- L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
Water-cooled self-contained unit controller (IPU2) · BACnet points list
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) BACnet points list
Updated 6 November 2026
The IPU2 controller of the L-Series water-cooled self-contained units speaks BACnet MS/TP on Port 1 (Modbus is also offered). The table lists about 170 objects: air and condenser water temperatures, refrigerant pressures, compressor and heat stage status, condenser water and waterside economizer valves, duct static and supply fan VFD values, setpoints and limits, BAS inputs, and BAS commands for occupancy, unit stop, morning warm-up, ventilation and heating.
This page lists 167 BACnet objects for the York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) — 57 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
- Equipment
- Water-cooled self-contained unit controller (IPU2)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 167 (57 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 23000 + MAC address
- Also known as
- LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
Connect to Port 1 of the IPU2 control board on BACnet MS/TP. Command occupancy with OCCUPNCY_CMD (BV 12), stop or release the unit with UNIT_STOP (BV 17) and write the occupied zone setpoints; read supply air, zone and condenser water temperatures, supply fan status, unit mode and the alarm input.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 12 | OCCUPNCY_CMD | Occupancy command (1 = occupied) | Write |
| BV 17 | UNIT_STOP | Unit stop (1 = stopped, 0 = normal) | Write |
| AV 21 | OCC_ZN_COOL | Occupied zone cooling setpoint, °F | Write |
| AV 22 | OCC_ZN_HEAT | Occupied zone heating setpoint, °F | Write |
| AI 58 | UNIT_MODE | Current operating mode index | Read |
| BI 59 | SUPPLY_FAN | Supply fan on/off | Read |
| AI 46 | SUP_AIR_TEMP | Supply air temperature, °F | Read |
| AI 60 | ZONE_TEMP | Zone temperature, °F | Read |
| AI 90 | WTR_TEMP_ENT | Entering condenser water temperature | Read |
| BI 2 | ALARM | Unit alarm (FLT = faulted) | Read |
Enable & remote start
OCCUPNCY_CMD (BV 12) puts the unit in occupied (1) or unoccupied (0) mode and UNIT_STOP (BV 17) stops it (1) or returns it to normal operation (0). SYSTEM_STOP (AV 35) can turn off individual compressor systems.
Sensors & values from the BMS
ZONE_TMP_BAS (AV 40) lets the BAS supply zone temperature on a constant volume unit; OAT_CURR_BAS (AV 49) and OA_RH_BAS (AV 50) supply outdoor temperature and humidity when the airside economizer is selected; UND_TEMP_BAS / UND_HUMD_BAS (AV 37/36) feed under-floor values on FlexSys units.
Network setup
- BACnet MS/TP must use Port 1 of the IPU2 board; Port 2 is the RS-232 terminal port.
- Set the MAC address (1-127) with the SW2 DIP switches (switch 8 always ON) or the SERVICE key; the default device instance is 23000 plus the MAC address.
- A different device instance is set with DE MODIFIER ADDRESS x 100 + DE MODIFIER OFFSET; to keep the automatic instance, DE MODIFIER OFFSET must be -1.
- Cycle unit power after changing the MAC address or the port settings.
Watch out for
- Setpoints, limits and enable values are setup values; don't write them cyclically.
- Many points only exist on FlexSys, VAV or constant volume units, or with options such as the waterside economizer.
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | ACT_DSP_SP | Duct Static Setpoint | inH2O | Read | |
| AI | 3 | ACT_MIN_POS | Active Minimum Position | % | Read | |
| AI | 4 | ACT_SAT_SP | Supply Air Setp | °F | Read | |
| BImin | 2 | ALARM | Alarm | Read | ||
| BI | 1 | AMORN_WA_ACT | Adapt Morn Warm Up Active | Read | ||
| AI | 5 | AV_PRS_A_SUC | Avg Press Suction A | Read | ||
| AI | 2 | AV_PRS_DIS | Avg Press Discharge A | Read | ||
| AI | 6 | BYPASS_DAMPER | Bypass Damper | % | Read | |
| AI | 64 | BYP_VALV_POS | Bypass Valve Position | Read | ||
| BI | 3 | COMP_A | Compressor A | Read | ||
| BI | 4 | COMP_B | Compressor B | Read | ||
| BI | 5 | COMP_C | Compressor C | Read | ||
| BI | 6 | COMP_D | Compressor D | Read | ||
| BI | 7 | COMP_E | Compressor E | Read | ||
| BI | 8 | COMP_F | Compressor F | Read | ||
| AI | 15 | COMP_A_LOAD | Compressor A Load | % | Read | |
| AI | 9 | COMP_A_OPER | Compressor 1A Oper Hrs | h | Read | |
| AI | 10 | COMP_B_OPER | Compressor 1B Oper Hrs | h | Read | |
| AI | 11 | COMP_C_OPER | Compressor 2A Oper Hrs | h | Read | |
| AI | 12 | COMP_D_OPER | Compressor 2B Oper Hrs | h | Read | |
| AI | 13 | COMP_E_OPER | Compressor 3A Oper Hrs | h | Read | |
| AI | 14 | COMP_F_OPER | Compressor 3B Oper Hrs | h | Read | |
| AI | 66 | COMP_A_STAT | Comp Sys A Status | Read | ||
| AI | 67 | COMP_B_STAT | Comp Sys B Status | Read | ||
| AI | 68 | COMP_C_STAT | Comp Sys C Status | Read | ||
| AI | 69 | COMP_D_STAT | Comp Sys D Status | Read | ||
| AI | 70 | COMP_E_STAT | Comp Sys E Status | Read | ||
| AI | 71 | COMP_F_STAT | Comp Sys F Status | Read | ||
| BI | 12 | COMP_STAT_A | Safety Input Chain A | Read | ||
| BI | 13 | COMP_STAT_B | Safety Input Chain B | Read | ||
| BI | 14 | COMP_STAT_C | Safety Input Chain C | Read | ||
| BI | 67 | COMP_STAT_D | Safety Input Chain D | Read | ||
| BI | 68 | COMP_STAT_E | Safety Input Chain E | Read | ||
| BI | 69 | COMP_STAT_F | Safety Input Chain F | Read | ||
| AI | 65 | COMP_STG_SEQ | Comp Staging Seq | Read | ||
| AV | 41 | COND_BYP_MAX | Cond Bypass Max Pos | % | Write | |
| AV | 42 | COND_BYP_MIN | Cond Valve Min Pos | % | Write | |
| AI | 75 | COND_PRS_OUT | Condenser Pressure PI Output | % | Read | |
| AI | 76 | COND_TYPE | Condenser Type | Read | ||
| AI | 72 | COND_VAL_INS | Cond Valves Install | Read | ||
| BI | 66 | COND_WTR_CNT | Cond Water Control | Read | 0=Dis, 1=Ena | |
| AI | 73 | COND_WTR_FLW | Cond Water Flow | Read | ||
| AI | 74 | COND_WTR_VAL | Cond Water Valve | % | Read | |
| AI | 17 | DCT_STAT_PR1 | Duct Static Pres 1 | inH2O | Read | |
| AI | 77 | DCT_STAT_PR2 | Duct Static Pres 2 | inH2O | Read | |
| BV | 4 | DEW_PNT_RST | Dew Point Reset | Write | 0=Off, 1=On | |
| AV | 3 | DSP_HI_SP | Duct Static High Setp | inH2O | Write | |
| AV | 4 | DSP_LO_SP | Duct Static Low Setp | inH2O | Write | |
| AV | 5 | DSP_RST_BAS | Duct Static Pres Rst Bas | % | Write | |
| AI | 18 | ECON_ME_USED | Economizer Method Active | Read | ||
| BV | 5 | ECONO_INSTAL | Economizer Installed | Write | 0=Off, 1=On | |
| AV | 6 | ECONO_METHOD | Econo Method To Use | Write | ||
| AI | 16 | ECONO_VALVE | Economized Valve Position | Read | ||
| AI | 19 | ECON_STATUS | Econo Sys Status | Read | ||
| AV | 7 | EL_AIR_TMP_H | Evap Leaving Air Temp High Setpoint | °F | Write | |
| AV | 8 | EL_AIR_TMP_L | Evap Leaving Air Temp Low Setpoint | °F | Write | |
| AI | 20 | EVAP_AIR_TMP | Flex Evap Temp Current | °F | Read | |
| BI | 25 | FILTER_STATS | Filter Status | Read | ||
| BV | 6 | FLSYS_REHEAT | FlexSys Reheat | Write | 0=Disabled, 1=Enabled | |
| BI | 33 | FREEZESTAT | Hot Water Frz Status | Read | ||
| BI | 26 | FURN_OUT_1 | Electric Heat Stage 1 | Read | ||
| BI | 27 | FURN_OUT_2 | Electric Heat Stage 2 | Read | ||
| BI | 28 | FURN_OUT_3 | Electric Heat Stage 3 | Read | ||
| BI | 29 | FURN_OUT_4 | Electric Heat Stage 4 | Read | ||
| BV | 7 | HEAT_ENABLE | Heating System | Write | 0=Disabled, 1=Enabled | |
| AV | 9 | HEATING_SAT | Heating Sat | °F | Write | |
| AI | 24 | HEATING_VALV | Heating Valve | % | Read | |
| AI | 23 | HEAT_STAGES | Electric Heat Stages | Read | ||
| AI | 78 | HEATING_STAT | Heating System Status | Read | ||
| BV | 8 | HEAT_VACTION | Heating Valve Action | Write | 0=Direct Acting, 1=Reverse Acting | |
| BI | 34 | LOCAL_STOP | Local Stop | Read | ||
| AV | 10 | MAX_BYPASS | Maximum Bypass | % | Write | |
| AI | 79 | MIX_AIR_TEMP | Mixed Air Temp | Read | ||
| AV | 14 | MIXD_SAT_SP | Mixed Sat Limit | °F | Write | |
| BV | 9 | MORN_WARM_UP | Morning Warm Up Enable | Write | 0=Enabled, 1=Disabled | |
| BV | 10 | MORN_WUP_CMD | Morning Warm Up Cmnd | Write | 0=Off, 1=On | |
| BI | 37 | NEED_DEHUMID | Need for Dehumidification | Write | ||
| BV | 11 | NIGHT_SETBAC | Night Set Back (for Heating) | Write | 0=Off, 1=On | |
| AI | 25 | OA_DAMPER | OA Damper | % | Read | |
| AV | 16 | OA_DAMP_MIN | OA Damper Min Position | % | Write | |
| AV | 17 | OA_DAMP_MAX | OA Damper Max Position | % | Write | |
| AI | 26 | OA_ENTHALPY | Outside Air Enthalpy | Btu/lb | Read | |
| AV | 18 | OA_ENTH_SP | OA Enthalpy Setp | Btu/lb | Write | |
| AI | 29 | OA_REL_HUMID | Outside Air Humidity | % | Read | |
| AV | 50 | OA_RH_BAS | Outside Air Humidity Building Automation System (BAS) | Write | ||
| AI | 30 | OA_TEMP | Outside Air Temperature (OAT) BAS | °F | Read | |
| AV | 49 | OAT_CURR_BAS | OAT BAS | Write | ||
| AV | 19 | OAT_HIGH_SAT | OAT for High SAT | °F | Write | |
| AV | 20 | OAT_LOW_SAT | OAT for Low SAT | °F | Write | |
| BI | 35 | OCC_MODE | Occupancy Mode | Read | ||
| BI | 36 | OCC_STATE | Occupancy State | Read | ||
| BVmin | 12 | OCCUPNCY_CMD | Occupancy Command | Write | 0=Unoccupied, 1=Occupied | |
| AVmin | 21 | OCC_ZN_COOL | Occupied Zone Cooling Setp | °F | Write | |
| AVmin | 22 | OCC_ZN_HEAT | Occupied Zone Heating Setp | °F | Write | |
| AV | 43 | PR_DIS_SPMIN | Discharge Pressure Sp Min | Write | ||
| AV | 46 | PR_DIS_SPMAX | Discharge Pressure Sp Max | Write | ||
| AI | 31 | PRS_A_DISCH | Pressures Discharge A | psi | Read | |
| AI | 32 | PRS_A_SUCTION | Pressures Suction A | psi | Read | |
| AI | 33 | PRS_B_DISCH | Pressures Discharge B | psi | Read | |
| AI | 34 | PRS_B_SUCTION | Pressures Suction B | psi | Read | |
| AI | 35 | PRS_C_DISCH | Pressures Discharge C | psi | Read | |
| AI | 36 | PRS_C_SUCTION | Pressures Suction C | psi | Read | |
| AI | 80 | PRS_D_DISCH | Pressures Discharge D | psi | Read | |
| AI | 83 | PRS_D_SUCTION | Pressures Suction D | psi | Read | |
| AI | 81 | PRS_E_DISCH | Pressures Discharge E | psi | Read | |
| AI | 84 | PRS_E_SUCTION | Pressures Suction E | psi | Read | |
| AI | 82 | PRS_F_DISCH | Pressures Discharge F | psi | Read | |
| AI | 85 | PRS_F_SUCTION | Pressures Suction F | psi | Read | |
| AV | 48 | RA_DIFF_BAS | Return Air Differential BAS | Write | ||
| AV | 15 | RAT_HEAT_SP | RAT Heating Setp | °F | Write | |
| AV | 23 | RAT_COOL_SP | RAT Cooling Setp | °F | Write | |
| AV | 24 | RAT_HIGH_SAT | RAT for High SAT | °F | Write | |
| AV | 25 | RAT_LOW_SAT | RAT for Low SAT | °F | Write | |
| BI | 40 | RDY_RUN_C1A | Ready to Run Comp A | Read | ||
| BI | 43 | RDY_RUN_C2B | Ready to Run Comp D | Read | ||
| BI | 44 | RDY_RUN_C3A | Ready to Run Comp E | Read | ||
| BI | 45 | RDY_RUN_C3B | Ready to Run Comp F | Read | ||
| BI | 46 | RDY_STOP_C1A | Ready to Stop Comp A | Read | ||
| BI | 47 | RDY_STOP_C1B | Ready to Stop Comp B | Read | ||
| BI | 48 | RDY_STOP_C2A | Ready to Stop Comp C | Read | ||
| BI | 49 | RDY_STOP_C2B | Ready to Stop Comp D | Read | ||
| BI | 50 | RDY_STOP_C3A | Ready to Stop Comp E | Read | ||
| BI | 51 | RDY_STOP_C3B | Ready to Stop Comp F | Read | ||
| AI | 37 | RET_AIR_BY_S | Active Bypass Active Sp | % | Read | |
| AI | 38 | RET_AIR_ENTH | Return Air Enthalpy | Btu/lb | Read | |
| AI | 39 | RET_AIR_HUMD | Return Air Humidity | % | Read | |
| AI | 40 | RET_AIR_TEMP | Return Air Temp | °F | Read | |
| AV | 47 | RST_ENT_BAS | Reset Enthalpy BAS | Write | ||
| AV | 26 | SAT_HIGH_SP | SAT High Setpoint | °F | Write | |
| AV | 27 | SAT_LOW_SP | SAT Low Setpoint | °F | Write | |
| AV | 28 | SAT_RST_BAS | Supply Air Temp RST BAS | Write | ||
| BI | 53 | SAT_TEMPER | SAT Tempering Enable | Read | ||
| BI | 55 | SF_PROV_SW | SF Proving Switch | Read | ||
| AV | 29 | SF_SPD_H_SAT | SF Speed for High SAT | % | Write | |
| AV | 30 | SF_SPD_L_SAT | SF Speed for Low SAT | % | Write | |
| BI | 70 | SF_VFD_BYPAS | SF VFD Bypass Mode | Read | ||
| AI | 86 | SF_VFD_BP_MO | SF VFD Bypass Mode | Read | ||
| AV | 31 | STG_1_COOL | Stage 1 Cooling | °F | Write | |
| AV | 32 | STG_1_HEAT | Stage 1 Heating | °F | Write | |
| AV | 33 | STG_2_COOL | Stage 2 Cooling | °F | Write | |
| AV | 34 | STG_2_HEAT | Stage 2 Heating | °F | Write | |
| AI | 92 | SPLY_AIRFLOW | Piezometer Airflow (Displayed in CFM) | cfm | Read | |
| AImin | 46 | SUP_AIR_TEMP | Supply Air Temp | °F | Read | |
| AI | 48 | SUP_FAN_VFD | Supply Fan VFD | % | Read | |
| BImin | 59 | SUPPLY_FAN | Supply Fan | Read | ||
| AI | 87 | SUPPLY_STAT | Supply System Status | Read | ||
| AV | 35 | SYSTEM_STOP | System Stop | Write | ||
| AI | 55 | UND_FLR_DEWP | Under Floor Dew Point | % | Read | |
| AI | 56 | UND_FLR_HUMD | Under Floor Humidity | % | Read | |
| AI | 57 | UND_FLR_TEMP | Under Floor Temp | °F | Read | |
| AV | 36 | UND_HUMD_BAS | Under Floor Humidity BAS | % | Write | |
| AV | 37 | UND_TEMP_BAS | Under Floor Temp Bas | °F | Write | |
| AImin | 58 | UNIT_MODE | Unit Mode | Read | ||
| AI | 88 | UNIT_STAT | Unit Overall Status | Read | ||
| BVmin | 17 | UNIT_STOP | Unit Stop | Write | ||
| AV | 38 | UNOCC_ZN_COOL | Unoccupied Zone Cooling | °F | Write | |
| AV | 39 | UNOCC_ZN_HEAT | Unoccupied Zone Heating | °F | Write | |
| BI | 61 | VAV_HEAT | VAV Heat | Read | ||
| BV | 19 | VENT_ENABLE | Ventilation Enable | Write | 0=Off, 1=On | |
| AI | 89 | VENT_STAT | Vent Sys Status | Read | ||
| AV | 44 | WTR_ECN_DLTA | Water Econo Delta | °F | Write | |
| AV | 45 | WTR_ECN_MIN | Water Econo Min Pos | % | Write | |
| BI | 71 | WTR_FLOW_SW | Water Flow Switch | Read | ||
| AImin | 90 | WTR_TEMP_ENT | Water Temp Entering | Read | ||
| AI | 91 | WTR_TEMP_LEV | Water Temp Leaving | Read | ||
| AImin | 60 | ZONE_TEMP | Zone Temp | °F | Read | |
| AV | 40 | ZONE_TMP_BAS | Zone Temp BAS | °F | Write |
No points match these filters.
Object ID lookup: York L-Series LSWU/LSWD/LSWF IPU2 point IDs by name
AI1ACT_DSP_SPAI3ACT_MIN_POSAI4ACT_SAT_SPBI2ALARMBI1AMORN_WA_ACTAI5AV_PRS_A_SUCAI2AV_PRS_DISAI6BYPASS_DAMPERAI64BYP_VALV_POSBI3COMP_ABI4COMP_BBI5COMP_CBI6COMP_DBI7COMP_EBI8COMP_FAI15COMP_A_LOADAI9COMP_A_OPERAI10COMP_B_OPERAI11COMP_C_OPERAI12COMP_D_OPERAI13COMP_E_OPERAI14COMP_F_OPERAI66COMP_A_STATAI67COMP_B_STATAI68COMP_C_STATAI69COMP_D_STATAI70COMP_E_STATAI71COMP_F_STATBI12COMP_STAT_ABI13COMP_STAT_BBI14COMP_STAT_CBI67COMP_STAT_DBI68COMP_STAT_EBI69COMP_STAT_FAI65COMP_STG_SEQAV41COND_BYP_MAXAV42COND_BYP_MINAI75COND_PRS_OUTAI76COND_TYPEAI72COND_VAL_INSBI66COND_WTR_CNTAI73COND_WTR_FLWAI74COND_WTR_VALAI17DCT_STAT_PR1AI77DCT_STAT_PR2BV4DEW_PNT_RSTAV3DSP_HI_SPAV4DSP_LO_SPAV5DSP_RST_BASAI18ECON_ME_USEDBV5ECONO_INSTALAV6ECONO_METHODAI16ECONO_VALVEAI19ECON_STATUSAV7EL_AIR_TMP_HAV8EL_AIR_TMP_LAI20EVAP_AIR_TMPBI25FILTER_STATSBV6FLSYS_REHEATBI33FREEZESTATBI26FURN_OUT_1BI27FURN_OUT_2BI28FURN_OUT_3BI29FURN_OUT_4BV7HEAT_ENABLEAV9HEATING_SATAI24HEATING_VALVAI23HEAT_STAGESAI78HEATING_STATBV8HEAT_VACTIONBI34LOCAL_STOPAV10MAX_BYPASSAI79MIX_AIR_TEMPAV14MIXD_SAT_SPBV9MORN_WARM_UPBV10MORN_WUP_CMDBI37NEED_DEHUMIDBV11NIGHT_SETBACAI25OA_DAMPERAV16OA_DAMP_MINAV17OA_DAMP_MAXAI26OA_ENTHALPYAV18OA_ENTH_SPAI29OA_REL_HUMIDAV50OA_RH_BASAI30OA_TEMPAV49OAT_CURR_BASAV19OAT_HIGH_SATAV20OAT_LOW_SATBI35OCC_MODEBI36OCC_STATEBV12OCCUPNCY_CMDAV21OCC_ZN_COOLAV22OCC_ZN_HEATAV43PR_DIS_SPMINAV46PR_DIS_SPMAXAI31PRS_A_DISCHAI32PRS_A_SUCTIONAI33PRS_B_DISCHAI34PRS_B_SUCTIONAI35PRS_C_DISCHAI36PRS_C_SUCTIONAI80PRS_D_DISCHAI83PRS_D_SUCTIONAI81PRS_E_DISCHAI84PRS_E_SUCTIONAI82PRS_F_DISCHAI85PRS_F_SUCTIONAV48RA_DIFF_BASAV15RAT_HEAT_SPAV23RAT_COOL_SPAV24RAT_HIGH_SATAV25RAT_LOW_SATBI40RDY_RUN_C1ABI43RDY_RUN_C2BBI44RDY_RUN_C3ABI45RDY_RUN_C3BBI46RDY_STOP_C1ABI47RDY_STOP_C1BBI48RDY_STOP_C2ABI49RDY_STOP_C2BBI50RDY_STOP_C3ABI51RDY_STOP_C3BAI37RET_AIR_BY_SAI38RET_AIR_ENTHAI39RET_AIR_HUMDAI40RET_AIR_TEMPAV47RST_ENT_BASAV26SAT_HIGH_SPAV27SAT_LOW_SPAV28SAT_RST_BASBI53SAT_TEMPERBI55SF_PROV_SWAV29SF_SPD_H_SATAV30SF_SPD_L_SATBI70SF_VFD_BYPASAI86SF_VFD_BP_MOAV31STG_1_COOLAV32STG_1_HEATAV33STG_2_COOLAV34STG_2_HEATAI92SPLY_AIRFLOWAI46SUP_AIR_TEMPAI48SUP_FAN_VFDBI59SUPPLY_FANAI87SUPPLY_STATAV35SYSTEM_STOPAI55UND_FLR_DEWPAI56UND_FLR_HUMDAI57UND_FLR_TEMPAV36UND_HUMD_BASAV37UND_TEMP_BASAI58UNIT_MODEAI88UNIT_STATBV17UNIT_STOPAV38UNOCC_ZN_COOLAV39UNOCC_ZN_HEATBI61VAV_HEATBV19VENT_ENABLEAI89VENT_STATAV44WTR_ECN_DLTAAV45WTR_ECN_MINBI71WTR_FLOW_SWAI90WTR_TEMP_ENTAI91WTR_TEMP_LEVAI60ZONE_TEMPAV40ZONE_TMP_BAS
Integration notes
- Access is from the READ/WRITE column; descriptions are the user interface names from the table. Points marked FlexSys, VAV or CV only exist on those units.
- The table prints ACT_SLAB_CTL (Modbus 1102) as AI 5 and COMFORT_VENT (Modbus 1103) as AI 2, the same IDs as the pressure points AV_PRS_A_SUC and AV_PRS_DIS; those two writable on/off rows are left out because their real object IDs cannot be told from the doc.
- The economizer method selector appears twice as AV 6 (ECONO_METHOD and ECON_METHOD); it is listed once. Ten on/off settings and commands (ECONO_INSTAL, FLSYS_REHEAT, HEAT_ENABLE, HEAT_VACTION, MORN_WARM_UP, MORN_WUP_CMD, NIGHT_SETBAC, OCCUPNCY_CMD, UNIT_STOP, VENT_ENABLE) are printed with both a BV and an AV ID (AV 81-95); they are listed by the BV ID.
- Multistate status codes (unit mode, system status, compressor status) are published as AIs; the code lists are in the table description column and are not repeated here.
- Units are taken from the description column where it states them. The Modbus register addresses in the same table are not reproduced.
- The older Versecon YSWU/YSWD IPU (IPU1) IOM 145.05-NOM3 prints a largely overlapping list.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
How many BACnet points does the York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) have?
This list has 167 BACnet objects: 70 analog inputs, 45 analog values, 41 binary inputs, 11 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) BACnet points are writable?
57 of the 167 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP) BACnet documentation?
The source is L-Series Water-Cooled Self-Contained Units Model LSWU/LSWD/LSWF with IPU2 Control, 25-105 Ton - Installation, Operation and Maintenance (Table 42, BACnet MS/TP, Modbus, BACnet IP) (145.05-NOM7 (1019)), revision 2019-10-31, published free by York at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/2clxIXbzWLHpg~aPscPCsA/content.
What are the minimum BACnet points to integrate the York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)?
Start with BV 12 OCCUPNCY_CMD (Occupancy command (1 = occupied)); BV 17 UNIT_STOP (Unit stop (1 = stopped, 0 = normal)); AV 21 OCC_ZN_COOL (Occupied zone cooling setpoint, °F); AV 22 OCC_ZN_HEAT (Occupied zone heating setpoint, °F); AI 58 UNIT_MODE (Current operating mode index); BI 59 SUPPLY_FAN (Supply fan on/off); AI 46 SUP_AIR_TEMP (Supply air temperature, °F); AI 60 ZONE_TEMP (Zone temperature, °F); AI 90 WTR_TEMP_ENT (Entering condenser water temperature); BI 2 ALARM (Unit alarm (FLT = faulted)).
How do I enable BMS control of the York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)?
OCCUPNCY_CMD (BV 12) puts the unit in occupied (1) or unoccupied (0) mode and UNIT_STOP (BV 17) stops it (1) or returns it to normal operation (0). SYSTEM_STOP (AV 35) can turn off individual compressor systems.
Can the BMS supply sensor values to the York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)?
ZONE_TMP_BAS (AV 40) lets the BAS supply zone temperature on a constant volume unit; OAT_CURR_BAS (AV 49) and OA_RH_BAS (AV 50) supply outdoor temperature and humidity when the airside economizer is selected; UND_TEMP_BAS / UND_HUMD_BAS (AV 37/36) feed under-floor values on FlexSys units.
How do I check these points on the real L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: L-Series Water-Cooled Self-Contained Units Model LSWU/LSWD/LSWF with IPU2 Control, 25-105 Ton - Installation, Operation and Maintenance (Table 42, BACnet MS/TP, Modbus, BACnet IP) · 145.05-NOM7 (1019) · rev. 2019-10-31. Object names, instances and units are reproduced as published; descriptions are our own.