- Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
Rooftop unit (packaged, via BACnet IP gateway kit) · BACnet points list
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet points list
Updated 4 November 2026
These European York packaged units use the YKN2Open control, which speaks JCI Metasys N2 on RS-485. The S606791244 BMS kit adds a FieldServer QuickServer that converts N2 to BACnet IP (a sister kit, S606791245, does Modbus TCP). One QuickServer serves up to five units, each shown as its own virtual BACnet device with temperatures, enthalpies, run hours, an error code, setpoints, mode, fan mode, on/off and override/release flags.
This page lists 50 BACnet objects for the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
- Equipment
- Rooftop unit (packaged, via BACnet IP gateway kit)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 50 (18 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 11-15 (one virtual device per unit)
- Also known as
- Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
Wire the YKN2Open boards on an RS-485 N2 bus to the QuickServer, give each board an N2 address (1-5) with the YKTool, then read each unit as virtual device 11-15. Write ON/OFF, Mode, the occupied setpoints and fan mode, and read temperatures, Error Code and Status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ON/OFF | Unit on (1) / forced off (0) | Write |
| AV 8 | Mode | 0=Off, 1=Cool, 2=Heat, 3=Auto, 5=Emerg Heat | Write |
| AV 2 | Setpoint occupied cool | Occupied cooling setpoint, 10-32 °C | Write |
| AV 3 | Setpoint occupied heat | Occupied heating setpoint, 10-32 °C | Write |
| BV 1 | Fan Mode | 0 = fan auto, 1 = continuous | Write |
| AI 16 | Indoor Temperature | Room temperature | Read |
| AI 12 | Suply air Temperature | Supply air temperature | Read |
| AI 31 | Error Code | Active alarm number, see alarm table | Read |
| BV 3 | Status | Gateway comms with this unit (Online/Offline) | Read |
Enable & remote start
Once the gateway is communicating, any analog or digital command written from the BMS takes over that function: it can no longer be changed from the thermostat or YKTool. ON/OFF (BV 2) is the run command; holding it at 0 keeps the unit off.
Heartbeat & communication loss
No heartbeat point is described. If N2 communication to a unit is lost, Status (BV 3) goes Offline and the other objects keep their last values.
Network setup
- Kit S606791244 = FieldServer QuickServer FS-QS-1010-0122 (BACnet IP to Metasys N2); S606791245 is the Modbus TCP version.
- Up to 5 units per QuickServer on RS-485 (Belden 9272 or equal, max 1000 m), wired to J12 terminals 1-2 on each YKN2Open board; 150 ohm resistor on the last board.
- N2 link: 9600 baud, 8 data bits, no parity, 1 stop bit; set each board's N2 address (1-5) in YKTool menu 7 > Configuration.
- Set the QuickServer IP address with the FieldServer Toolbox application.
- Virtual BACnet device IDs 11-15 match N2 addresses 1-5.
Watch out for
- To reset an alarm write ON/OFF to 0 and back to 1 after 5 seconds, once the cause has cleared; leaving it at 0 keeps the unit off.
- After the BMS writes a setpoint or command, local changes from the thermostat or YKTool for that variable are locked out.
- Values are metric (°C).
- Poll only the variables the unit actually has, to avoid slow N2 updates.
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Suction Temperature 1 | Suction temperature, circuit 1, -50 to 160 °C | °C | Read | |
| AI | 2 | Liquid Temperature 1 | Liquid line temperature, circuit 1 | °C | Read | |
| AI | 3 | Outdoor Temperature | Outdoor air temperature | °C | Read | |
| AI | 4 | Suction Temperature 2 | Suction temperature, circuit 2 | °C | Read | |
| AI | 5 | Liquid Temperature 2 | Liquid line temperature, circuit 2 | °C | Read | |
| AI | 6 | Discharge Temperature 1 | Discharge temperature, circuit 1 | °C | Read | |
| AI | 7 | Discharge Temperature 2 | Discharge temperature, circuit 2 | °C | Read | |
| AI | 11 | Return Temperature | Return air temperature | °C | Read | |
| AImin | 12 | Suply air Temperature | Supply air temperature | °C | Read | |
| AI | 13 | Water HWC Temperature | Hot water coil water temperature | °C | Read | |
| AI | 14 | Outdor Enthalpy | Outdoor air enthalpy, 0-300 | Read | ||
| AI | 15 | Return Enthalpy | Return air enthalpy, 0-300 | Read | ||
| AImin | 16 | Indoor Temperature | Indoor (room) temperature, -30 to 70 °C | °C | Read | |
| AI | 17 | Economizer Door (out) | Economizer damper output, 0-100 % | % | Read | |
| AI | 18 | Water Coil (out) | Water coil valve output, 0-100 % | % | Read | |
| AI | 19 | Compressor 1 Hours | Compressor 1 run hours | h | Read | |
| AI | 20 | Compressor 2 Hours | Compressor 2 run hours | h | Read | |
| AI | 22 | Tandem Comp 1 Hours | Tandem compressor 1 run hours | h | Read | |
| AI | 23 | Tandem Comp 2 Hours | Tandem compressor 2 run hours | h | Read | |
| AI | 24 | Water Coil Hours | Water coil run hours | h | Read | |
| AI | 25 | Auxiliary Stage 1 Hours | Auxiliary heat stage 1 run hours | h | Read | |
| AI | 26 | Auxiliary Stage 2 Hours | Auxiliary heat stage 2 run hours | h | Read | |
| AI | 27 | Auxiliary Stage 3 Hours | Auxiliary heat stage 3 run hours | h | Read | |
| AI | 28 | Auxiliary Stage 4 Hours | Auxiliary heat stage 4 run hours | h | Read | |
| AI | 29 | Indoor Fan Hours | Indoor fan run hours | h | Read | |
| AI | 30 | Outdoor Fan 1 Hours | Outdoor fan 1 run hours | h | Read | |
| AImin | 31 | Error Code | Alarm code; doc range 11-46, table also lists 91-99 | Read | ||
| AI | 32 | Outdoor Fan 2 Hours | Outdoor fan 2 run hours | h | Read | |
| AI | 34 | Exhaust fan Hours | Exhaust fan run hours | h | Read | |
| AI | 35 | Water Bomb Hours | Water pump run hours | h | Read | |
| AI | 36 | General Power Hours | Unit powered hours, 0-100000 | h | Read | |
| AV | 1 | Minimum air renovation (Input) | Minimum fresh-air (damper) setting, 0-100 % | % | Write | |
| AVmin | 2 | Setpoint occupied cool | Occupied cooling setpoint, 10-32 °C | °C | Write | |
| AVmin | 3 | Setpoint occupied heat | Occupied heating setpoint, 10-32 °C | °C | Write | |
| AVmin | 8 | Mode | Operating mode command | Write | 0=OFF, 1=Cool, 2=Heat, 3=Auto, 5=Emerg Heat | |
| BVmin | 1 | Fan Mode | Indoor fan: auto or continuous | Write | 0=Fan auto, 1=Fan manual continuo | |
| BVmin | 2 | ON/OFF | Unit on/off; 0 then 1 after 5 s resets an alarm | Write | 0=OFF (forced), 1=ON. Reset | |
| BV | 101 | Override Minimum air renovation (Input) | Override flag for Minimum air renovation (Input) | Write | Open-Close (state text 6) | |
| BV | 102 | Override Setpoint occupied cool | Override flag for Setpoint occupied cool | Write | Open-Close (state text 6) | |
| BV | 103 | Override Setpoint occupied heat | Override flag for Setpoint occupied heat | Write | Open-Close (state text 6) | |
| BV | 104 | Override Mode | Override flag for Mode | Write | Open-Close (state text 6) | |
| BV | 105 | Override Fan Mode | Override flag for Fan Mode | Write | Open-Close (state text 6) | |
| BV | 106 | Override ON/OFF | Override flag for ON/OFF | Write | Open-Close (state text 6) | |
| BV | 107 | Release Minimum air renovation (Input) | Release flag for Minimum air renovation (Input) | Write | Open-Close (state text 6) | |
| BV | 108 | Release Setpoint occupied cool | Release flag for Setpoint occupied cool | Write | Open-Close (state text 6) | |
| BV | 109 | Release Setpoint occupied heat | Release flag for Setpoint occupied heat | Write | Open-Close (state text 6) | |
| BV | 110 | Release Mode | Release flag for Mode | Write | Open-Close (state text 6) | |
| BV | 111 | Release Fan Mode | Release flag for Fan Mode | Write | Open-Close (state text 6) | |
| BV | 112 | Release ON/OFF | Release flag for ON/OFF | Write | Open-Close (state text 6) | |
| BVmin | 3 | Status | Gateway link to this unit (DA_Comm_OK) | Read | Inactive=Offline, Active=Online |
No points match these filters.
Object ID lookup: York Roomtop RTC/RTH-L with YKN2Open BMS kit point IDs by name
AI1Suction Temperature 1AI2Liquid Temperature 1AI3Outdoor TemperatureAI4Suction Temperature 2AI5Liquid Temperature 2AI6Discharge Temperature 1AI7Discharge Temperature 2AI11Return TemperatureAI12Suply air TemperatureAI13Water HWC TemperatureAI14Outdor EnthalpyAI15Return EnthalpyAI16Indoor TemperatureAI17Economizer Door (out)AI18Water Coil (out)AI19Compressor 1 HoursAI20Compressor 2 HoursAI22Tandem Comp 1 HoursAI23Tandem Comp 2 HoursAI24Water Coil HoursAI25Auxiliary Stage 1 HoursAI26Auxiliary Stage 2 HoursAI27Auxiliary Stage 3 HoursAI28Auxiliary Stage 4 HoursAI29Indoor Fan HoursAI30Outdoor Fan 1 HoursAI31Error CodeAI32Outdoor Fan 2 HoursAI34Exhaust fan HoursAI35Water Bomb HoursAI36General Power HoursAV1Minimum air renovation (Input)AV2Setpoint occupied coolAV3Setpoint occupied heatAV8ModeBV1Fan ModeBV2ON/OFFBV101Override Minimum air renovation (Input)BV102Override Setpoint occupied coolBV103Override Setpoint occupied heatBV104Override ModeBV105Override Fan ModeBV106Override ON/OFFBV107Release Minimum air renovation (Input)BV108Release Setpoint occupied coolBV109Release Setpoint occupied heatBV110Release ModeBV111Release Fan ModeBV112Release ON/OFFBV3Status
Integration notes
- The doc has no read/write column, so access is inferred. AV objects are marked In/Out (shown W); Fan Mode and ON/OFF are the unit's writable digital outputs; the Override and Release BVs are also shown W, but the doc doesn't say how they are used.
- Each unit appears as a separate virtual BACnet device (Virtual_Dev_11 to _15, device IDs 11-15) behind the QuickServer; the object list is the same on each.
- Status (BV 3) on each virtual device reads Online when the gateway is talking to that unit; other values hold their last reading when communication is lost.
- Error Code (AI 31) gives alarm numbers 11-46 for the YKN2Open board and 91-99 for thermostat/probe faults.
- Only map the points that exist on the unit's configuration and accessories; the doc warns extra variables slow the N2 polling.
- Names are printed as in the doc, including spelling (Suply, Outdor, Water Bomb = water pump).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
How many BACnet points does the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) have?
This list has 50 BACnet objects: 31 analog inputs, 4 analog values, 15 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet points are writable?
18 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) BACnet documentation?
The source is YKN2Open BMS BACnet/IP and Modbus TCP/IP - Installation and user manual (N-40462_EN 0716), published free by York at https://docs.johnsoncontrols.com/bas/api/khub/documents/bdk7s53yQ5tftUD6MrJq9g/content.
What are the minimum BACnet points to integrate the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)?
Start with BV 2 ON/OFF (Unit on (1) / forced off (0)); AV 8 Mode (0=Off, 1=Cool, 2=Heat, 3=Auto, 5=Emerg Heat); AV 2 Setpoint occupied cool (Occupied cooling setpoint, 10-32 °C); AV 3 Setpoint occupied heat (Occupied heating setpoint, 10-32 °C); BV 1 Fan Mode (0 = fan auto, 1 = continuous); AI 16 Indoor Temperature (Room temperature); AI 12 Suply air Temperature (Supply air temperature); AI 31 Error Code (Active alarm number, see alarm table); BV 3 Status (Gateway comms with this unit (Online/Offline)).
How do I enable BMS control of the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)?
Once the gateway is communicating, any analog or digital command written from the BMS takes over that function: it can no longer be changed from the thermostat or YKTool. ON/OFF (BV 2) is the run command; holding it at 0 keeps the unit off.
Does the York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP) need a BACnet heartbeat or have a communication timeout?
No heartbeat point is described. If N2 communication to a unit is lost, Status (BV 3) goes Offline and the other objects keep their last values.
How do I check these points on the real Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: YKN2Open BMS BACnet/IP and Modbus TCP/IP - Installation and user manual · N-40462_EN 0716. Object names, instances and units are reproduced as published; descriptions are our own.