  4. Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)

Packaged rooftop unit controller (Series 100, 50-65 ton) · BACnet points list

York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The 50-65 ton Series 100 rooftop's IPU control board speaks BACnet MS/TP on Port 1 and Modbus on Port 4. The table lists about 240 objects: air temperatures, pressures, airflows, CO2, unit mode and ten active fault and three warning codes as AIs; compressor, fan, heat and fault BIs; setpoints, limits and BAS inputs (zone, outdoor temperature and humidity) as AVs; and 0/1 BAS commands published as both AVs and BVs. Hot gas reheat points are included.

This page lists 243 BACnet objects for the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) — 98 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
Equipment
Packaged rooftop unit controller (Series 100, 50-65 ton)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
243 (98 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
23000 + MAC address
Also known as
YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU
Source document
Series 100 Single Packaged Rooftop Units 50-65 Ton, Mod F - Installation, Operation, Maintenance (Table 53, BACnet MS/TP, Modbus, BACnet IP) · 100.50-NOM5 (120) · rev. 2020-01-20
Download CSV 243 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)

Integration in brief

Connect to Port 1 of the IPU control board on BACnet MS/TP. Command occupancy with OCCUPNCY_CMD, stop or release the unit with UNIT_STOP and write the occupied zone setpoints; feed zone temperature through AV 40 if the control method is set to comm zone temp. Read supply air and zone temperatures, supply fan status, unit mode and the fault inputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 88OCCUPNCY_CMDOccupancy command (1 = occupied)Write
AV 93UNIT_STOPUnit stop (1 = stopped, 0 = normal)Write
AV 21OCC_ZN_COOLOccupied zone cooling setpointWrite
AV 22OCC_ZN_HEATOccupied zone heating setpointWrite
AI 58UNIT_MODECurrent operating mode indexRead
BI 59SUPPLY_FANSupply fan on/offRead
AI 46SUP_AIR_TEMPSupply air temperatureRead
AI 60ZONE_TEMPZone temperatureRead
BI 2COL/HEAT_FLTCooling/heating fault (1 = faulted)Read
AI 71FAULT_1Active fault code 1Read

Enable & remote start

OCCUPNCY_CMD (AV 88 or BV 12) puts the unit in occupied (1) or unoccupied (0) mode and UNIT_STOP (AV 93 or BV 17) stops it (1) or returns it to normal operation (0). BAS reset and BAS sensor inputs must first be enabled at the unit with the SERVICE key; AV 40 zone temperature needs the control method set to comm zone temp.

Sensors & values from the BMS

AV 40 ZONE_TEMP_BAS feeds zone temperature when the control method is set to comm zone temp. AV 55 OAT_CURR_BAS, AV 56 OAH_CURR_BAS and AV 61 HUM_LVL_BAS feed outdoor temperature, outdoor humidity and zone humidity once enabled in the unit. AV 43 CO2_INSIDE and the BAS reset values (duct static, supply air) must be enabled with the SERVICE key before they are used.

Network setup

Watch out for

York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

243 of 243 shown
Type
Access
Show
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet Points List
DescriptionStates
AI1ACT_DSP_SPDuct static press active SPRead
AI2ACT_MIN_FLOWActive minimum airflowRead
AI3ACT_MIN_POSActive minimum positionRead
AI4ACT_SAT_SPActive supply air temp SPRead
AV77ACT_SLAB_CTLActive slab control (FLEXSYS only)Write
BV1ACT_SLAB_CTLActive slab control (FLEXSYS only)Write
BI1AMORN_WA_ACTAdaptive morning warmup status (only used with internal time clock)Read
AI5BLD_STAT_PRSBuilding pressure currentRead
AV1BULD_PRES_SPBldg press SPWrite
AI6BYPASS_DAMPERBypass damper position (FLEXSYS only)Read
AI7CO2_1_OUTCO2 level of the outside airRead
AI8CO2_2_INCO2 level of the inside airRead
AV43CO2_INSIDECO2 lvl inside value BASWrite
AV2CO2_OFFSETCO2 offset SPWrite
BImin2COL/HEAT_FLTCooling/heating fault statusRead0=Normal (OKAY), 1=Fault(ed)
AV78COMFORT_VENTComfort ventilation (constant volume)Write0=OFF, 1=ON
BV2COMFORT_VENTComfort ventilation (constant volume)Write0=OFF, 1=ON
BI3COMP_1ACompressor 1A statusRead0=OFF, 1=ON
AI9COMP_1A_OPERComp 1A operating HRShoursRead
BI4COMP_1BCompressor 1B statusRead0=OFF, 1=ON
AI10COMP_1B_OPERComp 1B operating HRShoursRead
BI5COMP_2ACompressor 2A statusRead0=OFF, 1=ON
AI11COMP_2A_OPERComp 2A operating HRShoursRead
BI6COMP_2BCompressor 2B statusRead0=OFF, 1=ON
AI12COMP_2B_OPERComp 2B operating HRShoursRead
BI7COMP_3ACompressor 3A status (70-150 ton only)Read0=OFF, 1=ON
AI13COMP_3A_OPERComp 3A operating HRS (70-150 ton only)hoursRead
BI8COMP_3BCompressor 3B status (70-150 ton only)Read0=OFF, 1=ON
AI14COMP_3B_OPERComp 3B operating HRS (70-150 ton only)hoursRead
BI9COMP_LPCO_1Safety input LPCO CKT 1 statusRead0=Normal (OKAY), 1=Fault(ed)
BI10COMP_LPCO_2Safety input LPCO CKT 2 statusRead0=Normal (OKAY), 1=Fault(ed)
BI11COMP_LPCO_3Safety input LPCO CKT 3 status (70-150 ton only)Read0=Normal (OKAY), 1=Fault(ed)
BI12COMP_STAT_1Safety chain CKT 1 statusRead0=Normal (OKAY), 1=Fault(ed)
BI13COMP_STAT_2Safety chain CKT 2 statusRead0=Normal (OKAY), 1=Fault(ed)
BI14COMP_STAT_3Safety chain CKT 3 status (70-150 ton only)Read0=Normal (OKAY), 1=Fault(ed)
BI15COND_FAN_1ACond fan 1A/1 statusRead0=OFF, 1=ON
BI16COND_FAN_1BCond fan 1B/2 statusRead0=OFF, 1=ON
BI17COND_FAN_2ACond fan 2A/3 statusRead0=OFF, 1=ON
BI18COND_FAN_2BCond fan 2B/4 statusRead0=OFF, 1=ON
BI19COND_FAN_3ACond fan 3A/5 status (70-150 ton onlyRead0=OFF, 1=ON
BI20COND_FAN_3BCond fan 3B/6 status (70-150 ton only)Read0=OFF, 1=ON
AI15COND_FAN_SPDCond fan speedRead
AV79CONTINU_VENTContinuous ventilation (constant volume)Write0=OFF, 1=ON
BV3CONTINU_VENTContinuous ventilation (constant volume)Write0=OFF, 1=ON
AI16DCT_ST_PR_RTDuct static press reset%Read
AI17DCT_STAT_PRSDuct static press current (VAV or FLEXSYS)Read
AV80DEW_PNT_RSTDew point reset (FLEXSYS)Write0=OFF, 1=ON
BV4DEW_PNT_RSTDew point reset (FLEXSYS)Write0=OFF, 1=ON
AV3DSP_HI_LIMITDuct static reset high SP (VAV or FLEXSYS)Write
AV4DSP_LO_LIMITDuct static reset low SP (VAV or FLEXSYS)Write
AV5DSP_RST_BASDuct static press reset BAS (VAV or FLEXSYS)%Write
AI18ECON_ME_USEDECON method activeRead1=DRY BULB, 2=SINGLE ENTHALPY, 3=DUAL ENTHALPY, 4=BEST METHOD AVAIL
AI19ECON_STATUSECON system statusRead1=INSTALLED AND ACTIVE, 2=NOT INSTALLED, 3=DISABLED
AV81ECONO_INSTALEconomizer systemWrite0=OFF, 1=ON
BV5ECONO_INSTALEconomizer systemWrite0=OFF, 1=ON
AV6ECONO_METHODECON method to useWrite1=DRY BULB, 2=SINGLE ENTHALPY, 3=DUAL ENTHALPY, 4=BEST METHOD AVAIL
AV7EL_AIR_TMP_HEVAP leaving air temp high SP (FLEXSYS)Write
AV8EL_AIR_TMP_LEVAP leaving air temp low SP (FLEXSYS)Write
AI20EVAP_AIR_TMPFLEXSYS EVAP temp current (FLEXSYS)Read
AV52EXH_DAMPER/VFDExhaust damper BAS controlWrite
BI21EXH_FAN_STATExhaust fan statusRead0=OPEN, 1=CLOSED
BI22EXHAUST_FANExhaust fan output statusRead0=OFF, 1=ON
AI21EXHAUST_OUTExhaust damper position%Read
BI23FAN_FAULTFan fault statusRead0=NO FAULT, 1=FAULT
BI24FAN_GFan (G) statusRead0=OFF, 1=ON
AV82FAN_G_BASFan (G) BASWrite0=OFF, 1=ON
BV6FAN_G_BASFan (G) BASWrite0=OFF, 1=ON
AImin71FAULT_1Fault 1Read
AI72FAULT_2Fault 2Read
AI73FAULT_3Fault 3Read
AI74FAULT_4Fault 4Read
AI75FAULT_5Fault 5Read
AI76FAULT_6Fault 6Read
AI77FAULT_7Fault 7Read
AI78FAULT_8Fault 8Read
AI79FAULT_9Fault 9Read
AI80FAULT_10Fault 10Read
BI25FILTER_STATSFilter statusRead0=NORMAL (OKAY), 1=FAULT (CHANGE)
BI26FURN_OUT_1Elect heat stage 1 status staged gas furn 1 lo status mod gas furn 1A lowRead0=OFF, 1=ON
BI27FURN_OUT_2Elect heat stage 2 status staged gas furn 1 high status mod gas furn 1A highRead0=OFF, 1=ON
BI28FURN_OUT_3Elect heat stage 3 status staged gas furn 2 low status mod gas furn 2 lowRead0=OFF, 1=ON 6
BI29FURN_OUT_4Elect heat stage 4 status staged gas furn 2 high status mod gas furn 2 highRead0=OFF, 1=ON
BI30FURN_OUT_5Elect heat stage 5 status staged gas furn 3 low status mod gas furn 3 lowRead0=OFF, 1=ON
BI31FURN_OUT_6Elect heat stage 6 status staged gas furn 3 high status mod gas furn 3 highRead0=OFF, 1=ON
BI32FURN_OUT_7Elect heat stage 7 status mod gas furn 1B statusRead0=OFF, 1=ON
AV83HEAT_ENABLEHeating systemWrite0=USER DISABLED, 1=USER ENABLED
BV7HEAT_ENABLEHeating systemWrite0=USER DISABLED, 1=USER ENABLED
AI22HEAT_ENT_TEMPHeat entering tempRead
AI23HEAT_STAGESElectric heat stages or gas heat stagesRead
AV84HEAT_VACTIONHw valve actionWrite0=DIRECT, 1=REVERSE
BV8HEAT_VACTIONHw valve actionWrite0=DIRECT, 1=REVERSE
AV9HEATING_SATHeating suppy sir temp SP (VAV or FLEXSYS)Write
AI24HEATING_VLVHeating valve%Read
BI77HGRH_BLEED_VHGRH bleed valveRead
BV25HGRH_CONTROLHGRH controlWrite0=ENABLED, 1=DISABLED
AI81HGRH_SAT_ASPHGRH SAT-ACTIVE SPRead
AV59HGRH_SAT_HSPHGRH SAT high SP°FWrite
AV60HGRH_SAT_LSPHGRH SAT low SP°FWrite
AI67HGRH_VLV_POSHGRH valve positionRead
AV61HUM_LVL_BASHumidity level BAS%RHWrite
BI33HW_FRZ_STATHw/steam coil freezestat statusRead0=NO FAULT (OKAY), 1=FAULTED
BI34LOCAL_STOPLocal stop statusRead
AV10MAX_BYPASSMaximum bypass SP (FLEXSYS)Write
AV11MAX_FLOW_DVOutside air max flow SPCFMWrite
AV12MECH_LCK_TMPMech cooling lockout SPWrite
AV13MIN_FLOW_DVOutside air min flow SPCFMWrite
AV51MIN_OA_FLOMinimum OA flow setpointCFMWrite
AV14MIXD_SAT_LIMMX supply air temp SP (FLEXSYS)Write
AV85MORN_WARM_UPMorning warm upWrite0=ENABLED, 1=DISABLED
BV9MORN_WARM_UPMorning warm upWrite0=ENABLED, 1=DISABLED
AV86MORN_WUP_CMDMorn warmup commandWrite0=OFF, 1=ON
BV10MORN_WUP_CMDMorn warmup commandWrite0=OFF, 1=ON
AV87NIGHT_SETBACNight setback for heatingWrite0=OFF, 1=ON
BV11NIGHT_SETBACNight setback for heatingWrite0=OFF, 1=ON
AV56OAH_CURR_BASOutside humidity BAS%RHWrite
AV55OAT_CURR_BASOutside temp BAS°FWrite
AV16OA_DAMP_POS1OA damper minimum positionWrite
AV17OA_DAMP_POS2OA damper maximum positionWrite
AI25OA_DAMPEROA damper position current%Read
AV18OA_ENTH_LIMITOA enthalpy SPBTU/lbWrite
AI26OA_ENTHALPYOA enthalpyBTU/lbRead
AI27OA_FLO_PRS_1OA flow press 1Read
AI28OA_FLO_PRS_2OA flow press 2Read
AI61OA_FLOW_1IAQ damper air flows OA flow 1CFMRead
AI62OA_FLOW_2IAQ damper air flows OA flow 2Read
AI63OA_FLOW_TOTLOA flow totalCFMRead
AI29OA_REL_HUMIDOA humidity%Read
AI30OA_TEMPOA temperatureRead
AV19OAT_HIGH_SATOA temp SP for hi supply air temp (VAV, and only if SAT reset method isWrite
AV20OAT_LOW_SATOA temp SP for lo supply air temp (VAV, and only if SAT rest method isWrite
BI35OCC_MODEOccupancy mode statusRead
BI36OCC_STATEOccupancy state statusRead
AVmin21OCC_ZN_COOLOCC zone cooling SPWrite
AVmin22OCC_ZN_HEATOCC zone heating SPWrite
AVmin88OCCUPNCY_CMDOccupancy commandWrite0=UNOCC, 1=OCC
BV12OCCUPNCY_CMDOccupancy commandWrite0=UNOCC, 1=OCC
AI31PRS_1_DISCHDisch press CKT 1psigRead
AI32PRS_1_SUCTSuct press CKT 1psigRead
AI33PRS_2_DISCHDisch press CKT 2psigRead
AI34PRS_2_SUCTIONSuct press CKT 2psigRead
AI35PRS_3_DISCHDisch press CKT 3 (70- 150 ton only)psigRead
AI36PRS_3_SUCTSuct press CKT 3 (70-150 ton only)psigRead
AV89PUMP_DOWNPump downWrite0=ON, 1=OFF
BV13PUMP_DOWNPump downWrite0=ON, 1=OFF
BI37PUMP_DOWN_1Pump down LLSV 1 statusRead0=Pump Down LLSV (OFF), 1=Pump Down LLSV (ON)
BI38PUMP_DOWN_2Pump down LLSV 2 statusRead0=Pump Down LLSV (OFF), 1=Pump Down LLSV (ON)
BI39PUMP_DOWN_3Pump down LLSV 3 status (70-150 ton only)Read0=Pump Down LLSV (OFF), 1=Pump Down LLSV (ON)
AV42RA_DIFF_BASReturn air diff SP BAS (FLEXSYS)Write
AI82RA_HUM_ACTReturn air-humidity active%RHRead
AV23RAT_COOL_SPCooling return air temp SP (VAV or FLEXSYS)Write
AV15RAT_HEAT_SPHeating ret air temp SP (VAV or FLEXSYS)Write
AV24RAT_HIGH_SATRA temp SP for hi supply air temp (VAV, and only if SAT reset method isWrite
AV25RAT_LOW_SATRA temp SP for lo supply air temp (VAV, and only if SAT reset method isWrite
BI40RDY_RUN_C1AReady to run comp 1A statusRead
BI41RDY_RUN_C1BReady to run comp 1B statusRead
BI42RDY_RUN_C2AReady to run comp 2A statusRead
BI43RDY_RUN_C2BReady to run comp 2B statusRead
BI44RDY_RUN_C3AReady to run comp 3A status (70-150 ton only)Read
BI45RDY_RUN_C3BReady to run comp 3B status (70-150 ton only)Read
BI46RDY_STOP_C1AReady to stop comp 1A statusRead
BI47RDY_STOP_C1BReady to stop comp 1B statusRead
BI48RDY_STOP_C2AReady to stop comp 2A statusRead
BI49RDY_STOP_C2BReady to stop comp 2B statusRead
BI50RDY_STOP_C3AReady to stop comp 3A status (70-150 ton only)Read
BI51RDY_STOP_C3BReady to stop comp 3B status (70-150 ton only)Read
AI37RET_AIR_BY_SReturn air bypass active SP%Read
AI38RET_AIR_ENTHReturn air enthalpyRead
AI39RET_AIR_HUMDReturn air humidity%Read
AI40RET_AIR_TEMPReturn air temp current°FRead
AI41RET_FAN_OUTExhaust/return fan VFD%Read
AI42RET_FAN_PRESReturn fan pressure currentRead
BI52RET_FAN_STATReturn fan statusRead0=STOP/ VERIFICATION CKT OPEN, 1=RUN/ VERIFICATION CKT CLOSED
AV41RST_ENT_BASReset enthalpy SP BASWrite
AV26SAT_HIGH_LIMSuppy air temp hi SP°FWrite
AV27SAT_LOW_LIMSupply air temp lo SP°FWrite
AV28SAT_RST_BASSupply air temp reset BASWrite
AI43SAT_SUC_TMP1Saturated suct temp CKT 1°FRead
AI44SAT_SUC_TMP2Saturated suct temp CKT 2°FRead
AI45SAT_SUC_TMP3Saturated suct temp CKT 3 (70-150 ton only)°FRead
BI53SAT_TEMPERSupply air tempering statusRead
BI54SEN/MSC_FLTSensor/misc fault statusRead0=NO FAULT, 1=FAULTED
BI55SF_PROV_SWSupply fan statusRead0=STOP VERIFICATION/CKT OPEN, 1=RUN VERIFICATION/CKT CLOSED
AV29SF_SPD_H_SATFan speed SP for hi supply air tempWrite
AV30SF_SPD_L_SATFan speed SP for lo supply air tempWrite
BI56SMOKE_PUR_1Smoke purge 1 statusRead
BI57SMOKE_PUR_2Smoke purge 2 statusRead
BI58SMOKE_PUR_3Smoke purge 3 statusRead
AV90SMOKE_PUR1_BSmoke purge 1 BASWrite0=OFF, 1=ON
BV14SMOKE_PUR1_BSmoke purge 1 BASWrite0=OFF, 1=ON
AV91SMOKE_PUR2_BSmoke purge 2 BASWrite0=OFF, 1=ON
BV15SMOKE_PUR2_BSmoke purge 2 BASWrite0=OFF, 1=ON
AV92SMOKE_PUR3_BSmoke purge 3 BASWrite0=OFF, 1=ON) 6
BV16SMOKE_PUR3_BSmoke purge 3 BASWrite0=OFF, 1=ON) 6
AV31STG_1_COOL1ST stage cooling SP (cv/szvav)Write
AV32STG_1_HEAT1ST stage heating SP (cv/szvav)Write
AV33STG_2_COOL2ND stage cooling SP (cv/szvav)Write
AV34STG_2_HEAT2ND stage heating SP (cv/szvav)Write
AImin46SUP_AIR_TEMPSupply air temp current°FRead
AI47SUP_AIR_TRSTSupply air temp resetVDCRead
AI48SUP_FAN_VFDSupply fan VFD speed%Read
BImin59SUPPLY_FANSupply fan output statusRead0=OFF, 1=ON
AV35SYSTEM_STOPSystem stopWrite0=ALL CKTS CAN OPERATE, 1=SHUTS DOWN CKT 1, 2=SHUTS DOWN CKT 2, 3=SHUTS DOWN CKT 3
AV53SZ_MIN_VFDSingle zone minimum VFDWrite
AI49TEMP_1_SUCTSuct temp CKT 1°FRead
AI50TEMP_1_SUPERSuct superheat CKT 1°FRead
AI51TEMP_2_SUCTSuct temp CKT 2°FRead
AI52TEMP_2_SUPERSuct superheat CKT 2°FRead
AI53TEMP_3_SUCTSuct temp CKT 3 (70-150 ton only)°FRead
AI54TEMP_3_SUPERSuct superheat CKT 3 (70-150 ton only)°FRead
AI55UND_FLR_DEWPUnderfloor slab dew point (FLEXSYS)°FRead
AI56UND_FLR_HUMDUnderfloor air humidity (FLEXSYS)°FRead
AI57UND_FLR_TEMPUndefloor slab temp (FLEXSYS)°FRead
AV36UND_HUMD_BASUnderfloor air humidity BAS%Write
AV37UND_TEMP_BASUnderfloor slab temp BAS°FWrite
AImin58UNIT_MODECurrent oper modeRead0=OCC COOL, 1=OCC COOL LOW, 2=OCC COOL HIGH, 3=OCC COOL W/ BYP, 4=OCC COOL W/O BYP, 5=OCC HEAT, 6=OCC HEAT LOW, 7=OCC HEAT HIGH, 8=OCC STANDBY, 9=UNOCC COOL, 10=UNOCC COOL LOW, 11=UNOCC COOL HIGH, 12=UNOCC HEAT, 13=UNOCC HEAT LOW, 14=UNOCC HEAT HIGH, 15=UNOCC STANDBY, 16=COMFORT VENT COOL, 17=COMFORT VENT HEAT, 18=NIGHT SET-BACK, 19=MORNING WARM-UP, 20=OCC DEHUM W/ COOL, 21=OCC DEHUM COOL HI, 22=OCC DEHUM COOL LO, 23=UNOCC DEHUM W/ COOL, 24=UNOCC DEHUM COOL HI, 25=UNOCC DEHUM COOL LO 6
AVmin93UNIT_STOPUnit stopWrite0=NORMAL OPERATION, 1=UNIT STOPPED
BV17UNIT_STOPUnit stopWrite0=NORMAL OPERATION, 1=UNIT STOPPED
BI60UNSTABLE_SYSUnstable system status (not used)Read
AV38UNOCC_ZN_COOLUNOCC zone cooling SPWrite
AV39UNOCC_ZN_HEATUNOCC zone heating SPWrite
BI61VAV_HEATVAV heat relay statusRead
AV94VENT_CONTROLVentilation controlWrite0=FIXED MINIMUM, 1=DEMAND
BV18VENT_CONTROLVentilation controlWrite0=FIXED MINIMUM, 1=DEMAND
AI59VENT_DEM_OUTVentilation demand%Read
AV95VENT_ENABLEVentilation systemWrite0=OFF, 1=ON
BV19VENT_ENABLEVentilation systemWrite0=OFF, 1=ON
AI68WARNING_1Warning 1Read
AI69WARNING_2Warning 2Read
AI70WARNING_3Warning 3Read
AV96W1_LO_HEAT_BW1 lo heat BAS (CV only)Write0=OFF, 1=ON
BV20W1_LO_HEAT_BW1 lo heat BAS (CV only)Write0=OFF, 1=ON
BI62W1_LOW_HEATW1 low heat statusRead
AV97W2_HI_HEAT_BW2 high heat BAS (CV only)Write0=OFF, 1=ON
BV21W2_HI_HEAT_BW2 high heat BAS (CV only)Write0=OFF, 1=ON
BI63W2_HIGH_HEATW2 high heat statusRead
AV98Y1_LO_COOL_BY1 lo cool BAS (CV only)Write0=OFF, 1=ON
BV22Y1_LO_COOL_BY1 lo cool BAS (CV only)Write0=OFF, 1=ON
BI64Y1_LOW_COOLY1 low cool statusRead
AV99Y2_HI_COOL_BY2 high cool BAS (CV only)Write0=OFF, 1=ON
BV23Y2_HI_COOL_BY2 high cool BAS (CV only)Write0=OFF, 1=ON
BI65Y2_HIGH_COOLY2 high cool statusRead
AImin60ZONE_TEMPZone temp current°FRead
AV40ZONE_TEMP_BASZone temp BAS°FWrite
Object ID lookup: York YPAL Series 100 50-65 ton point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)

How many BACnet points does the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) have?

This list has 243 BACnet objects: 79 analog inputs, 74 analog values, 66 binary inputs, 24 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet points are writable?

98 of the 243 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP) BACnet documentation?

The source is Series 100 Single Packaged Rooftop Units 50-65 Ton, Mod F - Installation, Operation, Maintenance (Table 53, BACnet MS/TP, Modbus, BACnet IP) (100.50-NOM5 (120)), revision 2020-01-20, published free by York at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/PwDHFbfBgQxp4HQ4ucu1fw/content.

What are the minimum BACnet points to integrate the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?

Start with AV 88 OCCUPNCY_CMD (Occupancy command (1 = occupied)); AV 93 UNIT_STOP (Unit stop (1 = stopped, 0 = normal)); AV 21 OCC_ZN_COOL (Occupied zone cooling setpoint); AV 22 OCC_ZN_HEAT (Occupied zone heating setpoint); AI 58 UNIT_MODE (Current operating mode index); BI 59 SUPPLY_FAN (Supply fan on/off); AI 46 SUP_AIR_TEMP (Supply air temperature); AI 60 ZONE_TEMP (Zone temperature); BI 2 COL/HEAT_FLT (Cooling/heating fault (1 = faulted)); AI 71 FAULT_1 (Active fault code 1).

How do I enable BMS control of the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?

OCCUPNCY_CMD (AV 88 or BV 12) puts the unit in occupied (1) or unoccupied (0) mode and UNIT_STOP (AV 93 or BV 17) stops it (1) or returns it to normal operation (0). BAS reset and BAS sensor inputs must first be enabled at the unit with the SERVICE key; AV 40 zone temperature needs the control method set to comm zone temp.

Can the BMS supply sensor values to the York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?

AV 40 ZONE_TEMP_BAS feeds zone temperature when the control method is set to comm zone temp. AV 55 OAT_CURR_BAS, AV 56 OAH_CURR_BAS and AV 61 HUM_LVL_BAS feed outdoor temperature, outdoor humidity and zone humidity once enabled in the unit. AV 43 CO2_INSIDE and the BAS reset values (duct static, supply air) must be enabled with the SERVICE key before they are used.

How do I check these points on the real Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: Series 100 Single Packaged Rooftop Units 50-65 Ton, Mod F - Installation, Operation, Maintenance (Table 53, BACnet MS/TP, Modbus, BACnet IP) · 100.50-NOM5 (120) · rev. 2020-01-20. Object names, instances and units are reproduced as published; descriptions are our own.