  4. JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)

Make-up air unit / DOAS controller · BACnet points list

York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) BACnet points list

Updated 6 November 2026

Short answer

JDMA DOAS units with the D21 makeup air program expose 80 objects through the optional BACnet MS/TP card: unit state and occupancy-source selectors, a BMS occupancy command, space temperature, humidity and CO2 setpoints, discharge air setpoints, air temperatures, damper, fan, compressor and heat outputs, pressures, mode flags and alarms.

This page lists 80 BACnet objects for the York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.

Manufacturer
York
Model
JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
Equipment
Make-up air unit / DOAS controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
80 (21 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
77000
Also known as
JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air
Source document
Dedicated Outside Air Systems (DOAS) Operations Manual, Model JDMA - Manual for Makeup Air Control, Option D21 (Option D21 BACnet Point List) · 100.55-O2 (1015) · rev. 2015-10
Download CSV 80 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.

BMS integration notes: York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)

Integration in brief

Set AV 1007 OccMode_Sel to 2 (BMS) and command occupancy with BV 26 Occupied_BMS; AV 1006 State_Sel picks Auto, Cool, Heat or Off. Write the space temperature setpoint and, for BMS source units, supply fan speed and damper position. Read occupied status, supply fan status, discharge and space temperatures and the general alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1006State_SelUnit state: 2 Auto, 3 Cool, 4 Heat, 5 OffWrite
BV 26Occupied_BMSOccupancy command from the BMSWrite
AV 1007OccMode_SelOccupancy source; 2 = BMSWrite
AV 28SpcTempSPSpace temperature setpointWrite
AV 33SF_BMSSupply fan speed, % (BMS source units)Write
BV 25OccupiedOccupied mode in effectRead
BV 32SF_StsSupply fan proven onRead
AV 9DA_TempDischarge air temperatureRead
AV 25Spc_TempSpace temperatureRead
BV 1Alm_Rly_CmdUnit general alarmRead

Enable & remote start

AV 1006 State_Sel sets Auto, Cool, Heat or Off (default 5 = Off). Occupancy comes from the schedule, a digital input or the BMS as chosen by AV 1007 OccMode_Sel; with 2 = BMS the unit follows BV 26 Occupied_BMS.

Sensors & values from the BMS

Set BV 24 OA_Temp_Sel and BV 23 OA_Hum_Sel to BMS (1), then write AV 20 OA_Temp_BMS and AV 18 OA_Hum_BMS.

Network setup

Watch out for

York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

80 of 80 shown
Type
AnalogBinary
Access
Show
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) BACnet Points List
DescriptionStates
AV1CC_TempCooling Coil Discharge Air Temp°FRead
AV2Comp_Mod_OutDX Modulation Output % (range 0 to 100)%Read
AV3DA_NAClg_SPDischarge Air Temp Neutral Cooling SP (range 50 to 100), default 70°FWrite
AV4DA_NAHtg_SPDischarge Air Temp Neutral Heating SP (range 50 to 140), default 70°FWrite
AV5DA_SPDischarge Air Temp Active SP°FRead
AV6DA_SpcClg_SPDischarge Air Temp Space Cooling SP (range 50 to 100), default 55°FWrite
AV7DA_SpcHtCl_SPDischarge Air Temp Space Heat Mode Cooling SP (range 50 to 100), default 55°FWrite
AV8DA_SpcHtg_SPDischarge Air Temp Space Heating Sp (range 50 to 140), default 90°FWrite
AVmin9DA_TempDischarge Air Temp°FRead
AV10Damper_CmdDamper Output Command (range 0 to 100)%Read
AV11DhOADP_SPDehum OA Dew Point SP (range 50 to 100), default 58°FWrite
AV12EF_Spd_CmdExhaust Fan Speed Command (range 15 to 100)%Read
AV13ERV_DA_TempEnergy Recovery Wheel Discharge Air Temp°FRead
AV14Damper_BMSDamper Output BMS Command (range 0 to 100)%Write
AV15HX_Mod_CmdHeating Modulation Command (range 0 to 100)%Read
AV16MA_TempMixed Air Temp°FRead
AV17OA_Dew_PointOutside Air Dew Point°FRead
AV18OA_Hum_BMSOutdoor humidity from the BMS (used when OA_Hum_Sel = 1, BMS)%RHWrite
AV19OA_Hum_RawOutside Air Humidity%RHRead
AV20OA_Temp_BMSOutdoor air temperature from the BMS (used when OA_Temp_Sel = 1, BMS)°FWrite
AV21OA_Temp_RawOutside Air Temp°FRead
AV22OAChgOv_SPOA Change Over SP (range 45 to 80), default 65°FWrite
AV23RH_Mod_OutReheat Modulation Output % (range 0 to 100)%Read
AV24SF_VFD_CmdSupply Fan VFD Command (range 0 to 100)%Read
AVmin25Spc_TempSpace Temp°FRead
AV26SpcEffClgSPSpace Effective Cooling SP°FRead
AV27SpcEffHtgSPSpace Effective Heating SP°FRead
AVmin28SpcTempSPSpace Temp SP (range 65 to 85), default 72°FWrite
AV29RA_TempReturn Air Temperature°FRead
AV30RA_HumidityReturn Air Humidity%RHRead
AV31EA_TempExhaust Air Temperature°FRead
AV32EA_HumidityExhaust Air Humidity%RHRead
AVmin33SF_BMSSupply Fan Output BMS Command (range 0 to 100)%Write
AV1001Bldg_PressureBuilding Static Pressure; value x 1000in. WCRead
AV1002Bldg_Press_SPBuilding Static Pressure SP (range -500 to 500), default 100; value x 1000in. WCWrite
AV1003Duct_Press_SPDuct Static Pressure SP (range 0 to 2500), default 500; value x 1000in. WCWrite
AV1004Spc_HumSpace Humidity%RHRead
AV1005SpcHumSPSpace Humidity SP (range 35 to 75), default 55%RHWrite
AVmin1006State_SelState Select 2=AUTO 3=COOL 4=HEAT 5=OFF (range 2 to 5), default 5Write
AVmin1007OccMode_SelOcc Mode Select 0= Schedule 1= Digital Input 2= BMS (range 0 to 2), default 1Write
AV1008Spc_CO2Space CO2ppmRead
AV1009SpcCO2SPSpace CO2 SP (range 0 to 2,000), default 1,000ppmWrite
AV1010Duct_PressureDuct Static Pressure; value x 1000in. WCRead
BVmin1Alm_Rly_CmdUnit General Alarm Relay CommandRead0=Off, 1=On
BV2Comp_AlarmModulating Compressor General AlarmRead0=Off, 1=On
BV3Comp_Stg2_CmdCompressor Stage 2 CommandRead0=Off, 1=On
BV4Comp_Stg3_CmdCompressor Stage 3 CommandRead0=Off, 1=On
BV5Comp_Stg4_CmdCompressor Stage 4 CommandRead0=Off, 1=On
BV6EF_CmdExhaust Fan CmdRead0=Off, 1=On
BV7EF_StsExhaust Fan StatusRead0=Off, 1=On
BV8ERV_CmdEnergy Recovery Wheel CommandRead0=Off, 1=On
BV9Ext_OCCOccupied Mode InputRead0=Off, 1=On
BV10Ext_Switch_1External Damper Position Sw 1Read0=Off, 1=On
BV11Ext_Switch_2External Damper Position Sw 2Read0=Off, 1=On
BV12Htr_1_StsGas Heater 1 StatusRead0=Off, 1=On
BV13Htr_2_StsGas Heater 2 StatusRead0=Off, 1=On
BV14HX_Stg1_CmdHeating Stage 1 CommandRead0=Off, 1=On
BV15HX_Stg2_CmdHeating Stage 2 CommandRead0=Off, 1=On
BV16HX_Stg3_CmdHeating Stage 3 CommandRead0=Off, 1=On
BV17HX_Stg4_CmdHeating Stage 4 CommandRead0=Off, 1=On
BV18HX_Stg5_CmdHeating Stage 5 CommandRead0=Off, 1=On
BV19HX_Stg6_CmdHeating Stage 6 CommandRead0=Off, 1=On
BV20NA_Clg_MdNeutral Air Cooling ModeRead0=Off, 1=On
BV21NA_Dehum_MdNeutral Air Dehum ModeRead0=Off, 1=On
BV22NA_Htg_MdNeutral Air Heating ModeRead0=Off, 1=On
BV23OA_Hum_SelShare OA Humidity from BMS (0=Probe 1=BMS), default OffWrite0=Off, 1=On
BV24OA_Temp_SelShare OA Temp from BMS (0=Probe 1=BMS), default OffWrite0=Off, 1=On
BVmin25OccupiedOccupied Mode StatusRead0=Off, 1=On
BVmin26Occupied_BMSOccupied Mode BMS - Sets Unit Occupancy when OccMode_Sel is set to 2=BMS, default OffWrite0=Off, 1=On
BV27Phase_AlarmPhase Protection AlarmRead0=Off, 1=On
BV28Preheat_CmdElectric Preheat CommandRead0=Off, 1=On
BV29Reheat_AlarmModulating Reheat Compressor General AlarmRead0=Off, 1=On
BV30Safety_StsSafety Input StatusRead0=Normal, 1=Alarm
BV31SF_CmdSupply Fan CommandRead0=Off, 1=On
BVmin32SF_StsSupply Fan StatusRead0=Off, 1=On
BV33Spc_Clg_MdSpace Cooling ModeRead0=Off, 1=On
BV34Spc_Dehum_MdSpace Dehum ModeRead0=Off, 1=On
BV35Spc_Htg_MdSpace Heating ModeRead0=Off, 1=On
BV36Spc_HtgClg_MdSpace Heating Cooling ModeRead0=Off, 1=On
BV37Filter_StsMain or ERV Dirty Filter StatusRead0=Off, 1=On
Object ID lookup: York JDMA DOAS D21 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)

How many BACnet points does the York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) have?

This list has 80 BACnet objects: 43 analog values, 37 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) BACnet points are writable?

21 of the 80 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card) BACnet documentation?

The source is Dedicated Outside Air Systems (DOAS) Operations Manual, Model JDMA - Manual for Makeup Air Control, Option D21 (Option D21 BACnet Point List) (100.55-O2 (1015)), revision 2015-10, published free by York at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/GKywNRPcbHXBg1PrW2~4wQ/content.

What are the minimum BACnet points to integrate the York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)?

Start with AV 1006 State_Sel (Unit state: 2 Auto, 3 Cool, 4 Heat, 5 Off); BV 26 Occupied_BMS (Occupancy command from the BMS); AV 1007 OccMode_Sel (Occupancy source; 2 = BMS); AV 28 SpcTempSP (Space temperature setpoint); AV 33 SF_BMS (Supply fan speed, % (BMS source units)); BV 25 Occupied (Occupied mode in effect); BV 32 SF_Sts (Supply fan proven on); AV 9 DA_Temp (Discharge air temperature); AV 25 Spc_Temp (Space temperature); BV 1 Alm_Rly_Cmd (Unit general alarm).

How do I enable BMS control of the York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)?

AV 1006 State_Sel sets Auto, Cool, Heat or Off (default 5 = Off). Occupancy comes from the schedule, a digital input or the BMS as chosen by AV 1007 OccMode_Sel; with 2 = BMS the unit follows BV 26 Occupied_BMS.

Can the BMS supply sensor values to the York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)?

Set BV 24 OA_Temp_Sel and BV 23 OA_Hum_Sel to BMS (1), then write AV 20 OA_Temp_BMS and AV 18 OA_Hum_BMS.

How do I check these points on the real JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More York BACnet points lists

Source: Dedicated Outside Air Systems (DOAS) Operations Manual, Model JDMA - Manual for Makeup Air Control, Option D21 (Option D21 BACnet Point List) · 100.55-O2 (1015) · rev. 2015-10. Object names, instances and units are reproduced as published; descriptions are our own.