  4. YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)

Water-cooled centrifugal heat pump chiller (via SC-EQ card) · BACnet points list

York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) BACnet points list

Updated 7 November 2026

Short answer

The YKHT reaches a BAS through the SC-EQ communication card, which serves BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the unit and write the leaving chilled liquid setpoint, current limit, hot water setpoint and a heating/cooling mode. Read-only points cover evaporator and condenser temperatures and pressures, low and high stage discharge temperatures and vane positions, motor, starter and VSD values, heating setpoints, cooling capacity and efficiency, control sources, and multistate operation, fault, warning, modified-run and start-inhibit codes with analog copies.

This page lists 127 BACnet objects for the York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
Equipment
Water-cooled centrifugal heat pump chiller (via SC-EQ card)
Equipment type
Chillers
BACnet objects
127 (5 writable)
Transport
BACnet MS/TP
Firmware
SC-EQ release 5.12.0.17
Also known as
YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller
Source document
YT3 YKHT SC-EQ BAS Points List · rev. SC-EQ Release 5.12.0.17, 2026-07-29
Download CSV 127 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)

Integration in brief

Start and stop the unit with BV 1 and write the leaving chilled liquid setpoint (AV 1), current limit (AV 2) and, for heating, the hot water setpoint (AV 3) and mode (AV 4). Check the control-source points read BAS, then read MV 1 for the operating state, BV 5 for motor run, leaving water temperatures and % FLA, and MV 2 / MV 3 for safety and cycling shutdowns.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1REM RUN STOP CMDRemote run/stop (1 = run)Command
AV 4REM HEAT COOL MODEMode: 0 cooling, 1 heating, 2 bothCommand
AV 1REM LEAVING CHL TEMP SPRemote leaving chilled liquid setpointCommand
AV 3HOT WATER REMOTE SPRemote hot water setpointCommand
AV 2REMOTE INPUT CURRENT SPRemote current limit, %Command
MV 1UNIT OPERATION CODEOperating state (stopped, starting, running)Read
BV 5COMPR MOTOR STATUSCompressor motor runningRead
AV 5LEAVING CH LIQ TEMPLeaving chilled liquid temperatureRead
MV 2UNIT SAFETY FAULT CODESafety shutdown code (1 = none)Read
MV 3UNIT CYCLING FAULT CODECycling shutdown code (1 = none)Read

Enable & remote start

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop. MV 8 Run/Stop Control Source (Local, BAS, Hardwire) and MV 9-11 (cooling setpoint, heating setpoint and current limit sources) show where each command comes from; they should read BAS for BMS control. The sheet does not say how the sources are selected at the panel.

Network setup

Watch out for

York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

127 of 127 shown
Type
AnalogBinaryMulti-state
Access
Show
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) BACnet Points List
DescriptionStates
AVmin1REM LEAVING CHL TEMP SPRemote Leaving Chilled Liquid Setpoint°FCommand
AVmin2REMOTE INPUT CURRENT SPRemote Input Current Limit Setpoint%Command
AVmin3HOT WATER REMOTE SPRemote Hot Water Setpoint°FCommand
AVmin4REM HEAT COOL MODERemote Heating Cooling ModeCommand0=Cooling, 1=Heating, 2=Cooling and Heating
BVmin1REM RUN STOP CMDRemote Run/StopCommand0=Stop, 1=Run
AVmin5LEAVING CH LIQ TEMPLeaving Chilled Liquid Temperature°FRead
AV6ENTERING CH LIQ TEMPEntering Chilled Liquid Temperature°FRead
AV7EVAPORATOR PRESSUREEvaporator PressurePSIGRead
AV8CONDENSER PRESSURECondenser PressurePSIGRead
AV9OIL PRESSURE DIFERENTIALOil Pressure DifferentialPSIDRead
AV10ENTERING COND WATER TEMPEntering Condenser Liquid Temperature°FRead
AV11LEAVING COND WATER TEMPLeaving Condenser Liquid Temperature°FRead
AV12MOTOR CURRENT PCT FLAMotor % Full Load Amps%Read
AV13MOTOR PHASE A CURRENTMotor Phase A CurrentAmpsRead
AV14MOTOR PHASE B CURRENTMotor Phase B CurrentAmpsRead
AV15MOTOR PHASE C CURRENTMotor Phase C CurrentAmpsRead
AV16MOTOR PHASE A VOLTAGEMotor Phase A VoltageVoltsRead
AV17MOTOR PHASE B VOLTAGEMotor Phase B VoltageVoltsRead
AV18MOTOR PHASE C VOLTAGEMotor Phase C VoltageVoltsRead
AV19LEAVING CH LIQ TEMP ACT SPLeaving Chilled Liquid Setpoint - Selected°FRead
AV20EVAP SATURATION TEMPEvaporator Saturation Temperature°FRead
AV21COND SATURATION TEMPCondenser Saturation Temperature°FRead
AV22LS DISCHARGE TEMPLow Stage Discharge Temperature°FRead
AV23HS DISCHARGE TEMPHigh Stage Discharge Temperature°FRead
AV24OIL SUMP TEMPERATUREOil Sump Temperature°FRead
AV25COND REFRIGERANT LEVELCondenser Refrigerant Level%Read
AV26DELTA P DIV PDelta P / PRead
AV27OPERATING HOURSOperating HoursHrRead
AV28NUMBER OF STARTSNumber Of StartsRead
AV29OIL SUMP PRESSUREOil Sump PressurePSIGRead
AV30OIL PUMP PRESSUREOil Pump PressurePSIGRead
BVmin5COMPR MOTOR STATUSMotor RunRead0=Off, 1=On
BV6CH LIQ PUMP STATChilled Liquid PumpRead0=Off, 1=On
BV7START STOP SWITCH STATUSPanel Stop SwitchRead0=Off, 1=On
BV8CH LIQ FLOW SWITCH STATChilled Liquid Flow SwitchRead0=Open, 1=Closed
BV9CND FLOW SWITCH STATCondenser Liquid Flow SwitchRead0=Open, 1=Closed
BV10CND LIQ PUMP STATCondenser Liquid PumpRead0=Off, 1=On
AV31LS VGD POSLow Stage VGD Position%Read
AV32HS VGD POSHigh Stage VGD Position%Read
AV33HI WINDING TEMPHighest Winding Temperature°FRead
AV34MOTOR HOUSING TEMPMotor Housing Temperature°FRead
AV35VSD PHASE A CURRVSD Phase A CurrentAmpsRead
AV36VSD PHASE B CURRVSD Phase B CurrentAmpsRead
AV37VSD PHASE C CURRVSD Phase C CurrentAmpsRead
BV11VSD HARMONIC FILTER INSTHarmonic Filter InstalledRead0=False, 1=True
AV38ECONOMIZER PRESSUREEconomizer PressurePSIGRead
AV39ECON REFRIGERANT LEVELEconomizer Refrigerant Level%Read
MVmin1UNIT OPERATION CODEUnit Operation CodeRead1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Soft Shutdown, 12=Unit Coastdown, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown, 15=Unit Starting - MVVSD Startup - Drive Not Ready, 22=Unit Running - Cooling - No Abnormal Condition, 23=Unit Running - Cooling - Warning Active, 24=Unit Running - Cooling - Modified Run, 25=Unit Running - Heating - No Abnormal Condition, 26=Unit Running - Heating - Warning Active, 27=Unit Running - Heating - Modified Run, 28=Unit Running - Cooling & Heating - No Abnormal Condition, 29=Unit Running - Cooling & Heating - Warning Active, 30=Unit Running - Cooling & Heating - Modified Run
AV401UNIT OPERATION CODE AVUnit Operation Code AVRead0=Unit Stopped - Ready To Start, 1=Unit Stopped - Local Shutdown, 2=Unit Stopped - Remote Shutdown, 3=Unit Stopped - Warning Active, 4=Unit Stopped - Cycling Shutdown, 5=Unit Stopped - Safety Shutdown, 6=Unit Start Inhibit, 7=Unit Starting, 8=Unit Running - No Abnormal Condition, 9=Unit Running - Warning Active, 10=Unit Running - Soft Shutdown, 11=Unit Coastdown, 12=Unit Running - Modified Run, 13=Unit Stopped - Internal Shutdown, 14=Unit Starting - MVVSD Startup - Drive Not Ready, 21=Unit Running - Cooling - No Abnormal Condition, 22=Unit Running - Cooling - Warning Active, 23=Unit Running - Cooling - Modified Run, 24=Unit Running - Heating - No Abnormal Condition, 25=Unit Running - Heating - Warning Active, 26=Unit Running - Heating - Modified Run, 27=Unit Running - Cooling & Heating - No Abnormal Condition, 28=Unit Running - Cooling & Heating - Warning Active, 29=Unit Running - Cooling & Heating - Modified Run
MVmin2UNIT SAFETY FAULT CODEUnit Safety Fault CodeRead1=No Safety Faults Present, 2=Evaporator - Low Pressure, 3=Evaporator - Transducer Or Leaving Liquid Probe, 4=Evaporator - Transducer Or Temperature Sensor, 5=Condenser - High Pressure Contacts Open, 6=Condenser - High Pressure, 7=Condenser - Pressure Transducer Out Of Range, 8=Auxiliary Safety - Contacts Closed, 9=Discharge - Low Temperature, 10=Discharge - High Temperature, 11=Oil - High Sump Temperature, 12=Oil - Low Differential Pressure, 13=Oil - High Differential Pressure, 14=Oil - Pump Pressure Transducer Out Of Range, 15=Oil - Sump Pressure Transducer Out Of Range, 17=Sales Order - Invalid Compressor Model, 19=Oil - Differential Pressure Calibration, 20=Safety Stop, 21=Oil - Variable Speed Pump - Setpoint Not Achieved, 22=Control Panel - Power Failure, 23=Control Panel – Loss of Control Voltage, 24=MOTOR OR STARTER - CURRENT IMBALANCE, 25=Thrust Bearing - Proximity Probe Clearance, 26=Thrust Bearing - Proximity Probe Uncalibrated, 27=Thrust Bearing - Proximity Probe Out Of Range, 31=VSD - 105 % MOTOR CURRENT OVERLOAD, 51=Oil Or Condenser Transducer Error, 53=Evaporator - Low Pressure - Smart Freeze, 54=Surge Protection - Excess Surge, 57=Thrust Bearing - Proximity Probe Clearance, 59=Low Stage VGD Actuator – Positioning Fault, 62=Motor - High Winding Temperature, 63=Motor - High Bearing Temperature, 64=VSD - HIGH PHASE A INVERTER BASEPLATE TEMPERATURE, 65=VSD - HIGH PHASE B INVERTER BASEPLATE TEMPERATURE, 66=VSD - HIGH PHASE C INVERTER BASEPLATE TEMPERATURE, 68=Condenser - High Pressure - Stopped, 69=OIL - HIGH SUPPLY TEMPERATURE, 70=Motor - High Bearing Vibration, 76=VSD - LOW FREQUENCY DETECTED, 80=MVSSS - PHASE ROTATION, 81=MVSSS - MOTOR OR STARTER - CURRENT IMBALANCE, 82=MVSSS - 105% MOTOR CURRENT OVERLOAD, 83=MVSSS - HIGH INSTANTANEOUS CURRENT, 84=MVSSS - FAILED SCR, 85=MVSSS - HIGH HEATSINK TEMPERATURE, 86=MVSSS - GROUND FAULT, 87=MVSSS - CONTACTOR FAULT, 88=MVSSS - CONTROL BOARD FAULT, 89=MVSSS - DISCONNECT FAULT, 90=VSD - POWER TRANSFORMER HIGH TEMPERATURE, 91=VSD - HIGH OUTPUT FREQUENCY, 92=MVVSD - GROUND FAULT, 93=VSD - MAIN CONTROL BOARD FAULT, 94=MVVSD - CONTACTOR FAULT, 95=MVVSD - INTERLOCK FAULT, 106=VSD - HIGH INSTANTANEOUS CURRENT, 107=MOTOR CURRENT > 15 %FLA, 108=VSD - FREQUENCY > 0 HZ, 113=Motor – Cooling Coil Leak, 137=Oil – High Sump Pressure, 161=COMPRESSOR – LOW DISCHARGE SUPERHEAT, 162=MVSSS - HIGH HEATSINK 1 TEMPERATURE, 163=MVSSS - HIGH HEATSINK 2 TEMPERATURE, 164=MVSSS - HIGH HEATSINK 3 TEMPERATURE, 165=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 179=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 180=WATCHDOG - SOFTWARE REBOOT, 183=OIL - VARIABLE SPEED PUMP - HIGH RATE OF CHANGE, 187=OIL - LOW SUPPLY TEMPERATURE, 188=OIL – HIGH VISCOSITY, 189=OIL – LOW VISCOSITY, 190=OIL – HIGH DILUTION
AV402UNIT SAFETY FAULT CODE AVUnit Safety Fault Code AVRead0=No Safety Faults Present, 1=Evaporator - Low Pressure, 2=Evaporator - Transducer Or Leaving Liquid Probe, 3=Evaporator - Transducer Or Temperature Sensor, 4=Condenser - High Pressure Contacts Open, 5=Condenser - High Pressure, 6=Condenser - Pressure Transducer Out Of Range, 7=Auxiliary Safety - Contacts Closed, 8=Discharge - Low Temperature, 9=Discharge - High Temperature, 10=Oil - High Sump Temperature, 11=Oil - Low Differential Pressure, 12=Oil - High Differential Pressure, 13=Oil - Pump Pressure Transducer Out Of Range, 14=Oil - Sump Pressure Transducer Out Of Range, 16=Sales Order - Invalid Compressor Model, 18=Oil - Differential Pressure Calibration, 19=Safety Stop, 20=Oil - Variable Speed Pump - Setpoint Not Achieved, 21=Control Panel - Power Failure, 22=Control Panel – Loss of Control Voltage, 23=MOTOR OR STARTER - CURRENT IMBALANCE, 24=Thrust Bearing - Proximity Probe Clearance, 25=Thrust Bearing - Proximity Probe Uncalibrated, 26=Thrust Bearing - Proximity Probe Out Of Range, 30=VSD - 105 % MOTOR CURRENT OVERLOAD, 50=Oil Or Condenser Transducer Error, 52=Evaporator - Low Pressure - Smart Freeze, 53=Surge Protection - Excess Surge, 56=Thrust Bearing - Proximity Probe Clearance, 58=Low Stage VGD Actuator – Positioning Fault, 61=Motor - High Winding Temperature, 62=Motor - High Bearing Temperature, 63=VSD - HIGH PHASE A INVERTER BASEPLATE TEMPERATURE, 64=VSD - HIGH PHASE B INVERTER BASEPLATE TEMPERATURE, 65=VSD - HIGH PHASE C INVERTER BASEPLATE TEMPERATURE, 67=Condenser - High Pressure - Stopped, 68=OIL - HIGH SUPPLY TEMPERATURE, 69=Motor - High Bearing Vibration, 75=VSD - LOW FREQUENCY DETECTED, 79=MVSSS - PHASE ROTATION, 80=MVSSS - MOTOR OR STARTER - CURRENT IMBALANCE, 81=MVSSS - 105% MOTOR CURRENT OVERLOAD, 82=MVSSS - HIGH INSTANTANEOUS CURRENT, 83=MVSSS - FAILED SCR, 84=MVSSS - HIGH HEATSINK TEMPERATURE, 85=MVSSS - GROUND FAULT, 86=MVSSS - CONTACTOR FAULT, 87=MVSSS - CONTROL BOARD FAULT, 88=MVSSS - DISCONNECT FAULT, 89=VSD - POWER TRANSFORMER HIGH TEMPERATURE, 90=VSD - HIGH OUTPUT FREQUENCY, 91=MVVSD - GROUND FAULT, 92=VSD - MAIN CONTROL BOARD FAULT, 93=MVVSD - CONTACTOR FAULT, 94=MVVSD - INTERLOCK FAULT, 105=VSD - HIGH INSTANTANEOUS CURRENT, 106=MOTOR CURRENT > 15 %FLA, 107=VSD - FREQUENCY > 0 HZ, 112=Motor – Cooling Coil Leak, 136=Oil – High Sump Pressure, 160=COMPRESSOR – LOW DISCHARGE SUPERHEAT, 161=MVSSS - HIGH HEATSINK 1 TEMPERATURE, 162=MVSSS - HIGH HEATSINK 2 TEMPERATURE, 163=MVSSS - HIGH HEATSINK 3 TEMPERATURE, 164=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 178=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 179=WATCHDOG - SOFTWARE REBOOT, 182=OIL - VARIABLE SPEED PUMP - HIGH RATE OF CHANGE, 186=OIL - LOW SUPPLY TEMPERATURE, 187=OIL – HIGH VISCOSITY, 188=OIL – LOW VISCOSITY, 189=OIL – HIGH DILUTION
MVmin3UNIT CYCLING FAULT CODEUnit Cycling Fault CodeRead1=No Cycling Faults Present, 3=System Cycling - Contacts Open, 4=Oil - Low Temperature Differential, 5=Oil - Low Sump Temperature, 6=Control Panel - Power Failure, 7=Leaving Chilled Liquid - Low Temperature, 8=Leaving Chilled Liquid - Flow Switch Open, 9=Condenser - Flow Switch Open, 10=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 11=MOTOR CONTROLLER - LOSS OF CURRENT, 12=POWER FAULT, 16=Proximity Probe - Low Supply Voltage, 17=Oil - Variable Speed Pump - Drive Contacts Open, 18=VSD - INITIALIZATION FAILED, 19=Reserved, 26=VSD - SINGLE PHASE INPUT POWER, 29=VSD - LOW DC BUS VOLTAGE, 38=VSD - PRECHARGE - LOW DC BUS VOLTAGE, 40=VSD - RUN SIGNAL, 71=Control Panel – Loss of Control Voltage, 78=ECONOMIZER - PRESSURE XDCR OUT OF RANGE, 86=VSD - LOSS OF COOLING FAN, 87=VSD - HIGH INSTANTANEOUS CURRENT, 89=ECONOMIZER - LEVEL HIGH, 90=MVSSS - POWER FAULT, 91=MVSSS - HIGH SUPPLY LINE VOLTAGE, 92=MVSSS - LOW SUPPLY LINE VOLTAGE, 93=MVSSS - RUN SIGNAL, 96=MVSSS - LOGIC BOARD POWER SUPPLY, 97=MVSSS - PHASE LOSS, 98=REFRIGERANT TYPE NOT SET, 103=VSD - DC BUS VOLTAGE IMBALANCE - AU, 104=VSD - DC BUS VOLTAGE IMBALANCE - AL, 105=VSD - DC BUS VOLTAGE IMBALANCE - BU, 106=VSD - DC BUS VOLTAGE IMBALANCE - BL, 107=VSD - DC BUS VOLTAGE IMBALANCE - CU, 108=VSD - DC BUS VOLTAGE IMBALANCE - CL, 109=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AU, 110=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AL, 111=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BU, 112=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BL, 113=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CU, 114=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CL, 115=VSD - HIGH DC BUS VOLTAGE - AU, 116=VSD - HIGH DC BUS VOLTAGE - AL, 117=VSD - HIGH DC BUS VOLTAGE - BU, 118=VSD - HIGH DC BUS VOLTAGE - BL, 119=VSD - HIGH DC BUS VOLTAGE - CU, 120=VSD - HIGH DC BUS VOLTAGE - CL, 121=VSD - GATE DRIVER - ANU, 122=VSD - GATE DRIVER - ANL, 123=VSD - GATE DRIVER - AMU, 124=VSD - GATE DRIVER - AML, 125=VSD - GATE DRIVER - BNU, 126=VSD - GATE DRIVER - BNL, 127=VSD - GATE DRIVER - BMU, 128=VSD - GATE DRIVER - BML, 129=VSD - GATE DRIVER - CNU, 130=VSD - GATE DRIVER - CNL, 131=VSD - GATE DRIVER - CMU, 132=VSD - GATE DRIVER - CML, 133=VSD - INPUT POWER SUPPLY, 143=Low Stage VGD Actuator – Serial Communications, 155=MVSSS - SERIAL RECEIVE, 157=Leaving Condenser Liquid - High Temperature, 158=Condenser - Freeze Threat - Flow Switch Open, 174=Evaporator - Low Pressure, 175=Expansion I/O – Serial Communications, 176=Evaporator - Low Pressure - Smart Freeze, 187=MOTOR CONTROLLER - INITIALIZATION FAILURE, 188=MOTOR CONTROLLER - SERIAL COMMUNICATIONS
AV403UNIT CYCLING FAULT CODE AVUnit Cycling Fault Code AVRead0=No Cycling Faults Present, 2=System Cycling - Contacts Open, 3=Oil - Low Temperature Differential, 4=Oil - Low Sump Temperature, 5=Control Panel - Power Failure, 6=Leaving Chilled Liquid - Low Temperature, 7=Leaving Chilled Liquid - Flow Switch Open, 8=Condenser - Flow Switch Open, 9=MOTOR CONTROLLER - FAULT CONTACTS OPEN, 10=MOTOR CONTROLLER - LOSS OF CURRENT, 11=POWER FAULT, 15=Proximity Probe - Low Supply Voltage, 16=Oil - Variable Speed Pump - Drive Contacts Open, 17=VSD - INITIALIZATION FAILED, 18=Reserved, 25=VSD - SINGLE PHASE INPUT POWER, 28=VSD - LOW DC BUS VOLTAGE, 37=VSD - PRECHARGE - LOW DC BUS VOLTAGE, 39=VSD - RUN SIGNAL, 70=Control Panel – Loss of Control Voltage, 77=ECONOMIZER - PRESSURE XDCR OUT OF RANGE, 85=VSD - LOSS OF COOLING FAN, 86=VSD - HIGH INSTANTANEOUS CURRENT, 88=ECONOMIZER - LEVEL HIGH, 89=MVSSS - POWER FAULT, 90=MVSSS - HIGH SUPPLY LINE VOLTAGE, 91=MVSSS - LOW SUPPLY LINE VOLTAGE, 92=MVSSS - RUN SIGNAL, 95=MVSSS - LOGIC BOARD POWER SUPPLY, 96=MVSSS - PHASE LOSS, 97=REFRIGERANT TYPE NOT SET, 102=VSD - DC BUS VOLTAGE IMBALANCE - AU, 103=VSD - DC BUS VOLTAGE IMBALANCE - AL, 104=VSD - DC BUS VOLTAGE IMBALANCE - BU, 105=VSD - DC BUS VOLTAGE IMBALANCE - BL, 106=VSD - DC BUS VOLTAGE IMBALANCE - CU, 107=VSD - DC BUS VOLTAGE IMBALANCE - CL, 108=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AU, 109=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - AL, 110=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BU, 111=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - BL, 112=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CU, 113=VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE - CL, 114=VSD - HIGH DC BUS VOLTAGE - AU, 115=VSD - HIGH DC BUS VOLTAGE - AL, 116=VSD - HIGH DC BUS VOLTAGE - BU, 117=VSD - HIGH DC BUS VOLTAGE - BL, 118=VSD - HIGH DC BUS VOLTAGE - CU, 119=VSD - HIGH DC BUS VOLTAGE - CL, 120=VSD - GATE DRIVER - ANU, 121=VSD - GATE DRIVER - ANL, 122=VSD - GATE DRIVER - AMU, 123=VSD - GATE DRIVER - AML, 124=VSD - GATE DRIVER - BNU, 125=VSD - GATE DRIVER - BNL, 126=VSD - GATE DRIVER - BMU, 127=VSD - GATE DRIVER - BML, 128=VSD - GATE DRIVER - CNU, 129=VSD - GATE DRIVER - CNL, 130=VSD - GATE DRIVER - CMU, 131=VSD - GATE DRIVER - CML, 132=VSD - INPUT POWER SUPPLY, 142=Low Stage VGD Actuator – Serial Communications, 154=MVSSS - SERIAL RECEIVE, 156=Leaving Condenser Liquid - High Temperature, 157=Condenser - Freeze Threat - Flow Switch Open, 173=Evaporator - Low Pressure, 174=Expansion I/O – Serial Communications, 175=Evaporator - Low Pressure - Smart Freeze, 186=MOTOR CONTROLLER - INITIALIZATION FAILURE, 187=MOTOR CONTROLLER - SERIAL COMMUNICATIONS
MV4UNIT WARNING CODEUnit Warning CodeRead1=No Warnings Present, 2=Real-Time Clock Failure, 3=Setpoint Override, 4=Condenser Or Evaporator Transducer Error, 5=Evaporator - Low Pressure Limit, 6=Condenser - High Pressure Limit, 7=WARNING - OIL - HIGH SUPPLY TEMPERATURE, 8=COMPRESSOR - LOW DISCHARGE SUPERHEAT LIMIT, 9=WARNING - CONDENSER - HIGH TUBE CLEANING TIME, 13=WARNING - SALES ORDER - INVALID SERIAL NUMBER, 14=VGD Not Calibrated, 27=External I/O - Serial Communications, 28=WARNING - MMB - SERIAL COMMUNICATIONS, 30=Surge Protection - Excess Surge Limit, 31=Excess Surge Detected, 41=Motor – High Winding Temperature, 42=Motor – High Bearing Temperature, 43=Motor – High Bearing Vibration, 44=Motor – Bearing Vibration Baseline Not Set, 47=Condenser- Freeze Threat From Low Pressure, 48=Liquid Level Setpoint Not Achieved, 50=Loss Of Subcooler Liquid Seal, 51=Oil - High Sump Pressure, 79=COND OR ECON XDCR ERROR, 80=EVAP OR ECON XDCR ERROR, 88=ECON LIQUID LEVEL SETPOINT NOT ACHIEVED, 146=WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI, 147=WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI, 148=WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI, 149=WARNING - CHECK OIL SYSTEM, 150=WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE, 152=WARNING - CONTROL PANEL - INTERNAL ERROR, 153=WARNING - COMPRESSOR - LOW DISCHARGE SUPERHEAT, 154=WARNING - CONDENSER - LIQUID LEVEL STABILITY, 155=WARNING - OIL - LOW SUPPLY TEMPERATURE
AV404UNIT WARNING CODE AVUnit Warning Code AVRead0=No Warnings Present, 1=Real-Time Clock Failure, 2=Setpoint Override, 3=Condenser Or Evaporator Transducer Error, 4=Evaporator - Low Pressure Limit, 5=Condenser - High Pressure Limit, 6=WARNING - OIL - HIGH SUPPLY TEMPERATURE, 7=COMPRESSOR - LOW DISCHARGE SUPERHEAT LIMIT, 8=WARNING - CONDENSER - HIGH TUBE CLEANING TIME, 12=WARNING - SALES ORDER - INVALID SERIAL NUMBER, 13=VGD Not Calibrated, 26=External I/O - Serial Communications, 27=WARNING - MMB - SERIAL COMMUNICATIONS, 29=Surge Protection - Excess Surge Limit, 30=Excess Surge Detected, 40=Motor – High Winding Temperature, 41=Motor – High Bearing Temperature, 42=Motor – High Bearing Vibration, 43=Motor – Bearing Vibration Baseline Not Set, 46=Condenser- Freeze Threat From Low Pressure, 47=Liquid Level Setpoint Not Achieved, 49=Loss Of Subcooler Liquid Seal, 50=Oil - High Sump Pressure, 78=COND OR ECON XDCR ERROR, 79=EVAP OR ECON XDCR ERROR, 87=ECON LIQUID LEVEL SETPOINT NOT ACHIEVED, 145=WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI, 146=WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI, 147=WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI, 148=WARNING - CHECK OIL SYSTEM, 149=WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE, 151=WARNING - CONTROL PANEL - INTERNAL ERROR, 152=WARNING - COMPRESSOR - LOW DISCHARGE SUPERHEAT, 153=WARNING - CONDENSER - LIQUID LEVEL STABILITY, 154=WARNING - OIL - LOW SUPPLY TEMPERATURE
MV5UNIT CONTROL SOURCEUnit Control SourceRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
AV405UNIT CONTROL SOURCE AVUnit Control Source AVRead0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote
MV6UNIT MODIFIED RUN CODEUnit Modified Run CodeRead1=No Modified Run Conditions Present, 5=Motor - Pulldown Limit, 6=Motor - High Current Limit, 7=Motor Controller - Input Pulldown Limit, 8=Motor Controller - High Input Power Limit, 9=Load Control Mode, 10=COMPRESSOR - SUCTION FLOW LIMIT, 11=VSD - DC BUS ACTIVE, 12=VSD - Input Pulldown Limit, 14=Discharge – Low Superheat Limit
AV406UNIT MODIFIED RUN CODE AVUnit Modified Run Code AVRead0=No Modified Run Conditions Present, 4=Motor - Pulldown Limit, 5=Motor - High Current Limit, 6=Motor Controller - Input Pulldown Limit, 7=Motor Controller - High Input Power Limit, 8=Load Control Mode, 9=COMPRESSOR - SUCTION FLOW LIMIT, 10=VSD - DC BUS ACTIVE, 11=VSD - Input Pulldown Limit, 13=Discharge – Low Superheat Limit
MV7UNIT START INHIBIT CODEUnit Start Inhibit CodeRead1=No Inhibit Faults Present, 2=ANTI-RECYCLE, 8=MOTOR CONTROLLER - INITIALIZATION IN PROGRESS, 10=MVSSS - HIGH HEATSINK TEMPERATURE - STOPPED, 12=Line Frequency Not Set, 13=Oil – High Sump Pressure - Stopped, 14=Low Stage VGD Actuator – Feedback Not Calibrated, 17=Low Stage VGD Actuator – Stroke Not Calibrated, 21=MVSSS - HIGH HEATSINK 1 TEMPERATURE - STOPPED, 22=MVSSS - HIGH HEATSINK 2 TEMPERATURE - STOPPED, 23=MVSSS - HIGH HEATSINK 3 TEMPERATURE - STOPPED, 25=OIL – HIGH DILUTION INHIBIT, 26=OIL – LOW VISCOSITY INHIBIT, 27=OIL – LOW TEMPERATURE DIFFERENTIAL, 28=ECONOMIZER - LEVEL HIGH STOPPED
AV407UNIT START INHIBIT CODE AVUnit Start Inhibit Code AVRead0=No Inhibit Faults Present, 1=ANTI-RECYCLE, 7=MOTOR CONTROLLER - INITIALIZATION IN PROGRESS, 9=MVSSS - HIGH HEATSINK TEMPERATURE - STOPPED, 11=Line Frequency Not Set, 12=Oil – High Sump Pressure - Stopped, 13=Low Stage VGD Actuator – Feedback Not Calibrated, 16=Low Stage VGD Actuator – Stroke Not Calibrated, 20=MVSSS - HIGH HEATSINK 1 TEMPERATURE - STOPPED, 21=MVSSS - HIGH HEATSINK 2 TEMPERATURE - STOPPED, 22=MVSSS - HIGH HEATSINK 3 TEMPERATURE - STOPPED, 24=OIL – HIGH DILUTION INHIBIT, 25=OIL – LOW VISCOSITY INHIBIT, 26=OIL – LOW TEMPERATURE DIFFERENTIAL, 27=ECONOMIZER - LEVEL HIGH STOPPED
AV40PROX SENSOR ACT POSHigh Speed Thrust Bearing Proximity PositionMilsRead
AV41PROX SENSOR REF POSHigh Speed Thrust Bearing Proximity ReferenceMilsRead
AV42ANTI RECYCLE TIME REMAINAnti-Recycle Time RemainingMinRead
AV43VSD OUTPUT VOLTAGEVSD Output VoltageVoltsRead
AV44VSD PHS A OUT VOLT RMSVSD Phase A Output Voltage (RMS)VoltsRead
AV45VSD PHS B OUT VOLT RMSVSD Phase B Output Voltage (RMS)VoltsRead
AV46VSD PHS C OUT VOLT RMSVSD Phase C Output Voltage (RMS)VoltsRead
AV47VSD PHASE A OUTPT CURR PEAKVSD Phase A Output Current (Peak)AmpsRead
AV48VSD PHASE B OUTPT CURR PEAKVSD Phase B Output Current (Peak)AmpsRead
AV49VSD PHASE C OUTPT CURR PEAKVSD Phase C Output Current (Peak)AmpsRead
AV50VSD INPUT POWERVSD Input PowerkWRead
AV51VSD INPUT KWHVSD Input Kilowatt HourskWhRead
AV52VSD DC BUS VOLTAGEVSD DC Bus VoltageVoltsRead
AV53VSD OUTPUT FREQUENCYVSD Output FrequencyHzRead
AV54COND LEVEL CTRL VALVE CMDCondenser Level Control Valve Command%Read
AV55MTR SHAFT END TEMPMotor Bearing Shaft End Temperature°FRead
AV56MTR OP SHAFT END TEMPMotor Bearing Opposite Shaft End Temperature°FRead
AV57MTR WINDING AVG TEMPAverage Winding Temperature°FRead
AV58COND REFRIGERANT LEVEL SPCondenser Refrigerant Level Setpoint%Read
AV59DROP LEG REFRIG TEMPDrop Leg Refrigerant Temperature°FRead
AV60HEATING LOCAL SPLocal Heating Setpoint°FRead
AV61HEATING ACTIVE SPActive Heating Setpoint°FRead
AV62HEAT REC HEAD PRESS VLV CMDHeat Recovery/Head Pressure Control Valve Cmd%Read
AV63INPUT POWERInput PowerkWRead
AV64INPUT KWHInput Kilowatt HourskWhRead
AV65HOT GAS BYPASS COMMANDHot Gas Bypass Command%Read
BV12COND REF LEVEL CNTRL MODECondenser Level Control Valve ModeRead0=Auto, 1=Manual
AV66ECON SATURATION TEMP ACT SPEconomizer Active Saturation Temperature Setpoint°FRead
AV67ECON SATURATION TEMPEconomizer Saturation Temperature°FRead
AV68ECON MTR CURR OVERRIDE THRESHEconomizer Motor Current Override Threshold%Read
AV69ECON REFRIGERANT LEVEL SPEconomizer Active Level Setpoint%Read
BV13OIL STILL LIQ FEED SOLOil Still Liquid Feed SolenoidRead0=Off, 1=On
BV14MOTOR SPACE HEATER STATUSMotor Space HeaterRead0=Off, 1=On
BV15DISP UNITSDisplay UnitsRead0=Imperial, 1=SI
AV70MTR WINDING PH A TEMPMotor Winding Phase A Temperature°FRead
AV71MTR WINDING PH B TEMPMotor Winding Phase B Temperature°FRead
AV72MTR WINDING PH C TEMPMotor Winding Phase C Temperature°FRead
AV73MTR WINDING PH A2 TEMPMotor Winding Phase A2 Temperature°FRead
AV74MTR WINDING PH B2 TEMPMotor Winding Phase B2 Temperature°FRead
AV75MTR WINDING PH C2 TEMPMotor Winding Phase C2 Temperature°FRead
AV76VSD OIL PUMP CMD FREQUENCYVSD Oil Pump Command FrequencyHzRead
AV77EVAP SMALL TEMP DIFFEvaporator Small Temp Difference°F (diff)Read
AV78COND SMALL TEMP DIFFCondenser Small Temp Difference°F (diff)Read
AV79SUBCOOLER EFFECTIVENESSSubcooler EffectivenessRead
AV80SUBCOOLING TEMPSubcooling Temperature°F (diff)Read
MV8RUN STOP CTRL SOURCERun/Stop Control SourceRead0=Local, 1=BAS, 2=Hardwire
AV408RUN STOP CTRL SOURCE AVRun/Stop Control Source AVRead0=Local, 1=BAS, 2=Hardwire
MV9COOL SETP CTRL SOURCECooling Setp Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV409COOL SETP CTRL SOURCE AVCooling Setp Control Source AVRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
MV10HEAT SETP CTRL SOURCEHeating Setp Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV410HEAT SETP CTRL SOURCE AVHeating Setp Control Source AVRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
MV11CURR LIM CTRL SOURCECurrent Limit Control SourceRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV411CURR LIM CTRL SOURCE AVCurrent Limit Control Source AVRead0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM
AV81SSS PHASE A TEMPSSS Phase A Temperature°FRead
AV82SSS PHASE B TEMPSSS Phase B Temperature°FRead
AV83SSS PHASE C TEMPSSS Phase C Temperature°FRead
AV84L1 INPT CURR PEAKL1 Input Current PeakAmpsRead
AV85L2 INPT CURR PEAKL2 Input Current PeakAmpsRead
AV86L3 INPT CURR PEAKL3 Input Current PeakAmpsRead
AV87INPT KWH PWR METERInput kWh (Power Meter)kWhRead
AV88COOLG PCT CAPCooling Percent Capacity%Read
AV89COOLG CAP TONSCooling Capacity TonsTRRead
AV90COOLG PCT PWRCooling Percent Power%Read
AV91COOLG EFFCNCYCooling EfficiencykW/TonRead
AV92COOLG COPCooling COPRead
BV16HOT WATER CONTROL ENHot Water Control EnableRead0=Disabled, 1=Enabled
Object ID lookup: York YKHT (YT3) SC-EQ point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)

How many BACnet points does the York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) have?

This list has 127 BACnet objects: 103 analog values, 13 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) BACnet points are writable?

5 of the 127 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ) BACnet documentation?

The source is YT3 YKHT SC-EQ BAS Points List, revision SC-EQ Release 5.12.0.17, 2026-07-29, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/yo5s9kYw0NJUW_ajAYQYjQ/content.

What are the minimum BACnet points to integrate the York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)?

Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 4 REM HEAT COOL MODE (Mode: 0 cooling, 1 heating, 2 both); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 3 HOT WATER REMOTE SP (Remote hot water setpoint); AV 2 REMOTE INPUT CURRENT SP (Remote current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).

How do I enable BMS control of the York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)?

BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop. MV 8 Run/Stop Control Source (Local, BAS, Hardwire) and MV 9-11 (cooling setpoint, heating setpoint and current limit sources) show where each command comes from; they should read BAS for BMS control. The sheet does not say how the sources are selected at the panel.

How do I check these points on the real YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.