 2A/3 status | Read | 0=OFF, 1=ON | |
| BI | 18 | COND_FAN_2B | Cond fan 2B/4 status | Read | 0=OFF, 1=ON | |
| BI | 19 | COND_FAN_3A | Cond fan 3A/5 status (70-150 ton only | Read | 0=OFF, 1=ON | |
| BI | 20 | COND_FAN_3B | Cond fan 3B/6 status (70-150 ton only) | Read | 0=OFF, 1=ON | |
| AI | 15 | COND_FAN_SPD | Cond fan speed | Read | ||
| AV | 79 | CONTINU_VENT | Continuous ventilation (constant volume) | Write | 0=OFF, 1=ON | |
| BV | 3 | CONTINU_VENT | Continuous ventilation (constant volume) | Write | 0=OFF, 1=ON | |
| AI | 16 | DCT_ST_PR_RT | Duct static press reset | % | Read | |
| AI | 17 | DCT_STAT_PRS | Duct static press current (VAV or FLEXSYS) | Read | ||
| AV | 80 | DEW_PNT_RST | Dew point reset (FLEXSYS) | Write | 0=OFF, 1=ON | |
| BV | 4 | DEW_PNT_RST | Dew point reset (FLEXSYS) | Write | 0=OFF, 1=ON | |
| AV | 3 | DSP_HI_LIMIT | Duct static reset high SP (VAV or FLEXSYS) | Write | ||
| AV | 4 | DSP_LO_LIMIT | Duct static reset low SP (VAV or FLEXSYS) | Write | ||
| AV | 5 | DSP_RST_BAS | Duct static press reset BAS (VAV or FLEXSYS) | % | Write | |
| AI | 18 | ECON_ME_USED | ECON method active | Read | 1=DRY BULB, 2=SINGLE ENTHALPY, 3=DUAL ENTHALPY, 4=BEST METHOD AVAIL | |
| AI | 19 | ECON_STATUS | ECON system status | Read | 1=INSTALLED AND ACTIVE, 2=NOT INSTALLED, 3=DISABLED | |
| AV | 81 | ECONO_INSTAL | Economizer system | Write | 0=OFF, 1=ON | |
| BV | 5 | ECONO_INSTAL | Economizer system | Write | 0=OFF, 1=ON | |
| AV | 6 | ECONO_METHOD | ECON method to use | Write | 1=DRY BULB, 2=SINGLE ENTHALPY, 3=DUAL ENTHALPY, 4=BEST METHOD AVAIL | |
| AV | 7 | EL_AIR_TMP_H | EVAP leaving air temp high SP (FLEXSYS) | Write | ||
| AV | 8 | EL_AIR_TMP_L | EVAP leaving air temp low SP (FLEXSYS) | Write | ||
| AI | 20 | EVAP_AIR_TMP | FLEXSYS EVAP temp current (FLEXSYS) | Read | ||
| AV | 52 | EXH_DAMPER/VFD | Exhaust damper BAS control | Write | ||
| BI | 21 | EXH_FAN_STAT | Exhaust fan status | Read | 0=OPEN, 1=CLOSED | |
| BI | 22 | EXHAUST_FAN | Exhaust fan output status | Read | 0=OFF, 1=ON | |
| AI | 21 | EXHAUST_OUT | Exhaust damper position | % | Read | |
| BI | 23 | FAN_FAULT | Fan fault status | Read | 0=NO FAULT, 1=FAULT | |
| BI | 24 | FAN_G | Fan (G) status | Read | 0=OFF, 1=ON | |
| AV | 82 | FAN_G_BAS | Fan (G) BAS | Write | 0=OFF, 1=ON | |
| BV | 6 | FAN_G_BAS | Fan (G) BAS | Write | 0=OFF, 1=ON | |
| AImin | 71 | FAULT_1 | Fault 1 | Read | ||
| AI | 72 | FAULT_2 | Fault 2 | Read | ||
| AI | 73 | FAULT_3 | Fault 3 | Read | ||
| AI | 74 | FAULT_4 | Fault 4 | Read | ||
| AI | 75 | FAULT_5 | Fault 5 | Read | ||
| AI | 76 | FAULT_6 | Fault 6 | Read | ||
| AI | 77 | FAULT_7 | Fault 7 | Read | ||
| AI | 78 | FAULT_8 | Fault 8 | Read | ||
| AI | 79 | FAULT_9 | Fault 9 | Read | ||
| AI | 80 | FAULT_10 | Fault 10 | Read | ||
| BI | 25 | FILTER_STATS | Filter status | Read | 0=NORMAL (OKAY), 1=FAULT (CHANGE) | |
| BI | 26 | FURN_OUT_1 | Elect heat stage 1 status staged gas furn 1 lo status mod gas furn 1A low | Read | 0=OFF, 1=ON | |
| BI | 27 | FURN_OUT_2 | Elect heat stage 2 status staged gas furn 1 high status mod gas furn 1A high | Read | 0=OFF, 1=ON | |
| BI | 28 | FURN_OUT_3 | Elect heat stage 3 status staged gas furn 2 low status mod gas furn 2 low | Read | 0=OFF, 1=ON 6 | |
| BI | 29 | FURN_OUT_4 | Elect heat stage 4 status staged gas furn 2 high status mod gas furn 2 high | Read | 0=OFF, 1=ON | |
| BI | 30 | FURN_OUT_5 | Elect heat stage 5 status staged gas furn 3 low status mod gas furn 3 low | Read | 0=OFF, 1=ON | |
| BI | 31 | FURN_OUT_6 | Elect heat stage 6 status staged gas furn 3 high status mod gas furn 3 high | Read | 0=OFF, 1=ON | |
| BI | 32 | FURN_OUT_7 | Elect heat stage 7 status mod gas furn 1B status | Read | 0=OFF, 1=ON | |
| AV | 83 | HEAT_ENABLE | Heating system | Write | 0=USER DISABLED, 1=USER ENABLED | |
| BV | 7 | HEAT_ENABLE | Heating system | Write | 0=USER DISABLED, 1=USER ENABLED | |
| AI | 22 | HEAT_ENT_TEMP | Heat entering temp | Read | ||
| AI | 23 | HEAT_STAGES | Electric heat stages or gas heat stages | Read | ||
| AV | 84 | HEAT_VACTION | Hw valve action | Write | 0=DIRECT, 1=REVERSE | |
| BV | 8 | HEAT_VACTION | Hw valve action | Write | 0=DIRECT, 1=REVERSE | |
| AV | 9 | HEATING_SAT | Heating suppy sir temp SP (VAV or FLEXSYS) | Write | ||
| AI | 24 | HEATING_VLV | Heating valve | % | Read | |
| BI | 77 | HGRH_BLEED_V | HGRH bleed valve | Read | ||
| BV | 25 | HGRH_CONTROL | HGRH control | Write | 0=ENABLED, 1=DISABLED | |
| AI | 81 | HGRH_SAT_ASP | HGRH SAT-ACTIVE SP | Read | ||
| AV | 59 | HGRH_SAT_HSP | HGRH SAT high SP | °F | Write | |
| AV | 60 | HGRH_SAT_LSP | HGRH SAT low SP | °F | Write | |
| AI | 67 | HGRH_VLV_POS | HGRH valve position | Read | ||
| AV | 61 | HUM_LVL_BAS | Humidity level BAS | %RH | Write | |
| BI | 33 | HW_FRZ_STAT | Hw/steam coil freezestat status | Read | 0=NO FAULT (OKAY), 1=FAULTED | |
| BI | 34 | LOCAL_STOP | Local stop status | Read | ||
| AV | 10 | MAX_BYPASS | Maximum bypass SP (FLEXSYS) | Write | ||
| AV | 11 | MAX_FLOW_DV | Outside air max flow SP | CFM | Write | |
| AV | 12 | MECH_LCK_TMP | Mech cooling lockout SP | Write | ||
| AV | 13 | MIN_FLOW_DV | Outside air min flow SP | CFM | Write | |
| AV | 51 | MIN_OA_FLO | Minimum OA flow setpoint | CFM | Write | |
| AV | 14 | MIXD_SAT_LIM | MX supply air temp SP (FLEXSYS) | Write | ||
| AV | 85 | MORN_WARM_UP | Morning warm up | Write | 0=ENABLED, 1=DISABLED | |
| BV | 9 | MORN_WARM_UP | Morning warm up | Write | 0=ENABLED, 1=DISABLED | |
| AV | 86 | MORN_WUP_CMD | Morn warmup command | Write | 0=OFF, 1=ON | |
| BV | 10 | MORN_WUP_CMD | Morn warmup command | Write | 0=OFF, 1=ON | |
| AV | 87 | NIGHT_SETBAC | Night setback for heating | Write | 0=OFF, 1=ON | |
| BV | 11 | NIGHT_SETBAC | Night setback for heating | Write | 0=OFF, 1=ON | |
| AV | 56 | OAH_CURR_BAS | Outside humidity BAS | %RH | Write | |
| AV | 55 | OAT_CURR_BAS | Outside temp BAS | °F | Write | |
| AV | 16 | OA_DAMP_POS1 | OA damper minimum position | Write | ||
| AV | 17 | OA_DAMP_POS2 | OA damper maximum position | Write | ||
| AI | 25 | OA_DAMPER | OA damper position current | % | Read | |
| AV | 18 | OA_ENTH_LIMIT | OA enthalpy SP | BTU/lb | Write | |
| AI | 26 | OA_ENTHALPY | OA enthalpy | BTU/lb | Read | |
| AI | 27 | OA_FLO_PRS_1 | OA flow press 1 | Read | ||
| AI | 28 | OA_FLO_PRS_2 | OA flow press 2 | Read | ||
| AI | 61 | OA_FLOW_1 | IAQ damper air flows OA flow 1 | CFM | Read | |
| AI | 62 | OA_FLOW_2 | IAQ damper air flows OA flow 2 | Read | ||
| AI | 63 | OA_FLOW_TOTL | OA flow total | CFM | Read | |
| AI | 29 | OA_REL_HUMID | OA humidity | % | Read | |
| AI | 30 | OA_TEMP | OA temperature | Read | ||
| AV | 19 | OAT_HIGH_SAT | OA temp SP for hi supply air temp (VAV, and only if SAT reset method is | Write | ||
| AV | 20 | OAT_LOW_SAT | OA temp SP for lo supply air temp (VAV, and only if SAT rest method is | Write | ||
| BI | 35 | OCC_MODE | Occupancy mode status | Read | ||
| BI | 36 | OCC_STATE | Occupancy state status | Read | ||
| AVmin | 21 | OCC_ZN_COOL | OCC zone cooling SP | Write | ||
| AVmin | 22 | OCC_ZN_HEAT | OCC zone heating SP | Write | ||
| AVmin | 88 | OCCUPNCY_CMD | Occupancy command | Write | 0=UNOCC, 1=OCC | |
| BV | 12 | OCCUPNCY_CMD | Occupancy command | Write | 0=UNOCC, 1=OCC | |
| AI | 31 | PRS_1_DISCH | Disch press CKT 1 | psig | Read | |
| AI | 32 | PRS_1_SUCT | Suct press CKT 1 | psig | Read | |
| AI | 33 | PRS_2_DISCH | Disch press CKT 2 | psig | Read | |
| AI | 34 | PRS_2_SUCTION | Suct press CKT 2 | psig | Read | |
| AI | 35 | PRS_3_DISCH | Disch press CKT 3 (70- 150 ton only) | psig | Read | |
| AI | 36 | PRS_3_SUCT | Suct press CKT 3 (70-150 ton only) | psig | Read | |
| AV | 89 | PUMP_DOWN | Pump down | Write | 0=ON, 1=OFF | |
| BV | 13 | PUMP_DOWN | Pump down | Write | 0=ON, 1=OFF | |
| BI | 37 | PUMP_DOWN_1 | Pump down LLSV 1 status | Read | 0=Pump Down LLSV (OFF), 1=Pump Down LLSV (ON) | |
| BI | 38 | PUMP_DOWN_2 | Pump down LLSV 2 status | Read | 0=Pump Down LLSV (OFF), 1=Pump Down LLSV (ON) | |
| BI | 39 | PUMP_DOWN_3 | Pump down LLSV 3 status (70-150 ton only) | Read | 0=Pump Down LLSV (OFF), 1=Pump Down LLSV (ON) | |
| AV | 42 | RA_DIFF_BAS | Return air diff SP BAS (FLEXSYS) | Write | ||
| AI | 82 | RA_HUM_ACT | Return air-humidity active | %RH | Read | |
| AV | 23 | RAT_COOL_SP | Cooling return air temp SP (VAV or FLEXSYS) | Write | ||
| AV | 15 | RAT_HEAT_SP | Heating ret air temp SP (VAV or FLEXSYS) | Write | ||
| AV | 24 | RAT_HIGH_SAT | RA temp SP for hi supply air temp (VAV, and only if SAT reset method is | Write | ||
| AV | 25 | RAT_LOW_SAT | RA temp SP for lo supply air temp (VAV, and only if SAT reset method is | Write | ||
| BI | 40 | RDY_RUN_C1A | Ready to run comp 1A status | Read | ||
| BI | 41 | RDY_RUN_C1B | Ready to run comp 1B status | Read | ||
| BI | 42 | RDY_RUN_C2A | Ready to run comp 2A status | Read | ||
| BI | 43 | RDY_RUN_C2B | Ready to run comp 2B status | Read | ||
| BI | 44 | RDY_RUN_C3A | Ready to run comp 3A status (70-150 ton only) | Read | ||
| BI | 45 | RDY_RUN_C3B | Ready to run comp 3B status (70-150 ton only) | Read | ||
| BI | 46 | RDY_STOP_C1A | Ready to stop comp 1A status | Read | ||
| BI | 47 | RDY_STOP_C1B | Ready to stop comp 1B status | Read | ||
| BI | 48 | RDY_STOP_C2A | Ready to stop comp 2A status | Read | ||
| BI | 49 | RDY_STOP_C2B | Ready to stop comp 2B status | Read | ||
| BI | 50 | RDY_STOP_C3A | Ready to stop comp 3A status (70-150 ton only) | Read | ||
| BI | 51 | RDY_STOP_C3B | Ready to stop comp 3B status (70-150 ton only) | Read | ||
| AI | 37 | RET_AIR_BY_S | Return air bypass active SP | % | Read | |
| AI | 38 | RET_AIR_ENTH | Return air enthalpy | Read | ||
| AI | 39 | RET_AIR_HUMD | Return air humidity | % | Read | |
| AI | 40 | RET_AIR_TEMP | Return air temp current | °F | Read | |
| AI | 41 | RET_FAN_OUT | Exhaust/return fan VFD | % | Read | |
| AI | 42 | RET_FAN_PRES | Return fan pressure current | Read | ||
| BI | 52 | RET_FAN_STAT | Return fan status | Read | 0=STOP/ VERIFICATION CKT OPEN, 1=RUN/ VERIFICATION CKT CLOSED | |
| AV | 41 | RST_ENT_BAS | Reset enthalpy SP BAS | Write | ||
| AV | 26 | SAT_HIGH_LIM | Suppy air temp hi SP | °F | Write | |
| AV | 27 | SAT_LOW_LIM | Supply air temp lo SP | °F | Write | |
| AV | 28 | SAT_RST_BAS | Supply air temp reset BAS | Write | ||
| AI | 43 | SAT_SUC_TMP1 | Saturated suct temp CKT 1 | °F | Read | |
| AI | 44 | SAT_SUC_TMP2 | Saturated suct temp CKT 2 | °F | Read | |
| AI | 45 | SAT_SUC_TMP3 | Saturated suct temp CKT 3 (70-150 ton only) | °F | Read | |
| BI | 53 | SAT_TEMPER | Supply air tempering status | Read | ||
| BI | 54 | SEN/MSC_FLT | Sensor/misc fault status | Read | 0=NO FAULT, 1=FAULTED | |
| BI | 55 | SF_PROV_SW | Supply fan status | Read | 0=STOP VERIFICATION/CKT OPEN, 1=RUN VERIFICATION/CKT CLOSED | |
| AV | 29 | SF_SPD_H_SAT | Fan speed SP for hi supply air temp | Write | ||
| AV | 30 | SF_SPD_L_SAT | Fan speed SP for lo supply air temp | Write | ||
| BI | 56 | SMOKE_PUR_1 | Smoke purge 1 status | Read | ||
| BI | 57 | SMOKE_PUR_2 | Smoke purge 2 status | Read | ||
| BI | 58 | SMOKE_PUR_3 | Smoke purge 3 status | Read | ||
| AV | 90 | SMOKE_PUR1_B | Smoke purge 1 BAS | Write | 0=OFF, 1=ON | |
| BV | 14 | SMOKE_PUR1_B | Smoke purge 1 BAS | Write | 0=OFF, 1=ON | |
| AV | 91 | SMOKE_PUR2_B | Smoke purge 2 BAS | Write | 0=OFF, 1=ON | |
| BV | 15 | SMOKE_PUR2_B | Smoke purge 2 BAS | Write | 0=OFF, 1=ON | |
| AV | 92 | SMOKE_PUR3_B | Smoke purge 3 BAS | Write | 0=OFF, 1=ON) 6 | |
| BV | 16 | SMOKE_PUR3_B | Smoke purge 3 BAS | Write | 0=OFF, 1=ON) 6 | |
| AV | 31 | STG_1_COOL | 1ST stage cooling SP (cv/szvav) | Write | ||
| AV | 32 | STG_1_HEAT | 1ST stage heating SP (cv/szvav) | Write | ||
| AV | 33 | STG_2_COOL | 2ND stage cooling SP (cv/szvav) | Write | ||
| AV | 34 | STG_2_HEAT | 2ND stage heating SP (cv/szvav) | Write | ||
| AImin | 46 | SUP_AIR_TEMP | Supply air temp current | °F | Read | |
| AI | 47 | SUP_AIR_TRST | Supply air temp reset | VDC | Read | |
| AI | 48 | SUP_FAN_VFD | Supply fan VFD speed | % | Read | |
| BImin | 59 | SUPPLY_FAN | Supply fan output status | Read | 0=OFF, 1=ON | |
| AV | 35 | SYSTEM_STOP | System stop | Write | 0=ALL CKTS CAN OPERATE, 1=SHUTS DOWN CKT 1, 2=SHUTS DOWN CKT 2, 3=SHUTS DOWN CKT 3 | |
| AV | 53 | SZ_MIN_VFD | Single zone minimum VFD | Write | ||
| AI | 49 | TEMP_1_SUCT | Suct temp CKT 1 | °F | Read | |
| AI | 50 | TEMP_1_SUPER | Suct superheat CKT 1 | °F | Read | |
| AI | 51 | TEMP_2_SUCT | Suct temp CKT 2 | °F | Read | |
| AI | 52 | TEMP_2_SUPER | Suct superheat CKT 2 | °F | Read | |
| AI | 53 | TEMP_3_SUCT | Suct temp CKT 3 (70-150 ton only) | °F | Read | |
| AI | 54 | TEMP_3_SUPER | Suct superheat CKT 3 (70-150 ton only) | °F | Read | |
| AI | 55 | UND_FLR_DEWP | Underfloor slab dew point (FLEXSYS) | °F | Read | |
| AI | 56 | UND_FLR_HUMD | Underfloor air humidity (FLEXSYS) | °F | Read | |
| AI | 57 | UND_FLR_TEMP | Undefloor slab temp (FLEXSYS) | °F | Read | |
| AV | 36 | UND_HUMD_BAS | Underfloor air humidity BAS | % | Write | |
| AV | 37 | UND_TEMP_BAS | Underfloor slab temp BAS | °F | Write | |
| AImin | 58 | UNIT_MODE | Current oper mode | Read | 0=OCC COOL, 1=OCC COOL LOW, 2=OCC COOL HIGH, 3=OCC COOL W/ BYP, 4=OCC COOL W/O BYP, 5=OCC HEAT, 6=OCC HEAT LOW, 7=OCC HEAT HIGH, 8=OCC STANDBY, 9=UNOCC COOL, 10=UNOCC COOL LOW, 11=UNOCC COOL HIGH, 12=UNOCC HEAT, 13=UNOCC HEAT LOW, 14=UNOCC HEAT HIGH, 15=UNOCC STANDBY, 16=COMFORT VENT COOL, 17=COMFORT VENT HEAT, 18=NIGHT SET-BACK, 19=MORNING WARM-UP, 20=OCC DEHUM W/ COOL, 21=OCC DEHUM COOL HI, 22=OCC DEHUM COOL LO, 23=UNOCC DEHUM W/ COOL, 24=UNOCC DEHUM COOL HI, 25=UNOCC DEHUM COOL LO 6 | |
| AVmin | 93 | UNIT_STOP | Unit stop | Write | 0=NORMAL OPERATION, 1=UNIT STOPPED | |
| BV | 17 | UNIT_STOP | Unit stop | Write | 0=NORMAL OPERATION, 1=UNIT STOPPED | |
| BI | 60 | UNSTABLE_SYS | Unstable system status (not used) | Read | ||
| AV | 38 | UNOCC_ZN_COOL | UNOCC zone cooling SP | Write | ||
| AV | 39 | UNOCC_ZN_HEAT | UNOCC zone heating SP | Write | ||
| BI | 61 | VAV_HEAT | VAV heat relay status | Read | ||
| AV | 94 | VENT_CONTROL | Ventilation control | Write | 0=FIXED MINIMUM, 1=DEMAND | |
| BV | 18 | VENT_CONTROL | Ventilation control | Write | 0=FIXED MINIMUM, 1=DEMAND | |
| AI | 59 | VENT_DEM_OUT | Ventilation demand | % | Read | |
| AV | 95 | VENT_ENABLE | Ventilation system | Write | 0=OFF, 1=ON | |
| BV | 19 | VENT_ENABLE | Ventilation system | Write | 0=OFF, 1=ON | |
| AI | 68 | WARNING_1 | Warning 1 | Read | ||
| AI | 69 | WARNING_2 | Warning 2 | Read | ||
| AI | 70 | WARNING_3 | Warning 3 | Read | ||
| AV | 96 | W1_LO_HEAT_B | W1 lo heat BAS (CV only) | Write | 0=OFF, 1=ON | |
| BV | 20 | W1_LO_HEAT_B | W1 lo heat BAS (CV only) | Write | 0=OFF, 1=ON | |
| BI | 62 | W1_LOW_HEAT | W1 low heat status | Read | ||
| AV | 97 | W2_HI_HEAT_B | W2 high heat BAS (CV only) | Write | 0=OFF, 1=ON | |
| BV | 21 | W2_HI_HEAT_B | W2 high heat BAS (CV only) | Write | 0=OFF, 1=ON | |
| BI | 63 | W2_HIGH_HEAT | W2 high heat status | Read | ||
| AV | 98 | Y1_LO_COOL_B | Y1 lo cool BAS (CV only) | Write | 0=OFF, 1=ON | |
| BV | 22 | Y1_LO_COOL_B | Y1 lo cool BAS (CV only) | Write | 0=OFF, 1=ON | |
| BI | 64 | Y1_LOW_COOL | Y1 low cool status | Read | ||
| AV | 99 | Y2_HI_COOL_B | Y2 high cool BAS (CV only) | Write | 0=OFF, 1=ON | |
| BV | 23 | Y2_HI_COOL_B | Y2 high cool BAS (CV only) | Write | 0=OFF, 1=ON | |
| BI | 65 | Y2_HIGH_COOL | Y2 high cool status | Read | ||
| AImin | 60 | ZONE_TEMP | Zone temp current | °F | Read | |
| AV | 40 | ZONE_TEMP_BAS | Zone temp BAS | °F | Write |
No points match these filters.
Object ID lookup: York YPAL Series 100 50-65 ton point IDs by name
AI1ACT_DSP_SPAI2ACT_MIN_FLOWAI3ACT_MIN_POSAI4ACT_SAT_SPAV77ACT_SLAB_CTLBV1ACT_SLAB_CTLBI1AMORN_WA_ACTAI5BLD_STAT_PRSAV1BULD_PRES_SPAI6BYPASS_DAMPERAI7CO2_1_OUTAI8CO2_2_INAV43CO2_INSIDEAV2CO2_OFFSETBI2COL/HEAT_FLTAV78COMFORT_VENTBV2COMFORT_VENTBI3COMP_1AAI9COMP_1A_OPERBI4COMP_1BAI10COMP_1B_OPERBI5COMP_2AAI11COMP_2A_OPERBI6COMP_2BAI12COMP_2B_OPERBI7COMP_3AAI13COMP_3A_OPERBI8COMP_3BAI14COMP_3B_OPERBI9COMP_LPCO_1BI10COMP_LPCO_2BI11COMP_LPCO_3BI12COMP_STAT_1BI13COMP_STAT_2BI14COMP_STAT_3BI15COND_FAN_1ABI16COND_FAN_1BBI17COND_FAN_2ABI18COND_FAN_2BBI19COND_FAN_3ABI20COND_FAN_3BAI15COND_FAN_SPDAV79CONTINU_VENTBV3CONTINU_VENTAI16DCT_ST_PR_RTAI17DCT_STAT_PRSAV80DEW_PNT_RSTBV4DEW_PNT_RSTAV3DSP_HI_LIMITAV4DSP_LO_LIMITAV5DSP_RST_BASAI18ECON_ME_USEDAI19ECON_STATUSAV81ECONO_INSTALBV5ECONO_INSTALAV6ECONO_METHODAV7EL_AIR_TMP_HAV8EL_AIR_TMP_LAI20EVAP_AIR_TMPAV52EXH_DAMPER/VFDBI21EXH_FAN_STATBI22EXHAUST_FANAI21EXHAUST_OUTBI23FAN_FAULTBI24FAN_GAV82FAN_G_BASBV6FAN_G_BASAI71FAULT_1AI72FAULT_2AI73FAULT_3AI74FAULT_4AI75FAULT_5AI76FAULT_6AI77FAULT_7AI78FAULT_8AI79FAULT_9AI80FAULT_10BI25FILTER_STATSBI26FURN_OUT_1BI27FURN_OUT_2BI28FURN_OUT_3BI29FURN_OUT_4BI30FURN_OUT_5BI31FURN_OUT_6BI32FURN_OUT_7AV83HEAT_ENABLEBV7HEAT_ENABLEAI22HEAT_ENT_TEMPAI23HEAT_STAGESAV84HEAT_VACTIONBV8HEAT_VACTIONAV9HEATING_SATAI24HEATING_VLVBI77HGRH_BLEED_VBV25HGRH_CONTROLAI81HGRH_SAT_ASPAV59HGRH_SAT_HSPAV60HGRH_SAT_LSPAI67HGRH_VLV_POSAV61HUM_LVL_BASBI33HW_FRZ_STATBI34LOCAL_STOPAV10MAX_BYPASSAV11MAX_FLOW_DVAV12MECH_LCK_TMPAV13MIN_FLOW_DVAV51MIN_OA_FLOAV14MIXD_SAT_LIMAV85MORN_WARM_UPBV9MORN_WARM_UPAV86MORN_WUP_CMDBV10MORN_WUP_CMDAV87NIGHT_SETBACBV11NIGHT_SETBACAV56OAH_CURR_BASAV55OAT_CURR_BASAV16OA_DAMP_POS1AV17OA_DAMP_POS2AI25OA_DAMPERAV18OA_ENTH_LIMITAI26OA_ENTHALPYAI27OA_FLO_PRS_1AI28OA_FLO_PRS_2AI61OA_FLOW_1AI62OA_FLOW_2AI63OA_FLOW_TOTLAI29OA_REL_HUMIDAI30OA_TEMPAV19OAT_HIGH_SATAV20OAT_LOW_SATBI35OCC_MODEBI36OCC_STATEAV21OCC_ZN_COOLAV22OCC_ZN_HEATAV88OCCUPNCY_CMDBV12OCCUPNCY_CMDAI31PRS_1_DISCHAI32PRS_1_SUCTAI33PRS_2_DISCHAI34PRS_2_SUCTIONAI35PRS_3_DISCHAI36PRS_3_SUCTAV89PUMP_DOWNBV13PUMP_DOWNBI37PUMP_DOWN_1BI38PUMP_DOWN_2BI39PUMP_DOWN_3AV42RA_DIFF_BASAI82RA_HUM_ACTAV23RAT_COOL_SPAV15RAT_HEAT_SPAV24RAT_HIGH_SATAV25RAT_LOW_SATBI40RDY_RUN_C1ABI41RDY_RUN_C1BBI42RDY_RUN_C2ABI43RDY_RUN_C2BBI44RDY_RUN_C3ABI45RDY_RUN_C3BBI46RDY_STOP_C1ABI47RDY_STOP_C1BBI48RDY_STOP_C2ABI49RDY_STOP_C2BBI50RDY_STOP_C3ABI51RDY_STOP_C3BAI37RET_AIR_BY_SAI38RET_AIR_ENTHAI39RET_AIR_HUMDAI40RET_AIR_TEMPAI41RET_FAN_OUTAI42RET_FAN_PRESBI52RET_FAN_STATAV41RST_ENT_BASAV26SAT_HIGH_LIMAV27SAT_LOW_LIMAV28SAT_RST_BASAI43SAT_SUC_TMP1AI44SAT_SUC_TMP2AI45SAT_SUC_TMP3BI53SAT_TEMPERBI54SEN/MSC_FLTBI55SF_PROV_SWAV29SF_SPD_H_SATAV30SF_SPD_L_SATBI56SMOKE_PUR_1BI57SMOKE_PUR_2BI58SMOKE_PUR_3AV90SMOKE_PUR1_BBV14SMOKE_PUR1_BAV91SMOKE_PUR2_BBV15SMOKE_PUR2_BAV92SMOKE_PUR3_BBV16SMOKE_PUR3_BAV31STG_1_COOLAV32STG_1_HEATAV33STG_2_COOLAV34STG_2_HEATAI46SUP_AIR_TEMPAI47SUP_AIR_TRSTAI48SUP_FAN_VFDBI59SUPPLY_FANAV35SYSTEM_STOPAV53SZ_MIN_VFDAI49TEMP_1_SUCTAI50TEMP_1_SUPERAI51TEMP_2_SUCTAI52TEMP_2_SUPERAI53TEMP_3_SUCTAI54TEMP_3_SUPERAI55UND_FLR_DEWPAI56UND_FLR_HUMDAI57UND_FLR_TEMPAV36UND_HUMD_BASAV37UND_TEMP_BASAI58UNIT_MODEAV93UNIT_STOPBV17UNIT_STOPBI60UNSTABLE_SYSAV38UNOCC_ZN_COOLAV39UNOCC_ZN_HEATBI61VAV_HEATAV94VENT_CONTROLBV18VENT_CONTROLAI59VENT_DEM_OUTAV95VENT_ENABLEBV19VENT_ENABLEAI68WARNING_1AI69WARNING_2AI70WARNING_3AV96W1_LO_HEAT_BBV20W1_LO_HEAT_BBI62W1_LOW_HEATAV97W2_HI_HEAT_BBV21W2_HI_HEAT_BBI63W2_HIGH_HEATAV98Y1_LO_COOL_BBV22Y1_LO_COOL_BBI64Y1_LOW_COOLAV99Y2_HI_COOL_BBV23Y2_HI_COOL_BBI65Y2_HIGH_COOLAI60ZONE_TEMPAV40ZONE_TEMP_BAS
Integration notes
- Access is from the READ/WRITE column. The table lists each 0/1 BAS command twice, as an AV (77-99) and a BV (1-23) with the same name; both are kept.
- Descriptions are the user interface names from the table. Points marked FlexSys, VAV, CV or a tonnage range only exist on those units.
- Units are taken from the description column where it states them (°F, "WC, CFM, %, ppm, psig).
- The Modbus register addresses in the same table are not reproduced.
- Compared with the 70-150 ton list this table adds FAULT_1-10 and WARNING_1-3 code AIs, hot gas reheat objects, and BAS outdoor temperature, outdoor humidity and zone humidity inputs; AV 15 is named RAT_HEAT_SP here.
- FAULT and WARNING objects carry code numbers from the fault and warning tables in the IOM.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
How many BACnet points does the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) have?
This list has 243 BACnet objects: 79 analog inputs, 74 analog values, 66 binary inputs, 24 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet points are writable?
98 of the 243 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet documentation?
The source is Series 100 Single Packaged Rooftop Units 50-65 Ton, Mod F - Installation, Operation, Maintenance (Table 53, BACnet MS/TP, Modbus, BACnet IP) (100.50-NOM5 (120)), revision 2020-01-20, published free by York at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/PwDHFbfBgQxp4HQ4ucu1fw/content.
What are the minimum BACnet points to integrate the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?
Start with AV 88 OCCUPNCY_CMD (Occupancy command (1 = occupied)); AV 93 UNIT_STOP (Unit stop (1 = stopped, 0 = normal)); AV 21 OCC_ZN_COOL (Occupied zone cooling setpoint); AV 22 OCC_ZN_HEAT (Occupied zone heating setpoint); AI 58 UNIT_MODE (Current operating mode index); BI 59 SUPPLY_FAN (Supply fan on/off); AI 46 SUP_AIR_TEMP (Supply air temperature); AI 60 ZONE_TEMP (Zone temperature); BI 2 COL/HEAT_FLT (Cooling/heating fault (1 = faulted)); AI 71 FAULT_1 (Active fault code 1).
How do I enable BMS control of the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?
OCCUPNCY_CMD (AV 88 or BV 12) puts the unit in occupied (1) or unoccupied (0) mode and UNIT_STOP (AV 93 or BV 17) stops it (1) or returns it to normal operation (0). BAS reset and BAS sensor inputs must first be enabled at the unit with the SERVICE key; AV 40 zone temperature needs the control method set to comm zone temp.
Can the BMS supply sensor values to the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?
AV 40 ZONE_TEMP_BAS feeds zone temperature when the control method is set to comm zone temp. AV 55 OAT_CURR_BAS, AV 56 OAH_CURR_BAS and AV 61 HUM_LVL_BAS feed outdoor temperature, outdoor humidity and zone humidity once enabled in the unit. AV 43 CO2_INSIDE and the BAS reset values (duct static, supply air) must be enabled with the SERVICE key before they are used.
How do I check these points on the real Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: Series 100 Single Packaged Rooftop Units 50-65 Ton, Mod F - Installation, Operation, Maintenance (Table 53, BACnet MS/TP, Modbus, BACnet IP) · 100.50-NOM5 (120) · rev. 2020-01-20. Object names, instances and units are reproduced as published; descriptions are our own.