Scroll chiller / heat pump / condensing unit · BACnet points list

York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

YORK scroll chillers, heat pumps and condensing units with the 031-02550 board have BACnet MS/TP, Modbus RTU and N2 built in. The BAS writes the remote setpoint, load limit stage, cooling range, heating setpoint, heat pump mode and start/stop (AV 1-7, BV 1). Everything else is read-only AI and BI objects: liquid and ambient temperatures, per-system suction and discharge values, EEV output, timers, cutouts and setpoints, compressor run status, operational and fault codes, and system alarms.

This page lists 86 BACnet objects for the York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
Equipment
Scroll chiller / heat pump / condensing unit
Equipment type
Chillers
BACnet objects
86 (8 writable)
Transport
BACnet MS/TP
Firmware
C.MMC.13.11 / 14.11 / 16.12 to C.MMC.13.23 / 14.23 / 16.23 (031-02755)
Also known as
YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16
Source document
Scroll Chiller/Heatpump/Condensing Unit Modbus RTU, BACnet MS/TP, N2 Data Map (SCROLL Native Comms) · rev. 2020-02-11
Download CSV 86 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)

Integration in brief

Put the unit in automatic/remote control (BI 20 reads Auto), then start/stop it with BV 1 and write the remote setpoint (AV 1) and, if needed, the load limit stage (AV 3). Read the leaving chilled liquid temperature, compressor run status, each system's operational code and the two system alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1START_STOPRemote start/stop (1 = run)Write
AV 1REM_SETPRemote leaving chilled liquid setpointWrite
AV 3LOAD_LIMITLoad limit stage (0, 1, 2)Write
AI 25S1_OP_CODESys 1 operational codeRead
BI 5S1_C1_RUNSys 1 compressor 1 runningRead
BI 20CNTL_MODELocal/remote control mode (1 = Auto)Read
AI 1LCHLTLeaving chilled liquid temperatureRead
BI 1S1_ALARMSystem 1 alarmRead
BI 2S2_ALARMSystem 2 alarmRead
AI 26S1_FLT_CODESys 1 fault code (0 = none)Read

Enable & remote start

BI 20 shows the local/remote control mode (0 = Manual, 1 = Auto). The sheet gives no point to change it and no write-enable point. On heat pumps AV 7 selects panel, cool or heat.

Network setup

Watch out for

York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

86 of 86 shown
Type
Access
Show
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) BACnet Points List
DescriptionStates
AVmin1REM_SETPRemote setpoint (99 = auto)°FWrite
AV2SP_REM_SP_S1Sys 1 Remote Setpoint (SP Unit)PSIWrite
AVmin3LOAD_LIMITLoad limit stage (0, 1 or 2)Write
AV4REM_CRRemote Cooling Range (DAT Unit)°FWrite
AV5SP_REM_SP_S2Sys 2 Remote Setpoint (SP Unit)PSIWrite
AV6REM_SP_HEATRemote Heating Setpoint (HP or YCWL HP)°FWrite
AV7HP_MODERemote heat pump mode (HP or YCWL HP)Write0=Panel, 1=Cool, 2=Heat
BVmin1START_STOPRemote Start/Stop CommandWrite0=Stop, 1=Run
AImin1LCHLTLeaving Chilled Liquid Temp°FRead
AI2RCHLTEntering Chilled Liquid Temp°FRead
AI3DATDischarge Air Temp (DAT Unit)°FRead
AI4S1_SUCT_TEMPSys 1 suction temp (EEV, cond units, R-410a/R-454B)°FRead
AI5OATAmbient Air Temp°FRead
AI6S1_SUCT_SHSys 1 Suction Superheat (EEV)°F (diff)Read
AI7S1_RUN_TIMESys 1 run time, secondsRead
AI8S1_SUCT_PRSys 1 Suction PressurePSIRead
AI9S1_DSCH_PRSys 1 Discharge PressurePSIRead
AI10S1_CIR_TEMPSys 1 Cooler Inlet Refrigerant Temp (R-407c)°FRead
AI11S1_DEF_TEMPSys 1 Defrost Temperature (HP)°FRead
AI12S1_EEV_OUTSys 1 EEV Output % (EEV)%Read
AI13S1_AR_TIMERSys 1 Anti-Recycle TimerRead
AI14AC_TIMERAnti-coincident timer, secondsRead
AI15S2_SUCT_TEMPSys 2 suction temp (EEV, cond units, R-410a/R-454B)°FRead
AI16S2_RUN_TIMESys 2 run time, secondsRead
AI17S2_SUCT_PRSys 2 Suction PressurePSIRead
AI18S2_DSCH_PRSys 2 Discharge PressurePSIRead
AI19S2_CIR_TEMPSys 2 Cooler Inlet Refrigerant Temp (R-407c)°FRead
AI20S2_DEF_TEMPSys 2 Defrost Temperature (HP)°FRead
AI21S2_SUCT_SHSys 2 Suction Superheat (EEV)°F (diff)Read
AI22S2_AR_TIMERSys 2 Anti-Recycle TimerRead
AI23S2_EEV_OUTSys 2 EEV Output % (EEV)%Read
AI24NUM_COMPSNumber of CompressorsRead
AImin25S1_OP_CODESys 1 Operational CodeRead0=No Abnormal Condition, 1=Unit Switch OFF, 2=System Switch OFF, 3=Lockout, 4=Unit Fault, 5=System Fault, 6=Remote Shutdown, 7=Daily Schedule Shutdown, 8=No Run Permissive, 9=No Cool Load, 10=Anti-Coincidence Timer Active, 11=Anti-Recycle Timer Active, 12=Manual Override, 13=Suction Limiting, 14=Discharge Limiting, 16=Load Limiting, 17=Compressor(s) Running, 18=Heatpump Load Limiting, 19=Pumping Down
AImin26S1_FLT_CODESys 1 Fault CodeRead0=No Fault Code, 2=Low Ambient Temperature, 4=Low Leaving Chilled Liquid Temperature, 5=High Discharge Pressure, 7=Low Suction Pressure, 18=MP/HPCO Fault, 19=Low Evaporator Temperature, 22=Unit Motor Current, 23=Low Superheat, 24=Sensor Fault, 25=Discharge Inhibit, 26=MP/HPCO Inhibit, 27=Pump Trip, 28=Pump Fail Make Flow, 29=High Ambient Temperature, 30=Anti-Vacuum Low Pressure Cutout, 31=Flow Switch Open, 32=Leaving Chilled Liquid Temperature Sensor Fault
AI27S2_OP_CODESys 2 Operational CodeRead0=No Abnormal Condition, 1=Unit Switch OFF, 2=System Switch OFF, 3=Lockout, 4=Unit Fault, 5=System Fault, 6=Remote Shutdown, 7=Daily Schedule Shutdown, 8=No Run Permissive, 9=No Cool Load, 10=Anti-Coincidence Timer Active, 11=Anti-Recycle Timer Active, 12=Manual Override, 13=Suction Limiting, 14=Discharge Limiting, 16=Load Limiting, 17=Compressor(s) Running, 18=Heatpump Load Limiting, 19=Pumping Down
AI28S2_FLT_CODESys 2 Fault CodeRead0=No Fault Code, 2=Low Ambient Temperature, 4=Low Leaving Chilled Liquid Temperature, 5=High Discharge Pressure, 7=Low Suction Pressure, 18=MP/HPCO Fault, 19=Low Evaporator Temperature, 22=Unit Motor Current, 23=Low Superheat, 24=Sensor Fault, 25=Discharge Inhibit, 26=MP/HPCO Inhibit, 27=Pump Trip, 28=Pump Fail Make Flow, 29=High Ambient Temperature, 30=Anti-Vacuum Low Pressure Cutout, 31=Flow Switch Open, 32=Leaving Chilled Liquid Temperature Sensor Fault
AI30S1_FAN_STAGESys 1 Condenser Fan StageRead
AI32S2_FAN_STAGESys 2 Condenser Fan StageRead
AI33CONTROL_MODEUnit control modeRead1=LW, 2=RW, 3=DA, 4=SP, 5=HC, 6=HP
AI34AR_TIMEAnti-Recycle Time ProgrammedRead
AI35LCHLT_CUTLeaving Chilled Liquid Temp Cutout°FRead
AI36LOW_AMB_CUTLow Ambient Temperature Cutout°FRead
AI37SUCT_P_CO_HTLow Suction Pressure Cutout Heating (HP)PSIRead
AI38L_SUCT_P_COLow Suction Pressure Cutout CoolingPSIRead
AI39H_DSCH_P_COHigh Discharge Pressure CutoutPSIRead
AI40COOL_SETPCooling Setpoint°FRead
AI41SP_SETP_S1Sys 1 Cooling Setpoint (SP Unit)PSIRead
AI42CONTROL_RGCooling Range°FRead
AI43SP_CTL_RG_S1Sys 1 Cooling Range (SP Unit)PSIRead
AI44SP_SETP_S2Sys 2 Cooling Setpoint (SP Unit)PSIRead
AI45HEAT_SETPHeating Setpoint (HP)°FRead
AI46SP_CTL_RG_S2Sys 2 Cooling Range (SP Unit)PSIRead
AI47HEAT_RANGEHeating Range (HP)°FRead
AI48S1_DSCH_TEMPSys 1 Discharge Temperature (EEV)°FRead
AI49S1_DSCH_SHSys 1 Discharge Superheat (EEV)°F (diff)Read
AI50S2_DSCH_TEMPSys 2 Discharge Temperature (EEV)°FRead
AI51S2_DSCH_SHSys 2 Discharge Superheat (EEV)°F (diff)Read
AI52LEAVING_HOTLeaving Liquid Hot Temp (R-410a/R-454B)°FRead
AI53RETURN_HOTReturn Liquid Hot Temp (R-410a/R-454B)°FRead
AI54R_COOL_SETPRemote Setpoint°FRead
AI55R_SP_SETP_S1Remote Setpoint 1 (SP Unit)PSIRead
AI56R_SP_SETP_S2Remote Setpoint 2 (SP Unit)PSIRead
AI57R_HEAT_SETPRemote Heating Setpoint (HP)°FRead
BImin1S1_ALARMSys 1 AlarmRead0=No Alarm, 1=Alarm
BImin2S2_ALARMSys 2 AlarmRead0=No Alarm, 1=Alarm
BI3EVAP_HTREvaporator Heater StatusRead
BI4EVAP_PUMPEvaporator PumpRead
BImin5S1_C1_RUNSys 1 Comp 1 RunRead
BI6S2_C1_RUNSys 2 Comp 1 RunRead
BI7S1_LLSVSys 1 Liquid Line Solenoid ValveRead
BI8S1_MODE_SVSys 1 Mode Solenoid Valve (HP)Read
BI9S1_HGBVSys 1 Hot Gas Bypass ValveRead
BI10S1_BHSBivalent heat step (YLAE HP) or compressor heater (chillers)Read
BI11S1_C2_RUNSys 1 Comp 2 RunRead
BI12S2_C2_RUNSys 2 Comp 2 RunRead
BI13S2_LLSVSys 2 Liquid Line Solenoid ValveRead
BI14S2_MODE_SVSys 2 Mode Solenoid Valve (HP)Read
BI15LEAD_SYSLead SystemRead0=Sys 1, 1=Sys 2
BI16S1_C3_RUNSys 1 Comp 3 RunRead
BI17S2_C3_RUNSys 2 Comp 3 RunRead
BI18CH_LIQ_TYPEChilled Liquid TypeRead0=Water, 1=Glycol
BI19AMB_MODEAmbient Control ModeRead0=Std Amb, 1=Low Amb
BImin20CNTL_MODELocal Remote Control ModeRead0=Manual, 1=Auto
BI21DATA_UNITDisplay UnitsRead0=Imperial, 1=SI
BI22AUTO_LLLead Lag Control ModeRead0=Manual, 1=Auto
BI23S2_HGBVSys 2 Hot Gas Bypass ValveRead
Object ID lookup: York YORK Scroll native point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)

How many BACnet points does the York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) have?

This list has 86 BACnet objects: 55 analog inputs, 7 analog values, 23 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) BACnet points are writable?

8 of the 86 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP) BACnet documentation?

The source is Scroll Chiller/Heatpump/Condensing Unit Modbus RTU, BACnet MS/TP, N2 Data Map (SCROLL Native Comms), revision 2020-02-11, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/PqH6~F3kNniq~6xHrGxQAQ/content.

What are the minimum BACnet points to integrate the York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)?

Start with BV 1 START_STOP (Remote start/stop (1 = run)); AV 1 REM_SETP (Remote leaving chilled liquid setpoint); AV 3 LOAD_LIMIT (Load limit stage (0, 1, 2)); AI 25 S1_OP_CODE (Sys 1 operational code); BI 5 S1_C1_RUN (Sys 1 compressor 1 running); BI 20 CNTL_MODE (Local/remote control mode (1 = Auto)); AI 1 LCHLT (Leaving chilled liquid temperature); BI 1 S1_ALARM (System 1 alarm); BI 2 S2_ALARM (System 2 alarm); AI 26 S1_FLT_CODE (Sys 1 fault code (0 = none)).

How do I enable BMS control of the York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)?

BI 20 shows the local/remote control mode (0 = Manual, 1 = Auto). The sheet gives no point to change it and no write-enable point. On heat pumps AV 7 selects panel, cool or heat.

How do I check these points on the real Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.