- YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card) · BACnet points list
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points list
Updated 4 November 2026
The YZ's SC-EQ card puts the chiller on a BACnet MS/TP trunk (it also speaks Modbus RTU and N2). The BAS can run/stop the chiller and write the leaving chilled liquid setpoint, input current limit and heating setpoint. Read-only points cover water temperatures, refrigerant pressures, VSD and harmonic filter values, magnetic bearing (MBC) mode, purge data, and operation, fault, warning and inhibit codes as MV objects with matching AV copies.
This page lists 113 BACnet objects for the York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
- Equipment
- Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
- Equipment type
- Chillers
- BACnet objects
- 113 (5 writable)
- Transport
- BACnet MS/TP
- Firmware
- SC-EQ software 4.2.0.20
- Default device instance
- 5000 + MAC address
- Also known as
- YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
- Source document
- YZ SC-EQ BAS Points List · rev. Rev 1.7, 2021-12-08
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
Wire the BAS to the SC-EQ J12 RS-485 port and set the MAC address; the card detects BACnet MS/TP. Run/stop the chiller with BV 1 and write the leaving chilled liquid setpoint (AV 1) and input current limit (AV 2). Read MV 1 for the operating state, BV 5 for motor run, the leaving water temperature and % FLA, and MV 2/MV 3 for safety and cycling shutdowns. MV 5 and MV 12-15 show whether the chiller is taking its commands from the BAS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | REM RUN STOP CMD | Remote run/stop (1 = run) | Command |
| AV 1 | REM LEAVING CHL TEMP SP | Remote leaving chilled liquid setpoint | Command |
| AV 2 | REMOTE INPUT CURRENT SP | Remote input current limit, % | Command |
| MV 1 | UNIT OPERATION CODE | Operating state (stopped, starting, running) | Read |
| BV 5 | COMPR MOTOR RUN | Compressor motor running | Read |
| MV 5 | UNIT CONTROL SOURCE | Control source; BAS for BMS control | Read |
| AV 6 | LEAVING CH LIQ TEMP | Leaving chilled liquid temperature | Read |
| AV 18 | MOTOR CURRENT PCT FLA | Motor current, % FLA (load indication) | Read |
| MV 2 | UNIT SAFETY FAULT CODE | Safety shutdown code (1 = none) | Read |
| MV 3 | UNIT CYCLING FAULT CODE | Cycling shutdown code (1 = none) | Read |
Enable & remote start
BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-3 are the remote setpoints. MV 5 shows the unit control source (Local, BAS, Analog, Digital, Remote); MV 12 shows the run/stop source (Local, BAS, Hardwire) and MV 13-15 the cooling setpoint, heating setpoint and current limit sources. Check they read BAS. The points list has no write-enable point.
Network setup
- The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.
- The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.
- The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID).
- MV 65001 Units sets whether the BAS sees IP or SI values, independent of the chiller display; set it to match the chiller.
Watch out for
- The remote (commandable) setpoints read as unreliable until the BAS writes them the first time.
- The SC-EQ only exposes the points that apply to the chiller it detects; if it replaces an E-Link, re-discover the device so old non-applicable points don't sit offline.
- Code points come in pairs: the MV state is the code + 1, and the AV copy (AV 52-59) carries the raw code.
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REM LEAVING CHL TEMP SP | Remote Leaving Chilled Liquid Setpoint | °F | Command | |
| AVmin | 2 | REMOTE INPUT CURRENT SP | Remote Input Current Limit Setpoint | % | Command | |
| AV | 3 | REM HEATING SP | Remote Heating Setpoint | °F | Command | |
| BVmin | 1 | REM RUN STOP CMD | Remote Run/Stop | Command | 0=Stop, 1=Run | |
| MV | 65001 | Units | Unit system reported by the SC-EQ | Write | 0=IP (English), 1=SI (Metric) | |
| BVmin | 5 | COMPR MOTOR RUN | Motor Run | Read | 0=Off, 1=On | |
| BV | 6 | CH LIQ PUMP STAT | Chilled Liquid Pump | Read | 0=Off, 1=On | |
| BV | 7 | CND LIQ PUMP STAT | Condenser Liquid Pump | Read | 0=Off, 1=On | |
| BV | 8 | CH LIQ FLOW SWITCH STAT | Chilled Liquid Flow Switch | Read | 0=Open, 1=Closed | |
| BV | 9 | CND FLOW SWITCH STAT | Condenser Liquid Flow Switch | Read | 0=Open, 1=Closed | |
| BV | 10 | START STOP SWITCH STATUS | Panel Stop Switch | Read | 0=Off, 1=On | |
| BV | 11 | VSD COOLING SYS STAT | VSD Cooling System | Read | 0=Off, 1=On | |
| BV | 12 | VSD HARMONIC FILTER INST | Harmonic Filter Installed | Read | 0=False, 1=True | |
| BV | 13 | COND REF LEVEL CNTRL MODE | Condenser Level Control Valve Mode | Read | 0=Auto, 1=Manual | |
| BV | 14 | PURGE TANK HIGH LEVEL SW | Purge Tank High Level Switch | Read | 0=Off, 1=On | |
| AV | 5 | LEAVING CH LIQ TEMP SEL SP | Leaving Chilled Liquid Setpoint - Selected | °F | Read | |
| AVmin | 6 | LEAVING CH LIQ TEMP | Leaving Chilled Liquid Temperature | °F | Read | |
| AV | 7 | ENTERING CH LIQ TEMP | Entering Chilled Liquid Temperature | °F | Read | |
| AV | 8 | ENTERING COND LIQ TEMP | Entering Condenser Liquid Temperature | °F | Read | |
| AV | 9 | LEAVING COND LIQ TEMP | Leaving Condenser Liquid Temperature | °F | Read | |
| AV | 10 | EVAPORATOR PRESSURE | Evaporator Pressure | PSIA | Read | |
| AV | 11 | CONDENSER PRESSURE | Condenser Pressure | PSIA | Read | |
| AV | 12 | EVAP SATURATION TEMP | Evaporator Saturation Temperature | °F | Read | |
| AV | 13 | COND SATURATION TEMP | Condenser Saturation Temperature | °F | Read | |
| AV | 14 | EVAP REFRIGERANT TEMP | Evaporator refrigerant temperature (sensor option) | °F | Read | |
| AV | 15 | DISCHARGE TEMP | Discharge Temperature | °F | Read | |
| AV | 16 | INPUT CURRENT ACT LIMIT | Active Input Current Limit | % | Read | |
| AV | 17 | INPUT CURRENT PCT FLA | Input % Full Load Amps | % | Read | |
| AVmin | 18 | MOTOR CURRENT PCT FLA | Motor % Full Load Amps | % | Read | |
| AV | 19 | VSD INPUT CURRENT | VSD Input Current (RMS) | Amps | Read | |
| AV | 20 | VSD PHASE A OUTPUT CURRENT | VSD Phase A Output Current (RMS) | Amps | Read | |
| AV | 21 | VSD PHASE B OUTPUT CURRENT | VSD Phase B Output Current (RMS) | Amps | Read | |
| AV | 22 | VSD PHASE C OUTPUT CURRENT | VSD Phase C Output Current (RMS) | Amps | Read | |
| AV | 23 | VSD OUTPUT VOLTAGE | VSD Output Voltage | Volts | Read | |
| AV | 24 | INPUT POWER | Input Power | kW | Read | |
| AV | 25 | INPUT KWH | Input Kilowatt Hours | kWh | Read | |
| AV | 26 | INPUT KWH LO | Input kWh low part (kWh = offset x 10,000 + low) | Read | ||
| AV | 27 | INPUT KWH OFFSET | Input kWh offset part (kWh = offset x 10,000 + low) | Read | ||
| AV | 28 | VSD DC BUS VOLTAGE | VSD DC Bus Voltage | Volts | Read | |
| AV | 29 | VSD DC BUS CURRENT | VSD DC Bus Current | Amps | Read | |
| AV | 30 | SURGE COUNT | Surge Count | Read | ||
| AV | 31 | VSD OUTPUT FREQUENCY | VSD Output Frequency | Hz | Read | |
| AV | 32 | VSD INTERNAL AMBIENT TEMP | VSD Internal Ambient Temp | °F | Read | |
| AV | 33 | VSD CONVERTER HSINK TEMP | VSD Converter Heatsink Temp | °F | Read | |
| AV | 34 | VSD BASEPLATE TEMP | VSD Baseplate Temperature | °F | Read | |
| AV | 35 | VSD PH A HEATSINK TEMP | VSD Phase A Heatsink Temperature | °F | Read | |
| AV | 36 | VSD PH B HEATSINK TEMP | VSD Phase B Heatsink Temperature | °F | Read | |
| AV | 37 | VSD PH C HEATSINK TEMP | VSD Phase C Heatsink Temperature | °F | Read | |
| AV | 38 | FILTER BASEPLATE TEMP | Harmonic Filter Baseplate Temperature (Harmonic Filter only) | °F | Read | |
| AV | 39 | FILTER MAX VOLTAGE THD | Harmonic Filter Max Voltage Total Harmonic Distortion (Harmonic Filter only) | % | Read | |
| AV | 40 | FILTER MAX CURRENT TDD | Harmonic Filter Max Current Total Demand Distortion (Harmonic Filter only) | % | Read | |
| AV | 41 | FILTER SUPPLY KVA | Harmonic Filter Total Supply KVA (Harmonic Filter only) | kVA | Read | |
| AV | 42 | MTR WINDING AVG TEMP | Average Winding Temperature | °F | Read | |
| AV | 43 | COND REFRIGERANT LEVEL SP | Condenser Refrigerant Level Setpoint | % | Read | |
| AV | 44 | COND REFRIGERANT LEVEL | Condenser Refrigerant Level | % | Read | |
| AV | 45 | COND LVL CTRL VLV CMD | Condenser Level Control Valve Command | % | Read | |
| AV | 46 | DROP LEG REFRIG TEMP | Drop Leg Refrigerant Temperature | °F | Read | |
| AV | 47 | HOT GAS BYPASS COMMAND | Hot Gas Bypass Command | % | Read | |
| AV | 48 | OPERATING HOURS | Operating Hours | Hr | Read | |
| AV | 49 | OPERATING HOURS LO | Operating hours low part (hours = offset x 10,000 + low) | Read | ||
| AV | 50 | OPERATING HOURS OFFSET | Operating hours offset part (hours = offset x 10,000 + low) | Read | ||
| AV | 51 | NUMBER OF STARTS | Number Of Starts | Read | ||
| MVmin | 1 | UNIT OPERATION CODE | Unit Operation Code | Read | 1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Soft Shutdown, 12=Unit Coastdown, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown, 15=Unit Starting - MVVSD Startup - Drive Not Ready, 22=Unit Running - Cooling - No Abnormal Condition, 23=Unit Running - Cooling - Warning Active, 24=Unit Running - Cooling - Modified Run, 25=Unit Running - Heating - No Abnormal Condition, 26=Unit Running - Heating - Warning Active, 27=Unit Running - Heating - Modified Run, 28=Unit Running - Cooling & Heating - No Abnormal Condition, 29=Unit Running - Cooling & Heating - Warning Active, 30=Unit Running - Cooling & Heating - Modified Run | |
| AV | 52 | UNIT OPERATION CODE AV | Unit Operation Code AV | Read | 0=Unit Stopped - Ready To Start, 1=Unit Stopped - Local Shutdown, 2=Unit Stopped - Remote Shutdown, 3=Unit Stopped - Warning Active, 4=Unit Stopped - Cycling Shutdown, 5=Unit Stopped - Safety Shutdown, 6=Unit Start Inhibit, 7=Unit Starting, 8=Unit Running - No Abnormal Condition, 9=Unit Running - Warning Active, 10=Unit Running - Soft Shutdown, 11=Unit Coastdown, 12=Unit Running - Modified Run, 13=Unit Stopped - Internal Shutdown, 14=Unit Starting - MVVSD Startup - Drive Not Ready, 21=Unit Running - Cooling - No Abnormal Condition, 22=Unit Running - Cooling - Warning Active, 23=Unit Running - Cooling - Modified Run, 24=Unit Running - Heating - No Abnormal Condition, 25=Unit Running - Heating - Warning Active, 26=Unit Running - Heating - Modified Run, 27=Unit Running - Cooling & Heating - No Abnormal Condition, 28=Unit Running - Cooling & Heating - Warning Active, 29=Unit Running - Cooling & Heating - Modified Run | |
| MVmin | 2 | UNIT SAFETY FAULT CODE | Unit Safety Fault Code | Read | 1=No Safety Faults Present, 2=Evaporator - Low Pressure, 3=Evaporator - Transducer Or Leaving Liquid Probe, 4=Evaporator - Transducer Or Temperature Sensor, 5=Condenser - High Pressure Contacts Open, 6=Condenser - High Pressure, 7=Condenser - Pressure Transducer Out Of Range, 8=Auxiliary Safety - Contacts Closed, 9=Discharge - Low Temperature, 10=Discharge - High Temperature, 11=Oil - High Sump Temperature, 12=Oil - Low Differential Pressure, 13=Oil - High Differential Pressure, 14=Oil - Pump Pressure Transducer Out Of Range, 15=Oil - Sump Pressure Transducer Out Of Range, 16=Motor - Lack of Motor Oil Change, 17=Sales Order - Invalid Compressor Model, 18=Sales Order – Invalid Gear Code, 19=Oil - Differential Pressure Calibration, 20=Safety Stop, 21=Oil - Variable Speed Pump - Setpoint Not Achieved, 22=Control Panel - Power Failure, 23=Control Panel – Loss of Control Voltage, 24=MOTOR OR STARTER - CURRENT IMBALANCE, 25=Thrust Bearing - Proximity Probe Clearance, 26=Thrust Bearing - Proximity Probe Uncalibrated, 27=Thrust Bearing - Proximity Probe Out Of Range, 28=Thrust Bearing - High Oil Temperature, 29=Thrust Bearing - Oil Temperature Sensor, 30=VSD - High Heatsink Temperature, 31=VSD - 105 % MOTOR CURRENT OVERLOAD, 32=VSD - HIGH PHASE A INVERTER HEATSINK TEMPERATURE, 33=VSD - HIGH PHASE B INVERTER HEATSINK TEMPERATURE, 34=VSD - HIGH PHASE C INVERTER HEATSINK TEMPERATURE, 35=VSD - HIGH CONVERTER HEATSINK TEMPERATURE, 36=VSD - PRECHARGE LOCKOUT, 37=HARMONIC FILTER - HIGH HEATSINK TEMPERATURE, 38=HARMONIC FILTER - HIGH TOTAL DEMAND DISTORTION, 39=LCSSS - PHASE ROTATION, 40=LCSSS - MOTOR OR STARTER - CURRENT IMBALANCE, 41=LCSSS - 105 % MOTOR CURRENT OVERLOAD, 42=LCSSS - HIGH INSTANTANEOUS CURRENT, 43=LCSSS - OPEN SCR, 44=LCSSS - PHASE A SHORTED SCR, 45=LCSSS - PHASE B SHORTED SCR, 46=LCSSS - PHASE C SHORTED SCR, 47=LCSSS - HIGH PHASE A HEATSINK TEMPERATURE, 48=LCSSS - HIGH PHASE B HEATSINK TEMPERATURE, 49=LCSSS - HIGH PHASE C HEATSINK TEMPERATURE, 50=Starter - Invalid Motor Selection, 51=Oil Or Condenser Transducer Error, 52=Evaporator - Low Pressure, 53=Evaporator - Low Pressure - Smart Freeze, 54=Surge Protection - Excess Surge, 55=VSD - HIGH INVERTER BASEPLATE TEMPERATURE, 56=HARMONIC FILTER - HIGH BASEPLATE TEMPERATURE, 57=Thrust Bearing - Proximity Probe Clearance, 58=Thrust Bearing - Limit Switch Open, 59=VGD Actuator – Positioning Fault, 60=Oil – Sump Or Pump Transducer Error, 61=Motor - High Housing Temperature, 62=Motor - High Winding Temperature, 63=Motor - High Bearing Temperature, 67=VSD - MOTOR CURRENT IMBALANCE, 68=Condenser - High Pressure - Stopped, 69=OIL – HIGH SUPPLY TEMPERATURE, 70=Motor - High Bearing Vibration, 71=SALES ORDER – INVALID MODEL NUMBER, 72=LCSSS - PHASE A OPEN SCR, 73=LCSSS - PHASE B OPEN SCR, 74=LCSSS - PHASE C OPEN SCR, 75=Motor - Lack Of Bearing Lubrication, 76=VSD - LOW FREQUENCY DETECTED, 77=VSD - Feedback Sensor, 78=VSD - Control Fault, 79=VSD - Drive Boot Failure, 80=MVSSS - PHASE ROTATION, 81=MVSSS - MOTOR OR STARTER - CURRENT IMBALANCE, 82=MVSSS - 105% MOTOR CURRENT OVERLOAD, 83=MVSSS - HIGH INSTANTANEOUS CURRENT, 84=MVSSS - FAILED SCR, 85=MVSSS - HIGH HEATSINK TEMPERATURE, 86=MVSSS - GROUND FAULT, 87=MVSSS - CONTACTOR FAULT, 88=MVSSS - CONTROL BOARD FAULT, 89=MVSSS - DISCONNECT FAULT, 90=VSD - POWER TRANSFORMER HIGH TEMPERATURE, 91=VSD - HIGH OUTPUT FREQUENCY, 92=MVVSD - GROUND FAULT, 93=VSD - MAIN CONTROL BOARD FAULT, 94=MVVSD - CONTACTOR FAULT, 95=MVVSD - INTERLOCK FAULT, 96=VSD - LOGIC BOARD PLUG, 97=VSD - INPUT CURRENT OVERLOAD, 98=VSD - HIGH PHASE A INPUT BASEPLATE TEMPERATURE, 99=VSD - HIGH PHASE B INPUT BASEPLATE TEMPERATURE, 100=VSD - HIGH PHASE C INPUT BASEPLATE TEMPERATURE, 101=MOTOR – LOW WINDING TEMPERATURE, 102=VSD - INVALID PWM SOFTWARE, 103=VSD - BASEPLATE TEMPERATURE IMBALANCE, 104=VSD - DC BUS PRE-REGULATION LOCKOUT, 105=VSD - GROUND FAULT, 106=VSD - HIGH INSTANTANEOUS CURRENT, 107=MOTOR CURRENT > 15 %FLA, 108=VSD - FREQUENCY > 0 HZ, 109=VSD - PHASE A INPUT DCCT, 110=VSD - PHASE B INPUT DCCT, 111=VSD - PHASE C INPUT DCCT, 112=VSD - HIGH TOTAL DEMAND DISTORTION, 113=Motor – Cooling Coil Leak, 114=MVVSD - Excessive Shutdowns, 115=Isolation Valves - Not Opened, 116=VSD - OUTPUT PHASE ROTATION, 117=VSD - Phase Locked Loop, 118=VSD - HIGH PHASE A INSTANTANEOUS CURRENT, 119=VSD - HIGH PHASE B INSTANTANEOUS CURRENT, 120=VSD - HIGH PHASE C INSTANTANEOUS CURRENT, 121=VSD - Line Voltage Phase Rotation, 122=VSD - INPUT DCCT OFFSET LOCKOUT, 123=VSD - LOGIC BOARD HARDWARE, 124=VSD - RECTIFIER PROGRAM FAULT, 125=VSD - INVERTER PROGRAM FAULT, 126=VSD - DC BUS LOCKOUT - DO NOT CYCLE POWER, 127=VSD - MOTOR CURRENT THD FAULT, 128=VSD - HIGH PHASE A MOTOR CURRENT, 129=VSD - HIGH PHASE B MOTOR CURRENT, 130=VSD - HIGH PHASE C MOTOR CURRENT, 131=VSD - HIGH PHASE A MOTOR BASEPLATE TEMPERATURE, 132=VSD - HIGH PHASE B MOTOR BASEPLATE TEMPERATURE, 133=VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATURE, 134=VSD - PHASE A MOTOR DCCT, 135=VSD - PHASE B MOTOR DCCT, 136=VSD - PHASE C MOTOR DCCT, 137=Oil – High Sump Pressure, 138=MBC – OVERSPEED FAULT, 139=MBC – WATCHDOG, 140=MBC – POWER SUPPLY FAULT, 141=MBC – HIGH HEATSINK TEMPERATURE, 142=MBC – HIGH DC BUS VOLTAGE, 143=MBC – AMPLIFIER FUSE, 144=MBC – HIGH BEARING J TEMPERATURE, 145=MBC – HIGH BEARING H1 TEMPERATURE, 146=MBC – HIGH BEARING H2 TEMPERATURE, 147=MBC – HIGH BEARING K TEMPERATURE, 148=MBC – GROUND FAULT, 149=MBC – LOW GATE VOLTAGE, 150=MBC – HIGH GATE VOLTAGE, 151=MBC – HIGH AMPLIFIER TEMPERATURE, 152=MBC – HIGH AMPLIFIER VOLTAGE, 153=MBC – FAULT CONTACTS OPEN, 154=MBC – INITIALIZATION FAILURE, 155=MBC – NOT LEVITATED, 156=SYSTEM – STARTUP FAILURE, 157=UPS – Battery Not Connected, 158=UPS – Inverter Low Battery Voltage, 159=MBC – SPEED SENSOR FAULT, 160=MBC – POWER FAIL LANDING, 161=COMPRESSOR – LOW DISCHARGE SUPERHEAT, 162=MVSSS - HIGH HEATSINK 1 TEMPERATURE, 163=MVSSS - HIGH HEATSINK 2 TEMPERATURE, 164=MVSSS - HIGH HEATSINK 3 TEMPERATURE, 165=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 166=VSD - HIGH PHASE A2 INSTANTANEOUS CURRENT, 167=VSD - HIGH PHASE B2 INSTANTANEOUS CURRENT, 168=VSD - HIGH PHASE C2 INSTANTANEOUS CURRENT, 169=VSD - HIGH PHASE A2 INVERTER BASEPLATE TEMPERATURE, 170=VSD - HIGH PHASE B2 INVERTER BASEPLATE TEMPERATURE, 171=VSD - HIGH PHASE C2 INVERTER BASEPLATE TEMPERATURE, 172=VSD - HIGH CONVERTER 2 HEATSINK TEMPERATURE, 173=VSD - MOTOR CURRENT 2 IMBALANCE, 174=VSD - MOTOR CURRENT MISMATCH, 175=VSD - HIGH PHASE A INPUT CURRENT, 176=VSD - HIGH PHASE B INPUT CURRENT, 177=VSD - HIGH PHASE C INPUT CURRENT, 178=VSD - HIGH INPUT CURRENT TDD, 179=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 180=WATCHDOG - SOFTWARE REBOOT, 181=VSD - PRECHARGE LOCKOUT 2, 182=VSD - BASEPLATE TEMPERATURE IMBALANCE 2, 183=OIL - VARIABLE SPEED PUMP - HIGH RATE OF CHANGE, 184=VSD - HIGH MOTOR HARMONICS, 185=VSD - CAPACITOR FAULT, 186=VSD - ELECTRICAL SIGNATURE BOARD | |
| AV | 53 | UNIT SAFETY FAULT CODE AV | Unit Safety Fault Code AV | Read | 0=No Safety Faults Present, 1=Evaporator - Low Pressure, 2=Evaporator - Transducer Or Leaving Liquid Probe, 3=Evaporator - Transducer Or Temperature Sensor, 4=Condenser - High Pressure Contacts Open, 5=Condenser - High Pressure, 6=Condenser - Pressure Transducer Out Of Range, 7=Auxiliary Safety - Contacts Closed, 8=Discharge - Low Temperature, 9=Discharge - High Temperature, 10=Oil - High Sump Temperature, 11=Oil - Low Differential Pressure, 12=Oil - High Differential Pressure, 13=Oil - Pump Pressure Transducer Out Of Range, 14=Oil - Sump Pressure Transducer Out Of Range, 15=Motor - Lack of Motor Oil Change, 16=Sales Order - Invalid Compressor Model, 17=Sales Order – Invalid Gear Code, 18=Oil - Differential Pressure Calibration, 19=Safety Stop, 20=Oil - Variable Speed Pump - Setpoint Not Achieved, 21=Control Panel - Power Failure, 22=Control Panel – Loss of Control Voltage, 23=MOTOR OR STARTER - CURRENT IMBALANCE, 24=Thrust Bearing - Proximity Probe Clearance, 25=Thrust Bearing - Proximity Probe Uncalibrated, 26=Thrust Bearing - Proximity Probe Out Of Range, 27=Thrust Bearing - High Oil Temperature, 28=Thrust Bearing - Oil Temperature Sensor, 29=VSD - High Heatsink Temperature, 30=VSD - 105 % MOTOR CURRENT OVERLOAD, 31=VSD - HIGH PHASE A INVERTER HEATSINK TEMPERATURE, 32=VSD - HIGH PHASE B INVERTER HEATSINK TEMPERATURE, 33=VSD - HIGH PHASE C INVERTER HEATSINK TEMPERATURE, 34=VSD - HIGH CONVERTER HEATSINK TEMPERATURE, 35=VSD - PRECHARGE LOCKOUT, 36=HARMONIC FILTER - HIGH HEATSINK TEMPERATURE, 37=HARMONIC FILTER - HIGH TOTAL DEMAND DISTORTION, 38=LCSSS - PHASE ROTATION, 39=LCSSS - MOTOR OR STARTER - CURRENT IMBALANCE, 40=LCSSS - 105 % MOTOR CURRENT OVERLOAD, 41=LCSSS - HIGH INSTANTANEOUS CURRENT, 42=LCSSS - OPEN SCR, 43=LCSSS - PHASE A SHORTED SCR, 44=LCSSS - PHASE B SHORTED SCR, 45=LCSSS - PHASE C SHORTED SCR, 46=LCSSS - HIGH PHASE A HEATSINK TEMPERATURE, 47=LCSSS - HIGH PHASE B HEATSINK TEMPERATURE, 48=LCSSS - HIGH PHASE C HEATSINK TEMPERATURE, 49=Starter - Invalid Motor Selection, 50=Oil Or Condenser Transducer Error, 51=Evaporator - Low Pressure, 52=Evaporator - Low Pressure - Smart Freeze, 53=Surge Protection - Excess Surge, 54=VSD - HIGH INVERTER BASEPLATE TEMPERATURE, 55=HARMONIC FILTER - HIGH BASEPLATE TEMPERATURE, 56=Thrust Bearing - Proximity Probe Clearance, 57=Thrust Bearing - Limit Switch Open, 58=VGD Actuator – Positioning Fault, 59=Oil – Sump Or Pump Transducer Error, 60=Motor - High Housing Temperature, 61=Motor - High Winding Temperature, 62=Motor - High Bearing Temperature, 66=VSD - MOTOR CURRENT IMBALANCE, 67=Condenser - High Pressure - Stopped, 68=OIL – HIGH SUPPLY TEMPERATURE, 69=Motor - High Bearing Vibration, 70=SALES ORDER – INVALID MODEL NUMBER, 71=LCSSS - PHASE A OPEN SCR, 72=LCSSS - PHASE B OPEN SCR, 73=LCSSS - PHASE C OPEN SCR, 74=Motor - Lack Of Bearing Lubrication, 75=VSD - LOW FREQUENCY DETECTED, 76=VSD - Feedback Sensor, 77=VSD - Control Fault, 78=VSD - Drive Boot Failure, 79=MVSSS - PHASE ROTATION, 80=MVSSS - MOTOR OR STARTER - CURRENT IMBALANCE, 81=MVSSS - 105% MOTOR CURRENT OVERLOAD, 82=MVSSS - HIGH INSTANTANEOUS CURRENT, 83=MVSSS - FAILED SCR, 84=MVSSS - HIGH HEATSINK TEMPERATURE, 85=MVSSS - GROUND FAULT, 86=MVSSS - CONTACTOR FAULT, 87=MVSSS - CONTROL BOARD FAULT, 88=MVSSS - DISCONNECT FAULT, 89=VSD - POWER TRANSFORMER HIGH TEMPERATURE, 90=VSD - HIGH OUTPUT FREQUENCY, 91=MVVSD - GROUND FAULT, 92=VSD - MAIN CONTROL BOARD FAULT, 93=MVVSD - CONTACTOR FAULT, 94=MVVSD - INTERLOCK FAULT, 95=VSD - LOGIC BOARD PLUG, 96=VSD - INPUT CURRENT OVERLOAD, 97=VSD - HIGH PHASE A INPUT BASEPLATE TEMPERATURE, 98=VSD - HIGH PHASE B INPUT BASEPLATE TEMPERATURE, 99=VSD - HIGH PHASE C INPUT BASEPLATE TEMPERATURE, 100=MOTOR – LOW WINDING TEMPERATURE, 101=VSD - INVALID PWM SOFTWARE, 102=VSD - BASEPLATE TEMPERATURE IMBALANCE, 103=VSD - DC BUS PRE-REGULATION LOCKOUT, 104=VSD - GROUND FAULT, 105=VSD - HIGH INSTANTANEOUS CURRENT, 106=MOTOR CURRENT > 15 %FLA, 107=VSD - FREQUENCY > 0 HZ, 108=VSD - PHASE A INPUT DCCT, 109=VSD - PHASE B INPUT DCCT, 110=VSD - PHASE C INPUT DCCT, 111=VSD - HIGH TOTAL DEMAND DISTORTION, 112=Motor – Cooling Coil Leak, 113=MVVSD - Excessive Shutdowns, 114=Isolation Valves - Not Opened, 115=VSD - OUTPUT PHASE ROTATION, 116=VSD - Phase Locked Loop, 117=VSD - HIGH PHASE A INSTANTANEOUS CURRENT, 118=VSD - HIGH PHASE B INSTANTANEOUS CURRENT, 119=VSD - HIGH PHASE C INSTANTANEOUS CURRENT, 120=VSD - Line Voltage Phase Rotation, 121=VSD - INPUT DCCT OFFSET LOCKOUT, 122=VSD - LOGIC BOARD HARDWARE, 123=VSD - RECTIFIER PROGRAM FAULT, 124=VSD - INVERTER PROGRAM FAULT, 125=VSD - DC BUS LOCKOUT - DO NOT CYCLE POWER, 126=VSD - MOTOR CURRENT THD FAULT, 127=VSD - HIGH PHASE A MOTOR CURRENT, 128=VSD - HIGH PHASE B MOTOR CURRENT, 129=VSD - HIGH PHASE C MOTOR CURRENT, 130=VSD - HIGH PHASE A MOTOR BASEPLATE TEMPERATURE, 131=VSD - HIGH PHASE B MOTOR BASEPLATE TEMPERATURE, 132=VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATURE, 133=VSD - PHASE A MOTOR DCCT, 134=VSD - PHASE B MOTOR DCCT, 135=VSD - PHASE C MOTOR DCCT, 136=Oil – High Sump Pressure, 137=MBC – OVERSPEED FAULT, 138=MBC – WATCHDOG, 139=MBC – POWER SUPPLY FAULT, 140=MBC – HIGH HEATSINK TEMPERATURE, 141=MBC – HIGH DC BUS VOLTAGE, 142=MBC – AMPLIFIER FUSE, 143=MBC – HIGH BEARING J TEMPERATURE, 144=MBC – HIGH BEARING H1 TEMPERATURE, 145=MBC – HIGH BEARING H2 TEMPERATURE, 146=MBC – HIGH BEARING K TEMPERATURE, 147=MBC – GROUND FAULT, 148=MBC – LOW GATE VOLTAGE, 149=MBC – HIGH GATE VOLTAGE, 150=MBC – HIGH AMPLIFIER TEMPERATURE, 151=MBC – HIGH AMPLIFIER VOLTAGE, 152=MBC – FAULT CONTACTS OPEN, 153=MBC – INITIALIZATION FAILURE, 154=MBC – NOT LEVITATED, 155=SYSTEM – STARTUP FAILURE, 156=UPS – Battery Not Connected, 157=UPS – Inverter Low Battery Voltage, 158=MBC – SPEED SENSOR FAULT, 159=MBC – POWER FAIL LANDING, 160=COMPRESSOR – LOW DISCHARGE SUPERHEAT, 161=MVSSS - HIGH HEATSINK 1 TEMPERATURE, 162=MVSSS - HIGH HEATSINK 2 TEMPERATURE, 163=MVSSS - HIGH HEATSINK 3 TEMPERATURE, 164=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 165=VSD - HIGH PHASE A2 INSTANTANEOUS CURRENT, 166=VSD - HIGH PHASE B2 INSTANTANEOUS CURRENT, 167=VSD - HIGH PHASE C2 INSTANTANEOUS CURRENT, 168=VSD - HIGH PHASE A2 INVERTER BASEPLATE TEMPERATURE, 169=VSD - HIGH PHASE B2 INVERTER BASEPLATE TEMPERATURE, 170=VSD - HIGH PHASE C2 INVERTER BASEPLATE TEMPERATURE, 171=VSD - HIGH CONVERTER 2 HEATSINK TEMPERATURE, 172=VSD - MOTOR CURRENT 2 IMBALANCE, 173=VSD - MOTOR CURRENT MISMATCH, 174=VSD - HIGH PHASE A INPUT CURRENT, 175=VSD - HIGH PHASE B INPUT CURRENT, 176=VSD - HIGH PHASE C INPUT CURRENT, 177=VSD - HIGH INPUT CURRENT TDD, 178=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 179=WATCHDOG - SOFTWARE REBOOT, 180=VSD - PRECHARGE LOCKOUT 2, 181=VSD - BASEPLATE TEMPERATURE IMBALANCE 2, 182=OIL - VARIABLE SPEED PUMP - HIGH RATE OF CHANGE, 183=VSD - HIGH MOTOR HARMONICS, 184=VSD - CAPACITOR FAULT, 185=VSD - ELECTRICAL SIGNATURE BOARD | |
| MVmin | 3 | UNIT CYCLING FAULT CODE | Unit Cycling Fault Code | Read | 1=No Cycling Faults Present, 2=Multiunit Cycling - Contacts Open, 3=System Cycling - Contacts Open, 4=Oil - Low Temperature Differential, 5=Oil - Low Sump Temperature, 6=Control Panel - Power Failure, 7=Leaving Chilled Liquid - Low Temperature, 8=Leaving Chilled Liquid - Flow Switch Open, 9=Condenser - Flow Switch Open, 10=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 11=MOTOR CONTROLLER - LOSS OF CURRENT, 12=POWER FAULT, 13=Control Panel - Schedule, 14=Starter - Low Supply Line Voltage, 15=Starter - High Supply Line Voltage, 16=Proximity Probe - Low Supply Voltage, 17=Oil - Variable Speed Pump - Drive Contacts Open, 18=VSD - INITIALIZATION FAILED, 19=VSD Shutdown - Requesting Fault Data…, 20=VSD - HIGH PHASE A INSTANTANEOUS CURRENT, 21=VSD - HIGH PHASE B INSTANTANEOUS CURRENT, 22=VSD - HIGH PHASE C INSTANTANEOUS CURRENT, 23=VSD - PHASE A GATE DRIVER, 24=VSD - PHASE B GATE DRIVER, 25=VSD - PHASE C GATE DRIVER, 26=VSD - SINGLE PHASE INPUT POWER, 27=VSD - HIGH DC BUS VOLTAGE, 28=VSD - LOGIC BOARD POWER SUPPLY, 29=VSD - LOW DC BUS VOLTAGE, 30=VSD - DC BUS VOLTAGE IMBALANCE, 31=VSD - HIGH INTERNAL AMBIENT TEMPERATURE, 32=VSD - INVALID CURRENT SCALE SELECTION, 33=VSD - LOW PHASE A INVERTER HEATSINK TEMPERATURE, 34=VSD - LOW PHASE B INVERTER HEATSINK TEMPERATURE, 35=VSD - LOW PHASE C INVERTER HEATSINK TEMPERATURE, 36=VSD - LOW CONVERTER HEATSINK TEMPERATURE, 37=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE, 38=VSD - PRECHARGE - LOW DC BUS VOLTAGE, 39=VSD - LOGIC BOARD PROCESSOR, 40=VSD - RUN SIGNAL, 41=VSD - SERIAL RECEIVE, 42=VSD - Stop Contacts Open, 43=Harmonic Filter - Logic Board Or Communications, 44=HARMONIC FILTER - HIGH DC BUS VOLTAGE, 45=HARMONIC FILTER - HIGH PHASE A CURRENT, 46=HARMONIC FILTER - HIGH PHASE B CURRENT, 47=HARMONIC FILTER - HIGH PHASE C CURRENT, 48=HARMONIC FILTER - PHASE LOCKED LOOP, 49=Harmonic Filter - Precharge - Low DC Bus Voltage, 50=HARMONIC FILTER - LOW DC BUS VOLTAGE, 51=HARMONIC FILTER - DC BUS VOLTAGE IMBALANCE, 52=HARMONIC FILTER - INPUT CURRENT OVERLOAD, 53=HARMONIC FILTER - LOGIC BOARD POWER SUPPLY, 54=HARMONIC FILTER - RUN SIGNAL, 55=HARMONIC FILTER - DC CURRENT TRANSFORMER 1, 56=HARMONIC FILTER - DC CURRENT TRANSFORMER 2, 57=LCSSS Initialization Failed, 58=LCSSS Shutdown - Requesting Fault Data…, 59=LCSSS - LOW PHASE A TEMPERATURE SENSOR, 60=LCSSS - LOW PHASE B TEMPERATURE SENSOR, 61=LCSSS - LOW PHASE C TEMPERATURE SENSOR, 62=LCSSS - PHASE LOCKED LOOP, 63=LCSSS - POWER FAULT, 64=LCSSS - HIGH SUPPLY LINE VOLTAGE, 65=LCSSS - LOW SUPPLY LINE VOLTAGE, 66=LCSSS - INVALID CURRENT SCALE SELECTION, 67=LCSSS - RUN SIGNAL, 68=LCSSS - SERIAL RECEIVE, 69=LCSSS - Stop Contacts Open, 70=Motor Auto Lubrication In Progress, 71=Control Panel – Loss of Control Voltage, 72=LCSSS – LOGIC BOARD PROCESSOR, 73=LCSSS - LOGIC BOARD POWER SUPPLY, 74=VSD - Serial Communications, 75=LCSSS - Serial Communications, 76=LCSSS - PHASE LOSS, 77=VSD - LOW INVERTER BASEPLATE TEMPERATURE, 78=Expansion I/O – Serial Communications, 82=Motor Controller - Contacts Open, 83=MVVSD - Serial Communications, 84=VSD - Input Power Transformer, 85=VSD - Input Over-Voltage, 86=VSD - LOSS OF COOLING FAN, 87=VSD - HIGH INSTANTANEOUS CURRENT, 88=MVSSS - Initialization Failed, 89=MVSSS Shutdown - Requesting Fault Data…, 90=MVSSS - POWER FAULT, 91=MVSSS - HIGH SUPPLY LINE VOLTAGE, 92=MVSSS - LOW SUPPLY LINE VOLTAGE, 93=MVSSS - RUN SIGNAL, 94=MVSSS - Serial Communications, 95=MVSSS - Stop Contacts Open, 96=MVSSS - LOGIC BOARD POWER SUPPLY, 97=MVSSS - PHASE LOSS, 98=REFRIGERANT TYPE NOT SET, 99=VSD - Serial Communications, 100=LCSSS - Serial Comms, 101=VSD - Serial Communications, 102=AutoDetect - Serial Communications, 103=VSD - DC BUS VOLTAGE IMBALANCE - AU, 104=VSD - DC BUS VOLTAGE IMBALANCE - AL, 105=VSD - DC BUS VOLTAGE IMBALANCE - BU, 106=VSD - DC BUS VOLTAGE IMBALANCE - BL, 107=VSD - DC BUS VOLTAGE IMBALANCE - CU, 108=VSD - DC BUS VOLTAGE IMBALANCE - CL, 109=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AU, 110=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AL, 111=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BU, 112=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BL, 113=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CU, 114=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CL, 115=VSD - HIGH DC BUS VOLTAGE - AU, 116=VSD - HIGH DC BUS VOLTAGE - AL, 117=VSD - HIGH DC BUS VOLTAGE - BU, 118=VSD - HIGH DC BUS VOLTAGE - BL, 119=VSD - HIGH DC BUS VOLTAGE - CU, 120=VSD - HIGH DC BUS VOLTAGE - CL, 121=VSD - GATE DRIVER - ANU, 122=VSD - GATE DRIVER - ANL, 123=VSD - GATE DRIVER - AMU, 124=VSD - GATE DRIVER - AML, 125=VSD - GATE DRIVER - BNU, 126=VSD - GATE DRIVER - BNL, 127=VSD - GATE DRIVER - BMU, 128=VSD - GATE DRIVER - BML, 129=VSD - GATE DRIVER - CNU, 130=VSD - GATE DRIVER - CNL, 131=VSD - GATE DRIVER - CMU, 132=VSD - GATE DRIVER - CML, 133=VSD - INPUT POWER SUPPLY, 134=VSD - HIGH PHASE A INPUT CURRENT, 135=VSD - HIGH PHASE B INPUT CURRENT, 136=VSD - HIGH PHASE C INPUT CURRENT, 137=VSD - HIGH PHASE A MOTOR CURRENT, 138=VSD - HIGH PHASE B MOTOR CURRENT, 139=VSD - HIGH PHASE C MOTOR CURRENT, 140=VSD - PHASE A INPUT GATE DRIVER, 141=VSD - PHASE B INPUT GATE DRIVER, 142=VSD - PHASE C INPUT GATE DRIVER, 143=VGD Actuator – Serial Communications, 144=VSD - INVALID VSD MODEL, 145=VSD - BASEPLATE TEMPERATURE IMBALANCE, 146=VSD - LOW PHASE A INPUT BASEPLATE TEMPERATURE, 147=VSD - LOW PHASE B INPUT BASEPLATE TEMPERATURE, 148=VSD - LOW PHASE C INPUT BASEPLATE TEMPERATURE, 149=VSD - PHASE LOCKED LOOP, 150=VSD - LINE VOLTAGE PHASE ROTATION, 151=VSD - PRECHARGE - LOW DC BUS VOLTAGE 1, 152=VSD - Input Voltage Imbalance, 153=VSD - DC BUS PRE-REGULATION, 154=VSD - LOGIC BOARD PROCESSOR, 155=MVSSS - SERIAL RECEIVE, 156=VSD - Identifying Drive…, 157=Leaving Condenser Liquid - High Temperature, 158=Condenser - Freeze Threat - Flow Switch Open, 159=Isolation Valves - Not Closed, 160=VSD - PHASE A INPUT DCCT OFFSET, 161=VSD - PHASE B INPUT DCCT OFFSET, 162=VSD - PHASE C INPUT DCCT OFFSET, 163=VSD - INVALID SETPOINTS, 164=VSD - PRECHARGE - LOW DC BUS VOLTAGE 2, 165=VSD - SERIAL RECEIVE, 166=VSD - PHASE A MOTOR GATE DRIVER, 167=VSD - PHASE B MOTOR GATE DRIVER, 168=VSD - PHASE C MOTOR GATE DRIVER, 169=VSD - LOW PHASE A MOTOR BASEPLATE TEMPERATURE, 170=VSD - LOW PHASE B MOTOR BASEPLATE TEMPERATURE, 171=VSD - LOW PHASE C MOTOR BASEPLATE TEMPERATURE, 172=VSD - NOT RUNNING, 173=Motor - Lack Of Bearing Lubrication, 174=Evaporator - Low Pressure, 175=Expansion I/O – Serial Communications, 176=Evaporator - Low Pressure - Smart Freeze, 177=MBC – LOW DC BUS VOLTAGE, 178=MBC – J RADIAL POSITION, 179=MBC – K RADIAL POSITION, 180=MBC – H AXIAL POSITION, 181=MBC – FAULT CONTACTS OPEN, 182=MBC – SERIAL COMMUNICATIONS, 183=SYSTEM – STARTUP FAILURE, 184=UPS – Line Low Battery Voltage, 185=MBC – CALIBRATION FAULT, 186=MBC – BEARING CALIBRATION REQUIRED, 187=MOTOR CONTROLLER - INITIALIZATION FAILURE, 188=MOTOR CONTROLLER - SERIAL COMMUNICATIONS, 191=VSD - HIGH PHASE A2 INSTANTANEOUS CURRENT, 192=VSD - HIGH PHASE B2 INSTANTANEOUS CURRENT, 193=VSD - HIGH PHASE C2 INSTANTANEOUS CURRENT, 194=VSD - PHASE A2 GATE DRIVER, 195=VSD - PHASE B2 GATE DRIVER, 196=VSD - PHASE C2 GATE DRIVER, 197=VSD - HIGH DC BUS 2 VOLTAGE, 198=VSD - LOW DC BUS 2 VOLTAGE, 199=VSD - DC BUS 2 VOLTAGE IMBALANCE, 200=VSD - LOW PHASE A2 INVERTER BASEPLATE TEMPERATURE, 201=VSD - LOW PHASE B2 INVERTER BASEPLATE TEMPERATURE, 202=VSD - LOW PHASE C2 INVERTER BASEPLATE TEMPERATURE, 203=VSD - LOW CONVERTER 2 HEATSINK TEMPERATURE, 204=VSD - PRECHARGE - DC BUS 2 VOLTAGE IMBALANCE, 205=VSD - PRECHARGE - LOW DC BUS 2 VOLTAGE 1, 206=VSD - PRECHARGE - LOW DC BUS 2 VOLTAGE 2, 207=VSD - DC BUS VOLTAGE MISMATCH, 208=UPS - NOT CHARGING, 209=VSD - SINGLE PHASE INPUT POWER 2, 210=VSD - 105% MOTOR CURRENT OVERLOAD, 211=VSD - BASEPLATE TEMPERATURE IMBALANCE 2 | |
| AV | 54 | UNIT CYCLING FAULT CODE AV | Unit Cycling Fault Code AV | Read | 0=No Cycling Faults Present, 1=Multiunit Cycling - Contacts Open, 2=System Cycling - Contacts Open, 3=Oil - Low Temperature Differential, 4=Oil - Low Sump Temperature, 5=Control Panel - Power Failure, 6=Leaving Chilled Liquid - Low Temperature, 7=Leaving Chilled Liquid - Flow Switch Open, 8=Condenser - Flow Switch Open, 9=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 10=MOTOR CONTROLLER - LOSS OF CURRENT, 11=POWER FAULT, 12=Control Panel - Schedule, 13=Starter - Low Supply Line Voltage, 14=Starter - High Supply Line Voltage, 15=Proximity Probe - Low Supply Voltage, 16=Oil - Variable Speed Pump - Drive Contacts Open, 17=VSD - INITIALIZATION FAILED, 18=VSD Shutdown - Requesting Fault Data…, 19=VSD - HIGH PHASE A INSTANTANEOUS CURRENT, 20=VSD - HIGH PHASE B INSTANTANEOUS CURRENT, 21=VSD - HIGH PHASE C INSTANTANEOUS CURRENT, 22=VSD - PHASE A GATE DRIVER, 23=VSD - PHASE B GATE DRIVER, 24=VSD - PHASE C GATE DRIVER, 25=VSD - SINGLE PHASE INPUT POWER, 26=VSD - HIGH DC BUS VOLTAGE, 27=VSD - LOGIC BOARD POWER SUPPLY, 28=VSD - LOW DC BUS VOLTAGE, 29=VSD - DC BUS VOLTAGE IMBALANCE, 30=VSD - HIGH INTERNAL AMBIENT TEMPERATURE, 31=VSD - INVALID CURRENT SCALE SELECTION, 32=VSD - LOW PHASE A INVERTER HEATSINK TEMPERATURE, 33=VSD - LOW PHASE B INVERTER HEATSINK TEMPERATURE, 34=VSD - LOW PHASE C INVERTER HEATSINK TEMPERATURE, 35=VSD - LOW CONVERTER HEATSINK TEMPERATURE, 36=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE, 37=VSD - PRECHARGE - LOW DC BUS VOLTAGE, 38=VSD - LOGIC BOARD PROCESSOR, 39=VSD - RUN SIGNAL, 40=VSD - SERIAL RECEIVE, 41=VSD - Stop Contacts Open, 42=Harmonic Filter - Logic Board Or Communications, 43=HARMONIC FILTER - HIGH DC BUS VOLTAGE, 44=HARMONIC FILTER - HIGH PHASE A CURRENT, 45=HARMONIC FILTER - HIGH PHASE B CURRENT, 46=HARMONIC FILTER - HIGH PHASE C CURRENT, 47=HARMONIC FILTER - PHASE LOCKED LOOP, 48=Harmonic Filter - Precharge - Low DC Bus Voltage, 49=HARMONIC FILTER - LOW DC BUS VOLTAGE, 50=HARMONIC FILTER - DC BUS VOLTAGE IMBALANCE, 51=HARMONIC FILTER - INPUT CURRENT OVERLOAD, 52=HARMONIC FILTER - LOGIC BOARD POWER SUPPLY, 53=HARMONIC FILTER - RUN SIGNAL, 54=HARMONIC FILTER - DC CURRENT TRANSFORMER 1, 55=HARMONIC FILTER - DC CURRENT TRANSFORMER 2, 56=LCSSS Initialization Failed, 57=LCSSS Shutdown - Requesting Fault Data…, 58=LCSSS - LOW PHASE A TEMPERATURE SENSOR, 59=LCSSS - LOW PHASE B TEMPERATURE SENSOR, 60=LCSSS - LOW PHASE C TEMPERATURE SENSOR, 61=LCSSS - PHASE LOCKED LOOP, 62=LCSSS - POWER FAULT, 63=LCSSS - HIGH SUPPLY LINE VOLTAGE, 64=LCSSS - LOW SUPPLY LINE VOLTAGE, 65=LCSSS - INVALID CURRENT SCALE SELECTION, 66=LCSSS - RUN SIGNAL, 67=LCSSS - SERIAL RECEIVE, 68=LCSSS - Stop Contacts Open, 69=Motor Auto Lubrication In Progress, 70=Control Panel – Loss of Control Voltage, 71=LCSSS – LOGIC BOARD PROCESSOR, 72=LCSSS - LOGIC BOARD POWER SUPPLY, 73=VSD - Serial Communications, 74=LCSSS - Serial Communications, 75=LCSSS - PHASE LOSS, 76=VSD - LOW INVERTER BASEPLATE TEMPERATURE, 77=Expansion I/O – Serial Communications, 81=Motor Controller - Contacts Open, 82=MVVSD - Serial Communications, 83=VSD - Input Power Transformer, 84=VSD - Input Over-Voltage, 85=VSD - LOSS OF COOLING FAN, 86=VSD - HIGH INSTANTANEOUS CURRENT, 87=MVSSS - Initialization Failed, 88=MVSSS Shutdown - Requesting Fault Data…, 89=MVSSS - POWER FAULT, 90=MVSSS - HIGH SUPPLY LINE VOLTAGE, 91=MVSSS - LOW SUPPLY LINE VOLTAGE, 92=MVSSS - RUN SIGNAL, 93=MVSSS - Serial Communications, 94=MVSSS - Stop Contacts Open, 95=MVSSS - LOGIC BOARD POWER SUPPLY, 96=MVSSS - PHASE LOSS, 97=REFRIGERANT TYPE NOT SET, 98=VSD - Serial Communications, 99=LCSSS - Serial Comms, 100=VSD - Serial Communications, 101=AutoDetect - Serial Communications, 102=VSD - DC BUS VOLTAGE IMBALANCE - AU, 103=VSD - DC BUS VOLTAGE IMBALANCE - AL, 104=VSD - DC BUS VOLTAGE IMBALANCE - BU, 105=VSD - DC BUS VOLTAGE IMBALANCE - BL, 106=VSD - DC BUS VOLTAGE IMBALANCE - CU, 107=VSD - DC BUS VOLTAGE IMBALANCE - CL, 108=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AU, 109=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AL, 110=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BU, 111=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BL, 112=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CU, 113=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CL, 114=VSD - HIGH DC BUS VOLTAGE - AU, 115=VSD - HIGH DC BUS VOLTAGE - AL, 116=VSD - HIGH DC BUS VOLTAGE - BU, 117=VSD - HIGH DC BUS VOLTAGE - BL, 118=VSD - HIGH DC BUS VOLTAGE - CU, 119=VSD - HIGH DC BUS VOLTAGE - CL, 120=VSD - GATE DRIVER - ANU, 121=VSD - GATE DRIVER - ANL, 122=VSD - GATE DRIVER - AMU, 123=VSD - GATE DRIVER - AML, 124=VSD - GATE DRIVER - BNU, 125=VSD - GATE DRIVER - BNL, 126=VSD - GATE DRIVER - BMU, 127=VSD - GATE DRIVER - BML, 128=VSD - GATE DRIVER - CNU, 129=VSD - GATE DRIVER - CNL, 130=VSD - GATE DRIVER - CMU, 131=VSD - GATE DRIVER - CML, 132=VSD - INPUT POWER SUPPLY, 133=VSD - HIGH PHASE A INPUT CURRENT, 134=VSD - HIGH PHASE B INPUT CURRENT, 135=VSD - HIGH PHASE C INPUT CURRENT, 136=VSD - HIGH PHASE A MOTOR CURRENT, 137=VSD - HIGH PHASE B MOTOR CURRENT, 138=VSD - HIGH PHASE C MOTOR CURRENT, 139=VSD - PHASE A INPUT GATE DRIVER, 140=VSD - PHASE B INPUT GATE DRIVER, 141=VSD - PHASE C INPUT GATE DRIVER, 142=VGD Actuator – Serial Communications, 143=VSD - INVALID VSD MODEL, 144=VSD - BASEPLATE TEMPERATURE IMBALANCE, 145=VSD - LOW PHASE A INPUT BASEPLATE TEMPERATURE, 146=VSD - LOW PHASE B INPUT BASEPLATE TEMPERATURE, 147=VSD - LOW PHASE C INPUT BASEPLATE TEMPERATURE, 148=VSD - PHASE LOCKED LOOP, 149=VSD - LINE VOLTAGE PHASE ROTATION, 150=VSD - PRECHARGE - LOW DC BUS VOLTAGE 1, 151=VSD - Input Voltage Imbalance, 152=VSD - DC BUS PRE-REGULATION, 153=VSD - LOGIC BOARD PROCESSOR, 154=MVSSS - SERIAL RECEIVE, 155=VSD - Identifying Drive…, 156=Leaving Condenser Liquid - High Temperature, 157=Condenser - Freeze Threat - Flow Switch Open, 158=Isolation Valves - Not Closed, 159=VSD - PHASE A INPUT DCCT OFFSET, 160=VSD - PHASE B INPUT DCCT OFFSET, 161=VSD - PHASE C INPUT DCCT OFFSET, 162=VSD - INVALID SETPOINTS, 163=VSD - PRECHARGE - LOW DC BUS VOLTAGE 2, 164=VSD - SERIAL RECEIVE, 165=VSD - PHASE A MOTOR GATE DRIVER, 166=VSD - PHASE B MOTOR GATE DRIVER, 167=VSD - PHASE C MOTOR GATE DRIVER, 168=VSD - LOW PHASE A MOTOR BASEPLATE TEMPERATURE, 169=VSD - LOW PHASE B MOTOR BASEPLATE TEMPERATURE, 170=VSD - LOW PHASE C MOTOR BASEPLATE TEMPERATURE, 171=VSD - NOT RUNNING, 172=Motor - Lack Of Bearing Lubrication, 173=Evaporator - Low Pressure, 174=Expansion I/O – Serial Communications, 175=Evaporator - Low Pressure - Smart Freeze, 176=MBC – LOW DC BUS VOLTAGE, 177=MBC – J RADIAL POSITION, 178=MBC – K RADIAL POSITION, 179=MBC – H AXIAL POSITION, 180=MBC – FAULT CONTACTS OPEN, 181=MBC – SERIAL COMMUNICATIONS, 182=SYSTEM – STARTUP FAILURE, 183=UPS – Line Low Battery Voltage, 184=MBC – CALIBRATION FAULT, 185=MBC – BEARING CALIBRATION REQUIRED, 186=MOTOR CONTROLLER - INITIALIZATION FAILURE, 187=MOTOR CONTROLLER - SERIAL COMMUNICATIONS, 190=VSD - HIGH PHASE A2 INSTANTANEOUS CURRENT, 191=VSD - HIGH PHASE B2 INSTANTANEOUS CURRENT, 192=VSD - HIGH PHASE C2 INSTANTANEOUS CURRENT, 193=VSD - PHASE A2 GATE DRIVER, 194=VSD - PHASE B2 GATE DRIVER, 195=VSD - PHASE C2 GATE DRIVER, 196=VSD - HIGH DC BUS 2 VOLTAGE, 197=VSD - LOW DC BUS 2 VOLTAGE, 198=VSD - DC BUS 2 VOLTAGE IMBALANCE, 199=VSD - LOW PHASE A2 INVERTER BASEPLATE TEMPERATURE, 200=VSD - LOW PHASE B2 INVERTER BASEPLATE TEMPERATURE, 201=VSD - LOW PHASE C2 INVERTER BASEPLATE TEMPERATURE, 202=VSD - LOW CONVERTER 2 HEATSINK TEMPERATURE, 203=VSD - PRECHARGE - DC BUS 2 VOLTAGE IMBALANCE, 204=VSD - PRECHARGE - LOW DC BUS 2 VOLTAGE 1, 205=VSD - PRECHARGE - LOW DC BUS 2 VOLTAGE 2, 206=VSD - DC BUS VOLTAGE MISMATCH, 207=UPS - NOT CHARGING, 208=VSD - SINGLE PHASE INPUT POWER 2, 209=VSD - 105% MOTOR CURRENT OVERLOAD, 210=VSD - BASEPLATE TEMPERATURE IMBALANCE 2 | |
| MV | 4 | UNIT WARNING CODE | Unit Warning Code | Read | 1=No Warnings Present, 2=Real-Time Clock Failure, 3=Setpoint Override, 4=Condenser Or Evaporator Transducer Error, 5=Evaporator - Low Pressure Limit, 6=Condenser - High Pressure Limit, 7=OIL – HIGH SUPPLY TEMPERATURE, 8=COMPRESSOR – LOW DISCHARGE SUPERHEAT LIMIT, 9=WARNING - CONDENSER - HIGH TUBE CLEANING TIME, 10=Standby Lube - Low Oil Pressure, 11=Warning - Standby Lube Inihibited, 13=WARNING - SALES ORDER - INVALID SERIAL NUMBER, 14=VGD Not Calibrated, 15=VGD Actuator Switch Open, 16=PRV Not Calibrated, 17=Vanes Uncalibrated - Fixed Speed, 18=WARNING - HARMONIC FILTER - OPERATION INHIBITED, 19=Harmonic Filter - Data Loss, 20=Auto Lube Req'd On Next Shutdown, 21=Auto Lube Grease Level Low, 22=Auto Lube Failed, 23=Motor Oil Change Suggested, 24=Motor Oil Change Required, 25=Lack of Motor Oil Change, 26=Seal Lubrication In Process, 27=External I/O - Serial Communications, 28=WARNING - MMB - SERIAL COMMUNICATIONS, 30=Surge Protection - Excess Surge Limit, 31=Excess Surge Detected, 32=WARNING - HARMONIC FILTER - INVALID MODEL, 33=Motor - High Housing Temperature, 34=KW Meter Not Calibrated, 35=Condenser Or VGD Sensor Failure, 36=Conditions Override VGD, 37=Motor Bearing Lube Suggested, 38=Motor Bearing Lube Required, 39=Motor Bearing Lube Not Done, 40=WARNING - HARMONIC FILTER - DATA LOSS, 41=Motor – High Winding Temperature, 42=Motor – High Bearing Temperature, 43=Motor – High Bearing Vibration, 44=Motor – Bearing Vibration Baseline Not Set, 45=WARNING - VSD - INPUT VOLTAGE IMBALANCE, 46=WARNING - HARMONIC FILTER - NOT RUNNING, 47=Condenser- Freeze Threat From Low Pressure, 48=Liquid Level Setpoint Not Achieved, 49=VSD - DC Bus Active, 50=WARNING - LOSS OF SUBCOOLER LIQUID SEAL, 51=Oil - High Sump Pressure, 52=ECON LCSSS - Invalid Current Scale Selection, 53=ECON LCSSS - Phase Loss, 54=ECON LCSSS - Phase Locked Loop, 55=ECON LCSSS - Power Fault, 56=ECON LCSSS - Run Signal, 57=ECON LCSSS - Motor Current Imbalance, 58=ECON LCSSS - 105 % Motor Current Overload, 59=ECON LCSSS - High Motor Current, 60=ECON LCSSS - High Supply Line Voltage, 61=ECON LCSSS - Low Supply Line Voltage, 62=ECON LCSSS - Open SCR, 63=ECON LCSSS - Phase A Shorted SCR, 64=ECON LCSSS - Phase B Shorted SCR, 65=ECON LCSSS - Phase C Shorted SCR, 66=ECON LCSSS - High Phase A Heatsink Temp - Stopped, 67=ECON LCSSS - High Phase B Heatsink Temp – Stopped, 68=ECON LCSSS - High Phase C Heatsink Temp - Stopped, 69=ECON LCSSS - High Phase A Heatsink Temperature, 70=ECON LCSSS - High Phase B Heatsink Temperature, 71=ECON LCSSS - High Phase C Heatsink Temperature, 72=ECON LCSSS - Low Phase A Temperature Sensor, 73=ECON LCSSS - Low Phase B Temperature Sensor, 74=ECON LCSSS - Low Phase C Temperature Sensor, 75=ECON LCSSS - Serial Receive, 76=ECON LCSSS - Logic Board Power Supply, 78=ECON LCSSS – Undefined Fault, 79=COND OR ECON XDCR ERROR, 80=EVAP OR ECON XDCR ERROR, 81=COND OR ECON VGD XDCR FAUILURE, 82=ECON HIGH STALL – VGD OVERRIDE, 83=ECON STANDBY LUBE – LOW OIL PRESSURE, 84=ECON SEAL LUBRICATION INHIBITED, 85=ECON MOTOR – BEARING LUBE SUGGESTED, 86=ECON MOTOR – BEARING LUBE REQUIRED, 87=ECON MOTOR – BEARING LUBE NOT DONE, 88=ECON LIQUID LEVEL SETPOINT NOT ACHIEVED, 89=ECONOMIZER – LEVEL HIGH, 90=ECON ANTI-RECYCLE, 91=ECON COMPRESSOR – PRV MOTOR SWITCH OPEN, 92=ECONOMIZER – PRESSURE XDCR FAILURE, 93=ECON COMPRESSOR – HPCO SWITCH OPEN, 94=ECON COMPRESSOR – GEAR RATIO INVALID, 95=ECON MOTOR – LINE FREQUENCY NOT SET, 96=ECON DISCHARGE – LOW TEMPERATURE, 97=ECON DISCHARGE – HIGH TEMPERATURE, 98=ECON THRUST BEARING – LIMIT SWITCH OPEN, 99=ECON OIL – VSD PUMP – FAULT CONTACTS OPEN, 100=ECON OIL – PUMP PRESSURE XDCR FAILURE, 101=ECON OIL – DIFF PRESSURE CALIBRATION, 102=ECON OIL – LOW DIFFERENTIAL PRESSURE, 103=ECON OIL – HIGH DIFFERENTIAL PRESSURE, 104=ECON OIL – VSD PUMP – SETPOINT NOT ACHIEVED, 105=ECON MOTOR CONTROLLER – LOSS OF CURRENT, 106=ECON MOTOR CONTROLLER – SERIAL COMMUNICATIONS, 107=ECON MOTOR CONTROLLER – INITIALIZATION FAILED, 108=ECON MOTOR CONTROLLER – FAULT CONTACTS OPEN, 109=ECON MOTOR – LACK OF BEARING LUBRICATION, 110=ECON MOTOR – CURRENT > 15 %FLA, 111=ECON COMPRESSOR – PRV NOT CALIBRATED, 112=ECONOMIZER – HIGH LEVEL (STOPPED), 113=SALES ORDER – INVALID MOTOR VOLTS OR FLA, 114=ECON MOTOR – HIGH WINDING TEMP, 115=ECON MOTOR – HIGH BEARING TEMP, 116=ECON MOTOR – HIGH BEARING VIBRATION, 117=ECON MOTOR – VIBRATION BASELINE NOT SET, 118=ECON MOTOR – HIGH WINDING TEMP SHUTDOWN, 119=ECON MOTOR – HIGH BEARING TEMP SHUTDOWN, 120=ECON MOTOR – HIGH BEARING VIBRATION SHUTDOWN, 121=ECON MOTOR – AUTO LUBRICATION IN PROGRESS, 122=ECON AUTO LUBE REG’D ON NEXT SHUTDOWN, 123=ECON AUTO LUBE GREASE LEVEL LOW, 124=ECON AUTO LUBE FAILED, 125=ECON MMB I/O SERIAL COMMUNICATIONS, 126=WARNING - UPS - BATTERY TEST FAILED, 127=MBC – LOW AMPLIFIER RESISTANCE, 128=MBC – HIGH AMPLIFIER RESISTANCE, 129=MBC – LOW AMPLIFIER CURRENT, 130=MBC – HIGH AMPLIFIER CURRENT, 131=MBC – POSITION SENSOR ERROR, 132=WARNING - UPS - NOT CHARGING, 133=UPS – Line Low Battery Voltage, 134=UPS – Battery Not Connected, 135=UPS – Check Battery Connection, 136=WARNING - PURGE - HIGH COIL TEMP, 137=WARNING - PURGE - HIGH COIL TEMP INHIBIT, 138=WARNING - PURGE - HIGH REGEN TANK TEMP, 139=WARNING - PURGE - HIGH LEVEL, 140=WARNING - PURGE - EXCESS PURGE, 141=WARNING - PURGE - EQUALIZATION LOW SUCTION TEMP, 142=WARNING - PURGE - POSSIBLE AIR IN SYSTEM, 143=WARNING - PURGE - OPERATION INHIBITED, 144=ECON MOTOR CONTROLLER – CONTACTS OPEN, 145=ECON MOTOR CONTROLLER – POWER FAULT, 147=WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI, 148=WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI, 149=WARNING - CHECK OIL SYSTEM, 150=WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE, 151=WARNING - SYSTEM - REPLACE FILTER-DRIER, 152=WARNING - CONTROL PANEL - INTERNAL ERROR | |
| AV | 55 | UNIT WARNING CODE AV | Unit Warning Code AV | Read | 0=No Warnings Present, 1=Real-Time Clock Failure, 2=Setpoint Override, 3=Condenser Or Evaporator Transducer Error, 4=Evaporator - Low Pressure Limit, 5=Condenser - High Pressure Limit, 6=OIL – HIGH SUPPLY TEMPERATURE, 7=COMPRESSOR – LOW DISCHARGE SUPERHEAT LIMIT, 8=WARNING - CONDENSER - HIGH TUBE CLEANING TIME, 9=Standby Lube - Low Oil Pressure, 10=Warning - Standby Lube Inihibited, 12=WARNING - SALES ORDER - INVALID SERIAL NUMBER, 13=VGD Not Calibrated, 14=VGD Actuator Switch Open, 15=PRV Not Calibrated, 16=Vanes Uncalibrated - Fixed Speed, 17=WARNING - HARMONIC FILTER - OPERATION INHIBITED, 18=Harmonic Filter - Data Loss, 19=Auto Lube Req'd On Next Shutdown, 20=Auto Lube Grease Level Low, 21=Auto Lube Failed, 22=Motor Oil Change Suggested, 23=Motor Oil Change Required, 24=Lack of Motor Oil Change, 25=Seal Lubrication In Process, 26=External I/O - Serial Communications, 27=WARNING - MMB - SERIAL COMMUNICATIONS, 29=Surge Protection - Excess Surge Limit, 30=Excess Surge Detected, 31=WARNING - HARMONIC FILTER - INVALID MODEL, 32=Motor - High Housing Temperature, 33=KW Meter Not Calibrated, 34=Condenser Or VGD Sensor Failure, 35=Conditions Override VGD, 36=Motor Bearing Lube Suggested, 37=Motor Bearing Lube Required, 38=Motor Bearing Lube Not Done, 39=WARNING - HARMONIC FILTER - DATA LOSS, 40=Motor – High Winding Temperature, 41=Motor – High Bearing Temperature, 42=Motor – High Bearing Vibration, 43=Motor – Bearing Vibration Baseline Not Set, 44=WARNING - VSD - INPUT VOLTAGE IMBALANCE, 45=WARNING - HARMONIC FILTER - NOT RUNNING, 46=Condenser- Freeze Threat From Low Pressure, 47=Liquid Level Setpoint Not Achieved, 48=VSD - DC Bus Active, 49=WARNING - LOSS OF SUBCOOLER LIQUID SEAL, 50=Oil - High Sump Pressure, 51=ECON LCSSS - Invalid Current Scale Selection, 52=ECON LCSSS - Phase Loss, 53=ECON LCSSS - Phase Locked Loop, 54=ECON LCSSS - Power Fault, 55=ECON LCSSS - Run Signal, 56=ECON LCSSS - Motor Current Imbalance, 57=ECON LCSSS - 105 % Motor Current Overload, 58=ECON LCSSS - High Motor Current, 59=ECON LCSSS - High Supply Line Voltage, 60=ECON LCSSS - Low Supply Line Voltage, 61=ECON LCSSS - Open SCR, 62=ECON LCSSS - Phase A Shorted SCR, 63=ECON LCSSS - Phase B Shorted SCR, 64=ECON LCSSS - Phase C Shorted SCR, 65=ECON LCSSS - High Phase A Heatsink Temp - Stopped, 66=ECON LCSSS - High Phase B Heatsink Temp – Stopped, 67=ECON LCSSS - High Phase C Heatsink Temp - Stopped, 68=ECON LCSSS - High Phase A Heatsink Temperature, 69=ECON LCSSS - High Phase B Heatsink Temperature, 70=ECON LCSSS - High Phase C Heatsink Temperature, 71=ECON LCSSS - Low Phase A Temperature Sensor, 72=ECON LCSSS - Low Phase B Temperature Sensor, 73=ECON LCSSS - Low Phase C Temperature Sensor, 74=ECON LCSSS - Serial Receive, 75=ECON LCSSS - Logic Board Power Supply, 77=ECON LCSSS – Undefined Fault, 78=COND OR ECON XDCR ERROR, 79=EVAP OR ECON XDCR ERROR, 80=COND OR ECON VGD XDCR FAUILURE, 81=ECON HIGH STALL – VGD OVERRIDE, 82=ECON STANDBY LUBE – LOW OIL PRESSURE, 83=ECON SEAL LUBRICATION INHIBITED, 84=ECON MOTOR – BEARING LUBE SUGGESTED, 85=ECON MOTOR – BEARING LUBE REQUIRED, 86=ECON MOTOR – BEARING LUBE NOT DONE, 87=ECON LIQUID LEVEL SETPOINT NOT ACHIEVED, 88=ECONOMIZER – LEVEL HIGH, 89=ECON ANTI-RECYCLE, 90=ECON COMPRESSOR – PRV MOTOR SWITCH OPEN, 91=ECONOMIZER – PRESSURE XDCR FAILURE, 92=ECON COMPRESSOR – HPCO SWITCH OPEN, 93=ECON COMPRESSOR – GEAR RATIO INVALID, 94=ECON MOTOR – LINE FREQUENCY NOT SET, 95=ECON DISCHARGE – LOW TEMPERATURE, 96=ECON DISCHARGE – HIGH TEMPERATURE, 97=ECON THRUST BEARING – LIMIT SWITCH OPEN, 98=ECON OIL – VSD PUMP – FAULT CONTACTS OPEN, 99=ECON OIL – PUMP PRESSURE XDCR FAILURE, 100=ECON OIL – DIFF PRESSURE CALIBRATION, 101=ECON OIL – LOW DIFFERENTIAL PRESSURE, 102=ECON OIL – HIGH DIFFERENTIAL PRESSURE, 103=ECON OIL – VSD PUMP – SETPOINT NOT ACHIEVED, 104=ECON MOTOR CONTROLLER – LOSS OF CURRENT, 105=ECON MOTOR CONTROLLER – SERIAL COMMUNICATIONS, 106=ECON MOTOR CONTROLLER – INITIALIZATION FAILED, 107=ECON MOTOR CONTROLLER – FAULT CONTACTS OPEN, 108=ECON MOTOR – LACK OF BEARING LUBRICATION, 109=ECON MOTOR – CURRENT > 15 %FLA, 110=ECON COMPRESSOR – PRV NOT CALIBRATED, 111=ECONOMIZER – HIGH LEVEL (STOPPED), 112=SALES ORDER – INVALID MOTOR VOLTS OR FLA, 113=ECON MOTOR – HIGH WINDING TEMP, 114=ECON MOTOR – HIGH BEARING TEMP, 115=ECON MOTOR – HIGH BEARING VIBRATION, 116=ECON MOTOR – VIBRATION BASELINE NOT SET, 117=ECON MOTOR – HIGH WINDING TEMP SHUTDOWN, 118=ECON MOTOR – HIGH BEARING TEMP SHUTDOWN, 119=ECON MOTOR – HIGH BEARING VIBRATION SHUTDOWN, 120=ECON MOTOR – AUTO LUBRICATION IN PROGRESS, 121=ECON AUTO LUBE REG’D ON NEXT SHUTDOWN, 122=ECON AUTO LUBE GREASE LEVEL LOW, 123=ECON AUTO LUBE FAILED, 124=ECON MMB I/O SERIAL COMMUNICATIONS, 125=WARNING - UPS - BATTERY TEST FAILED, 126=MBC – LOW AMPLIFIER RESISTANCE, 127=MBC – HIGH AMPLIFIER RESISTANCE, 128=MBC – LOW AMPLIFIER CURRENT, 129=MBC – HIGH AMPLIFIER CURRENT, 130=MBC – POSITION SENSOR ERROR, 131=WARNING - UPS - NOT CHARGING, 132=UPS – Line Low Battery Voltage, 133=UPS – Battery Not Connected, 134=UPS – Check Battery Connection, 135=WARNING - PURGE - HIGH COIL TEMP, 136=WARNING - PURGE - HIGH COIL TEMP INHIBIT, 137=WARNING - PURGE - HIGH REGEN TANK TEMP, 138=WARNING - PURGE - HIGH LEVEL, 139=WARNING - PURGE - EXCESS PURGE, 140=WARNING - PURGE - EQUALIZATION LOW SUCTION TEMP, 141=WARNING - PURGE - POSSIBLE AIR IN SYSTEM, 142=WARNING - PURGE - OPERATION INHIBITED, 143=ECON MOTOR CONTROLLER – CONTACTS OPEN, 144=ECON MOTOR CONTROLLER – POWER FAULT, 146=WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI, 147=WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI, 148=WARNING - CHECK OIL SYSTEM, 149=WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE, 150=WARNING - SYSTEM - REPLACE FILTER-DRIER, 151=WARNING - CONTROL PANEL - INTERNAL ERROR | |
| MVmin | 5 | UNIT CONTROL SOURCE | Unit Control Source | Read | 0=Local, 1=BAS, 2=Analog, 3=Digital, 4=Modem, 5=Remote | |
| AV | 56 | UNIT CONTROL SOURCE AV | Unit Control Source AV | Read | 0=Local, 1=BAS, 2=Analog, 3=Digital, 4=Modem, 5=Remote | |
| MV | 6 | UNIT MODIFIED RUN CODE | Unit Modified Run Code | Read | 1=No Modified Run Conditions Present, 5=Motor - Pulldown Limit, 6=Motor - High Current Limit, 7=Motor Controller - Input Pulldown Limit, 8=Motor Controller - High Input Power Limit, 9=Load Control Mode, 10=COMPRESSOR – SUCTION FLOW LIMIT, 11=VSD - DC BUS ACTIVE, 12=VSD - Input Pulldown Limit, 13=VSD - High Input Current Limit, 14=Discharge – Low Superheat Limit, 15=ECON MOTOR – HIGH CURRENT LIMIT, 16=ECON SEAL LUBRICATION IN PROGRESS, 17=ECON ECONOMIZER – RUN DISABLED, 18=ECON ECONOMIZER – NO DEMAND, 19=ECON COMPRESSOR – NO DEMAND (ECON STOPPED), 20=SEAL LUBRICATION IN PROGRESS | |
| AV | 57 | UNIT MODIFIED RUN CODE AV | Unit Modified Run Code AV | Read | 0=No Modified Run Conditions Present, 4=Motor - Pulldown Limit, 5=Motor - High Current Limit, 6=Motor Controller - Input Pulldown Limit, 7=Motor Controller - High Input Power Limit, 8=Load Control Mode, 9=COMPRESSOR – SUCTION FLOW LIMIT, 10=VSD - DC BUS ACTIVE, 11=VSD - Input Pulldown Limit, 12=VSD - High Input Current Limit, 13=Discharge – Low Superheat Limit, 14=ECON MOTOR – HIGH CURRENT LIMIT, 15=ECON SEAL LUBRICATION IN PROGRESS, 16=ECON ECONOMIZER – RUN DISABLED, 17=ECON ECONOMIZER – NO DEMAND, 18=ECON COMPRESSOR – NO DEMAND (ECON STOPPED), 19=SEAL LUBRICATION IN PROGRESS | |
| MV | 7 | UNIT START INHIBIT CODE | Unit Start Inhibit Code | Read | 1=No Inhibit Faults Present, 2=ANTI-RECYCLE, 3=Vane Motor Switch Open, 4=MOTOR CURRENT > 15 %FLA, 5=LCSSS - HIGH PHASE A HEATSINK TEMPERATURE - STOPPED, 6=LCSSS - HIGH PHASE B HEATSINK TEMPERATURE - STOPPED, 7=LCSSS - HIGH PHASE C HEATSINK TEMPERATURE - STOPPED, 8=MOTOR CONTROLLER - INITIALIZATION IN PROGRESS, 9=VSD - FREQUENCY > 0 HZ, 10=MVSSS - HIGH HEATSINK TEMPERATURE - STOPPED, 11=Line Voltage Not Set, 12=Line Frequency Not Set, 13=Oil - High Sump Pressure - Stopped, 14=VGD Actuator - Feedback Not Calibrated, 15=VGD Actuator - Limit Switch Open, 16=PRV Not Calibrated, 17=VGD Actuator - Stroke Not Calibrated, 18=MBC - INITIALIZATION IN PROGRESS, 19=MBC - BEARING CALIBRATION IN PROGRESS, 20=MBC - BEARING CLEARANCE CHECK IN PROGRESS, 21=MVSSS - HIGH HEATSINK 1 TEMPERATURE - STOPPED, 22=MVSSS - HIGH HEATSINK 2 TEMPERATURE - STOPPED, 23=MVSSS - HIGH HEATSINK 3 TEMPERATURE - STOPPED | |
| AV | 58 | UNIT START INHIBIT CODE AV | Unit Start Inhibit Code AV | Read | 0=No Inhibit Faults Present, 1=ANTI-RECYCLE, 2=Vane Motor Switch Open, 3=MOTOR CURRENT > 15 %FLA, 4=LCSSS - HIGH PHASE A HEATSINK TEMPERATURE - STOPPED, 5=LCSSS - HIGH PHASE B HEATSINK TEMPERATURE - STOPPED, 6=LCSSS - HIGH PHASE C HEATSINK TEMPERATURE - STOPPED, 7=MOTOR CONTROLLER - INITIALIZATION IN PROGRESS, 8=VSD - FREQUENCY > 0 HZ, 9=MVSSS - HIGH HEATSINK TEMPERATURE - STOPPED, 10=Line Voltage Not Set, 11=Line Frequency Not Set, 12=Oil - High Sump Pressure - Stopped, 13=VGD Actuator - Feedback Not Calibrated, 14=VGD Actuator - Limit Switch Open, 15=PRV Not Calibrated, 16=VGD Actuator - Stroke Not Calibrated, 17=MBC - INITIALIZATION IN PROGRESS, 18=MBC - BEARING CALIBRATION IN PROGRESS, 19=MBC - BEARING CLEARANCE CHECK IN PROGRESS, 20=MVSSS - HIGH HEATSINK 1 TEMPERATURE - STOPPED, 21=MVSSS - HIGH HEATSINK 2 TEMPERATURE - STOPPED, 22=MVSSS - HIGH HEATSINK 3 TEMPERATURE - STOPPED | |
| MV | 8 | UNIT INTERNAL FAULT CODE | Unit Internal Fault Code | Read | 1=No Internal Faults Present, 2=Internal Error - No Timer Handles Available, 3=Watchdog - Software Reboot, 4=Internal Error - Cannot Create Task, 6=INTERNAL ERROR - INVALID BRAM | |
| AV | 59 | UNIT INTERNAL FAULT CODE AV | Unit Internal Fault Code AV | Read | 0=No Internal Faults Present, 1=Internal Error - No Timer Handles Available, 2=Watchdog - Software Reboot, 3=Internal Error - Cannot Create Task, 5=INTERNAL ERROR - INVALID BRAM | |
| MV | 9 | ACTIVE PURGE MODE | Active Purge Mode | Read | 1=Standard, 2=Enhanced | |
| AV | 60 | ACTIVE PURGE MODE AV | Active Purge Mode AV | Read | 1=Standard, 2=Enhanced | |
| MV | 10 | PURGE CONTROL STATE | Purge Control State | Read | 1=Disabled, 2=Auto Inhibit, 3=Manual Inhibit, 4=Purge Off, 5=Purge On, 6=Purge Air, 7=Regen Heating, 8=Regen Drain, 9=Equalizing, 10=Purge Drain | |
| AV | 61 | PURGE CONTROL STATE AV | Purge Control State AV | Read | 1=Disabled, 2=Auto Inhibit, 3=Manual Inhibit, 4=Purge Off, 5=Purge On, 6=Purge Air, 7=Regen Heating, 8=Regen Drain, 9=Equalizing, 10=Purge Drain | |
| MV | 11 | MBC CONTROL MODE | MBC Control Mode | Read | 0=Undefined, 1=Delevitated, 2=Levitated, 3=Calibrating J, 4=Calibrating K, 5=Calibrating H | |
| AV | 62 | MBC CONTROL MODE AV | MBC Control Mode AV | Read | 0=Undefined, 1=Delevitated, 2=Levitated, 3=Calibrating J, 4=Calibrating K, 5=Calibrating H | |
| MV | 12 | RUN STOP CTRL SOURCE | Run/Stop Control Source | Read | 0=Local, 1=BAS, 2=Hardwire | |
| AV | 63 | RUN STOP CTRL SOURCE AV | Run/Stop Control Source AV | Read | 0=Local, 1=BAS, 2=Hardwire | |
| MV | 13 | COOL SETP CTRL SOURCE | Cooling Setp Control Source | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 64 | COOL SETP CTRL SOURCE AV | Cooling Setp Control Source AV | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| MV | 14 | HEAT SETP CTRL SOURCE | Heating Setp Control Source | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 65 | HEAT SETP CTRL SOURCE AV | Heating Setp Control Source AV | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| MV | 15 | CURR LIM CTRL SOURCE | Current Limit Control Source | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 66 | CURR LIM CTRL SOURCE AV | Current Limit Control Source AV | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 67 | TOTAL PURGE COUNT | Total Purge Count | Read | ||
| AV | 68 | EVAP SMALL TEMP DIFF | Evaporator Small Temp Difference | °F (diff) | Read | |
| AV | 69 | COND SMALL TEMP DIFF | Condenser Small Temp Difference | °F (diff) | Read | |
| AV | 70 | DISCHARGE SUPERHEAT | Discharge Superheat | °F (diff) | Read | |
| AV | 71 | SUBCOOLER EFFECTIVENESS | Subcooler Effectiveness | Read | ||
| AV | 72 | SUBCOOLING TEMP | Subcooling Temperature | °F (diff) | Read | |
| AV | 73 | DELTA P DIV P | Delta P / P | Read | ||
| AV | 74 | HEAD PRESSURE | Head Pressure | PSID | Read | |
| AV | 75 | MOTOR SPEED | Motor Speed | Hz | Read | |
| AV | 76 | AMB DEW POINT TEMP | Ambient Dew Point Temperature | °F | Read | |
| AV | 77 | MOTOR HOUSING TEMP | Motor Housing Temperature | °F | Read | |
| AV | 78 | MOTOR COOL VLV CMD | Motor Cooling Valve Command | % | Read | |
| AV | 79 | UPS BATTERY VOLTAGE | UPS Battery Voltage | Volts | Read | |
| AV | 80 | ACT ANTI-SURGE MIN FREQ | Active Anti-Surge Minimum Frequency | Hz | Read | |
| AV | 81 | VGD POSITION | VGD Position | % | Read | |
| AV | 82 | ENTERING HEAT COND LIQ TEMP | Entering Heating Condenser Liquid Temperature (Heat Recovery only) | °F | Read | |
| AV | 83 | LEAVING HEAT COND LIQ TEMP | Leaving Heating Condenser Liquid Temperature (Heat Recovery only) | °F | Read | |
| AV | 84 | HEATING ACTIVE SP | Active Heating Setpoint | °F | Read | |
| AV | 85 | HEAT REC HEAD PRESS VLV CMD | Heat recovery / head pressure control valve command | % | Read | |
| AV | 86 | HEATING LOCAL SP | Local Heating Setpoint | °F | Read | |
| AV | 87 | STALL VOLTAGE | Stall Voltage | Volts | Read |
No points match these filters.
Object ID lookup: York YZ point IDs by name
AV1REM LEAVING CHL TEMP SPAV2REMOTE INPUT CURRENT SPAV3REM HEATING SPBV1REM RUN STOP CMDMV65001UnitsBV5COMPR MOTOR RUNBV6CH LIQ PUMP STATBV7CND LIQ PUMP STATBV8CH LIQ FLOW SWITCH STATBV9CND FLOW SWITCH STATBV10START STOP SWITCH STATUSBV11VSD COOLING SYS STATBV12VSD HARMONIC FILTER INSTBV13COND REF LEVEL CNTRL MODEBV14PURGE TANK HIGH LEVEL SWAV5LEAVING CH LIQ TEMP SEL SPAV6LEAVING CH LIQ TEMPAV7ENTERING CH LIQ TEMPAV8ENTERING COND LIQ TEMPAV9LEAVING COND LIQ TEMPAV10EVAPORATOR PRESSUREAV11CONDENSER PRESSUREAV12EVAP SATURATION TEMPAV13COND SATURATION TEMPAV14EVAP REFRIGERANT TEMPAV15DISCHARGE TEMPAV16INPUT CURRENT ACT LIMITAV17INPUT CURRENT PCT FLAAV18MOTOR CURRENT PCT FLAAV19VSD INPUT CURRENTAV20VSD PHASE A OUTPUT CURRENTAV21VSD PHASE B OUTPUT CURRENTAV22VSD PHASE C OUTPUT CURRENTAV23VSD OUTPUT VOLTAGEAV24INPUT POWERAV25INPUT KWHAV26INPUT KWH LOAV27INPUT KWH OFFSETAV28VSD DC BUS VOLTAGEAV29VSD DC BUS CURRENTAV30SURGE COUNTAV31VSD OUTPUT FREQUENCYAV32VSD INTERNAL AMBIENT TEMPAV33VSD CONVERTER HSINK TEMPAV34VSD BASEPLATE TEMPAV35VSD PH A HEATSINK TEMPAV36VSD PH B HEATSINK TEMPAV37VSD PH C HEATSINK TEMPAV38FILTER BASEPLATE TEMPAV39FILTER MAX VOLTAGE THDAV40FILTER MAX CURRENT TDDAV41FILTER SUPPLY KVAAV42MTR WINDING AVG TEMPAV43COND REFRIGERANT LEVEL SPAV44COND REFRIGERANT LEVELAV45COND LVL CTRL VLV CMDAV46DROP LEG REFRIG TEMPAV47HOT GAS BYPASS COMMANDAV48OPERATING HOURSAV49OPERATING HOURS LOAV50OPERATING HOURS OFFSETAV51NUMBER OF STARTSMV1UNIT OPERATION CODEAV52UNIT OPERATION CODE AVMV2UNIT SAFETY FAULT CODEAV53UNIT SAFETY FAULT CODE AVMV3UNIT CYCLING FAULT CODEAV54UNIT CYCLING FAULT CODE AVMV4UNIT WARNING CODEAV55UNIT WARNING CODE AVMV5UNIT CONTROL SOURCEAV56UNIT CONTROL SOURCE AVMV6UNIT MODIFIED RUN CODEAV57UNIT MODIFIED RUN CODE AVMV7UNIT START INHIBIT CODEAV58UNIT START INHIBIT CODE AVMV8UNIT INTERNAL FAULT CODEAV59UNIT INTERNAL FAULT CODE AVMV9ACTIVE PURGE MODEAV60ACTIVE PURGE MODE AVMV10PURGE CONTROL STATEAV61PURGE CONTROL STATE AVMV11MBC CONTROL MODEAV62MBC CONTROL MODE AVMV12RUN STOP CTRL SOURCEAV63RUN STOP CTRL SOURCE AVMV13COOL SETP CTRL SOURCEAV64COOL SETP CTRL SOURCE AVMV14HEAT SETP CTRL SOURCEAV65HEAT SETP CTRL SOURCE AVMV15CURR LIM CTRL SOURCEAV66CURR LIM CTRL SOURCE AVAV67TOTAL PURGE COUNTAV68EVAP SMALL TEMP DIFFAV69COND SMALL TEMP DIFFAV70DISCHARGE SUPERHEATAV71SUBCOOLER EFFECTIVENESSAV72SUBCOOLING TEMPAV73DELTA P DIV PAV74HEAD PRESSUREAV75MOTOR SPEEDAV76AMB DEW POINT TEMPAV77MOTOR HOUSING TEMPAV78MOTOR COOL VLV CMDAV79UPS BATTERY VOLTAGEAV80ACT ANTI-SURGE MIN FREQAV81VGD POSITIONAV82ENTERING HEAT COND LIQ TEMPAV83LEAVING HEAT COND LIQ TEMPAV84HEATING ACTIVE SPAV85HEAT REC HEAD PRESS VLV CMDAV86HEATING LOCAL SPAV87STALL VOLTAGE
Integration notes
- Access is inferred: the sheet has no read/write column. The remote block (AV 1-3, BV 1) is treated as commandable and MV 65001 as writable; everything else as read-only.
- Status-code MVs (operation, safety, cycling, warning, modified run, start inhibit, internal fault) are the printed code + 1, as the doc's status code tables say; the AV copies (AV 52-59) carry the raw code. MVs with their own enum in the points table are shown as printed; BACnet multistate values start at 1, so the card may report the printed number + 1. Confirm by discovery.
- Harmonic filter, heat recovery, heat pump, hot gas bypass and dew point points only report when that option is fitted or enabled.
- Units shown are the IP units; with MV 65001 set to SI the card reports °C, kPa and so on.
- Spare objects (AV 4, BV 2-4 and the empty rows) are left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
How many BACnet points does the York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) have?
This list has 113 BACnet objects: 86 analog values, 11 binary values, 16 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points are writable?
5 of the 113 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet documentation?
The source is YZ SC-EQ BAS Points List, revision Rev 1.7, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/ZAyi0nhZO6~_x09W4LLALw/content.
What are the minimum BACnet points to integrate the York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)?
Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE INPUT CURRENT SP (Remote input current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR RUN (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; BAS for BMS control); AV 6 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 18 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).
How do I enable BMS control of the York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)?
BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop and AV 1-3 are the remote setpoints. MV 5 shows the unit control source (Local, BAS, Analog, Digital, Remote); MV 12 shows the run/stop source (Local, BAS, Hardwire) and MV 13-15 the cooling setpoint, heating setpoint and current limit sources. Check they read BAS. The points list has no write-enable point.
How do I check these points on the real YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)