  3. York
  4. YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)

Air-cooled screw chiller (via E-Link gateway) · BACnet points list

York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) BACnet points list

Updated 6 November 2026

Short answer

The E-Link gateway reads the YSAA board over YorkTalk 2 (4800 baud) and serves BACnet, N2, LON and Modbus objects named by YorkTalk page: remote setpoint and start/stop, chilled liquid and per-system refrigerant temperatures and pressures, run hours and timers, and status codes.

This page lists 67 BACnet objects for the York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
Equipment
Air-cooled screw chiller (via E-Link gateway)
Equipment type
Chillers
BACnet objects
67 (3 writable)
Transport
—
Firmware
Not stated
Also known as
YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550
Source document
YSAA BAS (ISN) E-Link points list · rev. 2018-01-12
Download CSV 67 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)

Integration in brief

Put the chiller in remote/ISN control at the panel, then start and stop it with the E-Link remote run/stop object and write the remote setpoint and current limit. Read the operating, safety and warning codes, run status and water temperatures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1YT2_S01_P07Remote start/stop (1 = run)Write
AV 1YT2_S01_P03Remote leaving chilled liquid setpointWrite
BV 21YT2_S01_P52Must read Remote (1) for BMS controlRead
MV 1YT2_S01_P56System 1 operating codeRead
AV 5YT2_S01_P11Leaving chilled liquid temperatureRead
AV 6YT2_S01_P12Entering chilled liquid temperatureRead
MV 2YT2_S01_P57System 1 fault codeRead
BV 5YT2_S01_P36System 1 alarm (1 = alarm)Read

Enable & remote start

The E-Link remote slots (AV 1-4, BV 1-4) are the BMS commands; the chiller panel must be set for remote (ISN/BAS) control for them to take effect.

Network setup

Watch out for

York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

67 of 67 shown
Type
AnalogBinaryMulti-state
Access
Show
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) BACnet Points List
DescriptionStates
AVmin1YT2_S01_P03Remote Setpoint°FWrite99=Auto
BVmin1YT2_S01_P07Start/Stop CommandWrite
BV4YT2_S01_P10History Buffer RequestWrite
AVmin5YT2_S01_P11Leaving Chilled Liquid Temp°FRead
AVmin6YT2_S01_P12Entering Chilled Liquid Temp°FRead
AV7YT2_S01_P13Evaporator Liquid Temp°FRead
AV9YT2_S01_P15Sys 1 Suction Temperature°FRead
AV10YT2_S01_P16Ambient Air Temperature°FRead
AV11YT2_S01_P17Sys 1 Suction Superheat°FRead
AV12YT2_S01_P18Sys 1 Run Time in secondsRead
AV13YT2_S01_P19Sys 1 Suction PressurepsiRead
AV14YT2_S01_P20Sys 1 Discharge PressurepsiRead
AV16YT2_S01_P22Sys 1 Run HoursRead
AV17YT2_S01_P23Sys 1 EEV Output % (EEV)%Read
AV18YT2_S01_P24Sys 1 Anti-Recycle Timer in secondsRead
AV19YT2_S01_P25Anti-Coincident Timer in secondsRead
AV20YT2_S01_P26Sys 2 Suction Temperature°FRead
AV21YT2_S01_P27Sys 2 Run Time in secondsRead
AV22YT2_S01_P28Sys 2 Suction PressurepsiRead
AV23YT2_S01_P29Sys 2 Discharge PressurepsiRead
AV25YT2_S01_P31Sys 2 Run HoursRead
AV26YT2_S01_P32Sys 2 Suction Superheat°FRead
AV27YT2_S01_P33Sys 2 Anti-Recycle Timer in secondsRead
AV28YT2_S01_P34Sys 2 EEV Output %%Read
BVmin5YT2_S01_P36Sys 1 AlarmRead0=No Alarm, 1=Alarm
BV6YT2_S01_P37Sys 2 AlarmRead0=No Alarm, 1=Alarm
BV7YT2_S01_P38Evaporator Heater StatusRead
BV8YT2_S01_P39Evaporator Pump StatusRead
BV9YT2_S01_P40Sys 1 Comp RunRead
BV10YT2_S01_P41Sys 1 SV Min LoadRead
BV11YT2_S01_P42Sys 1 SV LoadRead
BV12YT2_S01_P43Sys 1 SV UnloadRead
BV13YT2_S01_P44Sys 2 Comp RunRead
BV14YT2_S01_P45Sys 2 SV Min LoadRead
BV15YT2_S01_P46Sys 2 SV LoadRead
BV16YT2_S01_P47Sys 2 SV UnloadRead
BV19YT2_S01_P50Chilled Liquid TypeRead0=Water, 1=Glycol
BV20YT2_S01_P51Lead SystemRead0=Sys1, 1=Sys2
BVmin21YT2_S01_P52Local/Remote Control ModeRead0=Local, 1=Remote
BV22YT2_S01_P53UnitsRead0=Imperial, 1=SI
BV23YT2_S01_P54Lead/Lag Control ModeRead0=Manual, 1=Auto
MVmin1YT2_S01_P56Sys 1 Operational CodeRead
MVmin2YT2_S01_P57Sys 1 Fault CodeRead
MV3YT2_S01_P58Sys 2 Operational CodeRead
MV4YT2_S01_P59Sys 2 Fault CodeRead
MV6YT2_S01_P61Sys 1 Condenser Fan StageRead
MV8YT2_S01_P63Sys 2 Condenser Fan StageRead
AV30YT2_S01_P66Anti-Recycle Time ProgrammedRead
AV31YT2_S01_P67Leaving Chilled Liquid Temp Cutout°FRead
AV32YT2_S01_P68Low Ambient Temp Cutout°FRead
AV34YT2_S01_P70Low Suction Pressure Cutout CoolingpsiRead
AV35YT2_S01_P71High Discharge Pressure CutoutpsiRead
AV36YT2_S01_P72Remote Setpoint°FRead
AV37YT2_S01_P73Cooling Range°FRead
AV40YT2_S01_P76Sys 1 Discharge Temperature°FRead
AV41YT2_S01_P77Sys 1 Discharge Superheat°FRead
AV42YT2_S01_P78Sys 2 Discharge Temperature°FRead
AV43YT2_S01_P79Sys 2 Discharge Superheat°FRead
BV29YT2_S01_P84SCC Auto Detect AvailableRead
BV105YT2_S02_P36Option IndicatorRead0=Disabled, 1=Enabled
BV119YT2_S02_P50SCC Auto Detect Digit 1Read
BV120YT2_S02_P51SCC Auto Detect Digit 2Read
BV121YT2_S02_P52SCC Auto Detect Digit 3Read
BV122YT2_S02_P53SCC Auto Detect Digit 4Read
BV123YT2_S02_P54SCC Auto Detect Digit 5Read
BV124YT2_S02_P55SCC Auto Detect Digit 6Read
BV129YT2_S02_P84UnitsRead0=Imperial, 1=Metric
Object ID lookup: York YSAA E-Link point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)

How many BACnet points does the York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) have?

This list has 67 BACnet objects: 33 analog values, 28 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) BACnet points are writable?

3 of the 67 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2) BACnet documentation?

The source is YSAA BAS (ISN) E-Link points list, revision 2018-01-12, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/xvSi0e3Kwnf7B~5daaWaOw/content.

What are the minimum BACnet points to integrate the York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)?

Start with BV 1 YT2_S01_P07 (Remote start/stop (1 = run)); AV 1 YT2_S01_P03 (Remote leaving chilled liquid setpoint); BV 21 YT2_S01_P52 (Must read Remote (1) for BMS control); MV 1 YT2_S01_P56 (System 1 operating code); AV 5 YT2_S01_P11 (Leaving chilled liquid temperature); AV 6 YT2_S01_P12 (Entering chilled liquid temperature); MV 2 YT2_S01_P57 (System 1 fault code); BV 5 YT2_S01_P36 (System 1 alarm (1 = alarm)).

How do I enable BMS control of the York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)?

The E-Link remote slots (AV 1-4, BV 1-4) are the BMS commands; the chiller panel must be set for remote (ISN/BAS) control for them to take effect.

How do I check these points on the real YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: YSAA BAS (ISN) E-Link points list · rev. 2018-01-12. Object names, instances and units are reproduced as published; descriptions are our own.