Rooftop unit (packaged, via BACnet IP gateway kit) · BACnet points list

York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet points list

Updated 4 November 2026

Short answer

These European York packaged units use the YKN2Open control, which speaks JCI Metasys N2 on RS-485. The S606791244 BMS kit adds a FieldServer QuickServer that converts N2 to BACnet IP (a sister kit, S606791245, does Modbus TCP). One QuickServer serves up to five units, each shown as its own virtual BACnet device with temperatures, enthalpies, run hours, an error code, setpoints, mode, fan mode, on/off and override/release flags.

This page lists 50 BACnet objects for the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
Equipment
Rooftop unit (packaged, via BACnet IP gateway kit)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
50 (18 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
11-15 (one virtual device per unit)
Also known as
Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462
Source document
YKN2Open BMS BACnet/IP and Modbus TCP/IP - Installation and user manual · N-40462_EN 0716
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)

Integration in brief

Wire the YKN2Open boards on an RS-485 N2 bus to the QuickServer, give each board an N2 address (1-5) with the YKTool, then read each unit as virtual device 11-15. Write ON/OFF, Mode, the occupied setpoints and fan mode, and read temperatures, Error Code and Status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2ON/OFFUnit on (1) / forced off (0)Write
AV 8Mode0=Off, 1=Cool, 2=Heat, 3=Auto, 5=Emerg HeatWrite
AV 2Setpoint occupied coolOccupied cooling setpoint, 10-32 °CWrite
AV 3Setpoint occupied heatOccupied heating setpoint, 10-32 °CWrite
BV 1Fan Mode0 = fan auto, 1 = continuousWrite
AI 16Indoor TemperatureRoom temperatureRead
AI 12Suply air TemperatureSupply air temperatureRead
AI 31Error CodeActive alarm number, see alarm tableRead
BV 3StatusGateway comms with this unit (Online/Offline)Read

Enable & remote start

Once the gateway is communicating, any analog or digital command written from the BMS takes over that function: it can no longer be changed from the thermostat or YKTool. ON/OFF (BV 2) is the run command; holding it at 0 keeps the unit off.

Heartbeat & communication loss

No heartbeat point is described. If N2 communication to a unit is lost, Status (BV 3) goes Offline and the other objects keep their last values.

Network setup

Watch out for

York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

50 of 50 shown
Type
Binary
Access
Show
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet Points List
DescriptionStates
AI1Suction Temperature 1Suction temperature, circuit 1, -50 to 160 °C°CRead
AI2Liquid Temperature 1Liquid line temperature, circuit 1°CRead
AI3Outdoor TemperatureOutdoor air temperature°CRead
AI4Suction Temperature 2Suction temperature, circuit 2°CRead
AI5Liquid Temperature 2Liquid line temperature, circuit 2°CRead
AI6Discharge Temperature 1Discharge temperature, circuit 1°CRead
AI7Discharge Temperature 2Discharge temperature, circuit 2°CRead
AI11Return TemperatureReturn air temperature°CRead
AImin12Suply air TemperatureSupply air temperature°CRead
AI13Water HWC TemperatureHot water coil water temperature°CRead
AI14Outdor EnthalpyOutdoor air enthalpy, 0-300Read
AI15Return EnthalpyReturn air enthalpy, 0-300Read
AImin16Indoor TemperatureIndoor (room) temperature, -30 to 70 °C°CRead
AI17Economizer Door (out)Economizer damper output, 0-100 %%Read
AI18Water Coil (out)Water coil valve output, 0-100 %%Read
AI19Compressor 1 HoursCompressor 1 run hourshRead
AI20Compressor 2 HoursCompressor 2 run hourshRead
AI22Tandem Comp 1 HoursTandem compressor 1 run hourshRead
AI23Tandem Comp 2 HoursTandem compressor 2 run hourshRead
AI24Water Coil HoursWater coil run hourshRead
AI25Auxiliary Stage 1 HoursAuxiliary heat stage 1 run hourshRead
AI26Auxiliary Stage 2 HoursAuxiliary heat stage 2 run hourshRead
AI27Auxiliary Stage 3 HoursAuxiliary heat stage 3 run hourshRead
AI28Auxiliary Stage 4 HoursAuxiliary heat stage 4 run hourshRead
AI29Indoor Fan HoursIndoor fan run hourshRead
AI30Outdoor Fan 1 HoursOutdoor fan 1 run hourshRead
AImin31Error CodeAlarm code; doc range 11-46, table also lists 91-99Read
AI32Outdoor Fan 2 HoursOutdoor fan 2 run hourshRead
AI34Exhaust fan HoursExhaust fan run hourshRead
AI35Water Bomb HoursWater pump run hourshRead
AI36General Power HoursUnit powered hours, 0-100000hRead
AV1Minimum air renovation (Input)Minimum fresh-air (damper) setting, 0-100 %%Write
AVmin2Setpoint occupied coolOccupied cooling setpoint, 10-32 °C°CWrite
AVmin3Setpoint occupied heatOccupied heating setpoint, 10-32 °C°CWrite
AVmin8ModeOperating mode commandWrite0=OFF, 1=Cool, 2=Heat, 3=Auto, 5=Emerg Heat
BVmin1Fan ModeIndoor fan: auto or continuousWrite0=Fan auto, 1=Fan manual continuo
BVmin2ON/OFFUnit on/off; 0 then 1 after 5 s resets an alarmWrite0=OFF (forced), 1=ON. Reset
BV101Override Minimum air renovation (Input)Override flag for Minimum air renovation (Input)WriteOpen-Close (state text 6)
BV102Override Setpoint occupied coolOverride flag for Setpoint occupied coolWriteOpen-Close (state text 6)
BV103Override Setpoint occupied heatOverride flag for Setpoint occupied heatWriteOpen-Close (state text 6)
BV104Override ModeOverride flag for ModeWriteOpen-Close (state text 6)
BV105Override Fan ModeOverride flag for Fan ModeWriteOpen-Close (state text 6)
BV106Override ON/OFFOverride flag for ON/OFFWriteOpen-Close (state text 6)
BV107Release Minimum air renovation (Input)Release flag for Minimum air renovation (Input)WriteOpen-Close (state text 6)
BV108Release Setpoint occupied coolRelease flag for Setpoint occupied coolWriteOpen-Close (state text 6)
BV109Release Setpoint occupied heatRelease flag for Setpoint occupied heatWriteOpen-Close (state text 6)
BV110Release ModeRelease flag for ModeWriteOpen-Close (state text 6)
BV111Release Fan ModeRelease flag for Fan ModeWriteOpen-Close (state text 6)
BV112Release ON/OFFRelease flag for ON/OFFWriteOpen-Close (state text 6)
BVmin3StatusGateway link to this unit (DA_Comm_OK)ReadInactive=Offline, Active=Online
Object ID lookup: York Roomtop RTC/RTH-L with YKN2Open BMS kit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)

How many BACnet points does the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) have?

This list has 50 BACnet objects: 31 analog inputs, 4 analog values, 15 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet points are writable?

18 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet documentation?

The source is YKN2Open BMS BACnet/IP and Modbus TCP/IP - Installation and user manual (N-40462_EN 0716), published free by York at https://docs.johnsoncontrols.com/bas/api/khub/documents/bdk7s53yQ5tftUD6MrJq9g/content.

What are the minimum BACnet points to integrate the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)?

Start with BV 2 ON/OFF (Unit on (1) / forced off (0)); AV 8 Mode (0=Off, 1=Cool, 2=Heat, 3=Auto, 5=Emerg Heat); AV 2 Setpoint occupied cool (Occupied cooling setpoint, 10-32 °C); AV 3 Setpoint occupied heat (Occupied heating setpoint, 10-32 °C); BV 1 Fan Mode (0 = fan auto, 1 = continuous); AI 16 Indoor Temperature (Room temperature); AI 12 Suply air Temperature (Supply air temperature); AI 31 Error Code (Active alarm number, see alarm table); BV 3 Status (Gateway comms with this unit (Online/Offline)).

How do I enable BMS control of the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)?

Once the gateway is communicating, any analog or digital command written from the BMS takes over that function: it can no longer be changed from the thermostat or YKTool. ON/OFF (BV 2) is the run command; holding it at 0 keeps the unit off.

Does the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) need a BACnet heartbeat or have a communication timeout?

No heartbeat point is described. If N2 communication to a unit is lost, Status (BV 3) goes Offline and the other objects keep their last values.

How do I check these points on the real Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YKN2Open BMS BACnet/IP and Modbus TCP/IP - Installation and user manual · N-40462_EN 0716. Object names, instances and units are reproduced as published; descriptions are our own.